Exhibit Y - SECTION 238129 - VARIABLE-REFRIGERANT-FLOW HVAC SYSTEMS_Amend 02_page 32.pdf
PDF 81 KB Posted
- Attached to
- Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade
- Solicitation number
- 385515GMK
About this file
This document is a specification section from an AIA MasterSpec template for Variable-Refrigerant-Flow (VRF) HVAC Systems (Section 238129-32). The document addresses technical installation and quality control requirements for VRF HVAC systems and does not represent a solicitation, contract opportunity, or procurement document.
The specification establishes installation standards for balanced twisted-pair cable (compliant with TIA-568.2-D), open-cable installation (minimum 8 inches above ceilings with supports spaced no more than 30 inches apart), and electromagnetic interference (EMI) separation requirements per BICSI TDMM and TIA-569-E standards. It mandates firestopping compliance with Section 078413 and applicable industry standards, system identification per HVAC piping standards, and manufacturer field service requirements. Manufacturer's field service must be performed by manufacturer employees with primary responsibility for direct technical support, with factory-authorized representatives permitted to assist only under manufacturer employee supervision. The manufacturer is required to provide on-site visits during construction. This template section establishes baseline technical and quality control requirements for VRF HVAC system installation projects but contains no procurement information, pricing, timelines, or contracting details.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
VARIABLE-REFRIGERANT-FLOW HVAC
SYSTEMS
238129 - 32
Copyright © 2024 by the American Institute of Architects. Warning: This AIA MasterSpec based document is protected by U.S.
Copyright Law and International Treaties. A valid, current MasterSpec license is required for editing or use of this document.
Sensitivity: Highly Confidential
D. Balanced Twisted-Pair Cable Installation:
1. Comply with TIA-568.2-D.
2. Do not untwist balanced twisted-pair cables more than 1/2 inch at the point of termination to maintain cable geometry.
E. Open-Cable Installation:
1. Suspend copper cable not in a wireway or pathway a minimum of 8 inches above ceilings by cable supports not more than 30 inches apart.
2. Do not route cable through or on structural members or in contact with pipes, ducts, or other potentially damaging items. Do not run cables between structural members and corrugated panels.
F. Separation from EMI Sources: Comply with BICSI TDMM and TIA-569-E recommendations for separating unshielded cable from potential EMI sources including electrical power wiring and equipment.
3.13 FIRESTOPPING
A. Comply with requirements in Section 078413 "Penetration Firestopping".
B. Comply with TIA-569-E.
C. Comply with BICSI TDMM, "Firestopping" Chapter.
3.14 IDENTIFICATION
A. Identify system equipment, piping, tubing, and valves. Comply with requirements for identification specified in Section 230553 "Identification for HVAC Piping and Equipment."
3.15 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: Engage VRF HVAC system manufacturer's service representative to advise and assist installers; witness testing; and observe and inspect components, assemblies, and equipment installations, including controls and connections.
1. Field service must be performed by an employee of VRF HVAC system manufacturer whose primary job responsibilities are to provide direct technical support of its products.
a. Additional factory-authorized representatives may assist with completion of certain activities only if supervised by manufacturer's employee. A factory-authorized representative must not provide assistance without manufacturer's employee supervision.