DESIGNATIONS
SYMBOL SCHEDULE NOTES
SYMBOL
A. THESE SYMBOLS COMPRISE A STANDARD LIST, NOT ALL SYMBOLS
MAY APPEAR ON THESE DRAWINGS.
B. MOUNTING HEIGHTS INDICATED ARE STANDARD. DIMENSIONAL
NUMBERS INDICATED AT DEVICES SHALL OVERRIDE THESE
STANDARDS. MOUNTED HEIGHTS ARE TO THE CENTER OF THE DEVICE,
UNLESS NOTED OTHERWISE.
C. MOUNTING HEIGHTS INDICATED ARE FOR STUD WALL CONSTRUCTION.
WHEN BLOCK OR BRICK CONSTRUCTION IS USED, ADJUST MOUNTING
HEIGHTS TO ALIGN DEVICE PLATES WITH RUNNING JOINT.
D. REFER TO SPECIFICATIONS FOR FURTHER INFORMATION.
GENERAL
HEAVY DASHED LINE WEIGHT INDICATES
EXISTING ITEM TO BE REMOVED.
LIGHT SOLID LINE WEIGHT INDICATES EXISTING
ITEM TO REMAIN.
HEAVY SOLID LINE WEIGHT INDICATES NEW
ITEM OR NEW LOCATION.
REMOVE EXISTING ITEMR
REMOVE EXISTING ITEM AND RELOCATE AS INDICATEDRL
X
NL
EXISTING ITEM TO REMAIN
NEW LOCATION FOR RELOCATED ITEM
NOTES & TAGS
EQUIPMENT IDENTIFICATION TAG - SEE EQUIPMENT SCHEDULES
FEEDER SIZE TAG - SEE POWER RISER SCHEDULE
RACEWAYS
ELEC EQUIP CONNECTION TAG - SEE EQUIPMENT SCHEDULE
KEYNOTE
MISCELLANEOUS NOTE
CONDUIT CONCEALED IN CEILING OR WALLS
CONDUIT CONCEALED IN THE FLOOR OR BELOW
CONDUIT EXPOSED ON THE CEILING OR WALLS
CONDUIT BURIED UNDERGROUND (# = DEPTH)
CONDUIT WITH BEND DOWN
CONDUIT WITH BEND UP
CONDUIT WITH BUSHED END
CONDUIT WITH BREAK OR CONTINUATION
UG
CIRCUIT HOME RUN
- L1 INDICATES PANEL
- NUMBER
L1 1,3,5
CONDUCTOR COUNT - UNLESS NOTED OTHERWISE
/ SHORT HASH INDICATES 1#12 LINE
/ LONG HASH INDICATES 1#12 NEUTRAL
/ HASH W/DOT INDICATES 1#12 GROUND
PULL BOX, SIZE AS NOTED
JUNCTION BOX - WALL/CEILING MOUNT
WIREWAY, DUCT BANK, OR FLOOR DUCT AS NOTED
CABLE TRAY, TYPE/SIZE AS INDICATED
DESIGNATIONS
SIGNALS COMMUNICATIONS
SYMBOL
MTG
HT
DATA BOX - WALL MOUNT (# = WIRE COUNTS)
VOICE/DATA BOX - WALL MOUNT/FLOOR
BOX (# = WIRE COUNTS)
VOICE BOX - WALL MOUNT (# = WIRE COUNTS)
DOUBLE GANG VOICE BOX - HIGH WALL MOUNT
WIRELESS DATA HUB - WALL/CEILING MOUNT
18"
SPEAKER - WALL/CEILING MOUNT
HORN SPEAKER - WALL MOUNT
VOLUME SWITCH - WALL MOUNT
AUDIO JACK (M=MICROPHONE, A=AUXILIARY)
BUZZER - WALL/CEILING MOUNT
BELL - WALL/CEILING MOUNT
CHIME - WALL/CEILING MOUNT
CLOCK - WALL/CEILING MOUNT (# = DIAMETER)
PROJECTOR/VIDEO CAMERA/DOCUMENT
CAMERA - WALL/CEILING MOUNT
TV SYSTEM OUTLET - WALL/CEILING MOUNT
ANNUNCIATOR PANEL - WALL MOUNT
SECURITY
60"
96"
VERIFY
48"
18"
18"
96"
VERIFY
VERIFY
18"
WALL INTERCOM STATION (M=MASTER, R=REMOTE) 48"
96"
96"
96"
18"
96"
SECURITY - WALL MOUNT - TYPICAL
RX - REQUEST TO EXIT
ES - ELECTRIC STRIKE
EL - ELECTRIC LOCK
ML - MAGNETIC LOCK
TH - POWER TRANSFER HINGE
DC - DOOR CONTACT
ODC - OVERHEAD DOOR CONTACT
MS - MONITOR STRIKE
MD - MOTION DETECTOR
GB - GLASS BREAKER DETECTOR
W
PRJ
#/A xx
AUDIO VIDEO SYSTEM OUTLET - WALL/CEILING MOUNT 18"
A/V SYSTEMS CONTROLLER - WALL MOUNT 18"
SECURITY PANEL - WALL MOUNT VERIFY
P B
S
S
TV
S
J J
S
S
SECURITY
C C
IC
M
AM
V
VID
SECURITY CAMERA - WALL/CEILING MOUNT
VERIFY
CR - CARD READER
KP - KEYPAD
KS - KEY SWITCH
EP - EXIT PUSHBUTTON
M - MASTER STATION
SECURITY - CEILING MOUNT - TYPICAL
TV
AV AV
CX
LIGHTING CONTROL SEQUENCE - SEE SCHEDULE
LC
DESIGNATIONS
SWITCHES AND CONTROLS
SYMBOL
MTG
HT
SINGLE POLE TOGGLE SWITCH
DOUBLE POLE TOGGLE SWITCH
THREE WAY TOGGLE SWITCH
FOUR WAY TOGGLE SWITCH
TOGGLE SWITCH - "a" INDICATES SWITCHING a
48"
PILOT LIGHT TOGGLE SWITCH
ILLUMINATED TOGGLE - TOGGLE SWITCH
KEYED SWITCH
MOMENTARY CONTACT TOGGLE SWITCH
TIMER SWITCH
DIMMER SWITCH (# = WATTAGE)
OCCUPANCY SENSOR - CLG MOUNT
OCCUPANCY SENSOR WALL SWITCH
PHOTO ELECTRIC CELL
TIME CLOCK
CONTACTOR
RELAY
IL
K
MC
TS
OS
PUSH BUTTON STATION - BUTTONS AS INDICATED
FIRE ALARM
48"
48"
48"
48"
48"
48"
48"
48"
48"
48"
48"
48"
60"
60"
MANUAL PULL STATION
HEAT DETECTOR (#=FIXED TEMP, R=RATE OF RISE)
SMOKE DETECTOR (P=PHOTOELEC, I=IONIZATION)
DUCT MOUNTED PHOTOELECTRIC DETECTOR
BEAM DET (B-T=TRANSMITTER, B-R=RECEIVER)
COMBINATION SMOKE DETECTOR AND ALARM
REMOTE STATION - WALL/CEILING MOUNT
REMOTE INDICATOR LAMP - WALL/CEILING MOUNT
FLOW SWITCH
TAMPER SWITCH
MONITOR MODULE
CONTROL MODULE
FIRE/SMOKE DAMPER CONNECTION
DOOR HOLD OR DOOR HOLD CONNECTION
FIREMAN'S STATION - WALL MOUNT
STROBE - WALL/CEILING MOUNT (# = CANDELA)
BELL - WALL/CEILING MOUNT
BELL/STROBE - WALL/CEILING MOUNT (# = CANDELA)
CHIME - WALL/CEILING MOUNT
CHIME/STROBE - WALL/CEILING MOUNT (# = CANDELA)
HORN - WALL/CEILING MOUNT
HORN/STROBE - WALL/CEILING MOUNT (# = CANDELA)
SPEAKER - WALL/CEILING MOUNT
SPEAKER/STROBE - WALL/CEILING MOUNT
(# = CANDELA)
# R
P I
B-T
SA
RS RS
RL RL
FS
TS
MM
CM
SD
DH
48"
72"
72"
48"
82"
82"
82"
82"
82"
82"
82"
82"
82"
FIRE ALARM CONTROL PANEL - WALL MOUNT
F
F F
F F
F
F
F
F F
F F
F
F
F
F
F
F
S
PC
TC
C
R
F F
F F
F F
F F
F F
F F
F F S S
SS
FACP
D#
FS
MULTI SWITCH, MULTI GANG BOX 48"
COMBINATION FIRE ALARM/MASS
NOTIFICATION: SPEAKER/STROBE -
WALL/CEILING MOUNT(# = CANDELA)
82"F A
S SA F
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
PUSH BUTTON SWITCHB 48"
F F
F F C C
CC
DESIGNATIONS
LIGHTING
SYMBOL
MTG
HT
LIGHT FIXTURE ID - REFER TO LIGHT FIXTURE
SCHEDULE
(SCHEDULE OVERRIDES SYMBOL ABBREVIATION)
A - INDICATES LIGHT FIXTURE TYPE
# - INDICATES CIRCUIT NUMBER
b - INDICATES SWITCHING
LIGHT FIXTURE CIRCUIT TYPE
- NO HATCH INDICATES NORMAL CIRCUIT
- ANGLED HATCH INDICATES CRITICAL CIRCUIT
- SOLID HATCH INDICATES LIFE SAFETY CIRCUIT
TROFFER TYPE LIGHT FIXTURE, SIZE AS INDICATED -
CEILING MOUNT
CHANNEL OR INDUSTRIAL, LENGTH AS INDICATED
ROUND DOWNLIGHT, RECESSED OR SURFACE MOUNT
CEILING WALL WASH FIXTURE OR TRACK HEAD
SMALL MOUNT FIXTURE OR SCONCE
LINEAR RECESSED, LENGTH AS INDICATED
UNDER CABINET FIXTURE, LENGTH AS INDICATED
TRACK FIXTURE, NUMBER OF HEADS AS INDICATED
EMERGENCY BATTERY LIGHT - WALL/CEILING MOUNT
EXIT LIGHT, FILLED QUADRANT INDICATES FACES -
WALL/CEILING MOUNT
VERIFY
SITE LIGHTING ROUND OR SQUARE BOLLARD
SITE LIGHTING POLE FIXT, ROUND/RECTANGLE HEAD -
NUMBER OF HEADS INDICATED
POWER
18"
18"
18"
18"
18"
18"
18" b
A
LINEAR SUSPENDED , LENGTH AS INDICATED VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
VERIFY
18"
18"
18"
18"
18"
SQUARE DOWNLIGHT, RECESSED OR SURFACE MOUNT
CHANNEL OR INDUSTRIAL WALL MOUNT, LENGTH AS
INDICATED
ROUND OR SQUARE PENDANT
TAPE OR ROPE LIGHT
VANITY FIXTURE
WALL PACK
FLAG OR FLOOD LIGHT
BRANCH CIRCUIT PANEL
EQUIPMENT CABINET
TRANSFORMER
MOTOR OR MOTOR CONNECTION
MOTOR CONTROLLER, STARTER OF VFD
COMBINATION STARTER & DISCONNECT SWITCH
DISCONNECT SWITCH
MOTOR RATED TOGGLE
MANUAL MOTOR STARTER SWITCH WITH THERMAL
OVERLOAD
DUPLEX RECEPTACLE - WALL/CEILING MOUNT
EMERGENCY DUPLEX RECEPTACLE - WALL/CEILING
MOUNT
QUADPLEX RECEPTACLE - WALL/CEILING MOUNT
GFI RECEPTACLE, DUPLEX/QUADPLEX - WALL MOUNT
SPECIAL PURPOSE RECEPTACLE - WALL/CEILING
MOUNT
FLOOR BOX - DEVICES AS INDICATED
POWER POLE - DEVICES AS INDICATED
EMERGENCY SPECIAL PURPOSE RECEPTACLE -
WALL/CEILING MOUNT
MR
MMS
G G
P
DUPLEX RECEPTACLE - CONTROLLED - WALL/CEILING
MOUNT
C C
SPLIT DUPLEX RECEPTACLE - WALL/CEILING MOUNT
SIMPLEX RECEPTACLE - WALL/CEILING MOUNT
EMERGENCY SIMPLEX RECEPTACLE - WALL/CEILING
MOUNT
GFI RECEPTACLE, DUPLEX/QUADPLEX - CEILING MOUNT
EMERGENCY QUADPLEX RECEPTACLE - WALL/CEILING
MOUNT
GROUND REFERENCE BUS - AS NOTED - WALL/CEILING
MOUNT
VERIFY
XXX-X
EMERGENCY SPLIT DUPLEX RECEPTACLE -
WALL/CEILING MOUNT
VERIFY
VERIFY
VERIFY
VERIFY
ELECTRICAL ABBREVIATIONS
COPPER
DOWN
ELECTRICAL CONTRACTOR
ELECTRIC OR ELECTRICAL
EMERGENCY
ELECTRICAL METALLIC TUBING
ENCLOSURE
ELECTRIC PNEUMATIC
EMERGENCY POWER OFF
ELECTRIC WATER COOLER
FUSE OR FUSED
FIRE ALARM
FIRE ALARM CONTROL PANEL
FIRE-SMOKE DAMPER
GROUND
GROUND FAULT INTERRUPTER
ISOLATED GROUND
JUNCTION BOX
KILOVOLT
KILOVOLT-AMP
KILOWATT
KILOWATT-HOUR
MAIN CIRCUIT BREAKER
FILM VIEWER
MOMENTARY CONTACT
NATIONAL ELECTRICAL CODE
NOT IN CONTRACT
NOT TO SCALE
ON CENTER
PULL BOX
PUSHBUTTON
NORMALLY OPEN
NORMALLY CLOSED
MAIN SWITCHBOARD
PNEUMATIC ELECTRIC
POWER FACTOR
PHASE
PRIMARY
PANEL
REFRIGERATOR
SECONDARY
SWITCH
SWITCHBOARD
SPEAKER
ROOF TOP UNIT
RECEPTACLE
THERMOSTAT
TYPICAL
UNDER COUNTER
UNDERGROUND
TELEPHONE
UNLESS NOTED OTHERWISE
VOLT
VOLT-AMP
VOLTS ALTERNATING CURRENT
UNIT HEATER
VOLTS DIRECT CURRENT
WATT OR WIRE
WEATHERPROOF
TRANSFORMER
CU
DN
EC
ELEC
EM
EMT
ENCL
EP
EPO
EWC
F
FA
FACP
FSD
FV
G, GND
GFI
IG
JBOX
KV
KVA
KW
KWH
MC
MCB
MSB
NC
NEC
NIC
NO
NTS
OC
PB
PB
PE
PF
PH
PNL
PRI
RECEPT
REFG
RTU
SEC
SW
SWBD
SPKR
TEL
TSTAT
TYP
UC
UG
UH
UNO
V
VA
VAC
VDC
W
WP
XFMR
AMPERES
AUDIBLE ALARM
ADDENDUM
AVAILABLE FAULT CURRENT
ABOVE FINISHED FLOOR
AIR HANDLING UNIT
ALUMINUM
ANTENNA
CONDUIT OR CONTROLLED RECEPT
CIRCUIT BREAKER
CLOSED CIRCUIT TV
CIRCUIT
CABINET
A, AMP
AA
ADD
AFC
AFF
AHU
AL
ANT
C
CAB
CB
CCTV
CKT
ABOVE COUNTERAC
ARC FAULT CIRCUIT INTERRUPTERAFCI
BELOW FINISHED CEILING
BOLTED PRESSURE SWITCH
BFC
BPS
MAIN LUG ONLYMLO
MOTOR RATED SWITCHMRS
EMPTYMT
TAMPER RESISTANTTR
AUTOMATIC TRANSFER SWITCHATS
BUILDING AUTOMATION SYSTEMBAS
UNIVERSAL SERIAL BUSUSB
DB - DURESS PUSHBUTTON
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER: Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:1
:1
A
M
1361-E000
ELECTRICAL TITLE SHEET UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 59
06/04/2019
ELECTRICAL SHEET LIST
SHEET
NUMBER SHEET NAME
E000 ELECTRICAL TITLE SHEET
E001 ELECTRICAL ZONING PLAN
ED101 DEMOLITION LOWER LEVEL LIGHTING PLAN
ED102 DEMOLITION LOWER LEVEL POWER PLAN
ED103 DEMOLITION LOWER LEVEL SYSTEMS PLAN
ED130 DEMOLITION THIRD LEVEL PLAN
E101 LOWER LEVEL LIGHTING PLAN
E102 LOWER LEVEL POWER PLAN
E103 LOWER LEVEL SYSTEMS PLAN
E104 LOWER LEVEL INTERSTITIAL PLAN
E130 THIRD LEVEL PLAN
E152 PENTHOUSE POWER PLAN
E400 ENLARGED PLANS
E500 ELECTRICAL DETAILS
E501 ELECTRICAL DETAILS
E600 ELECTRICAL EQUIPMENT PLAN AND SCHEDULES
E601 ELECTRICAL SCHEDULES
E602 ELECTRICAL SCHEDULES
E603 SECURITY SURVEILLANCE PLAN AND SCHEDULE
E604 ELECTRICAL RISER
SHEET TOTAL: 20
Signature
Name
Date
Registration Number
Curtis D. Barlage, P.E.
45914Revisions: Date:
KEY NOTES:
GENERAL NOTES:
ELEC RM BQ-110E
IT CLOSET BQ-110D
AREA OF WORK
ELEC RM BT-103
IT CLOSET BT-104
E400
E400
ELEC RM BA-112
IT CLOSET BA-111
DD CC BB Z Y X W VAA
1 FOR 20A CIRCUIT BREAKER, #8AWG MAXIMUM DISTANCE FROM
SOURCE, ELEC ROOM BQ-110E, IS 163' AT 120V/16A.
FOR 20A CIRCUIT BREAKER, #6AWG MAXIMUM DISTANCE FROM
SOURCE, ELEC ROOM BQ-110E, IS 254' AT 120V/16A. #10AWG
MAXIMUM DISTANCE IS 247' AT 277V/16A.
FOR 20A CIRCUIT BREAKER, #4AWG MAXIMUM DISTANCE FROM
SOURCE, ELEC ROOM BQ-110E, IS 391' AT 120V/16A. #8AWG MAXIMUM
DISTANCE IS 376' AT 277V/16A.
UNHATCHED AREA IS FED FROM ELEC ROOM BT-103. FOR 20A
CIRCUIT BREAKER, #10AWG MAXIMUM DISTANCE IS 107' AT 120V/16A.
A.
B.
C.
D.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00 AM) AND WEEKENDS.
DO NOT REUSE EXISTING WIRING. PROVIDE NEW HOME RUNS UNLESS
NOTED OTHERWISE. PROVIDE DEDICATED NEUTRALS AS REQUIRED BY
THE NEC. HANDLE TIES OR MULTI POLE BREAKERS FOR SINGLE PHASE
LOADS ARE UNACCEPTABLE.
ROUTE CONDUITS IN A MANNER TO CONCEAL WHERE POSSIBLE.
#8AWG FOR 120V FEEDS / #10AWG FOR 277V FEEDS
#6AWG FOR 120V FEEDS / #10AWG FOR 277V FEEDS
#4AWG FOR 120V FEEDS / #8AWG FOR 277V FEEDS
LEGEND:
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:1
:2
A
M
1361-E001
ELECTRICAL ZONING PLAN UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 60
06/04/2019
Signature
Name
Date
Registration Number
DD CC BB Z Y X W V
AA
BA-108
CB79CB81
CB78
CB16
BR-118
BR-119A
BR-119
BR-122
BR-122A
BR-121 BR-120
BR-82
BR-123 BR-124
BR-113
BR-125
BR-126 BR-127
BR-128
BR-129
BR-130
BR-131
BR-115 BR-114
BR-116
BR-118A
BR-117A
BR-117B
BR-117
BR-102
BR-101
BR-113A
BR-113B
BR-103 BR-104
BR-112
CB58
NHBM3-1/1,3
NHBM3-1/12,14
NHBM3-1/7,9,11
NHBM3-1/5
CLBM3-1/5,7
NHBL2-1/3
DD CC BB Z Y X W VAA
A.
B.
C.
D.
E.
F.
G.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00AM)
REMOVE, REPLACE, RELOCATE, ETC. ANY ELECTRICAL DEVICES AND/OR
ANY CONDUIT/WIRING AS REQUIRED TO COMPLETE REMODELING AS
INDICATED IN THE CONTRACT DOCUMENTS.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE INDICATED
ON OWNER PROVIDED AS-BUILT DRAWINGS AND SITE VERIFICATION.
ACTUAL CONDITIONS MAY VARY FROM THE CONDITIONS INDICATED.
THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXACT
CONDITIONS.
ALL DEVICES, EQUIPMENT, CABLING, ETC. INDICATED IN THE CONTRACT
DOCUMENTS TO BE REMOVED SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH LOCAL AND
FEDERAL REGULATIONS. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION WORK. SEE ARCHITECTURAL DRAWINGS FOR PATCHING
DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
DEMOLISH HOME RUN WIRING BACK TO SOURCE UNLESS NOTED
OTHERWISE. DO NOT LEAVE CONDUCTORS ABANDONED IN WIREWAY
SYSTEMS LOCATED WITHIN THE INTERSTITIAL SPACES.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:2
:1
A
M
1361-ED101
DEMOLITION LOWER LEVEL
LIGHTING PLAN
UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 61
06/04/2019
1/8" = 1'-0"
LOWER LEVEL DEMOLITION LIGHTING PLAN
Signature
Name
Date
Registration Number
J
J
J
P
P
P P
P
P P
J
J
J
J
J
J
J
J
J
KEY NOTES:
GENERAL NOTES:
DD CC BB Z Y X W V
AA
BA-108
CB79CB81
CB78
CB16
BR-118
BR-119A
BR-119
BR-122
BR-122A
BR-121 BR-120
BR-82
BR-123
BR-124
BR-113
BR-125
BR-126 BR-127
BR-128
BR-129
BR-130
BR-131
BR-115 BR-114
BR-116
BR-118A
BR-117A
BR-117B
BR-117
BR-102
BR-101
BR-113A
BR-113B
BR-103
BR-104
BR-112
CB58
NLBM3-1B/20
NLBM3-2/3
NLBM3-2/5
NLBM3-2/11
NHBM3-1/13
NLBM3-2/21
NLBM3-2/20
NLBM3-1A/18
NLBM3-1A/14
NLBM3-1A/16
CLBM3-1/25 NLBM3-1A/19
NLBM3-1A/23
NLBM3-1A/21
NLBM3-1A/27
NLBM3-1A/25
NLBM3-1A/15
NLBM3-1A/13
NLBM3-1B/6
NLBM3-1B/4
NLBM3-1B/2
NLBM3-1A/4
NLBM3-1A/6
CLBM3-1/29
CLBM3-1/29
CLBM3-1/10
CLBM3-1/12
CLBM3-1/2
CLBM3-1/6
NLBM3-1B/22
CLBM3-1/24
CLBM3-1/22 CLBM3-1/26
NLBM3-1A/10,12
NLBM3-1A/8,10
CLBM3-1/23
CLBM3-1/19 CLBM3-1/21
CLBM3-1/37
NLBM3-1B/26
NLBM3-1A/24
CLBM3-1/30
CLBM3-1/31
CLBM3-1/39
CLBM3-1/16
CLBM3-1/14
CLBM3-1B/18
NLBL2-1A/6
NLBL2-1A/4
NLBL2-1A/2
DD CC BB Z Y X W VAA
1 DEMOLISH ELEVATOR EQUIPMENT, INCLUDING BUT NOT LIMITED TO
KEYPADS, MOTOR CONTROLLER, DISCONNECT, MOTOR, CONDUIT
AND WIRING/CABLING. GIVE OWNER FIRST RIGHT OF REFUSAL FOR
ASSOCIATED ELEVATOR EQUIPMENT.
A.
B.
C.
D.
E.
F.
G.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00AM)
REMOVE, REPLACE, RELOCATE, ETC. ANY ELECTRICAL DEVICES AND/OR
ANY CONDUIT/WIRING AS REQUIRED TO COMPLETE REMODELING AS
INDICATED IN THE CONTRACT DOCUMENTS.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE INDICATED
ON OWNER PROVIDED AS-BUILT DRAWINGS AND SITE VERIFICATION.
ACTUAL CONDITIONS MAY VARY FROM THE CONDITIONS INDICATED.
THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXACT
CONDITIONS.
ALL DEVICES, EQUIPMENT, CABLING, ETC. INDICATED IN THE CONTRACT
DOCUMENTS TO BE REMOVED SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH LOCAL AND
FEDERAL REGULATIONS. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION WORK. SEE ARCHITECTURAL DRAWINGS FOR PATCHING
DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
DEMOLISH HOME RUN WIRING BACK TO SOURCE UNLESS NOTED
OTHERWISE. DO NOT LEAVE CONDUCTORS ABANDONED IN WIREWAY
SYSTEMS LOCATED WITHIN THE INTERSTITIAL SPACES.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:2
:2
A
M
1361-ED102
DEMOLITION LOWER LEVEL
POWER PLAN
UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 62
06/04/2019
1/8" = 1'-0"
LOWER LEVEL DEMOLITION POWER PLAN
Signature
Name
Date
Registration Number
SS
S S
S
S
S
F
FS
F
F
F
F
F
FFSS
F FS
F
S
FS
FFS
FSF
S
S
F
FSF
F
F
F
FS FS
S
F
S
S
S
FS F
F FS
F FS
FS
F
FS F
C
C
CC
C
FSF
S
F FS
F FS
F
FS
FS F
S
F
FS
S
FF
FF
SFSF
VA
A
A
A C
X
AV
A
TV
TV
IC
IC
F
F
S
S FS
F S
S
SS
S
S
S
A
A
S
SS
S F
FS
F
S
S
KEY NOTES:
GENERAL NOTES:
DD CC BB Z Y X W V
AA
KPKP
DBDB
DB
DB
DB
AP
AP
AP
P
P
P
P
P
P
P
P
P
P
P
P P
P
P
P
P
P
P
P
INTRUSION
BA-108
CB79CB81
CB78
CB16
BR-118
BR-119A
BR-119
BR-122
BR-122A
BR-121 BR-120
BR-82
BR-123 BR-124
BR-113
BR-125
BR-126 BR-127
BR-128
BR-129
BR-130
BR-131
BR-115
BR-114
BR-116
BR-118A
BR-117A
BR-117B
BR-117
BR-102
BR-101
BR-113A
BR-113B
BR-103
BR-104
BR-112
CB58
RL
RL
RL RL
RL
RL
RL
RL
RL
RL
AP
RL
RL
RL
AP
RL
RL
RL
RL
RL
RL
RL
AP
AP
AP
RL
RL
RL
1(TYP)
DD CC BB Z Y X W VAA
1 TEMPORARILY SUPPORT DEVICES DURING DEMOLITION. REINSTALL
AFTER DEMOLITION AND NEW ACT CEILING HAS BEEN INSTALLED.
SEE SYSTEMS PLANS FOR NEW LOCATIONS.
DEMOLISH INTRUSION SYSTEM COMPONENTS AND HEAD-END UNIT.
GIVE OWNER FIRST RIGHT OF REFUSAL FOR ASSOCIATED
INTRUSTION SYSTEM EQUIPMENT.
GATE MAG LOCK AND KEYPAD/CARD READER TO REMAIN.
A.
B.
C.
D.
E.
F.
G.
H.
I.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00AM)
REMOVE, REPLACE, RELOCATE, ETC. ANY ELECTRICAL DEVICES AND/OR
ANY CONDUIT/WIRING AS REQUIRED TO COMPLETE REMODELING AS
INDICATED IN THE CONTRACT DOCUMENTS.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE INDICATED
ON OWNER PROVIDED AS-BUILT DRAWINGS AND SITE VERIFICATION.
ACTUAL CONDITIONS MAY VARY FROM THE CONDITIONS INDICATED.
THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXACT
CONDITIONS.
ALL DEVICES, EQUIPMENT, CABLING, ETC. INDICATED IN THE CONTRACT
DOCUMENTS TO BE REMOVED, SHALL BE DISPOSED OF IN
ACCORDANCE WITH LOCAL AND FEDERAL REGULATIONS. REFER TO
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION WORK. SEE ARCHITECTURAL DRAWINGS FOR PATCHING
DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
CLEAN AND PROTECT REMOVED FIRE ALARM DEVICES FOR
REINSTALLATION. EXISTING DETECTION DEVICES ARE GAMEWELL
"VELOCITI" SERIES.
DEMOLISH LOW VOLTAGE DEVICE CABLING BACK TO SOURCE WHEN
DEMOLISHING LOW VOLTAGE DEVICES.
DEMOLISH ANY FIRE/SMOKE DAMPERS AND DUCT DETECTORS, WHICH
MAY NOT BE SHOWN ON THE PLANS, THAT ARE PART OF DIV. 23
DEMOLISION. COORDINATE WITH THE MECHANICAL CONTRACTOR
DURING DEMOLITION.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:2
:3
A
M
1361-ED103
DEMOLITION LOWER LEVEL
SYSTEMS PLAN
UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 63
06/04/2019
1/8" = 1'-0"
LOWER LEVEL DEMOLITION SYSTEMS PLAN
Signature
Name
Date
Registration Number
N
IC
IC
F
N
S
N
F
F
N
N
KEY NOTES:
GENERAL NOTES:
JK
3F-117
3F-117A
3F-117B
3F-124
C3-49
C3-52
3F-115
3F-125
3F-120A
3F-120
NL3G1-1A/5
NH3G1-1/3
CL3G1-1/5
ACAC
AC
AC
AC
AC
AC AC
JK
3F-117
3F-117A
3F-117B
3F-124
C3-49
C3-52
3F-115
3F-125
3F-120A
3F-120
NL3G1-1B/20
NL3G1-1B/16
CL3G1-1/5
NL3G1-1B/12
DB
P
P
P
2 2
E
AC
AC
AC
JK
3F-117
3F-117A
3F-117B
3F-124
C3-49
C3-52
3F-115
3F-125
3F-120A
3F-120
E
1 INSPECT WALL SPACE. IF REQUIRED, REROUTE ANY SWITCH WIRING
THAT RUNS THROUGH THE DEMOLISHED WALL.
INSPECT WALL SPACE. IF REQUIRED, REROUTE ANY POWER WIRING
THAT RUNS THROUGH THE DEMOLISHED WALL.
INSPECT WALL SPACE. IF REQUIRED, REROUTE ANY SYSTEMS
CABLING AND/OR WIRING THAT RUNS THROUGH THE DEMOLISHED
WALL.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00AM)
REMOVE, REPLACE, RELOCATE, ETC. ANY ELECTRICAL DEVICES AND/OR
ANY CONDUIT/WIRING AS REQUIRED TO COMPLETE REMODELING AS
INDICATED IN THE CONTRACT DOCUMENTS.
DRAWINGS INDICATE EXISTING CONDITIONS AS THEY WERE INDICATED
ON OWNER PROVIDED AS-BUILT DRAWINGS AND SITE VERIFICATION.
ACTUAL CONDITIONS MAY VARY FROM THE CONDITIONS INDICATED.
THE CONTRACTOR IS RESPONSIBLE TO FIELD VERIFY EXACT
CONDITIONS.
ALL DEVICES, EQUIPMENT, CABLING, ETC. INDICATED IN THE CONTRACT
DOCUMENTS TO BE REMOVED SHALL BE THE RESPONSIBILITY OF THE
CONTRACTOR TO DISPOSE OF IN ACCORDANCE WITH LOCAL AND
FEDERAL REGULATIONS. REFER TO SPECIFICATIONS FOR ADDITIONAL
INFORMATION.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION WORK. SEE ARCHITECTURAL DRAWINGS FOR PATCHING
DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
DEMOLISH HOME RUN WIRING BACK TO SOURCE UNLESS NOTED
OTHERWISE. DO NOT LEAVE CONDUCTORS ABANDONED IN WIREWAY
SYSTEMS LOCATED WITHIN THE INTERSTITIAL SPACES.
CLEAN AND PROTECT REMOVED FIRE ALARM DEVICES FOR
REINSTALLATION. EXISTING DETECTION DEVICES ARE GAMEWELL
"VELOCITI" SERIES.
DEMOLISH LOW VOLTAGE DEVICE CABLING BACK TO SOURCE, IT
CLOSET 3F-122A, WHEN DEMOLISHING LOW VOLTAGE DEVICES.
DEMOLISH ANY FIRE/SMOKE DAMPERS AND DUCT DETECTORS, WHICH
MAY NOT BE SHOWN ON THE PLANS, THAT ARE PART OF DIV. 23
DEMOLISION. COORDINATE WITH THE MECHANICAL CONTRACTOR
DURING DEMOLITION.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:2
:4
A
M
1361-ED130
DEMOLITION THIRD LEVEL PLAN UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 64
06/04/2019
1/4" = 1'-0"
THIRD LEVEL DEMOLITION LIGHTING PLAN
1/4" = 1'-0"
THIRD LEVEL DEMOLITION POWER PLAN
1/4" = 1'-0"
THIRD LEVEL DEMOLITION SYSTEMS PLAN
Signature
Name
Date
Registration Number
D
D
D
D
D
D D
D
D
D
D
D
D D
DD
D
D
D
D
DDDD
D D
D
D
S
S
S
S
S
S S
S
D
D D
D D
D
D
D
D D
D
R
R
S
KEY NOTES:
GENERAL NOTES:
MECH
BR-101C
INVESTIGATIONAL
DRUG SERVICES
BR-117
INPATIENT
NARCOTIC
VAULT
BR-116
CONFERENCE/TRAINING
BR-124
OFFICE
BR-101E
HD BUFFER
ROOM
BR-118C
STORAGE HD
DRUGS
BR-119
STAFF LOUNGE
BR-125
WOMEN'S
LOCKERS
BR-122
GENERAL
PHARMACY
BR-113
WORK
STATIONS
BR-123
MECH
BR-108
ANTE ROOM
BR-118
OFFICE
BR-115
OFFICE
BR-101F
OFFICE
BR-101H
OFFICE
BR-101G
OFFICE
BR-114
OFFICE
BR-101B
OPEN OFFICE
BR-101D
NON HD BUFFER
ROOM
BR-118B
RECEIVING
BR-120
MEN'S LOCKER
BR-121
HSKP
BR-127
CONFERENCE
ROOM
BR-126
GENERAL
PHARMACY
BR-113
PICKUP
WINDOW
BR-128
RECEPTION
BR-101
DD CC BB Z Y X W V
AA
OPEN OFFICE
BR-101A
OS
OS
VS
VS
VS
VS VS
VS
VS
VS
VS
A4L
A4L
A4
A4L
A4
A4L
A4
A4
A4 3
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4C
A4C
A4C
A4C
A4C
A4C
A4C
A4L
A4L
A4L
A4L
A2L
A2R
A4R
A2R
A4R
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4
A4
A4
A4
A4
A4
A4
A4
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4
A4
A4
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A2L
A2L
A2L
A2L
A2L
A4R
A4R
A2R
A2R
A4R
A4C
A4C
A4C
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4C
A4C
A4C
A4C
A4C
A4
A4
A4
A4C
A4C
A4C
A4C 17
A4C
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4
A4L
A2L
A2L
A2L
A2L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A2L
A2L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A2L
A2L
A2L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
A4L
E1
W2
W2
W2
VS
E2
E1
E1
E1
E2
E1
OS
A4L
F4
F4
F4
F4
A4
F4
A4C
A4C
D1
D1
D1
D1
E1
A2L
A2L
A2L
A2L
A2L
A2L
A2L
A4
A4
A4
VS VS
OS
3s
4m4s
3s 3m
3m s m s m s s m s m s s s s ms s m m s msms m s m s m s m m s s m m s s m m s s m m s s m m s smms s s s s ss
3n 3e
3n
3e n n n n e nen n f b
EM
EM
f b f f bb f f f bbb b b b c n n c n n c c n m c n n c n c c c c n c c n c n c n c c n n c c c c cc n c n c n c c c c c n n nc c ccn n n c c c c c,n c,n
ELEC
BT-103
IT
BT-104
OFFICE
BR-110A
OFFICE
BR-110B
LHBB2-1
NHBM3-1
NHBM3-1
CLBM3-1A
CLBM3-1A
CLBM3-1A
NHBL2-1
s m
A4 A4
A4
U4 U4 U4
DD CC BB Z Y X W VAA
1 PROVIDE EMERGENCY RELAY FOR SWITCHED EMERGENCY A4
LUMINAIRE. INSTALL RELAY ABOVE CEILING GRID.
BR-113 NORMAL LOAD LIGHTING CONTROLLER, MODEL EATON
RC3DEHC-PL, OR APPROVED EQUAL. INSTALL CONTROLLER ABOVE
CEILING IN AN ACCESSIBLE LOCATION NEAR THE ASSOCIATED WALL
SWITCH. PROVIDE CAT6A CABLES FROM THE CONTROLLER TO THE
WALL SWITCHES. REFER TO THE CONTROLLER ELECTRICAL DETAIL
FOR ADDITIONAL INFORMATION.
BR-113 CRITICAL LOAD LIGHTING CONTROLLER, MODEL EATON
RC3DEHC-PL, OR APPROVED EQUAL. INSTALL CONTROLLER ABOVE
CEILING IN AN ACCESSIBLE LOCATION NEAR THE ASSOCIATED WALL
SWITCH. PROVIDE CAT6A CABLES FROM THE CONTROLLER TO THE
WALL SWITCHES. REFER TO THE CONTROLLER ELECTRICAL DETAIL
FOR ADDITIONAL INFORMATION.
TIE NEW LIGHT FIXTURES INTO THE EXISTING LIGHTING CIRCUIT.
ALIGN NEW LIGHT FIXTURES TO MATCH EXISTING LAYOUT.
SEAL LIGHTING-CONTROL DEVICES AND PENETRATIONS IN THIS
SPACE PER USP 800 REGULATION ISO CLASS 7 REQUIREMENTS.
A.
B.
C.
D.
E.
F.
G.
H.
I.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00 AM) AND WEEKENDS.
DO NOT REUSE EXISTING WIRING. PROVIDE NEW HOME RUNS UNLESS
NOTED OTHERWISE. PROVIDE DEDICATED NEUTRALS AS REQUIRED BY
THE NEC. HANDLE TIES OR MULTI POLE BREAKERS FOR SINGLE PHASE
LOADS ARE UNACCEPTABLE.
COORDINATE LOCATION AND INSTALLATION OF CEILING MOUNTED
EQUIPMENT WITH THE VA PRIOR TO ROUGH-IN.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION AND NEW WORK. SEE ARCHITECTURAL DRAWINGS FOR
PATCHING DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
INSTALL MINIMUM #10 AWG FOR ALL 120V CIRCUIT HOMERUNS IN
EXCESS OF 75' AND ALL 277V CIRCUIT HOMERUNS IN EXCESS OF 150'.
SEE SHEET E001 FOR SIZING HOMERUNS WHERE THE SOURCE PANEL IS
LOCATED IN ELEC ROOM BQ-110E.
ROUTE CONDUITS IN A MANNER TO CONCEAL WHERE POSSIBLE.
WHERE LIGHTING CONTROL DEVICES (OCCUPANCY / VACANCY
SENSORS, RELAY MODULES, ETC) ARE SHOWN ON PLANS, LOCATE
DEVICES IN EACH SPACE PER DEVICE TYPE AND MANUFACTURER
RECOMMENDATIONS. INSTALL ALL RELAYS AND/OR POWER PACKS IN
NEMA 1 ENCLOSURES TO ACHIEVE PLENUM RATINGS.
LIFE SAFETY LIGHTING SHALL BE UNSWITCHED UNLESS NOTED
OTHERWISE.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:1
:4
A
M
1361-E101
LOWER LEVEL LIGHTING PLAN UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 65
06/04/2019
1/8" = 1'-0"
LOWER LEVEL LIGHTING PLAN
Signature
Name
Date
Registration Number
P
P
J
P
P
P
P
P
P
P
J
P
P
P
P
P
P
P
J
J
J
J
J
KEY NOTES:
GENERAL NOTES:
MECH
BR-101C
INVESTIGATIONAL
DRUG SERVICES
BR-117
INPATIENT
NARCOTIC
VAULT
BR-116
CORRIDOR
CB-79
CONFERENCE/TRAINING
BR-124
OFFICE
BR-101E
HD BUFFER
ROOM
BR-118C
STORAGE HD
DRUGS
BR-119
STAFF LOUNGE
BR-125
WOMEN'S
LOCKERS
BR-122
WORK
STATIONS
BR-123
GENERAL
PHARMACY
BR-113
MECH
BR-108
ANTE ROOM
BR-118
OFFICE
BR-115
OFFICE
BR-101F
CORRIDOR
CB-16
OFFICE
BR-101H
OFFICE
BR-101G
OFFICE
BR-114
OFFICE
BR-101B
OPEN OFFICE
BR-101D
NON HD BUFFER
ROOM
BR-118B
RECEIVING
BR-120
MEN'S LOCKER
BR-121
OFFICE
BR-110A
OFFICE
BR-110B
HALL
BR-112
HSKP
BR-127
CONFERENCE
ROOM
BR-126
GENERAL
PHARMACY
BR-113
PICKUP
WINDOW
BR-128
RECEPTION
BR-101
AC
AC
AC
AC
USB
ACAC
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
AC
48"
AC
AC
96"
48"
48"
48"
48"
ACAC AC
UC
UC
UC
AC 01
AC 02
AC 03
48"
48"
ELEC
BT-103
IT
BT-104
/34CLBM3-1
10 10
2 2
17 17
2 2
2 2
AC
AC
AC
OPEN OFFICE
BR-101A
(TYP)
(TYP)
(TYP)
19 21 21 21
31 31
AC
AC
(TYP)
(TYP)
12 12
2 5
AC AC AC
AC
AC
PL
84"
AC
84"
AC
48"
AC
23 23 23
AC
AC
AC
UC
LLBB2-1
DD CC BB Z Y X W VAA
/18NLBM3-1B
/30NLBM3-1B
/32NLBM3-1B
/27NLBM3-1B
/29NLBM3-1B
/16NLBM3-1B
1 DEVICES ON THIS SIDE OF THE DASHED LINE ARE FED FROM PANEL
NLBL2-1A.
PROVIDE LEGRAND TELE-POWER POLE NP800 SERIES, OR APPROVED
EQUAL. PRIOR TO ORDERING, COORDINATE WITH THE COR FOR ANY
FURNITURE CONNECTION REQUIREMENTS. INSTALL SNAP-IN DIVIDER
ON THE POWER SIDE OF THE POLE, TO DIVIDE NORMAL AND
CRITICIAL POWER FOR NEW AND FUTURE WORK. FOR EACH TELE-
POWER POLE, ORDER ADD-ON POWER COVER BASED OFF DEVICE
QUANTITY SHOWN ON THIS SHEET AND THE EQUIPMENT PLAN
SHOWN ON SHEET E600. SEE SHEET E103 FOR SYSTEMS DEVICE
QUANTITY, AND ORDER ADD-ON TELECOMM COVER BASED OFF
DEVICE QUANTITY AND TYPE SHOWN.
PROVIDE AL5200 SERIES RACEWAY, OR APPROVED EQUAL. VERIFY
TOTAL DEVICE REQUIRED IN THE RACEWAY ON SHEETS E102, E103,
AND E600 PRIOR TO ORDERING ACCESSORY PLATES.
PROVIDE JUNCTION BOX FOR TAP CONDUCTORS FEEDING
AC-01/02/03. ASSUME 12" X 12" X 4". SEE ELECTRICAL RISER FOR
ADDITIONAL DETAILS.
PROVIDE 120V AMBER SURFACE MOUNT STROBE LIGHT. BASIS OF
DESIGN EDWARDS FLASHING XENON 89 SERIES. INDICATING LIGHT
CONTROL VIA PILOT LIGHT SWITCH LOCATED IN HD STORAGE.
DEVICES SHOWN IN THE DASHED REGION ARE FURNITURE FED FROM
THE WALL-MOUNTED JUNCTION BOX. SEE ARCHITECTURAL
ELEVATIONS PRIOR TO ROUGH-IN TO DETERMINE FURNITURE FEED
LOCATION.
SEAL ELECTRICAL DEVICES(RECEPTACLES, JUNCTIONS BOXES,
DISCONNECTS, SWITCHES, ETC) AND PENETRATIONS IN THIS SPACE
PER USP 800 REGULATION ISO CLASS 7 REQUIREMENTS.
IN-CABINET RECEPTACLE FOR REVERSE OSMOSIS WATER SYSTEM.
COORDINATE LOCATION WITH DIV 22 CONTRACTOR PRIOR TO
ROUGH-IN.
PROVIDE MOTOR RATED SWITCH AND CONNECTION TO POWERED
DOOR OPERATOR. SEE ARCHTECTURAL DRAWINGS AND SYSTEMS
PLANS FOR ADDITIONAL DOOR CONNECTION REQUIREMENTS.
PROVIDE 1 1/4" CONDUIT FROM DOOR OPERATOR TO LOW VOLTAGE
DEVICES AND DOOR OPERATOR PUSHBUTTONS.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00 AM) AND WEEKENDS.
DO NOT REUSE EXISTING WIRING. PROVIDE NEW HOME RUNS UNLESS
NOTED OTHERWISE. PROVIDE DEDICATED NEUTRALS AS REQUIRED BY
THE NEC. HANDLE TIES OR MULTI POLE BREAKERS FOR SINGLE PHASE
LOADS ARE UNACCEPTABLE.
COORDINATE LOCATION AND INSTALLATION OF CEILING MOUNTED
EQUIPMENT WITH THE VA PRIOR TO ROUGH-IN.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION AND NEW WORK. SEE ARCHITECTURAL DRAWINGS FOR
PATCHING DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
INSTALL MINIMUM #10 AWG FOR ALL 120V CIRCUIT HOMERUNS IN
EXCESS OF 75'.
ROUTE CONDUITS IN A MANNER TO CONCEAL WHERE POSSIBLE.
DEVICES SHOWN BACK-TO-BACK ARE FOR INTENT PURPOSES ONLY.
DO NOT INSTALL BACK-TO-BACK TO PREVENT NOISE TRAVEL. SEE
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ALL FURNITURE LAYOUTS ARE SHOWN FOR DESIGN INTENT
ONLY. FINAL LOCATIONS OF FURNITURE AND ASSOCIATED
POWER/DATA OUTLETS TO BE COORDINATED WITH OWNER.
REFER TO MECHANICAL ELECTRICAL (ME) SCHEDULES FOR ELECTRICAL
CONNECTION REQUIREMENTS TO MECHANICAL EQUIPMENT.
COORDINATE RECEPTACLE DEVICES NEXT TO COMMUNICATION
DEVICES, SUCH THAT THE DEVICES ARE MOUNTED NEXT TO EACH
OTHER.
UNLESS NOTED OTHERWISE, NORMAL POWER-FED DEVICES AND
EQUIPMENT ARE CIRCUITED TO PANEL NLBM3-1A. CRITICAL
(EMERGENCY) POWER-FED DEVICES AND EQUIPMENT ARE CIRCUITED
TO PANEL CLBM3-1.
REFER TO SHEET E600 FOR PHARMACY EQUIPMENT LOCATIONS AND
CONNECTIONS.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:1
:5
A
M
1361-E102
LOWER LEVEL POWER PLAN UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 66
06/04/2019
1/8" = 1'-0"
LOWER LEVEL POWER PLAN
Signature
Name
Date
Registration Number
S
S
SS
S
S
S
S
S
S
S
S
S S
S
S
S
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
FF
F
FFF
F
F
F
F
F
F
F
FS
FS
FFS
FS
F
S
FS
FS
FS
FS
FS
FS
FS FS
FS
FS
FS FSFS
FS
FS
FSFS
P
P
P
P
P
S
S
S
S
S
S
S
S
S
F
S
F
P
S
F
F
F
F
F
F
S
S
S
S
S S
S
P
P
P
S
S
S
S
S
S
S
S
S S S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
SS
S
S
S
S
S
P
P
P
P
P
P
P
S
S
S
S
F
S
S
F
S
S
S S
S
S
S
S
S
S S
S
FF
S
J
S
S
S
F
S
S
S
S
F
S
S
S
S
F
S
S
F
F F
S S
S
S
S
KEY NOTES: GENERAL NOTES:
DD CC BB Z Y X W V
AA
MECH
BR-101C
INVESTIGATIONAL
DRUG SERVICES
BR-117
INPATIENT
NARCOTIC
VAULT
BR-116
CORRIDOR
CB-79
CONFERENCE/TRAINING
BR-124
OFFICE
BR-101E
HD BUFFER
ROOM
BR-118C
STORAGE HD
DRUGS
BR-119
STAFF LOUNGE
BR-125
WOMEN'S
LOCKERS
BR-122
CORRIDOR
CB-81
GENERAL
PHARMACY
BR-113
WORK
STATIONS
BR-123
GENERAL
PHARMACY
BR-113
MECH
BR-108
ANTE ROOM
BR-118
OFFICE
BR-115
OFFICE
BR-101F
OFFICE
BR-101H
OFFICE
BR-101G
OFFICE
BR-114
OFFICE
BR-101B
OPEN OFFICE
BR-101D
NON HD BUFFER
ROOM
BR-118B
RECEIVING
BR-120
MEN'S LOCKER
BR-121
HSKP
BR-127
CONFERENCE
ROOM
BR-126
PICKUP
WINDOW
BR-128
RECEPTION
BR-101
Unoccupied
Unoccupied
OPEN OFFICE
BR-101A
KP
KP
KP
KP
KP
DB
DB
DB
DB
DB
DB
DB
DB DB
DB
DB
DB
W
W
2 2
W
AC
AC
W
48"
AC
AC
AP
AP
AP
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PP
P
PPP
P
P
P
P
AP
60"
AC
AC
KP
MD
MD
MD
MD
MD
MD
2 2
DB
P
DB
P
PP
AP
AP
ELEC
BT-103
IT
BT-104
DB
P
P
P
P
P
P
MD
MD
MD
MD
MD MD
MD
60" 2 2
2 2
2 2 2
AC
AC
AC
W
IC
IC
IC
IC
EP
EP
EP
EP
EP EP
IC
DB
DB
DB
DB
DB
DB
DB
DB
MI
DB
DB
KP
IC
MI
2 DB
KP
EPEP
DB
IC
MI
MI
DB
W
AC
2 2
WP
WP
2 2 2
DC
ES
CM
DC
ES
CM
DC
ES
DC
ES
DC
ES
DC
ES
DC
ES
DC
ES
CM
CM
WP
AC
AC
KP
DC
ES
CM
DC
ES
DC
ES
CM
DC
ES
DC
ES
CM
DC
ES
CM
CM
CM
KP
DD CC BB Z Y X W VAA
KP
KP
KP
KP
1 REFER TO POWER PLAN AND ELECTRICAL SCHEDULE SHEETS FOR
ADDITIONAL INFORMATION IN REGARDS TO THE FLOOR BOX.
REFER TO POWER PLAN AND ELECTRICAL SCHEDULE SHEETS FOR
ADDITIONAL INFORMATION IN REGARDS TO THE TELE-POWER POLES.
REFER TO POWER PLAN SHEET FOR ADDITIONAL INFORMATION IN
REGARDS TO THE SURFACE RACEWAY.
COMMUNICATION CABLES ON THIS SIDE OF THE LINE ORIGINATE
FROM IT CLOSET BQ-110D.
COMMUNICATION CABLES ON THIS SIDE OF THE LINE ORIGINATE
FROM IT CLOSET BT-104.
DEDICATED PHONE LINE FOR MCKESSON MOBILE MANAGER 50.
COORDINATE LOCATION WITH THE COR.
SEAL SYSTEMS DEVICES(VOICE/DATA, FIRE/SMOKE, PA SYSTEM,
INTERCOM AND SECURITY, CONDUITS, JUNCTIONS BOXES, ETC) AND
PENETRATIONS IN THIS SPACE PER USP 800 REGULATION ISO CLASS
7 REQUIREMENTS.
INSTALL WEATHERPROOF PA SYSTEM SPEAKER IN THE LOCATION
SHOWN ON THE PLANS. REFER TO ARCHITECTURAL REFLECTED
CEILING PLAN FOR CEILING LAYOUT.
FIRE ALARM SYSTEM TO INTERFACE WITH DOOR CONTROLLER. SEE
DOOR HARDWARE SPECIFICATON AND ARCHITECTURAL DRAWINGS
FOR ADDITIONAL INFORMATION.
NETWORKED INTERCOM STATION TO INTERFACE WITH DOOR
CONTROLLER. SEE DOOR HARDWARE SPECIFCATION AND
ARCHITECTURAL DRAWINGS FOR ADDITIONAL INFORMATION.
MODIFY EXISTING ACCESS CONTROL DEVICE FOR NEW DOOR.
DEVICES SHOWN IN THE DASHED REGION ARE FURNITURE FED FROM
THE WALL-MOUNTED JUNCTION BOX. SEE INTERCOM DETAILS,
ARCHITECTURAL ELEVATIONS PRIOR TO ROUGH-IN TO DETERMINE
FURNITURE FEED LOCATION.
AUDIO INTERCOM STATION TO COMMUNICATE WITH ADJACENT
BUFFER ROOM. PROVIDE 1-CALL AUDIO MASTER STATION AND
ASSOCIATED POWER SUPPLY; BASIS OF DESIGN AIPHONE LEM-1.
AUDIO INTERCOM STATION TO COMMMUNICATE WITH ADJACENT
MASTER STATION. PROVIDE STAINLESS STEEL AUDIO DOOR STATION;
BASIS OF DESIGN AIPHONE LE-SS-1G. PROVIDE 3/4" CONDUIT
BETWEEEN JBOXES AND ROUTE COMMUNICATION CABLING
BETWEEN MASTER/SLAVE INTERCOM STATION.
AUDIO INTERCOM STATION TO COMMUNICATE WITH ADJACENT
BUFFER ROOM. PROVIDE 3-CALL AUDIO MASTER STATION AND
ASSOCIATED POWER SUPPLY; BASIS OF DESIGN AIPHONE LEM-3.
INTRUSION SYSTEM KEYPAD.
INTRUSION SYSTEM SUBZONE FOR NARCOTICS VAULT DENOTED BY
DETAIL LINE. MAIN INTRUSION ZONE FOR REMAINING PHARMACY
AREA.
A.
B.
C.
D.
E.
F.
G.
H.
I.
J.
K.
L.
M.
N.
O.
P.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00 AM) AND WEEKENDS.
DO NOT REUSE EXISTING WIRING. PROVIDE NEW HOME RUNS UNLESS
NOTED OTHERWISE. PROVIDE DEDICATED NEUTRALS AS REQUIRED BY
THE NEC. HANDLE TIES OR MULTI POLE BREAKERS FOR SINGLE PHASE
LOADS ARE UNACCEPTABLE.
COORDINATE LOCATION AND INSTALLATION OF CEILING MOUNTED
EQUIPMENT WITH THE VA PRIOR TO ROUGH-IN.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION AND NEW WORK. SEE ARCHITECTURAL DRAWINGS FOR
PATCHING DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
INSTALL MINIMUM #10 AWG FOR ALL 120V CIRCUIT HOMERUNS IN
EXCESS OF 75'.
ROUTE CONDUITS IN A MANNER TO CONCEAL WHERE POSSIBLE.
DEVICES SHOWN BACK-TO-BACK ARE FOR INTENT PURPOSES ONLY.
DO NOT INSTALL BACK-TO-BACK TO PREVENT NOISE TRAVEL. SEE
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
ALL FURNITURE LAYOUTS ARE SHOWN FOR DESIGN INTENT
ONLY. FINAL LOCATIONS OF FURNITURE AND ASSOCIATED
POWER/DATA OUTLETS TO BE COORDINATED WITH OWNER.
ROUTE LOW VOLTAGE CABLING TO DATA ROOM AS INDICATED ON
DRAWINGS. PROVIDE CABLE COUNT AS INDICATED. ROUTE
VOICE/DATA CABLING IN INDICATED CABLE TRAYS. CABLING NOT IN
CABLE TRAY SHALL BE INSTALLED IN CONDUIT.
PROVIDE A DOUBLE GANG BOX WITH A SINGLE GANG MUDRING AND (1)
1" CONDUIT ROUTED TO ADJACENT CABLE TRAY FOR LOW VOLTAGE
ROUGH IN.
COORDINATE COMMUNICATION DEVICES NEXT TO RECEPTACLE
DEVICES SUCH THAT THE DEVICES ARE MOUNTED NEXT TO EACH
OTHER.
INSTALL SMOKE DETECTORS A MINIMUM OF 3' FROM SUPPLY
DIFFUSERS.
EXTEND EXISTING PUBLIC ADDRESS SYSTEM WIRING TO RELOCATED
PUBLIC ADDRESS SPEAKERS.
COORDINATE DURESS BUTTON WALL-MOUNTED LOCATION WITH THE
CONTRACTING OFFICER REPRESENTATIVE(COR) PRIOR TO ROUGH-IN.
ACCESS CONTROL WIRING TO EXTEND TO EXISTING HEAD END IN
TELECOMMUNICATIONS ROOM BQ-110e. EXPAND EXISTING SYSTEM TO
CONNECT NEW DEVICES.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:2
:0
A
M
1361-E103
LOWER LEVEL SYSTEMS PLAN UPGRADE PHARMACY 18
MINNEAPOLIS, MN
618-16-120
06/04/2019 CB JKProject Number 67
06/04/2019
1/8" = 1'-0"
LOWER LEVEL SYSTEMS PLAN
Signature
Name
Date
Registration Number
4 4 4 4 4 4
5 5 5555
DD CC BB Z Y X W VAA
1 PROVIDE WATERFALL FITTING AT THE END OF THE CABLE TRAY TO
TRANSITION TO VERTICAL CABLE TRAY. INSTALL VERTICAL CABLE
TRAY NEAR THE DATA RACK IN DATA CLOSET BQ-110D.
PROVIDE WATERFALL FITTING AT THE END OF THE CABLE TRAY TO
TRANSITION TO VERTICAL CABLE TRAY. INSTALL VERTICAL CABLE
TRAY NEAR THE DATA RACK IN DATA CLOSET BT-104.
PROVIDE 4"D x 24"W LOW VOLTAGE CABLE TRAY FROM THE DATA
CLOSET INTO THE FIRST FLOOR INTERSTITIAL SPACE. ROUTE IN
CLOSE PROXIMITY TO THE EXISTING LOW VOLTAGE WIREWAYS.
PROVIDE 4"D x 12"W LOW VOLTAGE CABLE TRAY AND TERMINATE
WHERE SHOWN.
PROVIDE 4"D x 24"W TO 4"D x 12"W FITTING.
A.
B.
C.
D.
E.
BUILDING WILL BE IN USE DURING CONSTRUCTION. SCHEDULE AND
CARRY OUT THE WORK IN SUCH A MANNER AS TO CAUSE THE OWNER A
MINIMUM OF INCONVENIENCE DUE TO SERVICE INTERRUPTION.
TEMPORARY SERVICES (FEEDER, BRANCH CIRCUIT, AND SIGNAL
SYSTEMS) SHALL BE INSTALLED IF ONE AREA OR PHASE OF
CONSTRUCTION DISRUPTS SERVICE TO ANOTHER AREA OF THE
BUILDING(S) OR IF THE EQUIPMENT, CONDUITS, OR FEEDERS HAVE TO
BE RELOCATED TO ALLOW CONSTRUCTION TO PROGRESS. SERVICE
INTERRUPTIONS SHALL BE CONFINED TO THE SMALLEST AREA
POSSIBLE AT ANY ONE TIME AND INTERRUPTIONS SHALL BE
SCHEDULED WITH THE OWNER'S SITE REPRESENTATIVE. THERE SHALL
BE DESIGNATED AREAS WHERE INTERRUPTIONS LIMITED TO AND SHALL
BE CONDUCTED AFTER HOURS (8:00 PM - 6:00 AM) MONDAY THROUGH
SATURDAY. AFTER SERVICE HAS BEEN RESTORED FOLLOWING AN
INTERRUPTION, INSPECT AREAS AFFECTED BY THE INTERRUPTION AND
BE RESPONSIBLE FOR RETURNING AUTOMATICALLY CONTROLLED
EQUIPMENT TO THE SAME OPERATING CONDITION WHICH EXISTED
PRIOR TO THE INTERRUPTION.
SIGNIFICANT NOISE PRODUCING WORK SHALL BE CONDUCTED AFTER
HOURS (8:00 PM - 6:00 AM) AND WEEKENDS.
PATCH ALL INTERSTITIAL PENETRATION VOIDS RESULTING FROM
DEMOLITION AND NEW WORK. SEE ARCHITECTURAL DRAWINGS FOR
PATCHING DETAILS. MAINTAIN FLOOR AND WALL RATINGS.
ROUTE CONDUITS IN A MANNER TO CONCEAL WHERE POSSIBLE.
ROUTE LOW VOLTAGE CABLING TO DATA ROOM AS INDICATED ON
DRAWINGS. PROVIDE CABLE COUNT AS INDICATED. ROUTE
VOICE/DATA CABLING IN INDICATED CABLE TRAYS. CABLING NOT IN
CABLE TRAY SHALL BE INSTALLED IN CONDUIT.
PLAN
NORTH
TRUE
NORTH
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
CONSTRUCTION
DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
AE PROJECT NUMBER:
KEY PLAN
BUILDING 70
Dwg. of 78Dunham Project No: 0419950-004
I hereby certify that this plan, specification, or report was prepared by me or under my direct supervision and that I am a duly Licensed Professional Engineer under the laws of the state of Minnesota.
CONSTRUCTION DOCUMENTS
C R e v it P ro je c ts
\1
M p ls P h a rm a c y R e n o
M
E P
R c h a d g .r v t
/5
/2
:2
:2
A
M
1361-E104
LOWER LEVEL INTERSTITIAL PLAN…