Exhibit U - 2-1-561_WH16 Elev Elec Rm_Amend 01_Sheet A05.pdf

PDF 439 KB Posted

Attached to
Wilson Hall Floor 16 Electric and Elevator Machine Rooms Fire Rating and Mechanical Upgrade
Solicitation number
385515GMK
Issued by

About this file

This is an architectural drawing document that provides wall types and construction details for the WH16 Electrical and Elevator Machine Rooms fire rating and mechanical upgrade project. The document is project number 2-1-561 and was issued for bidding on 08/17/2026 with Amendment 1 dated 11/20/2026.

The document specifies multiple wall construction types and finishes required for fire-rated wall assemblies. Paint Schedule requirements include Benjamin Moore Eco Spec N374 in Ivory White 925 with eggshell finish for interior surfaces. Wall Type EX (existing) requires one layer of 5/8" Type X gypsum board on both sides of existing walls. Wall Type A1 specifies two layers of 5/8" gypsum board on 3-5/8" metal studs 16" on center with sound attenuation blanket, achieving a 2-hour fire rating. New infill wall construction requires two layers of 1/2" Type X gypsum board on 3-5/8" metal studs on both sides to match existing wall thickness of 6-7/8". For concrete masonry unit (CMU) walls, abandoned openings must be infilled with solid masonry to full wall thickness using fire wall construction meeting 2-hour specifications per NFPA 80, with new mortar matching existing color and joint profiles. Exterior CMU surfaces require sealing with Sika Thorocoat 400 in Whip Cream color. All fire sealants must comply with specifications at joints and connections, including rated slip joint connections (UL Design U419). Door frames are specified as 90-minute rated with corner bead typical at all corners. The drawing includes six detail sheets at various scales showing typical plan details at infills for wall types and new door wall assemblies.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PAINT SCHEDULE

PT-1 BENJAMIN MOORE. ECO SPEC N374

COLOR: IVORY WHITE 925

EGG SHELL FINISH

PT-2 BENJAMIN MOORE. ECO SPEC N374

COLOR: IVORY WHITE 925

FLOOR SLAB

FIRE SEALANT BOTH SIDES AS

PER SPECIFICATIONS

2 HR. RATED WALL

EX.

EXISTING WALL TO REMAIN.

REFER TO WALL TYPE EX.

T.O. EXISTING STUD WALL

+/- 8'- 1" A.F.F. AT EL. 961'-5"

EX.EXIST.

EXISTING CONCRETE

BEAM

PROVIDE 5/8" TYPE X GWB ON

EXISTING WALL BOTH SIDES

SIM.

A-05

6 7/8"

2 LAYERS OF 5/8" GYP. BD. EACH SIDE ON 3-5/8"

MTL. STUDS 16" O.C.

STRUCTURE ABOVE, SEE

STRUCTURAL

6 1/8"

SOUND ATTENUATION BLANKET

FULL HT.

FLOOR SLAB

FIRE SEALANT BOTH SIDES

RATED SLIP JOINT

CONNECTION

UL DES U419

2 HR. RATED WALL

SIM.

A-05

(SIM)

EXISTING WALL TO REMAIN.

REFER TO WALL TYPE EX

ONE LAYER OF 5/8" TYPE X GWB ON BOTH SIDES EXISTING WALL

AND NEW INFILL

NOTE:

1. REMOVE ALL EXISTING MATERIAL FROM ABANDONED REGISTERS AND/OR EQUIPMENT.

2. CLEAN THE CAVITY AND PRIME AS NECESSARY FOR NEW 2-HR WALL CONSTRUCTION

INFILL.

3. FINAL WALL CONSTRUCTION TO MEET 2-HOUR WALL RATING.

E X

IS

T

NEW INFILL TO HAVE TWO LAYERS OF 1/2" TYPE X GWB

ON 3 5/8" METAL STUDS ON BOTH SIDES. MATCH EXISTING

WALL THICKNESS.

/8

EXISTING CMU WALL

PROVIDE NEW SOLID MASONRY INFILL TO MAINTAIN THE

REQUIRED FIRE -FESITANT RATING.

CMU TO FILL EXISTING VOID TO FULL WALL THICKNESS.

NEW MORTAR TO MATCH EXISTING COLOR AND JOINT PROFILE.

MUST BLEND WITH EXISTING CMU.

NOTE:

1. REMOVE ALL EXISTING MATERIAL FROM ABANDONED DUCTWORK AND/OR EQUIPMENT.

2. CLEAN THE CAVITY AND PRIME AS NECESSARY FOR NEW MORTAR APPLICATION.

3. NEW MORTAR JOINTS AND CMU INFILL TO MATCH EXISTING GROUT LINES AT ALL SIDES.

4. ABANDONED OPENINGS IN EXISTING 2-HOUR FIRE RATED CMU WALLS SHALL BE INFILLED

TO FULL WALL THICKNESS. PROVIDE TIGHT- FITTING SOLID MASONRY INFILL USING A FIRE

WALL CONSTRUCTION TO MEET 2-HOUR WALL SPECIFICATIONS AS PER NFPA 80

5. AT EXTERIOR WALL LOCATIONS, EXTERIOR SIDE OF CMU TO BE SEALED WITH SIKA

THOROCOAT 400 AS PER MANUFACTURER GUIDELINES. COLOR TO BE "WHIP CREAM".

REFER TO SPECIFICATION SECTION 099100

FLOOR SLAB

EXISTING 1 HOUR FIRE

WALL TO REMAIN.

REFER TO SHEET G-04

FOR REFERENCE.

ASSUME TWO LAYERS

OF 1/2" FIRECODE C

GWB ON 3 5/8" METAL

STUDS

EXISTING CEILING

HERCULITE 20 ON

3/4" PLYWOOD

TO BE REMOVED

T.O. EXISTING STUD WALL

+/- 8'- 1" A.F.F. AT EL. 961'-5"

EXISTING CONCRETE

BEAM

NEW TWO LAYERS 5/8" TYPE X

GWB AT TOP OF EXISTING GWB

EXISTING WALL TO REMAIN.

REFER TO WALL TYPE EX

GWB CORNER BEAD TYPICAL AT

ALL CORNERS

CEILING TO BE 2 HOUR FIRE RATING

TWO LAYERS OF 5/8" TYPE X GWB

BOTH SIDES ON 3 5/8" METAL STUDS

T.O. EXISTING STUD WALL

+/- 8'- 1" A.F.F. AT EL. 961'-5"

EXIST.

USG PAPER FACED

METAL CORNER

BEAD

EXISTING CONCRETE

BEAM

FIRE SEALANT AS PER

SPECIFICATIONS BOTH

SIDES

EDGE OF EXISTING SLAB

E X

IS

T

A1 ±10 5/8"

GWB CORNER BEAD

TYPICAL AT ALL CORNERS

NEW 5/8" TYPE X GWB APPLIED

TO EXIST. WALL

TYPICAL BOTH SIDES

EXTEND TO NEW OPENING.

NEW TWO LAYERS OF 5/8" GWB

ON 3 5/8" MTL STUDS

90 MIN. DOOR AND FRAME

REFER TO SCHEDULE AND

MANUFACTURER

INSTALLATION

REQUIREMENTS

NEW 5/8" TYPE X GWB ON TWO LAYERS OF

1/2" TYPE X GWB BOTH SIDES ON 3 5/8" MTL

STUDS

APPLY FIRE

SEALANT AT ALL

JOINTS AS PER

SPECIFICATIONS

A3

ALIGN

/8

SCALE:

PROJECT NO.

SHEET NO.

DESIGNED

DRAWN

CHECKED

APPROVED

ISD ENGINEERING DATE

PROJECT NAME.

SHEET NAME:

REVISION NO.FIMS. NO.

ISD

INFRASTRUCTURE

SERVICES DIVISION

C :\U se rs

\jd ra g ov i\D o cu m en ts

\2 -1

-5

1_ W

H

E le v

E le c R m _V

_j dr a go vi

.r vt

1/

/2

:2

9:

P M

WH16 ELEC. & ELEV.MACHINE ROOMS-

FIRE RATING & MECH. UPGRADE

WALL TYPES AND DETAILS A-05

2-1-561

/2

0/

A m m en dm en t 0

JAD

JAD

JAD

JAD

001REVISIONS

REV. DESCRIPTION DATE

ISSUE FOR CCR 01/30/2026

ISSUE FOR BIDDING 08/17/2026

1 AMMENDMENT 1 11/20/2026

1 1/2" = 1'-0"A-05

2 TYPE A1

1 1/2" = 1'-0"A-05

3 TYPE A2

3" = 1'-0"A-05

6 TYP. PLAN DETAIL AT INFILL- WALL TYPE A

3" = 1'-0"A-05

5 TYP. PLAN DETAIL AT INFILL- WALL TYPE B

1 1/2" = 1'-0"A-05

1 TYPE EX (EXISTING)

3" = 1'-0"A-05

7 TYPE A1

3" = 1'-0"A-05

DETAIL AT NEW DOOR WALL AND

EXISTING WALL TYPICAL

3"=1'-0"

SCALE FEET

1 1/2"=1'-0"

SCALE FEET