This document is a Sources Sought notice for a federal contract opportunity related to the Design-Bid-Build, FFG-62 Land Based Engineering Site project at the Philadelphia Navy Yard Annex in Philadelphia, PA.
The notice is seeking information from commercially available and interested suppliers capable of providing various products and services for the project, including card readers, power supply enclosures, access control system modules, request-to-exit devices, electric strikes, translucent wall panels, roof enclosures, fire alarm control panels, flood doors, thermal breaks, fire alarm radio transmitters, a Kinetix system, and fuel oil system equipment. Specific manufacturer and product requirements are provided for each item.
Interested vendors are requested to submit a capabilities statement package of no more than 5 pages by Friday, May 10, 2024 at 2:00 PM Eastern Daylight Time. Late responses will not be considered. This is a market research effort, and the government is not obligated to pay for any information received.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Power Supply Charger
LNL-AL600ULX-4CB6
Overview
The LNL-AL600ULX-4CB6 is a power-limited supply/charger that will convert a 115 VAC 50/60 Hz input, into a power-limited 12 VDC output.
Specifications
Input Power
Input 115 VAC 50/60 Hz, 1.9 amp
Thermal overload protection
Short circuit protection
Primary plug-able connector for incoming 115 VAC
Output Power
12 VDC, 4-port power limited outputs
Maximum 6 amps continuous supply current at 12 VDC
Four individual circuit breaker outputs rated @ 2.5 amps each
100 mV peak output voltage ripple
Indicators AC input and DC output LED indicators
Battery Charging
Built-in charger for sealed lead acid or gel type batteries (Optional ABT-12)
Automatic switchover to standby battery when AC fails
Maximum charge current 0.7 amp
Low battery and battery presence supervision (form C contacts)
AC fail supervision (form C contacts)
Zero voltage drop when switched over to battery backup
Regulatory Compliance
UL 294 and 1076-listed
ULC/ORD-C1076-M1986
S319/CSA C22.2 No. 205-M1983
Class 2 rated
FCC
Physical Dimensions
Power supply board dimensions: 4.5 x 7.25 x 1.8 in. (114 x 184 x 46 mm)
Enclosure dimensions: 24.25 x 18.25 x 4.75 in. (616 x 464 x 121 mm)
FEATURES & FUNCTIONALITY
• LNL-CTX6 enclosure (gray with Lenel logo)
• Offline power supply board - AL1012ULXBL
• Tamper switch
• Lenel lock with two keys
• 50 plastic snap-in stand-offs
• Battery leads
• Installation instructions
• Can accommodate up to 6 Lenel access control modules
Ordering
Part Number Description
LNL-AL600ULX-4CB6 115 VAC configuration
ABT-12 Battery backup option
LNL-CTX6 Cabinet only, with lock (24.25 x 18.25 x 4.75 in. / 616 x 464 x 121 mm)
(866) 788-5095
Specifications subject to change without notice.
© 2013 Lenel Systems International, Inc. All rights reserved. Lenel and OnGuard are registered trademarks of Lenel Systems International, Inc. All other trademarks and copyrights are the property of their respective owners.
LNL_TS_AL600ULX-4CB6_092513
lenel.com
File details come from the government source that posted it. Updated .