This is a construction document submission containing mechanical equipment schedules for the EHRM Infrastructure Upgrades project at the VA Pittsburgh Healthcare System H.J. Heinz Campus, located at 1010 Delafield Road, Pittsburgh, PA 15215. The document is prepared by IMEG Corp. (architect/engineer of record) and Awen Solutions Group, with final bid documents issued on June 27, 2025. Project number 646A-22-700 is designated as a fully sprinklered facility.

The schedules specify HVAC equipment requirements including: 23 split system units (Mitsubishi Electric models with cooling capacities ranging from 18-24 MBH, 208V single-phase power, and SEER2 ratings of 19.5-21.1); 12 VRF (Variable Refrigerant Flow) indoor units ranging from 1.5-2.5 tons utilizing R-32 refrigerant with wall-mounted configurations; 2 VRF modular outdoor condensing units (R-32, 96-192 MBH nominal capacity); 6 Computer Room Air Conditioning (CRAC) units serving data center cooling with capacities from 147.2-283.2 MBH using R-454B refrigerant and 480V three-phase power; and 6 air-cooled condenser units (ACC) in 12-27.5 ton configurations. All equipment includes specifications for electrical requirements (voltage, phase, amperage), physical dimensions, weights, disconnect types, controller/starter configurations, and manufacturer details. Equipment notes address condensate pump integration, BACnet controls connectivity, filter requirements, and field adjustment capabilities for air balancing.

View the file

Other files

File Type Posted
Amendment 36C77626R0071 0008.pdf PDF
Attachment 03- 646A-700.32.M.20260724.pdf PDF
Attachment 02- 646A-700.32.E.20260724.pdf PDF
Attachment 04- 238123.pdf PDF
Attachment 05- Tech Questions Tracker - Pitts-Heinz.docx DOCX document
Amendment 36C77626R0071 0007.pdf PDF
P03 - Brand Name Justification - Pittsburg Heinz Redacted_Redacted.pdf PDF
S06 - Amendment 36C77626R0071 0008.docx DOCX document
Attachment 02-Updated specs and drawings documents.zip ZIP file
Amendment 36C77626R0071 0006.pdf PDF
Amendment 0006- Attachment 01- Tech Questions- RFI responses.docx DOCX document
Amendment 36C77626R0071 0005.pdf PDF
36C77626R0071 0004.pdf PDF
Attachment 01- Tech Questions Tracker - Pitts-Heinz Partial.docx DOCX document
Amendment 36C77626R0071 0003.pdf PDF
Attachment 01-Site Visit Sign in Sheet.pdf PDF
36C77626R0071 0002.pdf PDF
Amendment 36C77626R0071 0001.pdf PDF
Amendment 0001 - Attachment 06-Site Visit Instructions.docx DOCX document
36C77626R0071_1.pdf PDF
Attachment 01-646A4-22-700 - Appx 1 Final Bid Docs V1.pdf PDF
Attachment 04-Wage Rates 5.21 Pittsburgh.pdf PDF
Attachment 05-Limitations on Subcontracting - Construction.pdf PDF
Attachment 06-Site Visit Instructions.docx DOCX document
Attachment 03-Specs-EHRM Upgrades Heinz Campus - 06-27-25.pdf PDF
Attachment 02-646A4-22-700 - Appx 1 Final Bid Docs V2.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

623 26TH AVENUE

ROCK ISLAND, IL 61201

P: 309.788.0673 F: 309.786.5967 www.imegcorp.com

PROJECT #23002990.00

CONSTRUCTION DOCUMENT SUBMISSION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

A u to d e s k D o c s

/H e in z V

A M

C E

H R

M

V

/6

A

-2

-7

.C A

M P

U S

.M .I

M E

G

H N

Z

C .r v t

/2

/2

:0

:4

P

M

00-MG600

MECHANICAL SCHEDULES

VA DIRECTOR 001

06.27.2025

EHRM INFRASTRUCTURE

UPGRADES - VAPHS H.J. HEINZ

CAMPUS 0

1010 DELAFIELD RD,

PITTSBURGH, PA 15215

646A-22-700

BRAGAR ANDPOP

NOTES:

1.INDOOR UNIT IS POWERED BY THE OUTDOOR UNIT.

2.PROVIDE WITH CONDENSATE PUMP BY MANUFACTURER OR AS RECOMMENDED BY THE MANUFACTURER.

3.PROVIDE WITH BACNET CONNECTION AND MANUFACTURER'S REMOTE TEMPERATURE SENSOR FOR INTEGRATION INTO THE EXISTING BUILDING AUTOMATION SYSTEM.

SPLIT SYSTEM UNIT SCHEDULE

TAG NAME AREA SERVED

INDOOR UNIT OUTDOOR UNIT ELECTRICAL

MANUFACTURER NOTES

AIRFLOW

(CFM)

COOLING

CAPACITY

(MBH)

MAX. DIMENSIONS

WEIGHT (LBS) MODEL SEER2

MAX. DIMENSIONS

WEIGHT (LBS) MODEL VOLTAGE PHASE

MCA

(AMPS) MOCP (AMPS)

DISCONNECT CONTROLLER/ STARTER

DEPTH (IN) WIDTH (IN) HEIGHT (IN) HEIGHT (IN) DEPTH (IN) WIDTH (IN) BY (NOTE A) BY (NOTE A) SCCR (AMPS)

SS-32-1 1A116 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-32-2 2A112 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-32-B BA110A 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-49-1 1A108A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-50-1A 1A129A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-50-G1 GA130A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-1-1 1A106 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-1-2 1A121 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-1-3 1B151 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-2-1 2A130 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-2-2 2B169 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-3-1 3A130 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-3-2 3B171 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-G-1 GA102A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-G-2 GA114 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-51-G-3 GB136 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-69-1 1A131 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-69-2 2A104 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-70-1-1 1A140A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-70-1-2 1A166 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-70-2-1 2A239A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-70-2-2 2A260 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

SS-70-B BA003 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3

G. CURB TYPE:

MFR = STANDARD CURB BY MANUFACTURER

GC = BY GENERAL CONTRACTOR

SAC = SOUND ATTENUATOR CURB

F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.

E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAME

PLATE RATING.

D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE, WITH

THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS

FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.

C. CONTROLLER STARTER TYPE:

FV = FULL VOLTAGE

WYE = WYE-DELTA

SS = SOLID STATE (SOFT START)

MS = MANUAL STARTER

VFD = VARIABLE FREQUENCY DRIVE

VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS

YD = WYE - DELTA

ECM = ELECTRONICALLY COMMUTATED MOTOR

B. DISCONNECT TYPE:

CB = CIRCUIT BREAKER

F = FUSED

NF = NON-FUSED

PLUG = PLUG AND CORD

A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND

INSTALLED BY:

MFR = MANUFACTURER

EC = ELECTRICAL CONTRACTOR.

MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BY

ELECTRICAL CONTRACTOR.

MFR/EC = FURNISHED LOOSE BY MANUFACTURER INSTALLED BY

ELECTRICAL CONTRACTOR.

TCC = TEMPERATURE CONTROL CONTRACTOR

SCHEDULE GENERAL NOTES:

NOTES:

1. INDOOR UNITS SELECTED TO MATCH EXISTING UNIT CAPACITY.

2. PROVIDE 30% FILTERS FOR EACH UNIT.

3. UNIT SHALL BE PROVIDED WITH CONDENSATE PUMP.

4. REFER TO SPECIFICATION 23 81 45 FOR DESCRIPTION OF CONTROLS.

5. INDOOR UNIT CFM SELECTED AT HIGH CFM. INDOOR UNIT SHALL HAVE CAPABILITY TO ADJUST CFM FOR FINAL AIR BALANCING UP OR DOWN THROUGH FIELD ADJUSTMENT.

6. UNIT SHALL BE PROVIDED WITH INTEGRAL LIFT/PUMP FOR CONDENSATE REMOVAL. IF NOT PROVIDED INTEGRAL WITH UNIT, CONTRACTOR SHALL PROVIDE SEPARATE CONDENSATE PUMP. CONDENSATE PUMP SHALL BE POWERED BY UNIT. IF NOT, MECHANCIAL CONTRACTOR IS RESPONSIBLE TO PROVIDE POWER FOR CONDENSATE PUMP.

VRF INDOOR UNIT SCHEDULE

TAG NAME AREA SERVED A

S

S O

C

IA

T E

D V

R F

C O

N D

E N

S

IN

G U

N

IT

C O

N F

IG

U

R A

T

IO

N

T O

N S

C F

M

REFRIGERANT DESIGN COOLING BTUH

D E

S

IG

N H

E A

T

IN

G T

O T

A L

B T

U H

ELECTRICAL MAX. DIMENSIONS WEIGHT (LBS)

MANUFACTURER MODEL NOTEST

Y

P E

S E

N S

IB

L

E

T O

T A

L

V O

L T

A G

E

P H

A S

E S

M O

C P

S C

C R

DISCONNECT

CONTROLLER

/ STARTER

W

ID

T H

D E

P T

H

H E

IG

H

T

O P

E R

A T

IN

G

B

Y (N

O T

E A

T

P

E (N

O T

E

(N

O T

E A

VRF-TU-71-1 GA120 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6

VRF-TU-71-2 GA119 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6

VRF-TU-71-3 GA119 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6

VRF-TU-71-4 GA104 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6

VRF-TU-71-5 1C122 VRF-CU-71-1 WALL MOUNTED 2 920 R-32 20558 20680 12536 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP024KM1M0A NOTES 1-6

VRF-TU-71-6 1C122 VRF-CU-71-1 WALL MOUNTED 1.5 438 R-32 12144 15510 9286 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6

VRF-TU-71-7 2C108 VRF-CU-71-1 WALL MOUNTED 1.5 438 R-32 12144 15510 9286 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6

VRF-TU-71-8 2C108 VRF-CU-71-1 WALL MOUNTED 1.5 438 R-32 12144 15510 9286 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6

VRF-TU-71-9 1A168 VRF-CU-71-2 WALL MOUNTED 2 920 R-32 20927 21602 16271 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP024KM1M0A NOTES 1-6

VRF-TU-71-10 1A168 VRF-CU-71-2 WALL MOUNTED 1.5 438 R-32 12446 16202 12052 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6

VRF-TU-71-11 2A127 VRF-CU-71-2 WALL MOUNTED 1.5 438 R-32 12446 16202 12052 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6

VRF-TU-71-12 2A127 VRF-CU-71-2 WALL MOUNTED 1.5 438 R-32 12446 16202 12052 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6

NOTES:

1. UNITS SHALL BE SELECTED FOR DESIGN COOLING LOAD.

2. COORDINATE ELECTRICAL CONNECTIONS WITH MANUFACTURER. UNIT IS SUPPLIED AS MULTIPLE MODULES. EACH MODULE REQUIRES A SEPARATE ELECTRICAL CONNECTION AND DISCONNECT.

3. NOMINAL COOLING CAPACITY RATED AT: INDOOR TEMP = 80°FDB/67°FWB, OUTDOOR TEMP = 95°FDB.

4. DESIGN COOLING CAPACITY SHALL BE RATED AT: INDOOR TEMP = 74°FDB/61.7°FWB, OUTDOOR TEMP = 96°FDB. EFFECTS OF ESTIMATED REFRIGERANT LINE LENGTH SHALL BE INCLUDED IN COMPUTING DESIGN CAPACITY.

5. DESIGN HEATING CAPACITY SHALL BE RATED AT: INDOOR TEMP = 70°FDB, OUTDOOR TEMP = -10°FDB. EFFECTS OF ESTIMATED REFRIGERANT LINE LENGTHS AND DEFROSTING SHALL BE INCLUDED IN COMPUTING DESIGN CAPACITY.

VRF MODULAR OUTDOOR UNIT SCHEDULE

TAG NAME AREA SERVED R

E

F R

IG

E

R A

N T

M A

X R

E F

R

IG

E R

A N

T C

H A

R G

E

L B

S

COOLING HEATING

N U

M B

E R

O F

C O

N N

E C

T E

D I N

D O

O R

U N

IT

S

C O

N N

E C

T

IO

N R

A T

IO

ELECTRICAL MAX. DIMENSIONS WEIGHT (LBS)

MANUFACTURER MODEL NOTESN

O

M

IN

A L

M B

H

N O

T E

D E

S

IG

N M

B H

N

O T

E

O P

E R

A T

IN

G

R A

N G

E

F D

B

D E

S

IG

N M

B H

N

O T

E

O P

E R

A T

IN

G

R A

N G

E

F D

B

V O

L T

A G

E

P H

A S

E S

M C

A

M O

C P

DISCONNECT CONTROLLER/STARTER

D E

P T

H

W

ID

T H

H E

IG

H

T

O P

E R

A T

IN

G

B Y

N

O T

E A

T Y

P E

N

O T

E B

B Y

N

O T

E A

S C

C R

VRF-CU-71-1 BUILDING 71 R-32 13.9 192 171 -10.0 104 60 8 103.1 208 3 60 100 MFR CB MFR 5000 29-7/16" 47-15/16" 70-13/16" 708 MITSUBISHI ELECTRIC TUHYE1923AMM0AN NOTES 1, 2

VRF-CU-71-2 BUILDING 71 R-32 11.7 96 93 -10.0 52 60 4 81.3 208 3 40 60 MFR CB MFR 5000 29-7/16" 36-1/4" 70-13/16" 598 MITSUBISHI ELECTRIC TUHYE0963AMM0AN NOTES 1, 2

Revisions: Date:

ADDENDUM #1 06/19/2026

ADDENDA DATA CENTER COOLING, Q.56 07/24/2026

NOTES:

1. UNIT TO BE IN DOWNFLOW CONFIGURATION FOR USE WITH AN UNDERFLOOR PLENUM. PROVIDE WITH TOP RETURN DUCT FLANGE.

2. PROVIDE WITH MANUFACTURER INSTALLED CONDENSATE PUMP.

3. PROVIDE WITH FLOOR STAND. COORDINATE HEIGHT WITH EXISTING PLENUM HEIGHT PRIOR TO ORDERING.

COMPUTER ROOM UNIT SCHEDULE (CRAC)

TAG

NAME

LOCATION FAN COOLING COIL 1 (DX) COOLING COIL 2 (CHILLED WATER) FILTER ELECTRICAL CONTROL MAXIMUM DIMENSIONS WEIGHT (LBS)

MANUFACTURER MODEL NOTESNAME NO.

CFM EXT S.P.

IN. WC

MOTOR REFRIGERANT

FLUID TYPE

MBH EAT LAT

FLUID TYPE TOTAL SENSIBLE

EAT LAT GPM W.P.D.

FT. HD. EWT °F LWT °F TYPE MERV VOLTS PH FLA MCA MOCP

DISCONNECT CNTLR/STARTER

SCCR DIAGRAM WIDTH HEIGHT DEPTH OPERATINGDESIGN kW TYPE TOTAL SENSIBLE DB °F WB °F DB °F WB °F DB °F DB °F DESIGN BY [A] TYPE [B] BY [A] TYPE [C]

CRAC-1 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3

CRAC-2 COMPUTER ROOM BA120 8,000 0.3 4.5 R-454B REFRIGERANT 147.2 147.2 72 60 54 52.9 CHILLED WATER 124.1 124.1 72 56.7 17.8 8.1 45 60 4" 8 480 3 36 A 39 A 50 A MFR CB MFR SS 10,000 A 1/00-MG700 7'-10" 7'-0 1/2" 2'-9 243/256" 2,425 ABOVEAIR MCE-042J NOTES 1-3

CRAC-3 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3

CRAC-4 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3

CRAC-5 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3

CRAC-6 COMPUTER ROOM BA120 8,000 0.3 4.5 R-454B REFRIGERANT 147.2 147.2 72 60 54 52.9 CHILLED WATER 124.1 124.1 72 56.7 17.8 8.1 45 60 4" 8 480 3 36 A 39 A 50 A MFR CB MFR SS 10,000 A 1/00-MG700 7'-10" 7'-0 1/2" 2'-9 243/256" 2,425 ABOVEAIR MCE-042J NOTES 1-3

NOTES:

1. PROVIDE UNIT WITH HAIL GUARD BY MANUFACTURER.

AIR COOLED CONDENSER SCHEDULE (ACC)

TAG

NAME

LOCATION AMBIENT TEMP °F

SERVICE

REFRIGERANT

TONS

FANS ELECTRICAL

CONTROL

DIAGRAM

CURB / PAD MAXIMUM DIMENSIONS WEIGHT (LBS)

MANUFACTURER MODEL NOTESNAME

SUMMER

DRY BULB

MINIMUM

DRY BULB TYPE

NO. OF

CIRCUITS QTY kW VOLTS PH FLA MCA MOCP

DISCONNECT CNTLR/STARTER

SCCR TYPE / BY [G] HEIGHT WIDTH HEIGHT DEPTH OPERATINGBY [A] TYPE [B] BY [A] TYPE [C]

ACCU-1 ON-GRADE 95 0 CRAC-1 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1

ACCU-2 ON-GRADE 95 0 CRAC-2 R-454B 2 12 1 3.4 480 3 4.7 A 5.8 A 15 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 6'-8" 5'-3 7/32" 5'-6" 1,570 ABOVEAIR XPX-042H NOTE 1

ACCU-3 ON-GRADE 95 0 CRAC-3 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1

ACCU-4 ON-GRADE 95 0 CRAC-4 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1

ACCU-5 ON-GRADE 95 0 CRAC-5 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1

ACCU-6 ON-GRADE 95 0 CRAC-6 R-454B 2 12 1 3.4 480 3 4.7 A 5.8 A 15 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 6'-8" 5'-3 7/32" 5'-6" 1,570 ABOVEAIR XPX-042H NOTE 1

1 = SENSOR ONLY

2 = SENSOR WITH ADJUSTMENT

3 = SENSOR WITH OVERRIDE

4 = SENSOR WITH ADJUSTMENT AND OVERRIDE.

[H] CONTROL / SENSOR TYPE

MFR = MANUFACTURER

MC = MECHANICAL CONTRACTOR

GC = BY GENERAL CONTRACTOR

[G] CURB / PAD BY:

STD = STANDARD CURB

SAC = SOUND ATTENUATOR CURB

CONC = CONCRETE BASE (HOUSEKEEPING PAD)

[G] CURB / PAD TYPE:

MUST BE WITHIN +/- 10% OF SCHEDULED RPM.

[F] RPM DEVIATION

NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF

MOTOR NAME PLATE RATING.

[E] HORSEPOWER LIMITATION

FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED

VALUE, WITH THE SCHEDULED WHEEL TYPE.

SUBSTITUTION OF BI OR BIA FANS FOR FC IS

ACCEPTABLE IF EFFICIENCY IS NOT LOWER.

[D] RPM LIMITATION

FV = FULL VOLTAGE

WYE = WYE-DELTA

SS = SOLID STATE (SOFT START)

MS = MANUAL STARTER

VFD = VARIABLE FREQUENCY DRIVE

VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS

ECM = ELECTRONICALLY COMMUTATED MOTOR

NOTE: PROVIDE SHAFT GROUNDING ON MOTORS

DRIVEN BY A VFD AS REQUIRED PER SPECIFICATIONS

22 05 13 AND 23 05 13.

[C] CONTROLLER STARTER TYPE:

CB = CIRCUIT BREAKER

F = FUSED

NF = NON-FUSED

PLUG = PLUG AND CORD

[B] DISCONNECT TYPE:

MFR = MANUFACTURER

EC = ELECTRICAL CONTRACTOR.

MC = FURNISHED BY MECHANICAL CONTRACTOR,

INSTALLED BY ELECTRICAL CONTRACTOR.

MFR/EC = FURNISHED LOOSE BY MANUFACTURER

INSTALLED BY ELECTRICAL CONTRACTOR.

TCC = TEMPERATURE CONTROL CONTRACTOR

[A] DISCONNECT AND CNTLR/STARTER FURNISHED

AND INSTALLED BY:

SCHEDULE GENERAL KEY

2 2

Sheets
00-MG600 - MECHANICAL SCHEDULES

File details come from the government source that posted it. Updated .