Attachment 03- 646A-700.32.M.20260724.pdf

PDF 478 KB Posted

Attached to
Z1DA--646A4-22-700 | EHRM Infrastructure Upgrades | Pittsburgh-Heinz, PA
Solicitation number
36C77626R0071
Issued by

About this file

This document is a construction drawing submission for mechanical infrastructure upgrades at the VA Pittsburgh Healthcare System H.J. Heinz Campus. The drawings depict basement-level mechanical plans (Drawing 32-MN100 and 32-MN401) for the EHRM Infrastructure Upgrades project located at 1010 Delafield Road, Pittsburgh, PA 15215, with Project Number 646A-22-700.

The mechanical plans show the layout of data center cooling systems in basement room BA120, including six Computer Room Air Conditioning (CRAC) units (CRAC-1 through CRAC-6), six accumulator tanks (ACCU-1 through ACCU-6), refrigerant piping, and chilled water/condensate piping connections. Key specifications include routing and sizing refrigerant piping per manufacturer recommendations, reconnecting existing chilled water and condensate piping to new CRAC units with duct termination at 18 inches from ceiling, and routing new refrigerant piping through existing wall penetrations following the same path as existing outdoor-to-indoor refrigerant lines. The facility is fully sprinklered with fire barriers (3-hour, 2-hour, and 1-hour ratings) and smoke barriers indicated throughout. The drawings are prepared by Awen Solutions Group and IMEG as the Architect/Engineer of Record, with a revision date of July 24, 2026 for data center cooling addenda Q.56. The document is marked as Final Bid Documents for construction.

View the file

Other files

File Type Posted
Amendment 36C77626R0071 0008.pdf PDF
Attachment 01- 646A-700.CAMPUS.M.20260724.pdf PDF
Attachment 04- 238123.pdf PDF
Attachment 05- Tech Questions Tracker - Pitts-Heinz.docx DOCX document
Attachment 02- 646A-700.32.E.20260724.pdf PDF
Amendment 36C77626R0071 0007.pdf PDF
S06 - Amendment 36C77626R0071 0008.docx DOCX document
P03 - Brand Name Justification - Pittsburg Heinz Redacted_Redacted.pdf PDF
Amendment 0006- Attachment 01- Tech Questions- RFI responses.docx DOCX document
Attachment 02-Updated specs and drawings documents.zip ZIP file
Amendment 36C77626R0071 0006.pdf PDF
Amendment 36C77626R0071 0005.pdf PDF
36C77626R0071 0004.pdf PDF
Attachment 01- Tech Questions Tracker - Pitts-Heinz Partial.docx DOCX document
Amendment 36C77626R0071 0003.pdf PDF
Attachment 01-Site Visit Sign in Sheet.pdf PDF
36C77626R0071 0002.pdf PDF
Amendment 0001 - Attachment 06-Site Visit Instructions.docx DOCX document
Amendment 36C77626R0071 0001.pdf PDF
36C77626R0071_1.pdf PDF
Attachment 01-646A4-22-700 - Appx 1 Final Bid Docs V1.pdf PDF
Attachment 04-Wage Rates 5.21 Pittsburgh.pdf PDF
Attachment 05-Limitations on Subcontracting - Construction.pdf PDF
Attachment 06-Site Visit Instructions.docx DOCX document
Attachment 02-646A4-22-700 - Appx 1 Final Bid Docs V2.pdf PDF
Attachment 03-Specs-EHRM Upgrades Heinz Campus - 06-27-25.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T

EMERGENCY

GENERATOR

BA116A

MECHANICAL

ROOM

BA116

ACTIVE STORAGE

BA117

INACTIVE

STORAGE

BA118

VISN INACT

STORAGE

BA119

COMPUTER ROOM

BA120

EQUIPMENT

SETUP & R&D LAB

BA120A

LOADING

BC4

UPS ROOM

BA118A

HELP DESK

BA101A

HELP DESK

BA101

VESTIBULE

BA100

LAN CLO

BA102

MALE TLT

BA103

HAC

BA104

FEMALE

LOUNGE

BA105

PROGRAMMING

BA106

OFFICE

BA107

MECH EQUIP

BA108

IT SUPPORT

BA110

MECHANICAL

EQUIPMENT

BA111

OFFICE

BA110C

OFFICE

BA110D

OFFICE

BA110E

OFFICE

BA110F

OFFICE

BA110B

NEW TR

BA110A

STORAGE

BA109

CORRIDOR

BC2

SOFTWARE

LIBRARY

BA115

TAPE VAULT

BA115A

TLT

BA114

TLT

BA112

ELEV

MACH RM

BA102A

CORRIDOR

BC1

CORRIDOR

BC3

FEMALE TLT

BA105A

OFFICE

BA107A

MECH

BA106C

PBX EXIST

BA110A.2

SS-32-B

SS-32-1

SS-32-2

TERMINATE

CONDENSATE 6"

ABOVE THE FLOOD

RIM OF MOP BASIN.

3/4"DPP

S U

C L

IQ

S U

C L

IQ

L

IQ

S U

C

32-MN402

32-MN401

ACCU-1 ACCU-2 ACCU-3 ACCU-6 ACCU-5 ACCU-4

CRAC-5CRAC-1

CRAC-2

CRAC-6

CRAC-3

CRAC-4

FIRE BARRIER, 3 HOUR

FIRE BARRIER, 2 HOUR

FIRE BARRIER, 1 HOUR

SMOKE BARRIER

NEW PARTITION

EXISTING PARTITION

DEMOLITION

PARTITION LEGEND

623 26TH AVENUE

ROCK ISLAND, IL 61201

P: 309.788.0673 F: 309.786.5967 www.imegcorp.com

PROJECT #23002990.00

CONSTRUCTION DOCUMENT SUBMISSION

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

P L A

N N

O R

T H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES:

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

A u to d e s k D o c s /H e in z V

A M

C E

H R

M

V

/6

A -2

-7

.3

.M

.I M

E G

H

N Z

C

.r v t

/2

/2

:4

:4

P

M

32-MN100

BASEMENT PLAN - MECHANICAL

06.27.2025

EHRM INFRASTRUCTURE

UPGRADES - VAPHS H.J. HEINZ

CAMPUS 32

1010 DELAFIELD RD

PITTSBURGH, PA 15215

646A-22-700

BRAGAR ANDPOP

1. ROUTE AND SIZE REFRIGERANT PIPING PER THE MANUFACTURER'S RECOMMENDATIONS.

Revisions: Date:

ADDENDA DATA CENTER COOLING, Q.56 07/24/2026

FIRE BARRIER, 3 HOUR

FIRE BARRIER, 2 HOUR

FIRE BARRIER, 1 HOUR

SMOKE BARRIER

NEW PARTITION

EXISTING PARTITION

DEMOLITION

PARTITION LEGEND

CRAC UNIT HAS A DUCT FLANGE ON

THE TOP OF THE UNIT. DUCT FROM

THE CONNECTION UPWARD AND

TERMINATE DUCT AT 18" FROM THE

CEILING. DUCT IZE SHALL MATCH

OPENING SIZE. (TYP. 6)

RECONNECT EXISTING CHILLED

WATER AND CONDENSATE PIPING TO

THE NEW CRAC UNIT. (TYP. 6)

CRAC-6

CRAC-3

CRAC-2

CRAC-1

SS-32-B

SS-32-1

SS-32-2

CRAC-5

CRAC-4

ACCU-1 ACCU-3 ACCU-5ACCU-2 ACCU-6 ACCU-4

SUC

LIQ

SUC

LIQ

S U

C

L

IQ

LIQ

SUC

SUC

LIQ

S U

C

L

IQ

SUC

LIQ

S U

C L

IQ

SUC

LIQ

L

IQ

S U

C

SUC

LIQ

LIQ

SUC

ROUTE NEW REFRIGERANT PIPING

THROUGH EXISTING WALL PENETRATION

AND FOLLOW SAME PATH AS EXISTING

REFRIGERANT PIPING FROM OUTDOOR

UNIT TO INDOOR UNIT (TYP.).

623 26TH AVENUE

ROCK ISLAND, IL 61201

P: 309.788.0673 F: 309.786.5967 www.imegcorp.com

PROJECT #23002990.00

CONSTRUCTION DOCUMENT SUBMISSION

2 2 4 6 8 10

1/4" = 1'-0"

FEETSCALE

P L A

N N

O R

T H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES:

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

A u to d e s k D o c s /H e in z V

A M

C E

H R

M

V

/6

A -2

-7

.3

.M

.I M

E G

H

N Z

C

.r v t

/2

/2

:4

:4

P

M

32-MN401

ENLARGED PLANS - BASEMENT - DC

BA120

06.27.2025

EHRM INFRASTRUCTURE

UPGRADES - VAPHS H.J. HEINZ

CAMPUS 32

1010 DELAFIELD RD

PITTSBURGH, PA 15215

646A-22-700

BRAGAR ANDPOPRevisions: Date:

ADDENDA DATA CENTER COOLING, Q.56 07/24/2026

1/4" = 1'-0"

BASEMENT - DC BA120 ENLARGED PLAN

Sheets
32-MN100 - BASEMENT PLAN - MECHANICAL
32-MN401 - ENLARGED PLANS - BASEMENT - DC BA120

File details come from the government source that posted it. Updated .