Exhibit U - 2-1-561_WH16 Elev Elec Rm_Amend 01_Sheet A05.pdf
PDF 439 KB Posted
- Attached to
- Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade
- Solicitation number
- 385515GMK
About this file
This is an architectural drawing document that provides wall types and construction details for the WH16 Electrical and Elevator Machine Rooms fire rating and mechanical upgrade project. The document is project number 2-1-561 and was issued for bidding on 08/17/2026 with Amendment 1 dated 11/20/2026.
The document specifies multiple wall construction types and finishes required for fire-rated wall assemblies. Paint Schedule requirements include Benjamin Moore Eco Spec N374 in Ivory White 925 with eggshell finish for interior surfaces. Wall Type EX (existing) requires one layer of 5/8" Type X gypsum board on both sides of existing walls. Wall Type A1 specifies two layers of 5/8" gypsum board on 3-5/8" metal studs 16" on center with sound attenuation blanket, achieving a 2-hour fire rating. New infill wall construction requires two layers of 1/2" Type X gypsum board on 3-5/8" metal studs on both sides to match existing wall thickness of 6-7/8". For concrete masonry unit (CMU) walls, abandoned openings must be infilled with solid masonry to full wall thickness using fire wall construction meeting 2-hour specifications per NFPA 80, with new mortar matching existing color and joint profiles. Exterior CMU surfaces require sealing with Sika Thorocoat 400 in Whip Cream color. All fire sealants must comply with specifications at joints and connections, including rated slip joint connections (UL Design U419). Door frames are specified as 90-minute rated with corner bead typical at all corners. The drawing includes six detail sheets at various scales showing typical plan details at infills for wall types and new door wall assemblies.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PAINT SCHEDULE
PT-1 BENJAMIN MOORE. ECO SPEC N374
COLOR: IVORY WHITE 925
EGG SHELL FINISH
PT-2 BENJAMIN MOORE. ECO SPEC N374
COLOR: IVORY WHITE 925
FLOOR SLAB
FIRE SEALANT BOTH SIDES AS
PER SPECIFICATIONS
2 HR. RATED WALL
EX.
EXISTING WALL TO REMAIN.
REFER TO WALL TYPE EX.
T.O. EXISTING STUD WALL
+/- 8'- 1" A.F.F. AT EL. 961'-5"
EX.EXIST.
EXISTING CONCRETE
BEAM
PROVIDE 5/8" TYPE X GWB ON
EXISTING WALL BOTH SIDES
SIM.
A-05
6 7/8"
2 LAYERS OF 5/8" GYP. BD. EACH SIDE ON 3-5/8"
MTL. STUDS 16" O.C.
STRUCTURE ABOVE, SEE
STRUCTURAL
6 1/8"
SOUND ATTENUATION BLANKET
FULL HT.
FLOOR SLAB
FIRE SEALANT BOTH SIDES
RATED SLIP JOINT
CONNECTION
UL DES U419
2 HR. RATED WALL
SIM.
A-05
(SIM)
EXISTING WALL TO REMAIN.
REFER TO WALL TYPE EX
ONE LAYER OF 5/8" TYPE X GWB ON BOTH SIDES EXISTING WALL
AND NEW INFILL
NOTE:
1. REMOVE ALL EXISTING MATERIAL FROM ABANDONED REGISTERS AND/OR EQUIPMENT.
2. CLEAN THE CAVITY AND PRIME AS NECESSARY FOR NEW 2-HR WALL CONSTRUCTION
INFILL.
3. FINAL WALL CONSTRUCTION TO MEET 2-HOUR WALL RATING.
E X
IS
T
NEW INFILL TO HAVE TWO LAYERS OF 1/2" TYPE X GWB
ON 3 5/8" METAL STUDS ON BOTH SIDES. MATCH EXISTING
WALL THICKNESS.
/8
EXISTING CMU WALL
PROVIDE NEW SOLID MASONRY INFILL TO MAINTAIN THE
REQUIRED FIRE -FESITANT RATING.
CMU TO FILL EXISTING VOID TO FULL WALL THICKNESS.
NEW MORTAR TO MATCH EXISTING COLOR AND JOINT PROFILE.
MUST BLEND WITH EXISTING CMU.
NOTE:
1. REMOVE ALL EXISTING MATERIAL FROM ABANDONED DUCTWORK AND/OR EQUIPMENT.
2. CLEAN THE CAVITY AND PRIME AS NECESSARY FOR NEW MORTAR APPLICATION.
3. NEW MORTAR JOINTS AND CMU INFILL TO MATCH EXISTING GROUT LINES AT ALL SIDES.
4. ABANDONED OPENINGS IN EXISTING 2-HOUR FIRE RATED CMU WALLS SHALL BE INFILLED
TO FULL WALL THICKNESS. PROVIDE TIGHT- FITTING SOLID MASONRY INFILL USING A FIRE
WALL CONSTRUCTION TO MEET 2-HOUR WALL SPECIFICATIONS AS PER NFPA 80
5. AT EXTERIOR WALL LOCATIONS, EXTERIOR SIDE OF CMU TO BE SEALED WITH SIKA
THOROCOAT 400 AS PER MANUFACTURER GUIDELINES. COLOR TO BE "WHIP CREAM".
REFER TO SPECIFICATION SECTION 099100
FLOOR SLAB
EXISTING 1 HOUR FIRE
WALL TO REMAIN.
REFER TO SHEET G-04
FOR REFERENCE.
ASSUME TWO LAYERS
OF 1/2" FIRECODE C
GWB ON 3 5/8" METAL
STUDS
EXISTING CEILING
HERCULITE 20 ON
3/4" PLYWOOD
TO BE REMOVED
T.O. EXISTING STUD WALL
+/- 8'- 1" A.F.F. AT EL. 961'-5"
EXISTING CONCRETE
BEAM
NEW TWO LAYERS 5/8" TYPE X
GWB AT TOP OF EXISTING GWB
EXISTING WALL TO REMAIN.
REFER TO WALL TYPE EX
GWB CORNER BEAD TYPICAL AT
ALL CORNERS
CEILING TO BE 2 HOUR FIRE RATING
TWO LAYERS OF 5/8" TYPE X GWB
BOTH SIDES ON 3 5/8" METAL STUDS
T.O. EXISTING STUD WALL
+/- 8'- 1" A.F.F. AT EL. 961'-5"
EXIST.
USG PAPER FACED
METAL CORNER
BEAD
EXISTING CONCRETE
BEAM
FIRE SEALANT AS PER
SPECIFICATIONS BOTH
SIDES
EDGE OF EXISTING SLAB
E X
IS
T
A1 ±10 5/8"
GWB CORNER BEAD
TYPICAL AT ALL CORNERS
NEW 5/8" TYPE X GWB APPLIED
TO EXIST. WALL
TYPICAL BOTH SIDES
EXTEND TO NEW OPENING.
NEW TWO LAYERS OF 5/8" GWB
ON 3 5/8" MTL STUDS
90 MIN. DOOR AND FRAME
REFER TO SCHEDULE AND
MANUFACTURER
INSTALLATION
REQUIREMENTS
NEW 5/8" TYPE X GWB ON TWO LAYERS OF
1/2" TYPE X GWB BOTH SIDES ON 3 5/8" MTL
STUDS
APPLY FIRE
SEALANT AT ALL
JOINTS AS PER
SPECIFICATIONS
A3
ALIGN
/8
SCALE:
PROJECT NO.
SHEET NO.
DESIGNED
DRAWN
CHECKED
APPROVED
ISD ENGINEERING DATE
PROJECT NAME.
SHEET NAME:
REVISION NO.FIMS. NO.
ISD
INFRASTRUCTURE
SERVICES DIVISION
C :\U se rs
\jd ra g ov i\D o cu m en ts
\2 -1
-5
1_ W
H
E le v
E le c R m _V
_j dr a go vi
.r vt
1/
/2
:2
9:
P M
WH16 ELEC. & ELEV.MACHINE ROOMS-
FIRE RATING & MECH. UPGRADE
WALL TYPES AND DETAILS A-05
2-1-561
/2
0/
A m m en dm en t 0
JAD
JAD
JAD
JAD
001REVISIONS
REV. DESCRIPTION DATE
ISSUE FOR CCR 01/30/2026
ISSUE FOR BIDDING 08/17/2026
1 AMMENDMENT 1 11/20/2026
1 1/2" = 1'-0"A-05
2 TYPE A1
1 1/2" = 1'-0"A-05
3 TYPE A2
3" = 1'-0"A-05
6 TYP. PLAN DETAIL AT INFILL- WALL TYPE A
3" = 1'-0"A-05
5 TYP. PLAN DETAIL AT INFILL- WALL TYPE B
1 1/2" = 1'-0"A-05
1 TYPE EX (EXISTING)
3" = 1'-0"A-05
7 TYPE A1
3" = 1'-0"A-05
DETAIL AT NEW DOOR WALL AND
EXISTING WALL TYPICAL
3"=1'-0"
SCALE FEET
1 1/2"=1'-0"
SCALE FEET
File details come from the government source that posted it. Updated .