Exhibit V - SECTION 042000 - MASONRY_Amend 02_Page 3.pdf
PDF 72 KB Posted
- Attached to
- Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade
- Solicitation number
- 385515GMK
About this file
This document is a specification section for Unit Masonry (04 20 00) that establishes materials and construction standards for masonry work.
The specification requires compliance with TMS 602/ACI 530.1/ASCE 6 standards for masonry construction, with modifications as specified in contract documents. Concrete masonry units (CMU) must meet ASTM C 90 requirements, manufactured to nominal dimensions minus 3/8 inch, with normal weight density classification unless otherwise indicated. For two-hour rated walls, medium weight density classifications per UL 618 are mandated. The specification prohibits use of masonry units with chips, cracks, or other defects that are exposed in completed work and located within 20 feet vertically or horizontally of walking surfaces.
Mortar and grout materials must comply with specific ASTM standards: Portland cement per ASTM C 150/C 150M (Type I or II, with Type III permitted for cold-weather construction), hydrated lime per ASTM C 207 Type S, and aggregate per ASTM C 144 for mortar and ASTM C 404 for grout. Exposed mortar requires washed aggregate of natural sand or crushed stone; joints less than 1/4 inch thick require aggregate graded with 100 percent passing the No. 16 sieve. White and colored mortar aggregates are specified separately to achieve required color. Water must be potable. Ties and anchors shall extend at least 1-1/2 inches into veneer with minimum 5/8-inch cover on the outside face.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UNIT MASONRY
04 20 00 - 3
A. Masonry Standard: Comply with TMS 602/ACI 530.1/ASCE 6, except as modified by requirements in the Contract Documents.
B. Defective Units: Referenced masonry unit standards may allow a certain percentage of units to contain chips, cracks, or other defects exceeding limits stated. Do not use units where such defects are exposed in the completed Work and will be within 20 feet vertically and horizontally of a walking surface.
2.2 CONCRETE MASONRY UNITS
A. CMU, General: ASTM C 90.
1. Density Classification: Normal weight unless otherwise indicated.
2. Size (Width): Manufactured to dimensions 3/8 inch less than nominal dimension
3. For two hour rated walls, use medium weight density classifications per UL 618.
2.3 MORTAR AND GROUT MATERIALS
A. Portland Cement: ASTM C 150/C 150M, Type I or II, except Type III may be used for cold-weather construction. Provide natural color or white cement as required to produce mortar color indicated.
B. Hydrated Lime: ASTM C 207, Type S.
C. Portland Cement-Lime Mix: Packaged blend of portland cement and hydrated lime containing no other ingredients.
D. Aggregate for Mortar: ASTM C 144.
1. For mortar that is exposed to view, use washed aggregate consisting of natural sand or crushed stone.
2. For joints less than 1/4 inch thick, use aggregate graded with 100 percent passing the No. 16 sieve.
3. White-Mortar Aggregates: Natural white sand or crushed white stone.
4. Colored-Mortar Aggregates: Natural sand or crushed stone of color necessary to produce required mortar color.
E. Aggregate for Grout: ASTM C 404.
F. Water: Potable.
2.4 TIES AND ANCHORS
A. General: Ties and anchors shall extend at least 1-1/2 inches into veneer but with at least a 5/8-inch cover on outside face.