4-26KP08 Riverton HS Football Field Sports Upgrade - Drawings.pdf
PDF 2 MB Posted
- Solicitation number
- 26KP08
- Issued by
- Salt Lake County, Utah
About this file
This is a set of construction drawings for the Riverton High School Football Field Sports Upgrade project issued by the Jordan School District in South Jordan, Utah. The project involves comprehensive upgrades to the stadium's lighting and audio-visual systems, with electrical, mechanical, and audiovisual components. The scope of work includes demolition of existing stadium light fixtures while retaining poles for reuse, installation of new pole-mounted lighting controllers and fixtures, provision of new mini-split heating and cooling systems for the press box with Mitsubishi 18,000 BTU units, relocation of existing telecommunications equipment into a new AV rack, installation of new wireless access points and patch panels, and complete audio-visual system upgrades including speakers, microphones, amplifiers, and control systems. The drawings, dated February 19, 2026, are prepared by licensed engineers and include detailed mechanical symbols and schedules, electrical demolition plans, electrical panel specifications, and audiovisual system layouts with signal flow diagrams.
The project requires coordination among multiple trades including mechanical contractors, electrical contractors (Division 26), and AV systems integrators (Division 27). Existing electrical equipment includes a Square D HOMC12UC Series panelboard (BL24) that will receive new circuits for the mini-split system and new transformer installation. The mechanical scope includes installation of a new 30 KVA 480V to 208V step-down transformer with associated breakers and conductors, plus heat trace cables for exterior condensate piping. The audiovisual system incorporates a comprehensive audio distribution network with multiple speakers positioned around the field and bleachers, dual wireless microphone receivers, mixing console, amplifiers with 3000W and 2250W capacities, network switches, and a touch panel controller housed in a rack-mounted equipment enclosure. All installations must comply with the National Electrical Code, International Building Code, and manufacturer specifications, with contractors required to conduct site visits prior to bidding and coordinate extensively with existing utility systems, including cellular equipment on-site that must be protected throughout construction.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
ES
SI
R
UT
AH
TE OF
S T A
P
L EN
P ro je c t
N
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
T h is d ra w in g i s t h e c o p y ri g h te d p ro p e rt y o f R e s o lu t G ro u p
U n a u th o ri z e d d u p lic a ti o n p u b lic a ti o n o r d is tr ib u ti o n i s s tr ic tl y p ro h ib it e d
U s e o f th is d ra w in g i s a t th e u s e r' s o w n r is k a n d
R e s o lu t G ro u p d is c la im s a n y l ia b il it y f o r d a m a g e s o r lo s s e s a ri s in g f ro m i ts u s e
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
FEBRUARY 19, 2026
SITE ADDRESS
DRAWING INDEXVICINITY MAPCONSULTANTS
ELECTRICAL:
RESOLUT GROUP
181 E 5600 S,Suite 200 Murray, UT 84107 Phone:(801) 530-3148
SOUTH JORDAN, UTAH
RIVERTON HIGH SCHOOL FOOTBALL FIELD
2/19/2026
Riverton High School Football Field Sports Upgrade
/1
/2
:3 :4
P
M A u to d e s k D o c s /2
J
S D
R iv e rt o n
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
/2
J S
D R iv e rt o n H
S F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250866
BR
RESOLUT
TITLE SHEET
E1
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
R
IV
E R
T O
N H
IG
H
S C
H O
O L
W
R iv e rt o n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
JORDAN SCHOOL DISTRICT
RIVERTON HIGH SCHOOL 12476 2700 W,
Riverton, UT 84065
ELECTRICAL SHEET LIST
E1 TITLE SHEET
E1.1 SYMBOLS, SCHEDULES, NOTES AND DIAGRAMS
E1.2 ELECTRICAL DEMOLITION
E2 RIVERTON HIGH SCHOOL ELECTRICAL PLAN
E4 ELECTRICAL PANEL SCHEDULES
XE3 ELECTRICAL DIAGRAMS
TA1 AUDIOVISUAL NOTES, LEGENDS, & SCHEDULES
TA2 RIVERTON HIGH SCHOOL SOUND PLAN
TA4 AUDIOVISUAL DIAGRAMS
REVISIONS
MARK DATE DESCRIPTION
M
S
S
M
CO2
CO
H2
HZG
NO2
O2
HS
H
T
TC
TH
TS
KEYNOTE SYMBOL
CONTINUATION SYMBOL
SHEET NUMBER WHERE DETAIL IS PLACED
DETAIL NUMBER ON SHEET
PLAN REVISION NUMBER
GENERAL PLAN SYMBOLS
ROOM NAME / NUMBER
POINT WHERE NEW CONNECTS TO EXISTING
AREA BEING DEMOLISHED
AREA NOT IN CONTRACT
* NOTE *
ALL OF GENERAL NOTES ON THIS SHEET ARE TO BE APPLIED TO ALL OTHER DRAWINGS IN THIS SET.THE
SYMBOLS AND ABBREVIATIONS SHOWN ON THIS SHEET MAY OR MAY NOT BE USED IN THIS SET OF
DRAWINGS.
GRILLE, REGISTER, DIFFUSERS
AIRFLOW
CATALOG THROW PERFORMANCE
NECK SIZE / MODULE SIZE
EXISTING DUCT TO REMAIN
OVAL DUCT SIZE (WIDTH / HEIGHT)
SQ. DUCT SIZE (WIDTH X HEIGHT)
HVAC SYMBOLS
RECT. SUPPLY DUCT RISE / DROP
MECHANICAL EQUIPMENT
ROUND DUCT SIZE (DIAMETER)
DUCT TO BE DEMOLISHED
EQUIPMENT BY OTHERS
(REFER TO OTHER
DISCIPLINES)
EXISTING TO REMAIN
EQUIPMENT
Ø ROUND
ABV ABOVE
AC AIR CONDITIONING
AD AREA DRAIN
ADD ADDENDUM
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
ALT ALTERNATE
AP ACCESS PANEL
ARCH ARCHITECT/ARCHITECTURAL
BFF BELOW FINISHED FLOOR
BLW BELOW
BTU BRITISH THERMAL UNITS
BTUH BRITISH THERMAL UNITS PER HOUR
CAP CAPACITY
CB CATCH BASIN
CFM CUBIC FEET PER MINUTE
CLG CEILING
CO CLEAN OUT
CW COLD WATER
D DEGREE
DB DRY BULB
DIA DIAMETER
DN DOWN
DW DISTILLED WATER
EA EACH
EAT ENTERING AIR TEMPERATURE
ELEC ELECTRICAL
EQUIP EQUIPMENT
EWC ELECTRIC WATER COOLER
EWT ENTERING WATER TEMPERATURE
E/A EXHAUST AIR
EXIST EXISTING
F DEGREES FAHRENHEIT
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FL FLOOR
FO FUEL OIL
FOV FUEL OIL VENT
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FPM FEET PER MINUTE
FS FLOOR SINK
FT FOOT/FEET
FTR FIN TUBE RADIATION
GAL GALLON
GF GAS-FIRED
GC GENERAL CONTRACTOR
GPM GALLONS PER MINUTE
GW GREASE WASTE
HB HOSE BIB
HP HORSE POWER
HTG HEATING
HTR HEATER
HW HOT WATER
HYD HYDRANT
ID INDIRECT
IN INCH
INV INVERT
LB POUND
LB/HR POUNDS PER HOUR
LAT LEAVING AIR TEMPERATURE
LP LOW PRESSURE
LPG LIQUEFIED PETROLEUM GAS
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MAX MAXIMUM
MBH ONE THOUSAND BTU PER HOUR
MCF ONE THOUSAND CUBIC FEET
MD MOTORIZED DAMPER
MECH MECHANICAL
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MTR MOTOR
MU/A MAKE-UP/AIR
NC NOISE CRITERIA
NC NORMALLY CLOSED
NIC NOT IN CONTRACT
NO NUMBER
NO NORMALLY OPEN
NTS NOT TO SCALE
O OXYGEN
O/A OUTSIDE AIR
ORD OVERFLOW ROOF DRAIN
PD PRESSURE DROP
PIV POST INDICATOR VALVE
PLBG PLUMBING
PRESS PRESSURE
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIG POUNDS PER SQUARE INCH GAUGE
PWR POWER
R DUCT RISER
R/A RETURN AIR
RCP RADIANT CEILING PANEL
RD ROOF DRAIN
REC RECESSED
RED REDUCER
RH RELATIVE HUMIDITY
RL/A RELIEF AIR
RM ROOM
RPM REVOLUTIONS PER MINUTE
RW RAIN WATER
SF SQUARE FOOT
S/A SUPPLY AIR
SAN SANITARY
SF SQUARE FOOT
SD SMOKE DAMPER
SM SURFACE MOUNT
SP STANDPIPE
SP STATIC PRESSURE
STM STEAM
T THERMOSTAT
TD TEMPERATURE DROP
TDR TRENCH DRAIN
TEMP TEMPERATURE
TYP TYPICAL
UG UNDERGROUND
VAC VACUUM
V VENT
VAV VARIABLE AIR VOLUME
VENT VENTILATION
VTR VENT THROUGH ROOF
W WASTE
WB WET BULB
WCO WALL CLEAN OUT
WH WALL HYDRANT
ABBREVIATIONS
TYPE (SEE SCHEDULE)
MAX NC RATING
DESIGN AIRFLOW RATE
DESIGN WATER FLOW
OPERATING WEIGHT
HEATING CAPACITY
NOMINAL COOLING CAPACITY
EXISTING RELOCATED
EQUIPMENT
AC AIR CONDITIONING UNIT
ACCU AIR COOLING CONDENSING UNIT
AHU AIR HANDLING UNIT
AS AIR SEPARATOR
B BOILER
CH CHILLER
CT COOLING TOWER
CUH CABINET UNIT HEATER
CHWP CHILLED WATER PUMP
DBP DOMESTIC WATER BOOSTER PUMP
DC DUCT MOUNTED COIL
DCP DOMESTIC WATER CIRCULATING PUMP
EF EXHAUST FAN
EDC ELECTRIC DUCT COIL
ET EXPANSION TANK
EWH ELECTRIC WATER HEATER
FCU FAN COIL UNIT
FP FIRE PUMP
GI GREASE INTERCEPTOR
GRV GRAVITY ROOF VENTILATOR
HWP HEATING WATER PUMP
HRU HEAT RECOVERY UNIT
PRV POWER ROOF VENTILATOR
RE RETURN/EXHAUST FAN
RTU ROOFTOP UNIT
SP SUMP PUMP
UH UNIT HEATER
WH WATER HEATER
EQUIPMENT ABBREVIATIONS
DAMPER TYPES
ROUND SUPPLY DUCT RISE / DROP
RECT. RETURN DUCT RISE / DROP
ROUND RETURN DUCT RISE / DROP
RECT. EXHAUST DUCT RISE / DROP
ROUND EXHAUST DUCT RISE / DROP
BOTTOM OF EQUIPMENT HEIGHT
NECK SIZE
AIRFLOW
AIRFLOW
MOUNTING ELEVATION (CENTERLINE)
NOMINAL DUCT SIZE
AIRFLOW
NECK SIZE/ SLOT(S)/ ACTIVE LENGTH
AIRFLOW
MOUNTING ELEVATION (CENTERLINE)
NOMINAL DUCT SIZE
AIRFLOW
NECK SIZE / MODULE SIZE
MAX NC RATING
TYPE COUNT FOR SPACE
UNIT IDENTITY
GAS SUPPLY INPUT RATE
THROW PATTERN
SIDEWALL SUPPLY
GRILLE
ROUND CEILING
DIFFUSER
SQUARE CEILING
DIFFUSER
SIDEWALL RETURN
GRILLE
CEILING RETURN
POINT WHERE EXISTING IS TO BE DEMOLISHED
24"x12"
24"/12" FO
18"Ø
(E)AHU-2
RTU-1
10.0 ton
RTU-1
180000 Btu/h
180 CFH
3.7 GPM
VAV 1-2
(R)AHU-3
FLUE
C/A
SA
SA
VA
OA
TA
RA
RLA
EA
GEA
LH
(E)
EF-XX
500 CFM
AC-1
AFF:7'-0"
6"Ø
CD11 100
TYP. X 4
10"Ø/24x24 H6/9/1729
CD3 500
8"Ø/2s/4'-0"L
LD8 200
18"x10"
SG1 500
AFF:9'-0"
16"x16"
RG1 800
AFF:9'-0"
12"x12"/24x24
RG2 500
ET-1
379 lb
Room
LINEAR DIFFUSER
SUPPLY AIR - LOW PRESSURE
SUPPLY AIR - MEDIUM PRESSURE
VENTILATION AIR
OUTDOOR AIR
RETURN AIR
TRANSFER AIR
RELIEF AIR
GENERAL EXHAUST AIR
GREASE EXHAUST DUCT
LABORATORY HOOD
FLUE GAS VENT
COMBUSTION AIR
MANUAL DAMPER
MOTORIZED (ATC) DAMPER
BACKDRAFT DAMPER
SMOKE DAMPER
FIRE DAMPER
COMB. FIRE/ SMOKE DAMPER
MECHANICAL PIPING SYMBOLS
EXISTING PIPE TO REMAIN
PIPE TO BE DEMOLISHED
ABOVE GROUND PIPING
NOMINAL PIPE SIZE
BELOW GROUND PIPING
PIPE SLOPE (WHEN APPLICABLE)
MECHANICAL DEVICES
VALVE TYPES
PIPE RISE / DROP
2"
1/8" / 12" SLOPE
(E)
CHWR
CHWS
GCHWR
GCHWS
CD
CWR
CWS
GHWR
GHWS
GWR
GWS
HWR
HWS
NER
NES
G
LP
RL
RS
RD
LPS
LPCR
PC
HPS
HPCR
CHILLED-WATER RETURN
CHILLED-WATER SUPPLY
GLYCOL CHILLED-WATER RETURN
GLYCOL CHILLED-WATER SUPPLY
CONDENSATE DRAIN
CONDENSER-WATER RETURN
CONDENSER-WATER SUPPLY
GLYCOL HEAING-WATER RETURN
GLYCOL HEATING-WATER SUPPLY
GROUND LOOP-WATER RETURN
GROUND LOOP-WATER SUPPLY
HOT-WATER RETURN
HOT-WATER SUPPLY
NET ENERGY LOOP RETURN
NET ENERGY LOOP SUPPLY
NATURAL GAS
LIQUID PROPANE
REFRIGERANT LIQUID
REFRIGERANT GAS
REFRIGERANT DISCHARGE
LOW PRESSURE STEAM
CONDENSATE RETURN (LOW PRESSURE)
PUMPED CONDENSATE
HIGH PRESSURE STEAM
CONDENSATE RETURN (HIGH PRESSURE)
SHUTOFF
BAL
BFV
CHECK
CHECK
CIRC
GATE
GLOBE
LOCK
PRV
QUICK
STRAIN
M-CNTRL
3-WAY CNTRL
GAS-CNTRL
PLUG
GAS COCK
REG
BALL VALVE
BALANCING VALVE
BUTTERFLY VALVE
CHECK VALVE
ALTERNATE CHECK VALVE
CIRCUIT SETTER
GATE VALVE
GLOBE VALVE
LOCKED SHIELD VALVE
PRESSURE REDUCING VALVE
QUICK OPENING VALVE
FLUID STRAINER
ELEC. CONTROL VALVE
3-WAY ELEC. VALVE
EMERGENCY GAS SHUTOFF
PLUG VALVE
GAS SHUTOFF COCK
GAS REGULATOR
AHU-1 UNIT IDENTITY
TEMPERATURE SENSOR
TEMP/ HUMIDITY SENSOR
TEMP/ CO2 SENSOR
THERMOSTAT
HUMIDISTAT
HUMIDITY SENSOR
CARBON DIOXIDE DETECTOR
CARBON MONOXIDE DETECTOR
HYDROGEN GAS DETECTOR
HAZARDOUS GAS DETECTOR
NITROGEN DIOXIDE DETECTOR
OXYGEN GAS DETECTOR
HVAC GENERAL NOTES
1 COORDINATE EXACT MOUNTING LOCATION OF ALL THERMOSTATS WITH LATEST REVISION OF
ARCHITECTURAL ELEVATION AND FURNISHINGS PLANS, TYPICAL.
2 THE MECHANICAL CONTRACTOR SHALL PROVIDE FIRE, SMOKE OR COMBINATION FIRE/SMOKE
DAMPERS AT ALL LOCATIONS SHOWN ON THE CONTRACT DOCUMENTS AND AS REQUIRED TO MEET
THE INTEGRITY OF ALL SMOKE AND FIRE PARTITIONS. THE CONTRACTOR SHALL REFER TO THE LATEST ARCHITECTURAL LIFE SAFETY PLANS FOR ALL FIRE AND SMOKE PARTITION LOCATIONS.
DAMPERS ARE TO BE PROVIDED WITH SHUTOFF/TEST SWITCH AT EACH LOCATION.
3 INSTALL ALL TERMINAL BOXES IN EASILY ACCESSIBLE AND SERVICEABLE LOCATIONS, MEETING ALL
MANUFACTURERS REQUIRED CLEARANCES ON EACH SIDE, SEE DETAILS, TYPICAL.
4 THE MECHANICAL CONTRACTOR SHALL PROVIDE CEILING MOUNTED ACCESS DOORS FOR ALL FIRE, SMOKE AND COMBINATION FIRE/SMOKE DAMPERS INSTALLED ABOVE INACCESSIBLE CEILING.
FIELD VERIFY EXACT INSTALLATION LOCATIONS PRIOR TO COMMENCING WORK AND COORDINATE
INSTALLATIONS WITH LATEST ARCHITECTURAL REFLECTED CEILING PLANS.
5 PROVIDE ACCESS DOORS TO ACCESS VAV BOX CONTROLS ABOVE HARD CEILINGS. PROVIDE
MINIMUM 24" X 24".
6 THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE
CONTRACT DOCUMENTS.
7 PROVIDE ACCESS TO ALL TEMPERATURE CONTROLS ABOVE CEILING. LOCATE IN ACCESSIBLE
LOCATION. WHERE THERE ARE HARD CEILINGS, THE CONTRACTOR SHALL PROVIDE 24" X 24"
ACCESS DOOR.
8 SUPPLY AND RETURN PIPING TO COILS ARE THE SAME SIZE.
9 CONTRACTOR SHALL LOCATE TEMPERATURE SENSORS AT 4'-0" AFF, A MINIMUM OF 8" FROM LIGHT
SWITCH, UNLESS OTHERWISE NOTED ON THE ARCHITECT'S ELEVATIONS. COORDINATE EXACT
LOCATIONS WITH ARCHITECT.
10 CONDENSATE DRAINS SHALL BE SUPPLIED FOR ALL COOLING EQUIPMENT. CONTRACTOR SHALL
ENSURE PROPER INSTALLATION AND DRAINAGE AS REQUIRED BY FEDERAL, STATE, AND LOCAL
CODES. CONDENSATE PIPING SHALL BE TYPE "L" COPPER UNLESS OTHERWISE NOTED IN THE
SPECIFICATIONS.
11 PROVIDE A 6" HOUSEKEEPING PAD FOR EACH PIECE OF MECHANICAL EQUIPMENT THAT IS FLOOR
MOUNTED. COORDINATE SIZES WITH MECHANICAL EQUIPMENT SELECTED.
12 ALL SUPPLY, RETURN, AND EXHAUST DUCTWORK SHALL BE RATED FOR PRESSURE CLASS OF 2"
W.G. UNLESS NOTED OTHERWISE ON THE PLANS OR IN THE SPECIFICATIONS.
13 THIS CONTRACTOR SHALL BE REQUIRED TO REPLACE FILTERS ON HVAC EQUIPMENT AFTER ALL
DUST PRODUCING CONSTRUCTION HAS BEEN COMPLETED AND PRIOR TO THE FINAL PUNCH.
PROJECT REQUIREMENTS
1 THE PROJECT GENERAL NOTES APPLY TO ALL
2 REMOVE ALL UNUSED PIPING, DUCTWORK, EQUIPMENT, AND ACCESSORIES.
3 THE MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR FIELD VERIFYING ALL EXISTING CONDITIONS FOR PLUMBING AND MECHANICAL SYSTEMS WITHIN THE SCOPE OF WORK SPACE AND WITHIN CLOSE PROXIMITY TO THE SCOPE OF WORK SPACE. THE CONTRACTOR WILL FIELD VERIFY AS MUCH AS IS REASONABLE BEFORE THE FINAL BID. AFTER THE FINAL BID THE CONTRACTOR WILL
NOTIFY THE OWNER, ARCHITECT, AND MECHANICAL DESIGN ENGINEER IMMEDIATELY UPON
DISCOVERY OF EXISTING CONDITIONS THAT MAY AFFECT THE DESIGN.
4 THE MECHANICAL CONTRACTOR SHALL PERFORM SERVICE AND REPAIR ON THE EXISTING
EQUIPMENT AND ITS ACCESSORIES AS FOLLOWS: CLEAN ALL COILS, REPLACE THE FILTERS AND
BELTS, INSPECT, REPAIR, OR REPLACE THE ECONOMIZERS, DRIVERS AND FAN BEARINGS,
MOTORS, CONTROL COMPONENTS, VALVES, AND ANY OTHER ITEM NECESSARY FOR A COMPLETE
AND PROPER OPERATING SYSTEM. THIS CONTRACTOR SHALL ALSO VISIT THE SITE, PRIOR TO
FINAL BIDDING, AND VERIFY ALL EXISTING SITE CONDITIONS. PROVIDE ALL MATERIAL AND
COMPONENTS AS NEEDED TO BRING THE UNITS TO FULL COMPLIANCE OF THE OWNER’S CRITERIA
AND LOCAL AUTHORITY HAVING JURISDICTION.
5 WHERE FLOOR DRAINS OCCUR WITH THE LIMITS OF CONSTRUCTION, PREVENT CONSTRUCTION
DEBRIS FROM ENTERING DRAIN BODY BY SEALING DRAIN OPENING PRIOR TO START OF WORK.
UNSEAL DRAINS AT COMPLETION OF CONSTRUCTION.
6 COORDINATE INSTALLATION OF PIPING, DUCTWORK, CONDUIT, LIGHTS, CABLE TRAY, STRUCTURE, EQUIPMENT, CEILINGS, ARCHITECTURAL COMPONENTS, AND ANYTHING ELSE PERTAINING TO THE
PROJECT TO PREVENT CONFLICTS.
7 THE CONTRACTOR SHALL BE FAMILIAR WITH ALL THE CONDITIONS BOTH EXISTING AND THOSE ILLUSTRATED BY THESE DOCUMENTS AND THOSE OF OTHER DISCIPLINES, INCLUDING, BUT NOT LIMITED TO ARCHITECTURAL, CIVIL, ELECTRICAL, VENTILATION, PLUMBING, AND OTHER SYSTEMS
INVOLVED ON THIS PROJECT.
8 FINAL PRODUCT SHALL BE A COMPLETE AND FUNCTIONING SYSTEM, AND SHALL CONFORM TO ALL
REQUIREMENTS OF APPLICABLE FEDERAL, STATE, AND LOCAL CODES, INCLUDING BUT NOT
LIMITED TO THE INTERNATIONAL BUILDING CODE, INTERNATIONAL MECHANICAL CODE, AND
INTERNATIONAL PLUMBING CODE.
9 LOCATE EQUIPMENT REQUIRING ACCESS 2'-0" MAXIMUM ABOVE CEILING.
10 COORDINATE INSTALLATION OF DUCTWORK, PIPING AND MECHANICAL EQUIPMENT WITH NEC
CLEARANCES INCLUDING THE SPACE ABOVE ELECTRICAL PANELS, TRANSFORMERS AND OTHER
ELECTRICAL EQUIPMENT. NO PIPING OR DUCTWORK TO RUN OVER ELECTRICAL PANELS, VFD'S OR MCC'S. PROTECT EQUIPMENT WITH A 42" DEEP ZONE IN FRONT OF PANELS, VFD'S AND MCC'S.
PROVIDE PANS IF REQUIRED UNDER PIPING.
11 PROVIDE SLEEVES AND/OR OPENINGS TO RUN PIPES AND DUCTS THROUGH FOUNDATIONS,
FLOORS, WALLS, AND ROOF.
12 TRANSITION PIPING AND DUCTWORK SIZES TO MATCH THE SIZE OF EQUIPMENT CONNECTION.
13 ALL PIPE AND DUCT SIZES SHOWN SHALL BE CONTINUED IN THE DIRECTION OF FLOW UNTIL
ANOTHER SIZE IS SHOWN.
14 FOR DETAILS, EQUIPMENT CONNECTIONS, AND PIPE SIZES NOT SHOWN ON THE SEGMENTS, REFER
TO DETAILS, SCHEDULES, AND SPECIFICATIONS.
15 INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE RESPECTIVE MANUFACTURER'S WRITTEN
INSTALLATION INSTRUCTIONS, AT A LEVEL OF WORKMANSHIP CONSISTENT WITH THE
SPECIFICATIONS.
16 MECHANICAL CONTRACTOR SHALL ENSURE THAT ALL EQUIPMENT IS PROVIDED AND INSTALLED
WITH CLEARANCES PER MANUFACTURERS RECOMMENDATIONS. THE CONTRACTOR SHALL
MAINTAIN PROPER SERVICE SPACE FOR COIL PULLS, BAS DEVICES, MAINTENANCE ACCESS, ETC.
17 INSTALL EXPOSED PIPING AND DUCTWORK AS HIGH AS PRACTICAL IN ROOMS WITHOUT CEILINGS.
18 LOCATIONS OF PIPING, DUCTWORK AND EQUIPMENT, AS INDICATED ON THE DRAWING, ARE
APPROXIMATE AND SUBJECT TO MINOR ADJUSTMENTS IN THE FIELD, INCLUDING, BUT NOT LIMITED
TO, OFFSETS AND TRANSITIONS. NEW DUCTWORK, PIPING AND EQUIPMENT SHALL BE
COORDINATED WITH STRUCTURE, LIGHTS, REFLECTED CEILING PLANS, CABLE TRAY, ELECTRICAL CONDUIT, PLUMBING, MECHANICAL AND FIRE PROTECTION PIPING, MEDICAL GASES, ALL OTHER
TRADES AND ALL OTHER EXISTING CONDITIONS TO AVOID INTERFERENCE IN THE FIELD..
19 THE CONTRACTOR SHALL INFORM THE DESIGNER OF ANY PROPOSED DEVIATIONS FROM THE
CONTRACT DOCUMENTS.
20 IF CONTRACTOR ENCOUNTERS MATERIAL WHICH MAY CONTAIN ASBESTOS, IMMEDIATELY STOP
WORK IN THIS AREA AND NOTIFY THE OWNER.
21 DETAILS REFERENCE ALL SHEETS.
22 INSTALL ALL PIPING AND DUCTWORK WITHOUT FORCING OR SPRINGING.
23 LOCATE VALVING, ACCESSORIES, AND EQUIPMENT IN ACCESSIBLE LOCATIONS. WHERE LOCATED ABOVE HARD CEILING PROVIDE AN ACCESS DOOR IN CEILING. MINIMUM ACCESS DOOR SIZE OF 24"
X 24". COORDINATE EXACT LOCATION AND STYLE WITH ARCHITECT. EQUIPMENT SHALL BE
LOCATED IN THE CEILING CAVITY SO IT CAN BE SAFELY SERVICED FROM SOMEONE STANDING ON A
LADDER PLACED BELOW THE CEILING ACCESS.
24 WHERE VALVING, ACCESSORIES, OR EQUIPMENT IS LOCATED IN A WALL, PROVIDE AN
APPROPRIATELY SIZED ACCESS DOOR. COORDINATE ACCESS DOOR SIZE, LOCATION, AND STYLE
WITH ARCHITECT.
25 CONTRACTOR TO PROVIDE VALVE IDENTIFICATION AND LOCATION ON ALL CEILING TILES WHERE
VALVES ARE LOCATED.
L I C
E N
S E
D
PROFESS IONA
L
E N
G I N
E E
R
No. 4775391-2202
S
T A
T E OF U
T
A H
SPENCER W.
HOWELL
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T I
S I
N C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
02/19/2026
/1
/2
:3
:5
A
M A u to d e s k D o c s /2
J
S D
R iv e rt o n
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
/2
J S
D R iv e rt o n H
S F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250866
SK
MJ
MECHANICAL
SYMBOLS,
LEGENDS AND
ABBREVIATIONS
M001
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
R
IV
E R
T O
N H
IG
H
S C
H O
O L
W
R iv e rt o n
U T
F O
O T
B A
L L F
IE
L
D L
IG
H
T
IN
G /S
O U
N D
U P
G R
A D
E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
REVISIONS
Title Sheet Revision
1 1
X X X X X X X X X X X X
X
X X X X X X X X X X X X
SSI-1 SSI-22
2 4
T T
36 6
SSO-1 SSO-2
OUTDOOR
CONDENSING
UNIT
RL
RS
R L
R S
INDOOR UNIT
FACTORY ROOF STAND
PROVIDE CURB
FOR PIPE
ROUTING, SEAL
WATER TIGHT.
LOCATE UNIT MINIMUM 3-
INCHES BELOW CEILING
CEILING
PRESS BOX SPLIT SYSTEM SCHEDULE
ID MANUFACTURER
NOMINAL NOMINAL
INDOOR UNIT OUTDOOR UNIT REFRIGERANT
NOTES
COOLING HEATING
CAPACITY CAPACITY @ 47°F CFM DIMENSIONS AMPS DIMENSIONS WEIGHT AMPS
(BTU/H) (BTU/H) MODEL NUMBER RANGE W" x D" x H" (MCA) VOLTS/PH/HZ. MODEL NUMBER W" x H" x D" (LBS.) (MCA) MOCP VOLTS/PH/HZ. TYPE LIQUID GAS
SSI-1 / SSO-1 MITSUBISHI 18,000 22,000 PKA-AK18NL 320-425 36 X 12 X 10 1.0 208/1/60 PUZ-AH18NL 32 X 25 X 12 100 11 28 208/1/60 R454B 1/4 1/2 1-10
SSI-2 / SSO-2 MITSUBISHI 18,000 22,000 PKA-AK18NL 320-425 36 X 12 X 10 1.0 208/1/60 PUZ-AH18NL 32 X 25 X 12 100 11 28 208/1/60 R454B 1/4 1/2 1-10
1. CONDENSING UNIT TO BE SIZE MATCHED TO INDOOR UNIT AND TO BE BY SAME MANUFACTURER AS INDOOR UNIT.
2. PROVIDE FACTORY MOUNTED STAND FOR CONDENSING UNIT.
3. PROVIDE FACTORY WIND BAFFLE AND LOW AMBIENT HEAD CONTROLLER TO ALLOW COOLING OPERATION DOWN TO 0 DEG. F. D.B.
4. WIRELESS REMOTE CONTROLLER. PROVIDE WALL MOUNTED HOLDER.
5. PROVIDE ACCESSORY CONDENSATE PUMP FOR INDOOR UNIT.
6. INDOOR UNIT IS TO BE POWERED FROM OUTDOOR UNIT.
7. PROVIDE WITH DISCONNECT AT OUTDOOR UNIT.
8. PROVIDE WITH BACNET INTERFACE.
9. PROVIDE WITH HAIL GUARDS.
10. PROVIDE LINE-HIDE LINE SET COVER SYSTEM.
L I C
E N
S E
D
PROFESS IONA
L
E N
G I N
E E
R
No. 4775391-2202
S
T A
T E OF U
T
A H
SPENCER W.
HOWELL
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T I
S I
N C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
02/19/2026
/1
/2
:3
:5
A
M A u to d e s k D o c s /2
J
S D
R iv e rt o n
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
/2
J S
D R iv e rt o n H
S F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250866
SK
MJ
MECHANICAL
PLANS
M101
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
R
IV
E R
T O
N H
IG
H
S C
H O
O L
W
R iv e rt o n
U T
F O
O T
B A
L L F
IE
L
D L
IG
H
T
IN
G /S
O U
N D
U P
G R
A D
E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
1/2" = 1'-0"
PRESS BOX MECHANICAL DEMOLITION PLAN
1/2" = 1'-0"
PRESS BOX MECHANICAL PLAN
1/2" = 1'-0"
PRESS BOX MECHANICAL ROOF PLAN
KEYNOTES
1 REMOVE CEILING HEATER AND ALL ASSOCIATED CONTROLS.
2 COORDINATE FINAL UNIT LOCATION AND ELEVATION WITH SITE CONDITIONS.
3 ROUTE CONDENSATE TO FLOOR AND PENETRATE FLOOR TO EXTERIOR, ROUTE DOWN COLUMN
BELOW BLEACHERS AND TERMINATE WITH INSECT SCREEN MINIMUM 12" ABOVE FINISHED GRADE.
COORDINATE PIPE ROUTING WITH SITE CONDITIONS.
4 ROUTE REFRIGERANT PIPING TO/FROM THE REAR OF THE INDOOR UNIT. COORDINATE WITH SITE
CONDITIONS.
5 LOCATE REMOTE CONTROL 48"-60" ABOVE FINISHED FLOOR, COORDINATE EXACT PLACEMENT
WITH OWNER.
6 PROVIDE HEAT TRACE ON EXTERIOR CONDENSATE PIPING PROVIDE CHROMALOX SRF HEATING
CABLE OR EQUIVALENT. FIELD VERIFY LENGTHS AND COORDINATE WITH ELECTRICAL.
0 2' 4'1'
0 2' 4'1'
0 2' 4'1'
NOT TO SCALEM101
4 WALL MOUNTED DUCTLESS SPLIT SYSTEM DETAIL
CR
D
EV EV
DO
M
TV
J
P#
FB PT
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X
X W
A P
W A
P X
X
N
J
P#
VFD
F
TC
D##
XX
POWER SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
S
WALL MOUNTED RECEPTACLE
SWITCHED RECEPTACLE
EMERGENCY RECEPTACLE
GROUND FAULT RECEPTACLE
RECEPTACLE MODIFIERS:
##": HEIGHT AFF OC
WP: WEATHERPROOF IN-USE
COVER
T: TAMPER-PROOF
U: RECEPTACLE WITH USB OUTLET
G: GROUND FAULT
18"
18"
D Q SP
18"
18"
RECEPTACLE (SPECIFIC HEIGHT)
ISOLATED GROUND RECEPTACLE
7,26, SP W/CAP
GENERAL NOTE
B
18"
SWITCH MODIFIERS:
K: KEYED
T: TIMER
M: MANUAL STARTER THERMAL
OVERLOAD SWITCH
EMERGENCY POWER OFF PUSH BUTTON
DOOR OPENER PUSH PLATE
ELECTRICAL POWER METER
FUSED DISCONNECT SWITCH
TOMBSTONE RECEPTACLE*
CORD REEL, DEVICE VARIES
CORD DROP, DEVICE VARIES
MULTI-OUTLET ASSEMBLY
FILLED SQUARES INDICATE 120V OUTLET
OPEN SQUARES INDICATE WITH USB
SINGLE / DUAL PORT ELECTRICAL VEHICLE
CHARGER
POWER POLE
NON-FUSED DISCONNECT SWITCH
MAGNETIC STARTER
MAGNETIC STARTER WITH FUSED DISCONNECT
POWER RELAY
PUSHBUTTON
VARIABLE FREQUENCY DRIVE
SURGE PROTECTION DEVICE
TRANSFORMER:
SEE SINGLE-LINE DIAGRAM FOR DESCRIPTION &
REQUIREMENTS.
TX
7, 25
GENERAL LEGEND
SYMBOL DESCRIPTION NOTES
SOLID ARCHED LINES INDICATE UNSWITCHED
POWER CIRCUITING
DASHED ARCHED LINES INDICATE SWITCHED
POWER CIRCUITING
ONE CIRCUIT, HOME RUN TO PANEL
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
4" CONCRETE
BASE
MAIN DISTRIBUTION PANEL 6'-6" TO TOP 8
FLUSH PANELBOARD 6'-6" TO TOP 8
SURFACE PANELBOARD 6'-6" TO TOP 8
TWO CIRCUITS, HOME RUN TO PANEL -
THREE CIRCUITS, HOME RUN TO PANEL -
CONDUIT RUN CONCEALED IN FLOOR OR GROUND -
CONDUIT RUN CONCEALED IN WALL OR CEILING -
CONDUIT UP -
CONDUIT DOWN -
CONDUIT STUB LOCATION CAP CONDUIT
CONDUIT / CIRCUIT CONTINUATION -
GROUND BUS BAR
CABLE TRAY
SOLID BOTTOM
LADDER
BASKET
MOUNTING
AS NOTED
8+18"
EQUIPMENT CEILING RACK
EQUIPMENT CABINET/RACK
EQUIPMENT 2-POST CABINET/RACK
TELEPHONE DEMARCATION BOARD +18" 25
AS NOTED 18, 25
SEE SPEC.
AS NOTED 18, 25
SEE SPEC.
CEILING
EXISTING --
DEMO --
TEMPORARY --
NEW --
CONDUIT
OHP: OVERHEAD POWER SERVICE
UGP: UNDERGROUND POWER
SERVICE
UGF: UNDERGROUND FIBER
SERVICE
TEL: TELEPHONE SERVICE
POWER DISTRIBUTION EQUIPMENT SYMBOLS
CONTROLLED RECEPTACLE 7+18" OR AS
NOTED
SPD PROTECTED RECEPTACLE 7+18" OR AS
NOTED
TIME CLOCK +60" -
NOT IN CONTRACT --
MAGNETIC STARTER WITH BREAKER DISCONNECT
MOTOR
CEILING MOUNTED RECEPTACLE CEILING
TV BACKBOX FLAT PANEL
HEIGHT +12"
NOTES:
1. HATCHED FILL INDICATES DISTRIBUTION PANEL OR
SWITCHBOARD.
2. SOLID FILL INDICATES BRANCH PANEL OR LOAD CENTER.
3. DASHED BOX INDICATES CODE-REQUIRED CLEARANCE
(WIDTH & DEPTH).
4. DOOR INDICATES FRONT OF RECESSED PANEL.
H P
1A
LP
1A
M D
P
SB1
POWER TAGS LEGEND
JUNCTION BOX
x
JUNCTION BOX
D1 (DEFAULT)
M1/2 = D1 M3/4 =D2
CONDUIT CABLE TYPE CONDUIT SIZING GUIDE
(1) 3/4" C.
(1) 1" C.
(1) 1" C.
(1) MA/LA
(1) S##
(2) S##
MA / LA TYPE CABLE
(18) CABLES PER 3/4" C.
(23) CABLES PER 1" C.
(77) CABLES PER 1-1/2" C.
S## TYPE CABLE
(3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
CABLE GROUP
D2 (DEFAULT)
MD = D1
MT = D1
(1) 1" C. (1) UTP (8) CABLES PER 1" C.
(20) CABLES PER 1-1/2" C.
D1
D2
(1) 1" C. (1) UTP 5
ROUGH-IN PER
BACK BOX SCH.
SCH AS NOTED
(1) MA
(2) UTP
(1) MA
AS NOTED
D1 (DEFAULT) (1) 1-1/2" C. (1) VGA + (2) LA
(1) HD + (2) LA
(1) VGA + (1) HD
+ (2) LA
VGA (1-4) CABLES PER 1-1/2" C.
HD (1-3) CABLES PER 2" C.
D3
D3
D1
D2
D1
D1
D2
D1
(1) 1" C.
(1) STP
(1) UTP
(1) UTP
(1) STP
(1) STP
(1) STP
(1) STP
(1) STP
(1) STP
IN MILLWORK,
UNDER FURNITURE,
OR AS NOTED
D1 (DEFAULT) (1) 1" C.
(#) UTP
(#) STP
D2 (DEFAULT) (1) 1-1/2" C. (2) UTP + (2) LA
+ (2) S16
AS NOTED5
D1 (DEFAULT) (1) 3/4" C. AS NOTED
AS NOTED5
D1
D4
(1) 1" C.
(2) LA
(2) LA
(18) CABLES PER 3/4" C.
(23) CABLES PER 1" C.
(77) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1" C. AS NOTED (7) CABLES PER 1" C.
(12) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1" C. (1) CT OR
(1) BUS
(7) CABLES PER 1" C.
(12) CABLES PER 1-1/4" C.
D2 (DEFAULT)
D1
NO BACK BOX
PER SCH
PER SCH
(1) 1" C.
(1) S##
(2) S##
(1) UTP
(1) UTP/BUS
5 (DEFAULT)
NA AS NOTED
PER SCH (1) 1" C. (1) S##
PER SIGNAL
FLOW
TV BACK BOX (2) 1-1/2" C. AS NOTED AS NOTED
(2) A1 (DEFAULT)
(1) FOR POWER
(1) 1" C. (1) UTP
(1) CT
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1" C. AS NOTED AS NOTED5
AS NOTED
PER SCH
D1
AS NOTED IN
SCH
(1) 3/4" 5
D1 (DEFAULT) (1) 1" C. (1) UTP 5
D1 OR D2 (1) 1-1/2" C. AS NOTED AS NOTEDAS NOTED
(6) CABLES PER 1" C.
(16) CABLES PER 1-1/2" C.
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
(1) 1" C. (1) STP
(1) UTP
(1) UTP
(1) STP
(1) STP
(1) STP
(1) STP
(1) STP
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
S## TYPE CABLE
(3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
UTP TYPE CABLE
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
(1) 1-1/2" C. AS NOTED
(3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
AS NOTEDAS NOTED
(4) CABLES PER 1" C.
(9) CABLES PER 1-1/2" C.
D1 (DEFAULT) (1) 1-1/2" C. (1) UTP
(1) STP
AS NOTED5
B1 (DEFAULT) (1) 1" C. (1) S##
PER SIGNAL
FLOW
4 (3-10) CABLES PER 1" C.
(7-18) CABLES PER 1-1/2" C.
S: SIMPLEX D: DUPLEX
Q: FOURPLEX SP: SPECIAL PURPOSE
FLOOR BOX / POKE-THRU
- SEE SCHEDULE FOR TYPE INFORMATION
AS NOTED
AUDIOVISUAL SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
ANALOG AUDIO WALL PLATE
M#: MICROPHONE XLR-F, #
INDICATES QTY M1/M2 = D1 J-BOX,
M3/M4 = D2 J-BOX
AX: AUXILIARY INPUT, 3.5MM/RCA
CONNECTION, WALL PLATE
T: XLR MALE CONNECTION
TS: 1/4 TS CONNECTION
NL1: SPEAKER LEVEL SPEAKON
OUTPUT 1 CONNECTION,
CABLE PER SIGNAL FLOW
NL2: SPEAKER LEVEL, SPEAKON
OUTPUT 2 CONNECTION,
CABLE PER SIGNAL FLOW
MOUNTING COMMENTS
W F C W: WALL F: FLOOR BOX C: CEILING
RECEPTACLE
HEIGHT /
FLOOR BOX
OR AS
NOTED
DIGITAL AUDIO WALL PLATE
MD: DUAL MICROPHONE XLR-F/1/4"
INPUT AUDIO TRANSCEIVER
MT: DUAL MICROPHONE XLR-F INPUT
AUDIO TRANSCEIVER
M2D: MICROPHONE (2) XLR-F INPUT
& (2) XLR-M OUTPUT UTP AUDIO
TRANSCEIVER
M4D: MICROPHONE (4) XLR-F INPUT
UTP AUDIO TRANSCEIVER
MXT: DUAL MICROPHONE XLR-F &
AUXILIARY 3.5 INPUT WITH 3.5MM
OUTPUT UTP AUDIO TRANSCEIVER
7, 25
SWITCH
HEIGHT OR
AS NOTED
DIGITAL BLUETOOTH WALL PLATE
BT: BLUETOOTH AUDIO RECEIVER
BXT: BLUETOOTH & AUXILIARY
3.5MM INPUT/OUTPUT AUDIO
TRANSCEIVER
7, 25
SWITCH
HEIGHT /
CEILING
OR AS NOTED
MICROPHONE DEVICES
MB: TABLE TOP BOUNDARY
MICROPHONE
MC#: MICROPHONE CEILING ARRAY
# = IDENTIFIES TYPE
MW: WALL MOUNTED MICROPHONE
7, 25
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
PASSIVE VIDEO WALL PLATE
VG: RGBHV VIDEO VGA INPUT W/
3.5MM AUDIO
HD: HIGH DEFINITION HDMI INPUT
HV: HIGH DEFINITION HDMI INPUT
& RGBHV VIDEO VGA INPUT
W/3.5MM AUDIO
ACTIVE VIDEO TRANSCEIVER, TRANSMITTER, OR
RECEIVER WALL PLATE
EN#: AVoIP NETWORK ENCODER
DC#: AVoIP NETWORK DECODER
TxH: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI INPUT
TxD: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI & RGBHV
VGA INPUT W/3.5MM AUDIO
RxH: HDBaseT RECEIVER, HIGH
DEFINITION HDMI OUTPUT
US#: USB EXTENSION INPUT/
OUTPUT # = IDENTIFIES TYPE
CHD: HDBaseT TRANSMITTER, DUAL
HIGH DEFINITION HDMI INPUT
HDU: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI INPUT W/3.5MM
AUDIO & USB INPUT/OUTPUT
7, 25
ACTIVE VIDEO TRANSCEIVER, TRANSMITTER, OR
RECEIVER SURFACE MOUNTED DEVICE
EN#: AVoIP NETWORK ENCODER
DC#: AVoIP NETWORK DECODER
Tx: HDBaseT TRANSMITTER, HIGH
HDMI INPUT
Rx: HDBaseT RECEIVER, HIGH
DEFINITION HDMI OUTPUT
TxM: HDBaseT TRANSMITTER
MULTIPLE INPUT SWITCHER,
OR AS NOTED.
US#: USB EXTENSION INPUT/
OUTPUT # = IDENTIFIES TYPE
HDU: HDBaseT TRANSMITTER, HIGH
DEFINITION HDMI INPUT W/3.5M
AUDIO & USB INPUT/OUTPUT
7, 25
CATEGORY CONNECTION, WALL PLATE
AV#: 8P8C FEMALE CONNECTOR
# INDICATES QTY
TxT: SHIELDED 8P8C FEMALE
CONNECTOR REFER TO SIGNAL
FLOW FOR CONNECTION QTY
SUBSCRIPT INDICATES POINT TO
POINT CONNECTION. REFER TO
SIGNAL FLOW
7, 25
AS NOTEDCLASSROOM SOUND AMPLIFICATION/AMPLIFIER
CSA: CLASSROOM SOUND AMP
7, 5
SWITCH
HEIGHT OR
AS NOTED
2-WAY INTERCOMMUNICATION STATION WITH 1/2
BUTTON
CAL: CALL SWITCH
7, 24
SWITCH
HEIGHT OR
AS NOTED
PERFORMANCE VENUE WALL PLATE
CI: CREWCOM HEADSET INPUT, 4-XLR-F
CIS: CREWCOM TALK BACK WALL
STATION
+108" OR
AS NOTED
ANTENNA EMITTER / RECEIVER
ALS: ASSISTIVE LISTENING SYSTEM
RF ANTENNA OR IR EMITTER
AT: WIRELESS MICROPHONE
RECEIVING ANTENNA
+96" / CEILING
OR AS NOTED
INFRARED PARTITION SENSOR
IR: PARTITION SENSOR
7, 25
SWITCH
HEIGHT OR
AS NOTED
USER INTERFACE DEVICE
V: VOLUME CONTROL, STEREO
OR MONO
SV: COLUMN CONTROL WITH
SOURCE SELECTOR
TP#: TOUCH PANEL
TT#: TABLE TOP TOUCH PANEL
RS#: ROOM SCHEDULING TOUCH
PANEL OR SIGN
KP#: KEYPAD, REFER TO SCH FOR
ROUGH-IN, # IDENTIFIES TYPE
7, 25
7, 23, 25
7, 23, 25
7, 23, 25
7, 24
FURNITURE /
MILLWORK
TABLE / FURNITURE BOX
TB#: TABLE BOX, # IDENTIFIES TYPE
AS NOTED
LOUDSPEAKER
REFER TO LEGEND & SCH FOR TYPE,
FLOOR BOX LOUDSPEAKER IS IN-GROUND /
LANDSCAPE LOUDSPEAKER
AS NOTEDFLAT PANEL DISPLAY
D##: DISPLAY TYPE, # IDENTIFIES TYPE
AS NOTEDPROJECTOR SCREEN
SC#: PROJECTOR SCREEN, # IDENTIFIES
TYPE
UNDER FLAT
PANEL
SOUND BAR
SB#: SOUND BAR, # IDENTIFIES TYPE
19, 23
VIDEO PROJECTOR,
P#: PROJECTOR, # IDENTIFIES TYPE
AS NOTED /
SWITCH
HEIGHT
CUSTOM JUNCTION BOX, REFER TO BACK BOX SCH,
C##: CUSTOM BACK BOX, #
IDENTIFIES TYPE
SSW: PROJECTOR SCREEN
CONTROLLER
+36" OR AS
NOTED
AV CONFERENCING / BROADCAST CAMERA 19
AS NOTEDGROMMET PASS THROUGH PLATE
GP#: # IDENTIFIES QTY OF GANGS
AS NOTED 7
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
RECEPTACLE
HEIGHT /
FLOOR BOX /
CEILING
OR AS NOTED
DATA NETWORK SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
DATA OUTLET (SINGLE CABLE) 18" WALL/
FLOOR/CEILING
DATA OUTLET (TWO CABLES) 18" WALL/
FLOOR/CEILING
DATA OUTLET (THREE CABLES) 18" WALL/
FLOOR/CEILING
SERIES-X COAXIAL CABLE OUTLET
DISTRIBUTED ANTENNA SYSTEM (DAS)
PUBLIC SAFETY AND/OR
CELLULAR/COMMERCIAL
ANT: ANTENNA
BDA: BI-DIRECTIONAL AMPLIFIER
SPL: SPLITTER
VIA: VIA
108" WALL,
CEILING,
ABOVE
CEILING, OR AS
NOTED
WIRELESS ACCESS POINT* 96" WALL/
CEILING
W F C W: WALL F: FLOOR C: CEILING
NURSE CALL SYMBOLS LEGEND
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
NURSE CALL CONTROLLER
GI: GRAPHICAL INTERFACE
ROOM STATION
RCB: ROOM CONTROL BOARD
MS: MASTER STATION
+46" WALL OR
AS NOTED
NURSE CALL CORRIDOR LIGHT
NUMBER OF LIGHTS AS INDICATED
NURSE CALL DEVICE
B: CODE BLUE
D: DUTY STATION
E: EMERGENCY
P: PATIENT CALL
PL: PULL STATION
S: STAFF
NURSE CALL CONTROL UNIT
NCAP: NURSE CALL ANNUNCIATION PANEL
NCHS: NURSE CALL HOST CONTROLLER
NCPS: NURSE CALL POWER SUPPLY
NCTC: NURSE CALL TERMINAL CABINET
NCUPS: NURSE CALL UNINTERRUPTIBLE
POWER SUPPLY
CEILING
+46" WALL OR
AS NOTED
+46" WALL OR
AS NOTED
GROUND ROD
GROUND ROD WITH TEST WELL
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION CONDUCTOR SPLICE
STATIC GROUND RECEPTACLE
GROUNDING AND LIGHTNING PROTECTION SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTED -
AS NOTEDLOUDSPEAKER
REFER TO LEGEND & SCH FOR TYPE
7 (CLG)
18" WALL/
FLOOR/CEILING
EQUIPMENT SYSTEM PANELS
ACS: ACCESS CONTROL PANEL
IDS: INTRUSION DETECTION PANEL
PSP: POWER SUPPLY PANEL
RP#: LIGHTING PANEL
DAS: DISTRIBUTED ANTENNA SYSTEM
ERCCS: FIRST RESPONDERS RADIO SYSTEM
CATV: CABLE TV CONTENT EQUIPMENT
7, 13
CEILING
CEILING
+46" 7, REFER TO
SPEC
+46" 7
+46" 7
8, 9
8, 9, 10, 11
8, 9, 10, 11
8, 9, 10, 11
+72"
+60"
+60"
+60"
+60"
AS NOTED
+46"
18, 25
SEE SPEC.
7, 22
7, 25
7, 25
7, 25
7, 25
7, 25
EXIT SIGNAGE
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
WALL-MOUNTED FIXTURES, TYPICAL
(VARIOUS SYMBOLS)
LINEAR, CEILING MOUNTED LIGHT FIXTURE
(VARIOUS DIMENSIONS, DOTS INDICATE PENDANT
MOUNT)
RECESSED DOWNLIGHT FIXTURE
CHEVRON INDICATES WALL WASH
DIRECTIONAL LIGHT, TRACK OR FLOOD LIGHT
LINEAR LIGHT, TAPE LIGHT
LIGHTING FIXTURE SYMBOLS LEGEND
NOTE:
1. SWITCH IDS ARE UNIQUE PER SPACE.
2. A SWITCH WITHOUT A TAGGED ID CONTROLS ALL LIGHTING FIXTURES WITHIN A SPACE.
3. ID TAGS MAY BE USED ON CONTROL DEVICES OTHER THAN SWITCHES, SUCH AS OCCUPANCY
SENSORS OR CONTACTORS.
4. ABSENCE OF A SWITCH DESIGNATION ON A LIGHTING FIXTURE INDICATES FIXTURE IS
CONTROLLED BY THE ONLY SWITCH IN THE SPACE.
5. AN "x" IN PLACE OF THE SWITCH DESIGNATION INDICATES UNSWITCHED.
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
CEILING
CEILING
AS NOTED
AS NOTED
WALL/CEILING
WALL/CEILING
1, 2
1, 2
1, 3, 5, 12
1, 3, 5, 12
EMERGENCY EGRESS LIGHT FIXTURE CEILING 1, 2, 4
CRITICAL EGRESS LIGHT FIXTURE CEILING 1, 2, 4
CIRCULAR, CEILING MOUNTED LIGHT FIXTURE
CENTER DOT INDICATES PENDANT
CEILING 1, 2, 4
EMERGENCY LIGHTING UNIT, INTEGRAL BATTERY WALL/CEILING 1
CW W: WALL C: CEILING
LIGHTING TAGS LEGEND
EXIT SIGNAGE WITH AUXILIARY HEAD
SHADING & ARROWS INDICATE FACES &
DIRECTIONAL CHEVRONS
AS NOTED
AREA LIGHT POLE & FIXTURE
POST-TOP LIGHT POLE & FIXTURE
BOLLARD LIGHT
ARROWS INDICATE DIRECTION
SWITCH
SWITCH MODIFIERS:
3: 3-WAY
4: 4-WAY
K: KEYED
D: DIMMING
T: TIMER
P: SWITCH W/ PILOT LIGHT
CONCRETE
BASE
CONCRETE
BASE
CONCRETE
BASE
LIGHTING CONTROL SYMBOLS
SYMBOL DEVICE/FIXTURE DESCRIPTION MOUNTING NOTES
46"
1, 14
REFER TO DIA
1, 14
REFER TO DIA
1, 14
REFER TO DIA
6, 7
STEP LIGHT FIXTURE AS NOTED 1
IN-GRADE LIGHT FIXTURE AS NOTED 1
MOMENTARY CONTACT SWITCH 46" 6, 7
LOW VOLTAGE WALL STATION
(SUBSCRIPT INDICATES CONFIGURATION)
46" 6, 7
CEILING FAN CEILING -
LIGHTING CONTACTOR
LIGHTING CONTROL TOUCH SCREEN
WALL
46"
SENSORS/SWITCHES:
PC: PHOTO-ELECTRIC CONTROL
OS: OCCUPANCY SENSOR SWITCH
DL: DAYLIGHT HARVESTING SENSOR
AS NOTED 6, 7, 28
6,7
SWITCH PACKS:
AP: AUXILIARY PACK
PP: POWER PACK
ABOVE
CEILING
6, 28
CONTROL:
RC: DIGITAL ROOM CONTROLLER
(SUBSCRIPT = NUMBER OF RELAYS)
EP: EMERGENCY LIGHTING CONTROL
UNIT
ABOVE
CEILING
REFER TO DIA
AND SPEC
CW W: WALL C: CEILING
FIXTURE ID (UPPERCASE UNDERLINED LETTER)
PANEL ID (NUMBERS & UPPERCASE LETTERS) - CIRCUIT NUMBER
RELAY ID (UPPERCASE LETTERS)
FIXTURE CONTROL ZONE ID (LOWERCASE LETTER)
#: INDICATES SWITCH TYPE
LOWERCASE LETTER: INDICATES SWITCH ID
Project #: 250866
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
A H
TE OF
S
TA
P
L EN
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
S A
L T
L A
K E
T .G
E O
R G
E
02/19/26
CONSTRUCTION DOCUMENTS
/1
/2
:3 :4
P
M A u to d e s k D o c s /2
J
S D
R iv e rt o n
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
/2
J S
D R iv e rt o n H
S F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250866
BR
RESOLUT
SYMBOLS,
SCHEDULES,
NOTES AND
DIAGRAMS
E1.1
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
R
IV
E R
T O
N H
IG
H
S C
H O
O L
W
R iv e rt o n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
GENERAL NOTES
1. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL LIGHTING FIXTURES.
2. VERIFY ALL EQUIPMENT DIMENSIONS AND LOCATIONS BEFORE BEGINNING ROUGH IN. CONSULT ALL APPLICABLE CONTRACT DRAWINGS AND SHOP DRAWINGS TO INSURE NEC CODE CLEARANCES REQUIRED
AROUND ALL ELECTRICAL EQUIPMENT.
3. CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC) OF ALL EQUIPMENT FURNISHED UNDER ALL DIVISIONS, INCLUDING ALL EXISTING EQUIPMENT TO BE RE-USED.
REVIEW ALL SHOP DRAWINGS AND EXISTING EQUIPMENT BEFORE BEGINNING ROUGH-IN.
4. SEE SECTION 265100 (16510) OF THE SPECIFICATION FOR REQUIRED COORDINATION MEETINGS WITH
MECHANICAL AND CEILING CONTRACTORS.
5. SEE APPLICABLE SHOP DRAWINGS FOR ROUGH IN LOCATION OF ALL EQUIPMENT, WIRING DEVICES, ETC.
WHERE APPLICABLE MOUNT ALL WIRING DEVICES ABOVE BACK SPLASH EXCEPT THOSE SERVING UNDER
COUNTER EQUIPMENT.
6. SEE SPECIFICATION FOR ENERGY SAVING LAMP AND BALLAST REQUIREMENTS.
7. FINISHES OF ALL LIGHT FIXTURES SHALL BE AS SELECTED BY ARCHITECT.
8. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COOPERATE WITH THE MECHANICAL CONTRACTOR SUCH THAT NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE OPERATION OF THE ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE INSTALLED IN, ENTER OR PASS THRU ELECTRICAL ROOMS OR SPACES, OR ABOVE OR
BELOW ELECTRICAL EQUIPMENT IN OTHER AREAS.
9. ELECTRICAL BOXES SHALL NOT BE LOCATED IN MASONRY COLUMNS IN BRICK WALLS OR IN GROUTED CELLS
ADJACENT TO OPENINGS. COORDINATE LOCATION OF BOXES WITH MASONRY CONTRACTOR.
10. ALL PENETRATIONS OF FIRE RATED FLOORS, WALLS, AND CEILINGS SHALL BE SEALED WITH APPROVED
MATERIAL TO MAINTAIN FIRE RATING OF SURFACE PENETRATED.
11. CONTRACTOR SHALL VERIFY FURNITURE LAYOUT PRIOR TO ANY FLOORBOX OR POKE-THRU INSTALLATION.
COORDINATE EXACT LOCATION OF FLOOR BOX OR POKE-THRU WITH OWNER AND FURNITURE PROVIDER PRIOR
TO ROUGH-IN.
12. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS SHALL BE RUN WITH
CONDUCTORS PER TABLE BELOW.
A. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
B. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO KEEP
BRANCH CIRCUIT VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
C. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT STAYS
WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF NECESSARY,CONTRACTOR SHALL
INCREASE WIRE AND CONDUIT SIZE TO MEET THE STANDARD AT NO ADDITIONAL COST TO
OWNER.
MAXIMUM LENGTH
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
ABBREV. DESCRIPTION ABBREV. DESCRIPTION
ABBREVIATIONS INDEX
# NUMBER
AC ALTERNATING CURRENT
A.F.F. ABOVE FINISH FLOOR
AIC AMPS INTERRUPTING CAPACITY
AM AMPS METER
AMP AMPERE
ANN ANNUNCIATOR
ATS AUTOMATIC TRANSFER SWITCH
AUX AUXILIARY
AWG AMERICAN WIRE GAUGE
BC BARE COPPER
BFG BELOW FINISH GRADE
C CONDUIT
CAB CABINET
CATB COMMUNITY ANTENNA TELEVISION
CATV CABLE TELEVISION
CKT CIRCUIT
CLG CEILING
CNTR CONTRACTOR
C.O. CONDUIT ONLY
CRT COMPUTER TERMINAL
CT CURRENT TRANSFORMER
CU COPPER
C/W COMPLETE WITH
DB DECIBEL
DC DIRECT CURRENT
DWG DRAWING
(E) EXISTING
EC EMPTY CONDUIT
EG EMERGENCY GENERATOR
EMT ELECTRICAL METALLIC TUBING
EX EXPLOSION PROOF
FACP FIRE ALARM CONTROL PANEL
FC FOOT CANDLE
FT FOOT
GFI GROUND FAULT INTERRUPTER
GND GROUND
GRC GALVANIZED RIGID CONDUIT
HP HORSE POWER
HZ HERTZ
IG ISOLATED GROUND
IMC INTERMEDIATE METALLIC CONDUIT
IN INCH
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT AMPERES
KVAR KILOVARS
KW KILOWATT
LRA LOCKED ROTOR AMPS
LTG LIGHTING
MNF MANUFACTURER
MAX MAXIMUM
MB MAIN BUS
MCC MOTOR CONTROL CENTER
MCM 1000 CIRCULAR MILLS
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MTG MOUNTING
MTR MOTOR
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECT. MANUFAC. ASSOC.
IFC INTERNATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION ASSOC.
N.I.C. NOT IN CONTRACT
NO NORMALLY OPENED
NTS NOT TO SCALE
OS & Y OUTSIDE SCREW & YOKE
PB PUSHBUTTON
PF POWER FACTOR
PFR PHASE FAILURE RELAY
PNL PANEL
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE CONDUIT
(R) RELOCATE
RECEP RECEPTACLE
REQ REQUIREMENT
RLA RATED LOAD AMPS
RMS ROOT MEAN SQUARE
SE SERVICE ENTRANCE
SPEC SPECIFICATIONS
SPKR SPEAKER
SS SELECTOR SWITCH
SW SWITCH
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL CABINET
TV TELEVISION
TYP TYPICAL
UG UNDERGROUND
RMP ROCKY MOUNTAIN POWER
UPS UNINTERRUPTED POWER SUPPLY
V VOLT (KV-KILOVOLT)
VA/R VOLT-AMPS/REACTIVE
VM VOLT METER
W WATTS
W/ WITH
WH WATTHOUR METER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFMR SW TRANSFER SWITCH
XP EXPLOSION PROOF
1P SINGLE-PHASE
2P TWO-POLE
3P THREE-POLE
4P FOUR-POLE
∅ PHASE
DEMOLITION NOTES
1. COORDINATE ALL NEW ELECTRICAL EQUIPMENT REQUIREMENTS AND MAKE CONNECTION TO EXISTING
SYSTEMS. THIS INCLUDES LIGHTING, POWER, SIGNAL, RACEWAY AND OTHER SYSTEMS INCLUDED UNDER
DIVISION 26 (16).
2. RELOCATE, REWIRE AND/OR RECONNECT EXISTING ELECTRICAL DEVICES AND/OR EQUIPMENT THAT FOR ANY
REASON OBSTRUCTS CONSTRUCTION.
3. CONCEAL ALL RACEWAY AND WIRING IN EXISTING WALLS, CEILINGS, FLOORS, ETC. EXCEPT WHERE THE USE OF
SURFACE METAL RACEWAYS (E.G. WIRE MOLD) IS INDICATED ON DRAWINGS OR IN SPEC.
4. LEAVE ALL EXISTING EQUIPMENT, IN PORTIONS OF THE BUILDING NOT BEING REMODELED, IN WORKING CONDITION. RESTORE ALL INTERRUPTED BRANCH CIRCUITS, FEEDERS, ETC. TO WORKING CONDITION.
5. EXISTING RACEWAYS MAY BE REUSED (IN PLACE) WHERE POSSIBLE, AND WHERE IN COMPLIANCE WITH THE SPECIFICATIONS AND THE INTENT OF THE CONTRACT DOCUMENTS. INSURE INTEGRITY OF EXISTING RACEWAY
BEFORE REUSE.
6. REMOVE ALL RACEWAYS, CONDUCTORS, BOXES, DEVICES, EQUIPMENT, ETC. THAT ARE NOT TO BE REUSED.
7. REMOVE EXISTING LIGHT FIXTURES WHICH ARE NOT TO BE REUSED, PLACE IN CARTON, LABEL APPROPRIATELY, AND RETURN TO OWNER, OR PROPERLY DISPOSE OF FIXTURES THAT THE OWNER CHOOSES NOT TO KEEP.
8. DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
9. DISCONNECT AND RECONNECT ANY/ALL FIXTURES, DEVICES, EQUIPMENT, ETC. REQUIRED FOR PROPER
COMPLETION OF THE WORK.
ELECTRICAL SHEET LIST
E1 TITLE SHEET
E1.1 SYMBOLS, SCHEDULES, NOTES AND DIAGRAMS
E1.2 ELECTRICAL DEMOLITION
E2 RIVERTON HIGH SCHOOL ELECTRICAL PLAN
E4 ELECTRICAL PANEL SCHEDULES
XE3 ELECTRICAL DIAGRAMS
TA1 AUDIOVISUAL NOTES, LEGENDS, & SCHEDULES
TA2 RIVERTON HIGH SCHOOL SOUND PLAN
TA4 AUDIOVISUAL DIAGRAMS
CELLULAR SITE UTILITY COORDINATION
ELECTRICAL SITE UTILITY INFORMATION HAS BEEN COORDINATED WITH THE FOLLOWING UTILITY COMPANY REPRESENTATIVES. VERIFY ALL LOCATIONS, DIMENSIONS, CLEARANCES, REGULATIONS, ETC, PRIOR TO
INSTALLATION. NOTIFY ENGINEER OF ANY REVISIONS REQUIRED.
CELLULAR COMPANY T-MOBILE
CONTACT PROPERTY MANAGEMENT
PHONE NO. (877) 373-0093
EMAIL NA
SITE ID SL52XC146/UT-SLC0248
SYMBOL LEGEND GENERAL NOTES
1. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR. DASHED BOX AROUND DEVICE
INDICATES INSTALLED IN CEILING.
2. WALL DEVICES NOTED WITH A CHEVRON INDICATE TO COORDINATE WITH MILLWORK SHOP
DRAWINGS & ELEVATIONS FOR HEIGHT.
3. TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN THIS SET OF DRAWINGS.
4. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE TYPES, MOUNTING REQUIREMENTS, WATTAGE
& DETAILS.
5. WIRE LIGHT FIXTURE FROM ADJACENT JUNCTION BOX.
6. CONNECT NEAREST UN-SWITCHED HOT CONDUCTOR TO EMERGENCY BALLAST.
7. LIGHT FIXTURES ARE SCALED WITHIN THE DRAWINGS BASED ON ACTUAL DIMENSIONS.
8. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
9. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
10. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
11. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
12. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE HEAVY DUTY (HD) DEVICE FOR
480 VOLT.
13. SIZE TO THE EQUIPMENT BEING CONTROLLED.
14. PROVIDE H.O.A. & S.S. PUSHBUTTONS AS REQUIRED.
15. DOUBLE ARROWS INDICATES A DOUBLE FACE UNIT.
16. FOR WATER COOLER LOCATION, REFER TO DIAGRAM R002. FOR ALL OTHER LOCATIONS,
MOUNT AT +16" TO BOTTOM OF BOX FROM FINISHED FLOOR, OR AS NOTED.
17. ARROWS SHOWN ON DEVICE INDICATE AIMING DIRECTION.
18. COORDINATE WITH DOOR HARDWARE SUPPLIER.
19. MOUNT ON TRACK OF OVERHEAD DOOR, 6" FROM TOP OF DOOR, UNLESS OVERHEAD DOOR IS
A ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
20. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
21. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW INDICATES FRONT OF RACK.
22. HEIGHT MEASURED TO BOTTOM OF THE DEVICE FROM FINISHED FLOOR.
23. PROVIDE MUD RING &/OR BOX COVER APPROPRIATE FOR DEVICE/FIXTURE SERVED.
24. REFER TO DIAGRAMS, ELEVATIONS, & SCHEDULES FOR CUSTOM ROUGH-IN REQUIREMENTS.
25. ROUGH-IN TO BE HORIZONTAL.
26. REFER TO MANUFACTURER'S RECOMMENDED CABLE REQUIREMENTS FOR EXACT CABLE
REQUIRED.
27. FOLLOW BICSI STANDARDS FOR CABLE ROUTING & DISTANCES.
28. SUBSCRIPT INDICATES NEMA CONFIGURATION.
29. USE A 4" X 4" BOX WITH A MUD RING TO MATCH THE DEVICE & INSTALLATION.
30. USE WITH POWER PACK.
31. PROVIDE UL LISTED DEVICE COMPATIBLE WITH THE FIRE ALARM PANEL/SYSTEM.
32. CAMERA TYPES ARE INDICATED INSIDE THE CAMERA SYMBOL.
EXISTING FIELD LIGHT
DISCONNECTS UNDER BLEACHERS
J J J J J
J JJJ
JJ
J
J
OS
JJJJJ
JJ
JJJJJ
J J J
JJ J
JJ
J
JJ JJ J
T
T
D2 D2 D3
D5
D1
D5 D5 D5D5D5
D5D5D5D5
D2 D2
D5 D5
D5
TA2
E1.2
E1.2
E1.2
(E)BH6
(E)XFMR BL24
(E)BH6
THERMOSTAT (EXISTING) TO BE RELOCATED
EXISTING HEATER
EXISTING HEATER
(E)XFMR BL24
D7 D7
55A 3 PHASE 208V 30 SPACE
150A 3 PHASE 480V 42 SPACE
ALT 1
D9
ALT 1
D8
ALT 1
ALT 1
D12 D11
E1.2
D13
T4
T3
T2
T1
T5
D14
T6
Project #: 250866
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
A H
TE OF
S
TA
P
L EN
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
S A
L T
L A
.G
E O
R G
E
02/19/26
CONSTRUCTION DOCUMENTS
/1
/2
:3 :4
P
M A u to d e s k D o c s /2
J
S D
R iv e rt o n
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
/2
J S
D R iv e rt o n H
S F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250866
BR
RESOLUT
ELECTRICAL
DEMOLITION
E1.2
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
R
IV
E R
T O
N H
IG
H
S C
H O
O L
W
R iv e rt o n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
SCALE = 1" = 30'-0"
ELECTRICAL DEMOLITION PLAN
KEYNOTES
D1 EXISTING SPORTS LIGHT POLE DISCONNECTS TO REMAIN. CONTRACTOR SHALL PROTECT IN
PLACE.
D2 EXISTING STADIUM LIGHT FIXTURES TO BE DEMOLISHED. POLE TO REMAIN FOR REUSE.
EXISTING WIRE IS TO BE PULLED BACK AS NEEDED DURING CONSTRUCTION AND PROTECTED
FOR FUTURE REUSE. REFER TO E2 FOR NEW REQUIREMENTS.
D3 EXISTING CELLULAR UTILITIES ARE PRESENT ON THIS POLE. CONTRACTOR SHALL PROTECT ALL
CELLULAR EQUIPMENT IN PLACE. IF INTERACTION WITH UTILITY EQUIPMENT IS REQUIRED,
CONTRACTOR SHALL COORDINATE DIRECTLY AND CLOSELY WITH THE CELLULAR UTILITY
COMPANY PRIOR TO COMMENCING ANY WORK. ALL WORK SHALL BE PERFORMED IN A MANNER
THAT ENSURES NO INTERRUPTION TO CELLULAR SERVICES, UNLESS APPROVED BY THE
CELLULAR UTILITY REPRESENTATIVE, AND COMPLIES WITH PROJECT SPECIFICATIONS AND
SAFETY STANDARDS.
D5 EXISTING JUNCTION BOXES. CONTRACTOR SHALL PROTECT IN PLACE. ENSURE ALL BOXES AND
ASSOCIATED CONDUIT REMAIN UNDISTURBED DURING CONSTRUCTION ACTIVITIES, ANY
DAMAGE TO EXISTING EQUIPMENT SHALL BE REPAIRED OR REPLACED AT CONTRACTOR'S
EXPENSE. COORDINATE WITH ENGINEER IF RELOCATION OR MODIFICATION IS REQUIRED.
D7 ALT 1: EXISTING HEATERS TO BE DEMOLISHED AND REMOVED.DISCONNECT AND PULL BACK
ALL ASSOCIATED CONDUIT AND WIRING BACK TO THE PANEL. PATCH AND REPAIR WALL
FINISHES AS NEEDED.
D8 ALT 1: REMOVE THE EXISTING 3-POLE, 30A BREAKER CURRENTLY FEEDING THE TRANSFORMER.
D9 ALT 1: EXISTING TRANSFORMER TO BE DEMOLISHED. REMOVE ALL CABLING AND CONDUIT FROM
THE PRIMARY AND SECONDARY SIDE OF THE TRANSFORMER BACK TO ITS SOURCE.
DEMOLITION
D11 ALT 1: REMOVE EXISTING THERMOSTAT BACK TO ITS COURSE. PATCH AND REPAIR ALL
DAMAGED WALL AND CEILING FINISHES AS NEEDED. ENSURE FINISHES MATCH EXISTING
TEXTURE AND PAINT.
D12 EXISTING THERMOSTAT TO BE RELOCATED. EXTEND EXISTING CABLING AND CONDUIT AS
NEEDED TO NEW LOCATION SHOWN IN SHEET 'E2' FOR NEW LOCATION.
D13 EXISTING TELECOMMUNICATIONS ENCLOSURE SHALL BE REMOVED IN ITS ENTIRETY TO
ACCOMMODATE NEW RACK.
D14 DEMOLISH EXISTING 120V POWER WITHIN TELECOM ENCLOSURE. PULL BACK ALL CABLING BACK
TO ITS SOURCE.
T1 EXISTING FIBER CONNECTION AND TELECOMMUNICATIONS SWITCH SHALL BE RELOCATED INTO
THE NEW AV RACK.
T2 CONTRACTOR SHALL PROVIDE A NEW PATCH PANEL AND RECONNECT ALL EXISTING WIRING
INTO THE NEW AV RACK.
T3 EXISTING WIRELESS ACCESS POINT SHALL BE RELOCATED TO THE CEILING. EXTEND ALL
CABLING AS NEEDED.
T4 NEW TELE COMMUNICATION LINES SHALL BE ROUTED TO NEW PATCH PANEL.
T5 EXISTING FIBER SHALL BE RETERMINATED INTO A RACK MOUNT FIBER CASSETTE KIT.
T6 PROVIDE ALL REQUIRED HARDWARE FOR A COMPLETE AND FULLY FUNCTIONAL SYSTEM
INSTALLATION.
1/4" = 1'-0"
PRESS BOX LIGHTING DEMOLITION PLAN
1/4" = 1'-0"
PRESS BOX POWER DEMOLITION PLAN
ALT 1 ALT 1
REVISIONS
MARK DATE DESCRIPTION
NOT TO SCALE
EXISTING DISCONNECTS
NOT TO SCALE
EXISTING DISCONNECTS
OS
JJJJJ
JJ
JJJJJ
J J J
J
JJ
J
J
JJ JJ J
T
T
J J
FF JJ
EXISTING FIELD LIGHT
DISCONNECTS UNDER BLEACHERS
J J
J JJJ
JJ
J
J
(E)BH6BL24
NEW THERMOSTAT LOCATION
(E)XFMR BL24
E5
E6E6E6E6E6E6
CUTLER HAMMER POW-R-LINE PRL2A
ALT 1
E5
ALT 1
E8
E7
E6
ALT 1
ALT 1
ALT 1
BL24-31BL24-31BL24-31BL24-33BL24-33BL24-33
B L2
4-
B L2
4-
B L2
4-
WP
WP WP
WP
E4
ALT 1
BL24- 27,29
SSO-2
E4
ALT 1
BL24- 23,25
SSO-1
BL24-22 BL24-24
HEAT TAPE HEAT TAPE
WP WPWP WP
E2 E2
E2 E2
E2
E2
E2
KEYNOTES
E2 PROVIDE AND INSTALL NEW POLE-MOUNTED LIGHTING CONTROLLER(S) AND STADIUM
POLE-MOUNTED LIGHT FIXTURES AS INDICATED ON THE APPROVED LIGHTING MANUFACTURER
SHOP DRAWINGS. EXTEND EXISTING BRANCH CIRCUIT WIRING TO THE NEW LIGHTING
CONTROLLER(S). PROVIDE NEW CONDUCTORS FROM THE LIGHTING CONTROLLER(S) TO EACH
NEW LIGHT FIXTURE, COORDINATE ROUTING AND PROTECTION OF CONDUCTORS WITHIN POLES
AND HANDHOLES TO PREVENT MECHANICAL DAMAGE AND FACILITATE MAINTENANCE ACCESS.
INSTALLATION SHALL STRICTLY FOLLOW THE APPROVED LIGHTING MANUFACTURER SHOP
DRAWINGS. CONTRACTOR SHALL COORDINATE CLOSELY WITH THE LIGHTING MANUFACTURER
PRIOR TO COMMENCING WORK TO CONFIRM EQUIPMENT REQUIREMENTS, INTERCONNECTIONS,
CONTROL PROTOCOLS, WIRING METHODS, AND MOUNTING DETAILS. PROVIDE COMPLETE,
OPERATIONAL LIGHTING SYSTEM INCLUDING ALL ACCESSORIES, SUPPORTS, TERMINATIONS,
LABELING, TESTING, COMMISSIONING, AND FINAL DOCUMENTATION NECESSARY FOR PROPER
OPERATION.
E4 ALT1: PROVIDE NEW MINI-SPLIT SYSTEM. MOUNT EXTERIOR CONDENSING UNDER PRESSBOX.
INSTALL SINGLE-PHASE 208V, 20A CIRCUIT WITH (3) #12 AWG CONDUCTORS AND (1) #12 AWG
GROUND. ROUTE POWER TO EXISTING PANELBOARD '(E)BL24' [SQUARE D HOMC12UC SERIES
S01]. PROVIDE 2-POLE 20A BREAKER AND REARRANGE EXISTING BREAKERS AS REQUIRED TO
ACCOMMODATE NEW CIRCUIT. VERIFY BREAKER COMPATIBILITY WITH PANEL PRIOR TO
INSTALLATION. REFER TO MECHANICAL SPECIFICATION FOR ADDITIONAL INFORMATION ON MINI
SPLIT.
E5 ALT 1: INDOOR UNIT SHALL BE POWERED VIA CONDENSING UNIT. REFER TO MECHANICAL
SPECS FOR CABLING AND CONDUCTOR REQUIREMENTS.
E6 ALT 1: PROVIDE AND INSTALL NEW 3 POLE 50A BREAKER FOR NEW TRANSFORMER. INSTALL AND
TERMINATE (1) 1' C. WITH (3) 6 AWG CU CONDUCTORS AND (1) 8 AWG CU GROUNDING
ELECTRODE CONDUCTOR TO NEW TRANSFORMER.
E7 ALT 1: INSTALL NEW 3 PHASE, 30 KVA 480V TO 208V STEP‑DOWN TRANSFORMER. PROVIDE THE PROPER SUPPLY‑SIDE BONDING JUMPER IN ACCORDANCE WITH NEC 250.102(C)(1).
CONTRACTOR SHALL FURNISH AND INSTALL ALL REQUIRED COMPONENTS, FITTINGS, AND LUGS
TO PROVIDE A COMPLETE AND FULLY FUNCTIONAL INSTALLATION.
E8 ALT 1: INSTALL AND TERMINATE (1) 1' C. WITH (3) 6 AWG CU CONDUCTORS AND (1) 8 AWG CU
GROUNDING ELECTRODE CONDUCTOR FROM THE SECONDARY SIDE OF NEW TRANSFORMER TO
EXISTING PANEL. PROVIDE AND INSTALL NEW 3 POLE 100A BREAKER IN PANELBOARD '(E)BL24'.
Project #: 250866
HICKS
BRIAN
No. 7709037-2202
G
IN
E E R
ONA
O F
E
SS
I
R
UT
A H
TE OF
S
TA
P
L EN
PROJECT NO:
DRAWN BY:
CHK'D BY:
DATE:
T H
IS
P
R
IN
T
IS
IN
C
O L
O R
A
BCDEFGHIJKLMN
ABCDEFGHIJKLMN
S A
L T
L A
.G
E O
R G
E
02/19/26
CONSTRUCTION DOCUMENTS
/1
/2
:3 :4
P
M A u to d e s k D o c s /2
J
S D
R iv e rt o n
H S
F o o tb a ll
F ie ld S p o rt s U p g ra d e
/2
J S
D R iv e rt o n H
S F o o tb a ll
F ie ld S p o rt s U p g ra d e
E L E
C v
.r v t
2/19/26
250866
BR
RESOLUT
RIVERTON HIGH
SCHOOL
ELECTRICAL
PLAN
E2
J O
R D
A N
S C
H O
O L
D
IS
T R
IC
T
R
IV
E R
T O
N H
IG
H
S C
H O
O L
W
R iv e rt o n
U T
F O
O T
B A
L L F
IE
L D
L
IG
H T
IN
G
/S O
U N
D U
P G
R A
D E
JO
R
D A
N S
C H
O O
L D
IS
T
R
IC
T
GENERAL NOTES
1. DIVISION 26 SHALL VISIT THE SITE PRIOR TO BIDDING. BIDS SHALL SERVE AS EVIDENCE OF KNOWLEDGE OF EXISTING CONDITIONS. BIDDERS
SHALL EXAMINE THE SITE AND THE COMPLETE SET OF PLANS AND SPECIFICATIONS COVERING THE ENTIRE PROJECT. THEY SHALL BECAME
FULLY CONVERSANT WITH THE TYPE OF GENERAL CONSTRUCTIONS AS WELL AS ALL PERTINENT FACTS AFFECTING THE COST OF CARRYING
OUT THE WORK THEY WILL CONTRACT TO PERFORM. DIVISION 26 SHALL COORDINATE PROJECT PHASING WITH THE GENERAL CONTRACTOR
AND BID PERFORM RESPONSIBILITIES FOR THIS PROJECT TO CONTRACT EXPECTATIONS.
2. DIVISION 26 SHALL CONFIRM EXACT LOCATION OF EXISTING AND NEW EQUIPMENT WITH OWNERS. ROUGH-IN LOCATIONS ARE
DIAGRAMMATICALLY SHOWN ON THE DRAWINGS. EXISTING ELECTRICAL FIXTURES, DEVICES, EQUIPMENT, CIRCUITING AND/OR CONDITIONS
ARE NOT SPECIFIED UNLESS NOTED ON DRAWINGS. FINAL ROUTING OF THE CONDUITS, CIRCUITING, AND CABLING SHALL BE DETERMINED BY
THE CONTRACTOR AND CLOSELY COORDINATED WITH OWNER. ALL EXISTING CONDITIONS MUST BE VERIFIED WITHOUT EXCEPTION.
3. DIVISION 26 SHALL BLUE STAKE THE AREA OF NEW CONSTRUCTION PRIOR TO EXCAVATION FOR FOOTINGS, ETC. IDENTIFY BURIED ELECTRICAL
SYSTEMS (UTILITIES, POWER, COMMUNICATIONS, ETC.) AND COORDINATE LOCATIONS WITH THE GENERAL CONTRACTOR. IF EXISTING
ELECTRICAL SYSTEMS ARE DISTURBED (POWER, AUXILIARY, ETC.) ELECTRICAL CONTRACTOR SHALL MAKE NECESSARY REPAIRS (AS
APPROVED BY DISTRICT REPRESENTATIVE AS PART OF THIS CONTRACT.
4. CONTRACTOR TO CLOSELY COORDINATE ALL NEW AND EXISTING DEVICE LOCATIONS WITH CIVIL DRAWINGS. CONTRACTOR TO VERIFY ALL
FINAL GRADE REQUIREMENTS WITH CIVIL DRAWINGS.
5. COORDINATE DEMOLITION AND PROJECT PHASING REQUIREMENTS WITH THE ENTIRE CONSTRUCTION SET AND GENERAL CONTRACTOR.
PROVIDE SELECT…