Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade
Solicitation number
385515GMK
Issued by

About this file

This is a specification section for metal grating stairs from a construction contract document, specifically Section 055119. The specification establishes requirements for the design, fabrication, and installation of metal stairs with associated railings and guards, with all structural design delegated to a qualified professional engineer licensed in Illinois.

Submittals must include comprehensive shop drawings with plans, elevations, sections, details, and attachment points to other work, clearly indicating metal section sizes, thickness, profiles, holes, and field joints with plans provided at each level and locations of anchors, weld plates, and blocking for wall-mounted handrails. A delegated design submittal signed and sealed by the responsible professional engineer must include analysis data for stairs, railings, and guards. The fabricator must provide qualification data documenting the professional engineer's experience with delegated design services and state licensure in Illinois, along with welding certificates. Welding qualifications must comply with AWS D1.1/D1.1M "Structural Welding Code - Steel." Materials must be stored to permit easy inspection and identification, kept off ground on pallets or spacers, and protected from corrosion and deterioration, with no storage on structure that could cause distortion, damage, or overload. Any damaged materials or structures must be repaired or replaced as directed.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

METAL GRATING STAIRS 055119 - 2

1. Include plans, elevations, sections, details, and attachment to other work.

2. Indicate sizes of metal sections, thickness of metals, profiles, holes, and field joints.

3. Include plan at each level.

4. Indicate locations of anchors, weld plates, and blocking for attachment of wall-mounted handrails.

C. Delegated Design Submittal: For stairs, railings, and guards, including analysis data signed and sealed by the qualified professional engineer responsible for their preparation.

1.4 INFORMATIONAL SUBMITTALS

A. Qualification Data: For professional engineer's experience with providing delegated design engineering services of the kind indicated, including documentation that engineer is licensed in the State of IL in which Project is located.

B. Welding certificates.

1.5 QUALITY ASSURANCE

A. Installer Qualifications: Fabricator of products.

B. Welding Qualifications: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."

1.6 DELIVERY, STORAGE, AND HANDLING

A. Store materials to permit easy access for inspection and identification.

1. Keep steel members off ground and spaced by using pallets, dunnage, or other supports and spacers.

2. Protect steel members and packaged materials from corrosion and deterioration.

3. Do not store materials on structure in a manner that might cause distortion, damage, or overload to members or supporting structures.

a. Repair or replace damaged materials or structures as directed.

PART 2 - PRODUCTS

2.1 PERFORMANCE REQUIREMENTS

A. Delegated Design: Engage a qualified professional engineer, as defined in Section 014000 Section 014100 "Quality Requirements," to design stairs, railings, and guards, including attachment to building construction.

B. Structural Performance of Stairs: Metal stairs withstand the effects of gravity loads and jdragovi Cloud jdragovi Text Box