36E77619R0073-0004002.pdf
PDF 325 KB Posted
- Solicitation number
- 36E77619R0073
About this file
36E77619R0073 0004 M602 - MECHANICAL ELELCTRICAL SCHEDULES.pdf
View the file
Other files
Show all 39
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER: Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
STAMP
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M E
P R ja s o n g .r v t
/2
/2
:3
:0
A
M
1361-M602
MECHANICAL ELELCTRICAL
SCHEDULES
UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 JG SAProject Number 46
06/04/2019
06/04/2019
EQUIPMENT TAG APPLICATION
FACE & BYPASS DAMPERS
(YES/NO)
MIXING BOX
(YES/NO)
MINIMUM
OUTDOOR AIR CFM COOLING COIL HEATING COIL AIR PRE-FILTER AIR FINAL-FILTER HUMIDIFIER
SUPPLY
FAN RETURN FAN MANUFACTURER MODEL NUMBER MECHANICAL NOTES
70-AHPN 37 REPLACEMENT YES YES AHUCC 37 AHUHC 37 AHUPF 37 AHUFF 37 AHUH 37 AHUS 37 EXISTING EXTERNAL TEMTROL CUSTOM AHU 1
70-AVPN 4 MODIFICATION AROUND COOLING COIL N/A SEE SEQUENCES AHUCC 4 NA EXISTING AHUFF 4 NONE AHUS 4 N/A EXISTING RETROFIT MATERIALS 2
MECHANICAL NOTES:
1. UNIT WILL BE FULLY REPLACED WITH NEW CUSTOM AHU BUILT ON-SITE AS INDICATED ON PLANS/SPECS. REFER TO DRAWINGS FOR STAGING OF MATERIALS AND CONSTRUCTION PHASING.
2. EXISTING MAKE-UP AIR UNIT WILL BE MODIFIED TO TEMPORARILY SERVE EXISTING AREAS FOR AHPN-37 REPLACEMENT. REFER TO PLANS FOR MODIFICATIONS TO FLOOR AND ACCESS DOORS WITHIN EXISTING AHU CASING.
AIR HANDLING UNIT SCHEDULE
MECHANICAL (237313, 237316, 237333, 237339)
A. REFER TO CALCULATED AVAILABLE FAULT CURRENT COLUMN IN THE ELECTRICAL SCHEDULE BELOW FOR MINIMUM
REQUIRED AVAILABLE FAULT CURRENT (AFC) FOR SCHEDULED MANUFACTURER.
GENERAL MECHANICAL NOTES:
EQUIPMENT
TAG AHU SERVED CFM
COIL AIR WATER
SENSIBLE
CAPACITY
(MBH)
TOTAL
CAPACITY
(MBH) MANUFACTURER MODEL NUMBER
MECHANICAL
NOTES
NUMBER
OF COILS
EACH COIL SIZE
(W"xH") ROWS
FINS
PER
INCH
EAT LAT FACE
VELOCITY
(FPM)
APD (IN
W.C.)
EWT
(F)
LWT
(F) GPM
GLYCOL
TYPE
WPD
(FT)
DB
(F)
WB
(F)
DB
(F)
WB
(F)
AHUCC 4 70-AVPN 4 35,000 4 83"X40.5" 4 8 89 73 58.2 56.6 375 0.29" 42 54 300 NONE 4.6' 1,094 1,810 TEMTROL 5WC-4-40.5X83X4-8 AL 1,2,3,4
AHUCC 4 CHWC 08 35,000 4 83"X40.5" 4 8 89 73 58.2 56.6 375 0.29" 42 54 300 NONE 4.6' 1,094 1,810 TEMTROL 5WC-4-40.5X83X4-8 AL 1,2,3,4
AHUCC 37 70-AHPN 37 48,000 6 71"X33" 8 8 85 69 49.6 49.3 492 0.83" 42 54 438 NONE 10.8' 1,733 2,643 TEMTROL 5WC-8-33X71-8-8 AL 1,2,3
MECHANICAL NOTES:
1. FLOW AND CAPACITY IS TOTAL FOR THE AHU AT MINIMUM OUTDOOR AIRFLOW OPERATION.
2. PROVIDE COIL WITH 304 STAINLESS STEEL CASING AND SUPPORT RACK. DRAIN PAN SHALL BE DOUBLE SLOPED 316 STAINLESS STEEL.
3. REFER TO PIPING DETAILS FOR REQUIRED VALVES AND COMPONENTS. EACH COIL SHALL BE PROVIDED WITH INDIVIDUAL CIRCUIT SETTER BALANCING VALVES SO THAT FLOW IS EQUALLY DISTRIBUTED TO ALL COIL SECTIONS.
4. COILS TO BE SHIPPED LOOSE FOR FIELD INSTALLATION WITHIN EXISTING AHU CASING. CONTRACTOR TO FIELD FABRICATE FRAME AND DRAIN PANS AS REQUIRED.
AIR HANDLING UNIT - COOLING COIL SCHEDULE - CHILLED WATER
MECHANICAL (238216)
EQUIPMENT
TAG
AHU
SERVED CFM
COIL AIR STEAM
CAPACITY (MBH) MANUFACTURER
MODEL
NUMBER
MECHANICAL
NOTES
NUMBER
OF COILS
SIZE
(W"xH") ROWS
FINS
PER
INCH
EAT
(F)
LAT
(F)
FACE
VELOCITY
(FPM) APD (IN W.C.)
STEAM
CAPACITY
(LBS/HR)
INLET STEAM
PRESSURE
(PSIG)
AHUHC 37 70-AHPN 37 24,000 (X2) 2 58"X96" 2 8 -20 50 802 0.33" 1912 (EACH X2) 30 PSI 1775 (EACH X2) LJ WING VE - 5T 1,2,3,4
MECHANICAL NOTES:
1. FLOW AND CAPACITY IS TOTAL FOR THE AHU.
2. PROVIDE AS INTEGRAL FACE-AND-BYPASS COIL THAT INCLUDES ALL REQUIRED DAMPER ACTUATORS AND CONTROLS COMPONENTS.
3. REFER TO PIPING DETAILS FOR ALL REQUIRED PIPING COMPONENTS. INCLUDE ALL STEAM TRAP MONITORS SHOWN AND INTEGRATE INTO BAS.
4. DATA SHOWN IS FOR EACH COIL (X2). PREHEAT SHALL BE CABABLE OF ENTIRE 48,000 CFM OF FULL OUTDOOR AIRFLOW DURING SMOKE PURGE SEQUENCE.
5. PROVIDE 1/3 AND 2/3 CONTROL VALVES AND STEAM TRAPS WITH REMOTE MONITORING PER DRAWING DETAILS.
AIR HANDLING UNIT - HEATING COIL SCHEDULE - STEAM
MECHANICAL (238216)
MECHANICAL NOTES:
1. REFER TO PIPING DETAIL FOR INSTALLATION OF PRESSURIZAED DRAIN PAN TO HEAT ALL CONDENSATE BACK INTO STEAM.
2. ALL STEAM TRAPS WILL REQUIRE MONTIORS INTEGRATED INTO BUILDING AUTOMATION TO NOTIFY OF POTENTIAL TRAP FAILURES.
3. MOUNT HUMIDIFER UP HIGH ENOUGH TO ALLOW FOR ADEQUATE DRIP LEGS AND ELEVATION FOR CONDENSATE PIPING INDICATED.
AIR HANDLING UNIT - HUMIDIFIER SCHEDULE
MECHANICAL (238413)
EQUIPMENT
TAG AHU SERVED TYPE CFM
EAT DB
(F)
STEAM
CAPACITY
(LBS/HR)
INLET STEAM
PRESSURE
(PSIG)
NUMBER OF
MANIFOLDS
MANIFOLD
LENGTH
(IN)
TUBE
SPACING (IN)
ABSORPTION
DISTANCE
(FT) MANUFACTURER MODEL NUMBER
MECHANICAL
NOTES
AHUH 37 70-AHPN 37 PRESSURIZED PAN 48,000 60 683 30 PSI 24" 9" <18" DRISTEEM ULTRASORB XV 1,2,3
EQUIPMENT
TAG
AHU
SERVED TYPE CFM
NUMBER OF
MODULES
SIZE PER MODULE
(H"xL"xD")
EFFICIENCY
MERV
RATING
APD CLEAN
(IN W.C.)
APD AT 50%
LOADING (IN W.C.) MANUFACTURER
MODEL
NUMBER
MECHANICAL
NOTES
AHUPF 37 70-AHPN 37 PLEATED NOTE 1 NOTE 2 NOTE 2 35 8 0.35 0.61 HUNTAIR TYPE 8 SS 1,2
MECHANICAL NOTES:
1. SEE AIR HANDLING UNIT SCHEDULE.
2. COORDINATE WITH AIR HANDLING UNIT SUPPLIER FOR MAXIMUM FACE VELOCITY OF 500 FPM DEPTH OF FILTER TO BE 2".
AIR HANDLING UNIT - PREFILTER SCHEDULE
MECHANICAL (234100)
EQUIPMENT
TAG AHU SERVED
NUMBER OF
FANS TYPE CFM PER FAN TOTAL CFM ESP (IN W.C.)
TOTAL SP
(IN W.C.)
WHEEL
DIAMETER
(IN)
VFD
(YES/NO) FAN RPM BHP
DRIVE TYPE
(BELT/DIRECT) MANUFACTURER
MODEL
NUMBER MECHANICAL NOTES
AHUS 4 70-AVPN 4 9 / 12 FANWALL 3,888 / 5,833 35,000 / 70,000 3.5" / 7.0" 16" YES 3,039 / 3,373 6.13 / 6.28 DIRECT VENTROL 16-60-213T 1,2,3,4,6
AHUS 4 CHWC 08 12 FANWALL 4,363 48,000 6.5 16" YES 3,174 6.53 DIRECT VENTROL 16-90-213T 1,2,3,4,5
AHUS 37 70-AHPN 37 12 FANWALL 4,363 48,000 6.5" 18" YES 3,174 6.53 DIRECT VENTROL 18-90-213T 1,2,3,4,5
EQUIPMENT
TAG HP/LOAD VOLTAGE PHASE
CALCULATED
AFC
CONTROLLER DISCONNECT AT MOTOR
PANEL
CIRCUIT
NUMBER CONDUIT/FEEDER SIZE
ELECTRICAL
NOTESTYPE
FURNISHED BY/
INSTALLED BY LOCATION CTRL WIRE BY AMPS/TYPE
FUSE SIZE
(AMPS) NEMA TYPE
FURNISHED
BY/ INSTALLED
BY LOCATION
70-AHPN 4 104 FLA 480 V 3 - VFD MANUFACTURER AT UNIT MANUFACTUR
ER
150/CB N/A 1 DIV 26/DIV 26 AT UNIT EDP-NC 2,4,6 2"C. (4)#2, (1)#6G
70-AHPN 37 104 FLA 480 V 3 - VFD MANUFACTURER AT UNIT MANUFACTUR
ER
150/CB N/A 1 DIV 26/DIV 26 AT UNIT EDP-NC 38,40,42 2"C. (4)#2, (1)#6G
MECHANICAL NOTES:
1. PROVIDE FANWALL ARRAY WITH INDIVIDUAL VFD'S FOR EACH FAN MOTOR. ALL VFD'S SHALL BE MOUNTED IN ENCLSOURE WITH REMOTE DISPAY MOUNTED ON FRONT PANEL. INCLUDE DISCONNECT SWITCHES FOR EACH VFD/MOTOR TO REMOVE SINGLE FAN REPLACEMENT.
2. PROVIDE EACH FANWALL CUBE WITH INDIVIDUAL BACKDRAFT DAMPERS TO ISOLATE FROM SERVICE DURING SEQUENCING, OR MAINTENANCE/SERVICE.
3. VFD ENCLOSURE SHALL BE PREWIRED WITH SINGLE POINT OF CONNECTION WITH INPUT LINE REACTOR AND PRIMARY DISCONNECT.
4. START-UP TECHNICIAN SHALL VERIFY BALANCE OF FAN WHEELS TO BE IN ACCEPTABLE LEVEL OF TOLERANCE AFTER FEILD ASSEMBLY OF AHU CASING AND FANWALL CUBES. ISOLATE ENTIRE FANWALL ASSEMBLY WITH NEOPRENE PAD AT UNIT FLOOR.
5. AIRFLOWS SHOWN ARE WITH 'N+1' REDNEDNACY. SELECTION OF FANS SHALL ALLOW FOR FULL DESIGN AIRFLOW UNDER LOSS OF ONE FAN UNIT.
6. AIRFLOWS SHOWN ARE FOR TWO DISTINCT OPERATING CONDITIONS. EITHER IN TEMPORARY AHU SERVICE (OR POTENTIAL FLAGG ATRIUM PRESSURIZATION) OR SMOKE PURGE MODE MAKE-UP AIR. FAN SELECTION SHALL SATISFY BOTH MODES.
AIR HANDLING UNIT - SUPPLY FAN SCHEDULE
GENERAL ELECTRICAL NOTES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY
DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
B. MECHANICAL EQUIPMENT AND CORRESPONDING ELECTRICAL DISCONNECTS/CONTROLLERS SHALL HAVE A
STANDARD SHORT-
CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN IN THE SCHEDULE.
MECHANICAL (233416)
ELECTRICAL
ELECTRICAL NOTES:
CONTROLLER TYPES:
VFD - VARIABLE FREQUENCY MOTOR CONTROLLER
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT OVERLOADS)
A. REFER TO CALCULATED AVAILABLE FAULT CURRENT COLUMN IN THE ELECTRICAL SCHEDULE BELOW FOR MINIMUM
REQUIRED AVAILABLE FAULT CURRENT (AFC) FOR SCHEDULED MANUFACTURER.
GENERAL MECHANICAL NOTES:
EQUIPMENT
TAG
AHU
SERVED TYPE CFM
NUMBER OF
MODULES
SIZE PER MODULE
(H"xL"xD")
EFFICIENCY
MERV
RATING
APD CLEAN
(IN W.C.)
APD AT 50%
LOADING (IN W.C.) MANUFACTURER MODEL NUMBER
MECHANICAL
NOTES
AHUFF 4 70-AVPN 4 12" MINI-PLEAT 35,000 20 24"X24" 98 14 0.5 1.0 CAMFIL 3P GLIDE/PACK 1,2,3
AHUFF 4 CHWC 08 12" MINI-PLEAT 35,000 20 24"X24" 98 14 0.5 1.0 CAMFIL 3P GLIDE/PACK 1,2,3
AHUFF 37 70-AHPN 37 12"MINI-PLEAT NOTE 1 NOTE 2 NOTE 2 98 14 0.5 1.0 HUNTAIR - 1,2
MECHANICAL NOTES:
1. SEE AIR HANDLING UNIT SCHEDULE.
2. COORDINATE WITH AIR HANDLING UNIT SUPPLIER FOR MAXIMUM FACE VELOCITY OF 500 FPM DEPTH OF FILTER TO BE 12".
3. PROVIDE SIDE LOADING FILTER HOUSING FOR INSTALLATION OUTSIDE OF EXISTING AIR HANDLING UNIT, SEE DRAWING DETAILS.
AIR HANDLING UNIT - FINAL FILTER SCHEDULE
MECHANICAL (234133)
MAGNETIC STARTER SCHEDULE
GENERAL NOTES:
A. REFER TO ENCLOSED CONTROLLER SPECIFICATION FOR ACCESSORIES/MODIFIERS.
B. REFER TO MOTOR SCHEDULE FOR DISCONNECT REQUIRED AT MOTOR WHEN STARTER/DISCONNECT COMBINATION DOES NOT SATISFY THE REQUIREMENT.
NOTES:
STARTER TYPES:
FVNR - FULL VOLTAGE NON-REVERSING
FVR - FULL VOLTAGE REVERSING
RVS - REDUCED VOLTAGE STARTER
MULTI - MULTIPLE SPEED MAGNETIC STARTER
EQUIPMENT
TAG VOLTAGE PHASE
ENCLOSURE
(NEMA TYPE)
STARTER DISCONNECT AT STARTER
NOTESTYPE SIZE
CONTROL
VOLTAGE
DISCONNECT
(COMBINATION/
EXTERNAL) AMPS/TYPE
FUSE SIZE
(AMPS)
FURNISHED BY/
INSTALLED BY
EQUIPMENT
TAG APPLICATION CFM
MODULE SIZE
(W"xL")
DUCT
CONNECTION
SIZE (IN)
EFFICIENCY
(%) MANUFACTURER MODEL NUMBER MECHANICAL NOTES
FFU HEPA FILTER SEE DWGS 48"X24" SEE DWGS 99.99% ENVIRCO MAC 10 LEAC RSRC 1,2,3,4
EQUIPMENT
TAG HP/LOAD VOLTAGE PHASE
CALCULATED
AFC
CONTROLLER DISCONNECT AT MOTOR
PANEL
CIRCUIT
NUMBER CONDUIT/FEEDER SIZE
ELECTRICAL
NOTESTYPE
FURNISHED BY/
INSTALLED BY LOCATION CTRL WIRE BY AMPS/TYPE
FUSE SIZE
(AMPS) NEMA TYPE
FURNISHED
BY/ INSTALLED
BY LOCATION
FFU . 1 HP 208 V 1 - 3-SPEED
SWITCH
MANUFACTURER INTEGRAL MANUFACTURER MRS N/A 1 DIV 26/DIV 26 3F-117A CL3G1-2 2,4 3/4"C. (2)#12, (1)#12G 1,2
MECHANICAL NOTES:
1. FAN FILTER UNIT SHALL HAVE ACCESS FOR ROOM SIDE REPLACEABLE FILTER, MOTOR ASSEMBLY, AND CONTROL CARD. FILTER SHALL SET INSIDE KNIFE EDGE SEAL.
2. PROVIDE ROUND INLET CONNECTION TRANSITION OF SIZE INDOCATED ON DRAWINGS.
3. MOTOR SHALL BE A ECM BRUSHLESS MOTOR WITH SPEED CONTROL ADJUSTMENT FOR BALANCING PURPOSES.
4. PROVIDE PRESSURE DIFFERENTIAL SENSOR ACROSS HEPA FILETER AND INTEGRATE NOTIFICATION FOR FILTER CHANGES TO BUILDING AUTOMATION.
FAN FILTER UNIT SCHEDULE
GENERAL ELECTRICAL NOTES:
A. WHEN THE CONTROLLER TYPE IS A VFD OR MAGNETIC STARTER, REFER TO THE VARIABLE FREQUENCY
DRIVE CONTROLLER
SCHEDULE OR THE MAGNETIC STARTER SCHEDULE FOR MORE INFORMATION.
B. MECHANICAL EQUIPMENT AND CORRESPONDING ELECTRICAL DISCONNECTS/CONTROLLERS SHALL HAVE A
STANDARD SHORT-
CIRCUIT CURRENT RATING HIGHER THAN THE CALCULATED VALUE SHOWN IN THE SCHEDULE.
MECHANICAL (238219)
ELECTRICAL
ELECTRICAL NOTES:
1. CONNECT THE (5) FAN FILTER UNITS IN ROOM 3F-117A TO THE SAME CIRCUIT. EACH FAN FILTER IS RATED 390W.
2. DUE TO ISO 7 CLEANROOM STANDARDS, INSTALL MRS DISCONNECT IN ROOM 3F-117A. SEE SHEET E130 FOR LOCATION AND DETAILS.
CONTROLLER TYPES:
MMS - MANUAL MOTOR STARTER (WITH OVERLOADS)
CP - CONTROL PANEL
MAGS - MAGNETIC STARTER
MRS/MS - MOTOR RATED SWITCH (WITHOUT
OVERLOADS)
A. REFER TO CALCULATED AVAILABLE FAULT CURRENT COLUMN IN THE ELECTRICAL SCHEDULE BELOW FOR MINIMUM
REQUIRED AVAILABLE FAULT CURRENT (AFC) FOR SCHEDULED MANUFACTURER.
GENERAL MECHANICAL NOTES: