36E77619R0073-0004003.pdf
PDF 275 KB Posted
- Solicitation number
- 36E77619R0073
About this file
36E77619R0073 0004 M603 - MECHANICAL ELELCTRICAL SCHEDULES.pdf
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER: Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
STAMP
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M E
P R ja s o n g .r v t
/2
/2
:5
:4
P
M
1361-M603
MECHANICAL ELELCTRICAL
SCHEDULES
UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 JG SAProject Number 47
06/04/2019
06/04/2019
EQUIPMENT
TAG APPLICATION
FAN COOLING COIL HEATING HUMIDIFIER FILTER
MANUFACTURER MODEL NUMBER MECHANICAL NOTES
NUMBER
OF FANS
MOTOR HP
(EACH) CFM
ESP
(IN)
WATER AIR SENSIBLE
CAPACITY
(MBH)
TOTAL
CAPACITY
(MBH) TYPE LBS/HR KW TYPE MERV
EFFICIENCY
PRESSURE DROP
AT 50% LOADING
(IN W.C.)
EWT
(F)
LWT
(F) GPM GLYCOL TYPE
WPD
(FT)
EAT DB
(F)
EAT WB
(F)
LAT DB
(F)
LAT WB
(F)
AC 01 BR-118B COOLING 1 1.3 1450 0.8 44 54 6.1 NA 4.3 68 57 50 49 28.6 30.4 NA 10.8 - CANISTER 11 65 0.5 LEIBERT PW011CC1 1S209HCMRBF 1,2,3,4,5,6,7,8
AC 02 BR-118 COOLING 1 1.3 900 0.8 44 54 4.3 NA 4.3 68 56 50 49 17.8 21.5 NA 10.8 - CANISTER 11 65 0.5 LEIBERT PW011CC1 1S209HCMRBF 1,2,3,4,5,6,7,8
AC 03 BR-118C COOLING 1 1.3 1750 0.8 44 54 6.3 NA 4.3 58 57 49 48.5 17,270 31.5 NA 10.8 - CANISTER 11 65 0.5 LEIBERT PW011CC1 1S209HCMRBF 1,2,3,4,5,6,7,8
EQUIPMENT
TAG HP/LOAD VOLTAGE PHASE
CALCULATED
AFC
CONTROLLER DISCONNECT AT MOTOR
PANEL CIRCUIT NUMBER CONDUIT/FEEDER SIZE ELECTRICAL NOTESTYPE
FURNISHED BY/
INSTALLED BY LOCATION CTRL WIRE BY AMPS/TYPE
FUSE SIZE
(AMPS) NEMA TYPE
FURNISHED BY/
INSTALLED BY LOCATION
AC 01 7.6 FLA 480 V 3 - CP MANUFACTURER INTEGRAL MANUFACTURER 15/CB N/A 1 DIV 26/DIV 26 AT UNIT EHBM3-1 31,33,35 3/4"C. (3)#12, (1)#12G 1
AC 02 7.6 FLA 480 V 3 - CP MANUFACTURER INTEGRAL MANUFACTURER 15/CB N/A 1 DIV 26/DIV 26 AT UNIT EHBM3-1 31,33,35 3/4"C. (3)#12, (1)#12G 1
AC 03 7.6 FLA 480 V 3 - CP MANUFACTURER INTEGRAL MANUFACTURER 15/CB N/A 1 DIV 26/DIV 26 AT UNIT EHBM3-1 31,33,35 3/4"C. (3)#12, (1)#12G 1
MECHANICAL NOTES:
1. PROVIDE WITH UPFLOW DISCHARGE PLENUM WITH DUCT COLLAR.
2. PROVIDE WITH REAR RETURN FLOORSTAND.
3. PROVIDE WITH 2-WAY CONTROL VALVE AND ALL VENT/DRAIN, ISOLATION VALVES, STRAINERS, AND CIRCUIT SETTER FOR BALANCING PURPOSES.
4. PROVIDE WITH TWO SETS OF 2" PLEATED MERV 11 FILTERS. COORIDNATE STOARGE OF REPLACEMENT SET OF FILTERS WITH VA FACILITIES.
5. PROVIDE LIEBERT ICOM CONTROLLER MOUNTED DIRECTLY TO FRONT OF UNIT. INCLUDE BACNET NETWORK CARD FOR FULL INTEGRATION INTO EXISTING BUILDING AUTOMATION SYSTEM.
6. PROVIDE CONDENATE PUMP. ROUTE ALL CONDENSATE TO NEAREST FLOOR DRAIN OR SINK. INCLUDE CABLE TYPE LEAK DETECTION AROUND FLOOR DRAIN AND WIRE ALARM NOTIFICATION INTO BUILDING AUTOMATION AND LOCAL AUDIBLE ALARM.
7. PROVIDE BOTH HIGH TEMP AND SMOKE DETECORS WITHIN UNIT. WIRE BOTH ALARM NOTRIFICATION INTO BUILDING AUTOMATION SYSTEM.
8. PROVIDE WITH LARGE COMMUNICATION DISPLAY.
9. MANUFACURER TO SEND TECHNICIAN ON-SITE FOR FACTORY START-UP, VA FACILITY TRAINING, AND PERFORMANCE TESTING.
COMPUTER ROOM AIR CONDITIONING UNIT SCHEDULE - CHILLED WATER
GENERAL ELECTRICAL NOTES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY
DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
B. MECHANICAL EQUIPMENT AND CORRESPONDING ELECTRICAL DISCONNECTS/CONTROLLERS SHALL HAVE A
STANDARD SHORT-
CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN IN THE SCHEDULE.
MECHANICAL (238123)
ELECTRICAL
ELECTRICAL NOTES:
CONTROLLER TYPES:
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT
OVERLOADS)
A. REFER TO CALCULATED AVAILABLE FAULT CURRENT COLUMN IN THE ELECTRICAL SCHEDULE BELOW FOR MINIMUM
REQUIRED AVAILABLE FAULT CURRENT (AFC) FOR SCHEDULED MANUFACTURER.
GENERAL MECHANICAL NOTES:
EQUIPMENT TAG APPLICATION TYPE CFM ESP (IN W.C.) BHP FAN RPM
DRIVE
TYPE SONES
VFD
(YES/NO) MANUFACTURER MODEL NUMBER MECHANICAL NOTES
70.EF BR118C.1 BR-118C - TYPE A2 HOOD UTILITY 1400 1.5" 0.76 2809 BELT 16.5 NO GREENHECK 10 USF-300 2,3,4,5
70.EF BR118C.2 BR-118C - TYPE B2 HOOD UTILITY 800 3.5" 0.9 2809 BELT 16.5 NO GREENHECK 08 USF-300 2,3,4,5
EF 146 BR-119 - TYPE B2 HOOD UTILITY 600 3.0" EXISTING NOTE 1 BELT EXISTING NO EXISTING EXISTING 1
EQUIPMENT
TAG HP/LOAD VOLTAGE PHASE
CALCULATED
AFC
CONTROLLER DISCONNECT AT MOTOR
PANEL
CIRCUIT
NUMBER CONDUIT/FEEDER SIZE
ELECTRICAL
NOTESTYPE
FURNISHED BY/
INSTALLED BY LOCATION CTRL WIRE BY AMPS/TYPE
FUSE SIZE
(AMPS) NEMA TYPE
FURNISHED
BY/ INSTALLED
BY LOCATION
70.EF
BR118C.1
1 HP 480 V 3 - STARTER DIV 26/DIV 26 AT UNIT DIV 26 15/CB N/A 1 DIV 26/DIV 26 AT UNIT EDP-NC 14,16,18 3/4"C. (3)#12, (1)#12G
70.EF
BR118C.2
1 HP 480 V 3 - STARTER DIV 26/DIV 26 AT UNIT DIV 26 15/CB N/A 1 DIV 26/DIV 26 AT UNIT EDP-NC 13,15,17 3/4"C. (3)#12, (1)#12G
MECHANICAL NOTES:
1. REPLACE EXISTING FAN SHEAVE, DRIVE AND BELT AS REQUIRED TO ATTAIN SCHEDULED CFM.
2. CONTRACTOR TO RESHEAVE AND BALANCE UNIT ON SITE. NOTE THAT AIRFLOWS LISTED MAY BE FOR FUTURE VOLUME REQUIREMENTS AND COULD REQUIRE SIGNIFICANTLY LESS AIRFLOW BASED ON FINAL BSC HOOD SELECTION.
3. PROVIDE EACH NEW EXHAUST FAN WITH VFD FOR BALANCING PURPOSES. NO ISOLATION DAMPERS SHALL BE ALLOWED WITHIN HARZARDOUS EXHAUST DUCTWORK.
4. PROVIDE CONCRETE EQUIPMENT PAD AND SPRING TYPE VIBRATION ISOLATORS FOR EACH NEW EXHAUST FAN.
5. PROVIDE EACH FAN SCROLL WITH WELDED CONSTRUCTION AND HEAVY EPOXY COATING FOR CORROSION PROTECTION. ROUTE DISCHARGE DUCT UP THROUGH PENTHOUSE ROOF WITH DRAIN FOR WATER INFIILTRATION.
FAN SCHEDULE
GENERAL ELECTRICAL NOTES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY
DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
B. MECHANICAL EQUIPMENT AND CORRESPONDING ELECTRICAL DISCONNECTS/CONTROLLERS SHALL HAVE A
STANDARD SHORT-
CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN IN THE SCHEDULE.
MECHANICAL (233413, 233416, 233423)
ELECTRICAL
ELECTRICAL NOTES:
CONTROLLER TYPES:
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
A. REFER TO CALCULATED AVAILABLE FAULT CURRENT COLUMN IN THE ELECTRICAL SCHEDULE BELOW FOR MINIMUM
REQUIRED AVAILABLE FAULT CURRENT (AFC) FOR SCHEDULED MANUFACTURER.
GENERAL MECHANICAL NOTES:
Signature
Name
Date
Registration Number
Jason R. Gottwalt, P.E.
41360
Signature
Name
Date
Registration Number
Curtis D. Barlage, P.E.
45914
Revisions: Date:
Revision 1 Date 1
| Sheets |
| M603 - MECHANICAL ELELCTRICAL SCHEDULES |
File details come from the government source that posted it.