This is a construction document submission containing mechanical equipment schedules for the EHRM Infrastructure Upgrades project at the VA Pittsburgh Healthcare System H.J. Heinz Campus, located at 1010 Delafield Road, Pittsburgh, PA 15215. The document is prepared by IMEG Corp. (architect/engineer of record) and Awen Solutions Group, with final bid documents issued on June 27, 2025. Project number 646A-22-700 is designated as a fully sprinklered facility.
The schedules specify HVAC equipment requirements including: 23 split system units (Mitsubishi Electric models with cooling capacities ranging from 18-24 MBH, 208V single-phase power, and SEER2 ratings of 19.5-21.1); 12 VRF (Variable Refrigerant Flow) indoor units ranging from 1.5-2.5 tons utilizing R-32 refrigerant with wall-mounted configurations; 2 VRF modular outdoor condensing units (R-32, 96-192 MBH nominal capacity); 6 Computer Room Air Conditioning (CRAC) units serving data center cooling with capacities from 147.2-283.2 MBH using R-454B refrigerant and 480V three-phase power; and 6 air-cooled condenser units (ACC) in 12-27.5 ton configurations. All equipment includes specifications for electrical requirements (voltage, phase, amperage), physical dimensions, weights, disconnect types, controller/starter configurations, and manufacturer details. Equipment notes address condensate pump integration, BACnet controls connectivity, filter requirements, and field adjustment capabilities for air balancing.
View the file
Other files
Show all 26
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
623 26TH AVENUE
ROCK ISLAND, IL 61201
P: 309.788.0673 F: 309.786.5967 www.imegcorp.com
PROJECT #23002990.00
CONSTRUCTION DOCUMENT SUBMISSION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
FINAL BID DOCUMENTS
FULLY SPRINKLERED
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMP
321 4 5 6 7 8 9 10
Awen Solutions Group
215 N. Payne Street, Suite 122
Alexandria, VA 22314
A u to d e s k D o c s
/H e in z V
A M
C E
H R
M
V
/6
A
-2
-7
.C A
M P
U S
.M .I
M E
G
H N
Z
C .r v t
/2
/2
:0
:4
P
M
00-MG600
MECHANICAL SCHEDULES
VA DIRECTOR 001
06.27.2025
EHRM INFRASTRUCTURE
UPGRADES - VAPHS H.J. HEINZ
CAMPUS 0
1010 DELAFIELD RD,
PITTSBURGH, PA 15215
646A-22-700
BRAGAR ANDPOP
NOTES:
1.INDOOR UNIT IS POWERED BY THE OUTDOOR UNIT.
2.PROVIDE WITH CONDENSATE PUMP BY MANUFACTURER OR AS RECOMMENDED BY THE MANUFACTURER.
3.PROVIDE WITH BACNET CONNECTION AND MANUFACTURER'S REMOTE TEMPERATURE SENSOR FOR INTEGRATION INTO THE EXISTING BUILDING AUTOMATION SYSTEM.
SPLIT SYSTEM UNIT SCHEDULE
TAG NAME AREA SERVED
INDOOR UNIT OUTDOOR UNIT ELECTRICAL
MANUFACTURER NOTES
AIRFLOW
(CFM)
COOLING
CAPACITY
(MBH)
MAX. DIMENSIONS
WEIGHT (LBS) MODEL SEER2
MAX. DIMENSIONS
WEIGHT (LBS) MODEL VOLTAGE PHASE
MCA
(AMPS) MOCP (AMPS)
DISCONNECT CONTROLLER/ STARTER
DEPTH (IN) WIDTH (IN) HEIGHT (IN) HEIGHT (IN) DEPTH (IN) WIDTH (IN) BY (NOTE A) BY (NOTE A) SCCR (AMPS)
SS-32-1 1A116 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-32-2 2A112 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-32-B BA110A 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-49-1 1A108A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-50-1A 1A129A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-50-G1 GA130A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-1-1 1A106 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-1-2 1A121 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-1-3 1B151 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-2-1 2A130 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-2-2 2B169 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-3-1 3A130 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-3-2 3B171 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-G-1 GA102A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-G-2 GA114 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-51-G-3 GB136 450 18 9 11/32 35 11/32 11 25/32 28 PKA-AL18NL 19.5 24 13/16" 11 13/16" 34 19/64" 99 PUY-AK18NL 208 1 16.0 27 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-69-1 1A131 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-69-2 2A104 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-70-1-1 1A140A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-70-1-2 1A166 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-70-2-1 2A239A 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-70-2-2 2A260 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
SS-70-B BA003 775 24 11 5/8" 46 1/16" 14 3/8" 46 PKA-AK24NL 21.1 37 1/8" 14" 37 13/32" 155 PUY-AH24NL 208 1 22.0 37 EC MFR 5000 MITSUBISHI ELECTRIC NOTE 1, 2, 3
G. CURB TYPE:
MFR = STANDARD CURB BY MANUFACTURER
GC = BY GENERAL CONTRACTOR
SAC = SOUND ATTENUATOR CURB
F. MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
E. NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF MOTOR NAME
PLATE RATING.
D. FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED VALUE, WITH
THE SCHEDULED WHEEL TYPE. SUBSTITUTION OF BI OR BIA FANS
FOR FC IS ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
C. CONTROLLER STARTER TYPE:
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)
MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
YD = WYE - DELTA
ECM = ELECTRONICALLY COMMUTATED MOTOR
B. DISCONNECT TYPE:
CB = CIRCUIT BREAKER
F = FUSED
NF = NON-FUSED
PLUG = PLUG AND CORD
A. DISCONNECT AND CONTROLLER STARTER FURNISHED AND
INSTALLED BY:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR, INSTALLED BY
ELECTRICAL CONTRACTOR.
MFR/EC = FURNISHED LOOSE BY MANUFACTURER INSTALLED BY
ELECTRICAL CONTRACTOR.
TCC = TEMPERATURE CONTROL CONTRACTOR
SCHEDULE GENERAL NOTES:
NOTES:
1. INDOOR UNITS SELECTED TO MATCH EXISTING UNIT CAPACITY.
2. PROVIDE 30% FILTERS FOR EACH UNIT.
3. UNIT SHALL BE PROVIDED WITH CONDENSATE PUMP.
4. REFER TO SPECIFICATION 23 81 45 FOR DESCRIPTION OF CONTROLS.
5. INDOOR UNIT CFM SELECTED AT HIGH CFM. INDOOR UNIT SHALL HAVE CAPABILITY TO ADJUST CFM FOR FINAL AIR BALANCING UP OR DOWN THROUGH FIELD ADJUSTMENT.
6. UNIT SHALL BE PROVIDED WITH INTEGRAL LIFT/PUMP FOR CONDENSATE REMOVAL. IF NOT PROVIDED INTEGRAL WITH UNIT, CONTRACTOR SHALL PROVIDE SEPARATE CONDENSATE PUMP. CONDENSATE PUMP SHALL BE POWERED BY UNIT. IF NOT, MECHANCIAL CONTRACTOR IS RESPONSIBLE TO PROVIDE POWER FOR CONDENSATE PUMP.
VRF INDOOR UNIT SCHEDULE
TAG NAME AREA SERVED A
S
S O
C
IA
T E
D V
R F
C O
N D
E N
S
IN
G U
N
IT
C O
N F
IG
U
R A
T
IO
N
T O
N S
C F
M
REFRIGERANT DESIGN COOLING BTUH
D E
S
IG
N H
E A
T
IN
G T
O T
A L
B T
U H
ELECTRICAL MAX. DIMENSIONS WEIGHT (LBS)
MANUFACTURER MODEL NOTEST
Y
P E
S E
N S
IB
L
E
T O
T A
L
V O
L T
A G
E
P H
A S
E S
M O
C P
S C
C R
DISCONNECT
CONTROLLER
/ STARTER
W
ID
T H
D E
P T
H
H E
IG
H
T
O P
E R
A T
IN
G
B
Y (N
O T
E A
T
P
E (N
O T
E
(N
O T
E A
VRF-TU-71-1 GA120 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6
VRF-TU-71-2 GA119 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6
VRF-TU-71-3 GA119 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6
VRF-TU-71-4 GA104 VRF-CU-71-1 WALL MOUNTED 2.5 920 R-32 22657 25850 15787 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP030KM1M0A NOTES 1-6
VRF-TU-71-5 1C122 VRF-CU-71-1 WALL MOUNTED 2 920 R-32 20558 20680 12536 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP024KM1M0A NOTES 1-6
VRF-TU-71-6 1C122 VRF-CU-71-1 WALL MOUNTED 1.5 438 R-32 12144 15510 9286 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6
VRF-TU-71-7 2C108 VRF-CU-71-1 WALL MOUNTED 1.5 438 R-32 12144 15510 9286 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6
VRF-TU-71-8 2C108 VRF-CU-71-1 WALL MOUNTED 1.5 438 R-32 12144 15510 9286 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6
VRF-TU-71-9 1A168 VRF-CU-71-2 WALL MOUNTED 2 920 R-32 20927 21602 16271 208 1 15 A 5000 MFR/EC CB MFR 46-1/16" 11-5/8" 14-3/8" 46 MITSUBISHI ELECTRIC TPKFYP024KM1M0A NOTES 1-6
VRF-TU-71-10 1A168 VRF-CU-71-2 WALL MOUNTED 1.5 438 R-32 12446 16202 12052 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6
VRF-TU-71-11 2A127 VRF-CU-71-2 WALL MOUNTED 1.5 438 R-32 12446 16202 12052 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6
VRF-TU-71-12 2A127 VRF-CU-71-2 WALL MOUNTED 1.5 438 R-32 12446 16202 12052 208 1 15 A 5000 MFR/EC CB MFR 35-3/8" 9-5/16" 11-3/4" 28 MITSUBISHI ELECTRIC TPKFYP018LM1M0A NOTES 1-6
NOTES:
1. UNITS SHALL BE SELECTED FOR DESIGN COOLING LOAD.
2. COORDINATE ELECTRICAL CONNECTIONS WITH MANUFACTURER. UNIT IS SUPPLIED AS MULTIPLE MODULES. EACH MODULE REQUIRES A SEPARATE ELECTRICAL CONNECTION AND DISCONNECT.
3. NOMINAL COOLING CAPACITY RATED AT: INDOOR TEMP = 80°FDB/67°FWB, OUTDOOR TEMP = 95°FDB.
4. DESIGN COOLING CAPACITY SHALL BE RATED AT: INDOOR TEMP = 74°FDB/61.7°FWB, OUTDOOR TEMP = 96°FDB. EFFECTS OF ESTIMATED REFRIGERANT LINE LENGTH SHALL BE INCLUDED IN COMPUTING DESIGN CAPACITY.
5. DESIGN HEATING CAPACITY SHALL BE RATED AT: INDOOR TEMP = 70°FDB, OUTDOOR TEMP = -10°FDB. EFFECTS OF ESTIMATED REFRIGERANT LINE LENGTHS AND DEFROSTING SHALL BE INCLUDED IN COMPUTING DESIGN CAPACITY.
VRF MODULAR OUTDOOR UNIT SCHEDULE
TAG NAME AREA SERVED R
E
F R
IG
E
R A
N T
M A
X R
E F
R
IG
E R
A N
T C
H A
R G
E
L B
S
COOLING HEATING
N U
M B
E R
O F
C O
N N
E C
T E
D I N
D O
O R
U N
IT
S
C O
N N
E C
T
IO
N R
A T
IO
ELECTRICAL MAX. DIMENSIONS WEIGHT (LBS)
MANUFACTURER MODEL NOTESN
O
M
IN
A L
M B
H
N O
T E
D E
S
IG
N M
B H
N
O T
E
O P
E R
A T
IN
G
R A
N G
E
F D
B
D E
S
IG
N M
B H
N
O T
E
O P
E R
A T
IN
G
R A
N G
E
F D
B
V O
L T
A G
E
P H
A S
E S
M C
A
M O
C P
DISCONNECT CONTROLLER/STARTER
D E
P T
H
W
ID
T H
H E
IG
H
T
O P
E R
A T
IN
G
B Y
N
O T
E A
T Y
P E
N
O T
E B
B Y
N
O T
E A
S C
C R
VRF-CU-71-1 BUILDING 71 R-32 13.9 192 171 -10.0 104 60 8 103.1 208 3 60 100 MFR CB MFR 5000 29-7/16" 47-15/16" 70-13/16" 708 MITSUBISHI ELECTRIC TUHYE1923AMM0AN NOTES 1, 2
VRF-CU-71-2 BUILDING 71 R-32 11.7 96 93 -10.0 52 60 4 81.3 208 3 40 60 MFR CB MFR 5000 29-7/16" 36-1/4" 70-13/16" 598 MITSUBISHI ELECTRIC TUHYE0963AMM0AN NOTES 1, 2
Revisions: Date:
ADDENDUM #1 06/19/2026
ADDENDA DATA CENTER COOLING, Q.56 07/24/2026
NOTES:
1. UNIT TO BE IN DOWNFLOW CONFIGURATION FOR USE WITH AN UNDERFLOOR PLENUM. PROVIDE WITH TOP RETURN DUCT FLANGE.
2. PROVIDE WITH MANUFACTURER INSTALLED CONDENSATE PUMP.
3. PROVIDE WITH FLOOR STAND. COORDINATE HEIGHT WITH EXISTING PLENUM HEIGHT PRIOR TO ORDERING.
COMPUTER ROOM UNIT SCHEDULE (CRAC)
TAG
NAME
LOCATION FAN COOLING COIL 1 (DX) COOLING COIL 2 (CHILLED WATER) FILTER ELECTRICAL CONTROL MAXIMUM DIMENSIONS WEIGHT (LBS)
MANUFACTURER MODEL NOTESNAME NO.
CFM EXT S.P.
IN. WC
MOTOR REFRIGERANT
FLUID TYPE
MBH EAT LAT
FLUID TYPE TOTAL SENSIBLE
EAT LAT GPM W.P.D.
FT. HD. EWT °F LWT °F TYPE MERV VOLTS PH FLA MCA MOCP
DISCONNECT CNTLR/STARTER
SCCR DIAGRAM WIDTH HEIGHT DEPTH OPERATINGDESIGN kW TYPE TOTAL SENSIBLE DB °F WB °F DB °F WB °F DB °F DB °F DESIGN BY [A] TYPE [B] BY [A] TYPE [C]
CRAC-1 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3
CRAC-2 COMPUTER ROOM BA120 8,000 0.3 4.5 R-454B REFRIGERANT 147.2 147.2 72 60 54 52.9 CHILLED WATER 124.1 124.1 72 56.7 17.8 8.1 45 60 4" 8 480 3 36 A 39 A 50 A MFR CB MFR SS 10,000 A 1/00-MG700 7'-10" 7'-0 1/2" 2'-9 243/256" 2,425 ABOVEAIR MCE-042J NOTES 1-3
CRAC-3 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3
CRAC-4 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3
CRAC-5 COMPUTER ROOM BA120 14,000 0.3 4.5 R-454B REFRIGERANT 283.2 243.1 72 60 54.6 52 CHILLED WATER 222 222 72 56 35 25.1 45 59 4" 8 480 3 67.3 A 73.5 A 90 A MFR CB MFR SS 10,000 A 1/00-MG700 11'-0" 7'-0 1/2" 2'-9 243/256" 3,600 ABOVEAIR MCE-097J NOTES 1-3
CRAC-6 COMPUTER ROOM BA120 8,000 0.3 4.5 R-454B REFRIGERANT 147.2 147.2 72 60 54 52.9 CHILLED WATER 124.1 124.1 72 56.7 17.8 8.1 45 60 4" 8 480 3 36 A 39 A 50 A MFR CB MFR SS 10,000 A 1/00-MG700 7'-10" 7'-0 1/2" 2'-9 243/256" 2,425 ABOVEAIR MCE-042J NOTES 1-3
NOTES:
1. PROVIDE UNIT WITH HAIL GUARD BY MANUFACTURER.
AIR COOLED CONDENSER SCHEDULE (ACC)
TAG
NAME
LOCATION AMBIENT TEMP °F
SERVICE
REFRIGERANT
TONS
FANS ELECTRICAL
CONTROL
DIAGRAM
CURB / PAD MAXIMUM DIMENSIONS WEIGHT (LBS)
MANUFACTURER MODEL NOTESNAME
SUMMER
DRY BULB
MINIMUM
DRY BULB TYPE
NO. OF
CIRCUITS QTY kW VOLTS PH FLA MCA MOCP
DISCONNECT CNTLR/STARTER
SCCR TYPE / BY [G] HEIGHT WIDTH HEIGHT DEPTH OPERATINGBY [A] TYPE [B] BY [A] TYPE [C]
ACCU-1 ON-GRADE 95 0 CRAC-1 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1
ACCU-2 ON-GRADE 95 0 CRAC-2 R-454B 2 12 1 3.4 480 3 4.7 A 5.8 A 15 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 6'-8" 5'-3 7/32" 5'-6" 1,570 ABOVEAIR XPX-042H NOTE 1
ACCU-3 ON-GRADE 95 0 CRAC-3 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1
ACCU-4 ON-GRADE 95 0 CRAC-4 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1
ACCU-5 ON-GRADE 95 0 CRAC-5 R-454B 2 27.5 2 3.4 480 3 9.3 A 11.6 A 20 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 7'-1" 5'-2 49/256" 5'-6" 1,715 ABOVEAIR XPX-097H NOTE 1
ACCU-6 ON-GRADE 95 0 CRAC-6 R-454B 2 12 1 3.4 480 3 4.7 A 5.8 A 15 A MFR CB MFR SS 10,000 A 1/00-MG700 CONC 6" 6'-8" 5'-3 7/32" 5'-6" 1,570 ABOVEAIR XPX-042H NOTE 1
1 = SENSOR ONLY
2 = SENSOR WITH ADJUSTMENT
3 = SENSOR WITH OVERRIDE
4 = SENSOR WITH ADJUSTMENT AND OVERRIDE.
[H] CONTROL / SENSOR TYPE
MFR = MANUFACTURER
MC = MECHANICAL CONTRACTOR
GC = BY GENERAL CONTRACTOR
[G] CURB / PAD BY:
STD = STANDARD CURB
SAC = SOUND ATTENUATOR CURB
CONC = CONCRETE BASE (HOUSEKEEPING PAD)
[G] CURB / PAD TYPE:
MUST BE WITHIN +/- 10% OF SCHEDULED RPM.
[F] RPM DEVIATION
NO EQUIPMENT SHALL BE SELECTED ABOVE 90% OF
MOTOR NAME PLATE RATING.
[E] HORSEPOWER LIMITATION
FAN RPM SHALL NOT EXCEED 110% OF SCHEDULED
VALUE, WITH THE SCHEDULED WHEEL TYPE.
SUBSTITUTION OF BI OR BIA FANS FOR FC IS
ACCEPTABLE IF EFFICIENCY IS NOT LOWER.
[D] RPM LIMITATION
FV = FULL VOLTAGE
WYE = WYE-DELTA
SS = SOLID STATE (SOFT START)
MS = MANUAL STARTER
VFD = VARIABLE FREQUENCY DRIVE
VFD/B = VARIABLE FREQUENCY DRIVE WITH BYPASS
ECM = ELECTRONICALLY COMMUTATED MOTOR
NOTE: PROVIDE SHAFT GROUNDING ON MOTORS
DRIVEN BY A VFD AS REQUIRED PER SPECIFICATIONS
22 05 13 AND 23 05 13.
[C] CONTROLLER STARTER TYPE:
CB = CIRCUIT BREAKER
F = FUSED
NF = NON-FUSED
PLUG = PLUG AND CORD
[B] DISCONNECT TYPE:
MFR = MANUFACTURER
EC = ELECTRICAL CONTRACTOR.
MC = FURNISHED BY MECHANICAL CONTRACTOR,
INSTALLED BY ELECTRICAL CONTRACTOR.
MFR/EC = FURNISHED LOOSE BY MANUFACTURER
INSTALLED BY ELECTRICAL CONTRACTOR.
TCC = TEMPERATURE CONTROL CONTRACTOR
[A] DISCONNECT AND CNTLR/STARTER FURNISHED
AND INSTALLED BY:
SCHEDULE GENERAL KEY
2 2