This document is a sources sought notice for a federal contract opportunity regarding the Design-Bid-Build, FFG-62 Land Based Engineering Site at the Philadelphia Navy Yard Annex in Philadelphia, PA. The notice seeks to identify commercially available and interested suppliers capable of providing various equipment and components required for the project, including card readers, power supply enclosures, access control system modules, request-to-exit devices, electric strikes, translucent wall panels, roof enclosures, fire alarm control panels, flood doors, thermal breaks, fire alarm radio transmitters, fuel oil system equipment, and balanced magnetic switches. The notice provides detailed product specifications and requirements for each item, and requests that interested vendors submit a capabilities statement package of no more than 5 pages by Friday, May 10, 2024 at 2:00 PM EDT. This is a market research tool, and the government is not obligated to pay for any information received from potential sources.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

aes-corp.com

7707 Fire Subscribers

Feature Highlights

• Offers flexible power and configuration options.

• Engineered for backward compatibility with legacy systems.

• Enables future ready capabilities.

• Provides instant Subscriber status through front panel with Power and Trouble LEDs, a backlit LCD display, and Menu/Silence button.

• Includes dual communication/multiple communication technology (reporting over RF and

IP).

• Improves functionality with an adaptive Graphic User Interface (GUI) for programming via smartphones, tablets, and PCs.

• Built upon the solid foundation of AES-IntelliNet® patented mesh radio technology for use in private licensed wireless networks.

• Protects Subscriber units against unauthorized access and rogue activity with a password protected Dealer Code.

• Makes programming and streamlined troubleshooting easy with user friendly interface.

• Adds integrated supervision of 7794A AES-IntelliPro full data module.

• Provides versatile power options.

Key Benefits

IntelliNet® 2.0 Fire Subscribers

7707P-88-M IntelliNet 2.0 Fire Subscriber, 8-Zone with Multiple Communication Technologies (MCT), Red Enclosure

7707P-88-ULP-M

IntelliNet 2.0 Fire Subscriber, 8-Zone with 7794A AES-IntelliPro and Integrated Onboard Local Annunciator, plus Multiple Communication Technologies (MCT), Red Enclosure

7707P-44-M IntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with Multiple Communication Technologies (MCT), Red Enclosure

7707P-44-ULP-M

IntelliNet 2.0 Fire Subscriber, 4x4 Zone (4 Reversing Polarity, 4 Supervised) with 7794A AES-IntelliPro and Integrated oOnboard Local Annunciator, plus Multiple Communication Technologies MCT, Red Enclosure

Models https://aes-corp.com/ aes-corp.com

AES Corporation | 285 Newbury St. | Peabody, MA 01960 United States

© 2023 AES Corporation and AES-IntelliNet® are registered trademarks of AES Corporation. 7707_Rev4_10252023

Technical Specifications

DIMENSIONS

13”H x 8.5”W x 4.5”D (33cm H x 21.5cm W x 11.4cm D)

WEIGHT

• 15.85 lbs (7.2 kilograms) with

12Ah battery

• 7 lbs (3.2 kilograms) excluding battery

RADIO FREQUENCY

Standard Frequency Range:

450-470 MHz Contact AES for other UHF and VHF frequencies

ANTENNA

2.5 dB Tamper resistant antenna included

POWER INPUT

• 16.5V AC Class 2 Transformer

Transformer not included

• 24V DC External Regulated

Power Supply

• 24V DC Regulated Power

Supply from FACP AUX Power

BACKUP BATTERY

12 Ah with 7794A; 6 Ah without, UL recognized lead acid gel cell battery Size based on Subscriber configuration

CURRENT CONSUMPTION

Backup Battery Power

• Standby = .190A

• Transmit = .752A

• Optional 7794A = .165A, Standby and Alarm

ALARM SIGNAL INPUTS/ ZONES

• 8 Individually programmable

E.O.L. type zone inputs

• 4x4 Option with 4 reverse polarity input and 4 individually programmable E.O.L. type zone inputs

• Optional 7794A AES-IntelliPro for full data via Contact ID, Pulse, Modem IIe, and Modem IIIa2

UL LISTINGS

• UL 864 Standard for Control

Units and Accessories for Fire Alarm Systems, Edition 10

• ULC S559-04 Equipment for Fire Signal Receiving Centers and Systems, Edition 1

TROUBLE OUTPUT—ACK

DELAY/ANTENNA CUT

Form C relay, fail secure, rated 24V DC 1A resistive, unsupervised

RESET BUTTON

Located on main circuit board

OPERATING TEMPERATURE

32 to 120°F (0 to 49°C)

STORAGE TEMPERATURE

14 to 140°F (-10 to 60°C)

RELATIVE HUMIDITY

0 to 93%, non-condensing

PORTS

• (1) Ethernet

• (2) USBs

ANNUNCIATOR

Integrated Local Annunciator

PROGRAMMING INTERFACE

Web browser capable device accessible via smartphone, tablet, laptop, or PC

POWER OUTPUT

2 or 5 Watts Contact AES for other options

ENCLOSURE MATERIAL

Metal with paint finish

FINISH COLOR

Red

VISUAL INDICATORS

• Front panel LCD (2 x 20 alphanumeric character backlit display)

• Power and Trouble LEDs (ALM, Trouble, Tx, Rx, WA)

• Menu/ Silence button https://aes-corp.com/ https://www.linkedin.com/company/aes-corporation https://www.youtube.com/user/CorpAES/videos https://www.facebook.com/CorpAES