Attachment 02- 646A-700.32.E.20260724.pdf

PDF 539 KB Posted

Attached to
Z1DA--646A4-22-700 | EHRM Infrastructure Upgrades | Pittsburgh-Heinz, PA
Solicitation number
36C77626R0071
Issued by

About this file

These are electrical construction documents for infrastructure upgrades at the VA Pittsburgh Healthcare System (VAPHS) H.J. Heinz Campus 32, located at 1010 Delafield Road, Pittsburgh, PA 15215. The documents include a basement-level electrical plan (32-EN100) and electrical schedules (32-EN302) dated June 27, 2025, prepared by Awen Solutions Group and IMEG as the architect/engineer of record under Project Number 646A-22-700. The project represents the final bid documents phase and is fully sprinklered.

The electrical plans detail existing equipment to remain and new installations for data center cooling and power distribution infrastructure. Key electrical components include multiple PDU (Power Distribution Unit) panels designated PDU-A through PDU-E, CRAC (Computer Room Air Conditioning) units numbered 1 through 6 serving different floor sections, ACCU (Accumulator) units, UPS (Uninterruptible Power Supply) systems with batteries, an emergency generator, an automated transfer switch (ATS), and switchboards. The electrical schedules specify circuit details including breaker amperage ratings (ranging from 15A to 125A), wire gauges, voltage drops, and load calculations for panels A1, B1, PDU-B/D, and PDU-D/D located in the Computer Room (BA120) and Active Storage (BA117) areas. Total estimated demand loads include 28 kVA for PDU panels and 154.488 kVA for HVAC cooling systems at 480 volts delta configuration. The existing Emergency Power-Off (EPO) system will remain unchanged with testing before and after construction, and new receptacles for the Main Distribution Area (MDA) will be mounted in junction boxes between the raised floor and concrete floor.

View the file

Other files

File Type Posted
Amendment 36C77626R0071 0008.pdf PDF
Attachment 03- 646A-700.32.M.20260724.pdf PDF
Attachment 01- 646A-700.CAMPUS.M.20260724.pdf PDF
Attachment 04- 238123.pdf PDF
Attachment 05- Tech Questions Tracker - Pitts-Heinz.docx DOCX document
Amendment 36C77626R0071 0007.pdf PDF
P03 - Brand Name Justification - Pittsburg Heinz Redacted_Redacted.pdf PDF
S06 - Amendment 36C77626R0071 0008.docx DOCX document
Amendment 0006- Attachment 01- Tech Questions- RFI responses.docx DOCX document
Attachment 02-Updated specs and drawings documents.zip ZIP file
Amendment 36C77626R0071 0006.pdf PDF
Amendment 36C77626R0071 0005.pdf PDF
36C77626R0071 0004.pdf PDF
Attachment 01- Tech Questions Tracker - Pitts-Heinz Partial.docx DOCX document
Amendment 36C77626R0071 0003.pdf PDF
Attachment 01-Site Visit Sign in Sheet.pdf PDF
36C77626R0071 0002.pdf PDF
Amendment 0001 - Attachment 06-Site Visit Instructions.docx DOCX document
Amendment 36C77626R0071 0001.pdf PDF
36C77626R0071_1.pdf PDF
Attachment 01-646A4-22-700 - Appx 1 Final Bid Docs V1.pdf PDF
Attachment 04-Wage Rates 5.21 Pittsburgh.pdf PDF
Attachment 05-Limitations on Subcontracting - Construction.pdf PDF
Attachment 06-Site Visit Instructions.docx DOCX document
Attachment 03-Specs-EHRM Upgrades Heinz Campus - 06-27-25.pdf PDF
Attachment 02-646A4-22-700 - Appx 1 Final Bid Docs V2.pdf PDF
Show all 26

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

E

E

E

E

E

E

E

E

E

F

R

R

R R

R

R

E E EE E E

E

E

E

E

E

E

E

E

E

F

R

R

R R

R

R

E E EE E E

EMERGENCY

GENERATOR

BA116A

MECHANICAL

ROOM

BA116

ACTIVE STORAGE

BA117

INACTIVE

STORAGE

BA118

VISN INACT

STORAGE

BA119

COMPUTER ROOM

BA120

EQUIPMENT

SETUP & R&D LAB

BA120A

LOADING

BC4

UPS ROOM

BA118A

HELP DESK

BA101A

HELP DESK

BA101

VESTIBULE

BA100

LAN CLO

BA102

MALE TLT

BA103

HAC

BA104

FEMALE

LOUNGE

BA105

PROGRAMMING

BA106

OFFICE

BA107

MECH EQUIP

BA108

IT SUPPORT

BA110

MECHANICAL

EQUIPMENT

BA111

OFFICE

BA110C

OFFICE

BA110D

OFFICE

BA110E

OFFICE

BA110F

OFFICE

BA110B

NEW TR

BA110A

STORAGE

BA109

CORRIDOR

BC2

SOFTWARE

LIBRARY

BA115

TAPE VAULT

BA115A

TLT

BA114

TLT

BA112

ELEV

MACH RM

BA102A

CORRIDOR

BC1

CORRIDOR

BC3

FEMALE TLT

BA105A

OFFICE

BA107A

MECH

BA106C

PBX EXIST

BA110A.2

32-EN402

C1

EXISTING PBX BA110A TO

REMAIN

DP

PANEL NA

AIR DIST. PANEL

PANEL ECC PANEL NC

RD

B1

A1

NEAC

EM. GEN.

EMPD

NE1A

MDP

ATS-B

SWBD-B

ATS-A

SWBD-B

UPS-A

UPS-B

A

PDU-D/D

B

PDU-B/D

MBP PNL-A

MBP PNL-B

TAB-E

B32ANE2A

32TC

FSCP-E

PDU-D PDU-B STS-C PDU-C PDU-A PDU-E

CRAC-4/A1-14,16,18

CRAC-3/B1-14,16,18

CRAC-6/A1-26,28,30

CRAC-2/B1-2,4,6

CRAC-1/A1-2,4,6

CRAC-5/B1-26,28,30

SS-32-B/NE2T1-7,9

SS-32-1/EBT-7,9

SS-32-2/ECT-7,9

EPO-CRAC

EPO-UPS

GANN

ATS-ANN

UPS-ANN

FA-ANN

MTS-A

MTS-B

PDU-D/D-19,21,23

PDU-B/D-20,22,24

PDU-D/D-13,15,17

PDU-B/D-14,16,18

PDU-D/D-7,9,11

PDU-B/D-8,10,12

PDU-D/D-1,3,5

PDU-B/D-2,4,6

PDU-B/D-26,28,30

PDU-D/D-38,40,42

PDU-B/D-32,34,36

PDU-D/D-37,39,41

PDU-B/D-38,40,42

PDU-D/D-31,33,35

PDU-B/D-37,39,41

PDU-D/D-25,27,29

EPO-UPS

FDS-75 KVA SEC

TR-75

UPS BATT.MAINT.

UPS BATT.MAINT.

W/AT-8

FDS-SS-32-B

30A

FDS-SS-32-1

30A

FDS-SS-32-2

30A

EPO-UPS

32EA

(TYP.)

ACCU-1/A1-8,10,12 ACCU-2/B1-8,10,12 ACCU-3/B1-20,22,24 ACCU-6/A1-32,34,36 ACCU-5/B1-32,34,36 ACCU-4/A1-20,22,24

W/AT-8 W/AT-8

FIRE BARRIER, 3 HOUR

FIRE BARRIER, 2 HOUR

FIRE BARRIER, 1 HOUR

SMOKE BARRIER

NEW PARTITION

EXISTING PARTITION

DEMOLITION

PARTITION LEGEND

623 26TH AVENUE

ROCK ISLAND, IL 61201

P: 309.788.0673 F: 309.786.5967 www.imegcorp.com

PROJECT #23002990.00

CONSTRUCTION DOCUMENT SUBMISSION

5 5 10 15 20

1/8" = 1'-0"

FEETSCALE

P L A

N N

O R

T H

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

GENERAL NOTES:

SHEET NOTES:

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

A u to d e s k D o c s /H e in z V

A M

C E

H R

M

V

/6

A -2

-7

.3

.E

.I M

E G

H

N Z

C

.r v t

/2

/2

:0

:5

P

M

32-EN100

BASEMENT PLAN - ELECTRICAL

06.27.2025

EHRM INFRASTRUCTURE

UPGRADES - VAPHS H.J. HEINZ

CAMPUS 32

1010 DELAFIELD RD

PITTSBURGH, PA 15215

646A-22-700

EZ JF

A. REFER TO E000 FOR GENERAL NOTES.

B. ALL ELECTRICAL EQUIPMENT IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

C. ALL HVAC EQUIPMENT IS EXISTING TO REMAIN UNLESS OTHERWISE NOTED.

1. THE EXISTING EPO SYSTEM WILL REMAIN UNCHANGED. TESTING OF THE CURRENT SYSTEM AND ITS OPERATION WILL TAKE PLACE BEFORE CONSTRUCTION BEGINS AND AFTER. THE EPO CIRCUITS FOR THE UPS AND CRACS WILL BE DISCONNECTED AND RECONNECTED AFTER THE INSTALLATION OF THE

NEW EQUIPMENT. TYPICAL FOR ALL.

2. RECEPTACLES TO SERVE MDA SHALL BE MOUNTED IN A J-BOX IN THE SPACE BETWEEN THE RAISED

FLOOR AND CONCRETE FLOOR. REFER TO SHEET 32-EN300 FOR MORE INFORMATION.

Revisions: Date:

ADDENDA DATA CENTER COOLING, Q.56 07/24/2026

623 26TH AVENUE

ROCK ISLAND, IL 61201

P: 309.788.0673 F: 309.786.5967 www.imegcorp.com

PROJECT #23002990.00

CONSTRUCTION DOCUMENT SUBMISSION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

FINAL BID DOCUMENTS

FULLY SPRINKLERED

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD

A/E:

STAMP

321 4 5 6 7 8 9 10

Awen Solutions Group

215 N. Payne Street, Suite 122

Alexandria, VA 22314

A u to d e s k D o c s /H e in z V

A M

C E

H R

M

V

/6

A -2

-7

.3

.E

.I M

E G

H

N Z

C

.r v t

/2

/2

:0

:5

P

M

32-EN302

ELECTRICAL SCHEDULES

06.27.2025

EHRM INFRASTRUCTURE

UPGRADES - VAPHS H.J. HEINZ

CAMPUS 32

1010 DELAFIELD RD

PITTSBURGH, PA 15215

646A-22-700

EZ JF

CIRCUIT KEY NOTES: 1 - PROVIDE NEW BREAKER.

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 77.7 A

TOTAL CONNECTED AMPS: 77.72 A

TOTAL ESTIMATED DEMAND LOAD: 28 kVA

TOTAL CONNECTED LOAD: 28.00 kVA

Power 28 kVA 100.00% 28 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 77.78 77.78 77.78

Total Load: 9.33 kVA 9.33 kVA 9.33 kVA

-- 41 -- -- -- -- -- -- -- 1.17 1.17 -- -- -- -- -- -- -- 42 --

-- 39 -- -- -- -- -- -- -- 1.17 1.17 -- -- -- -- -- -- -- 40 --

1 37 MDA B-2 (BUS A) 20 A 3 12 12 12 0.37 1.17 1.17 0.42 12 12 12 3 20 A MDA B-1 (BUS A) 38 1

-- 35 EXISTING LOAD 20 A 1 -- -- -- 0 1.17 -- -- -- -- -- -- -- 36 --

-- 33 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 34 --

-- 31 EXISTING LOAD 30 A 2 -- -- -- 0 1.17 0.46 12 12 12 3 20 A FDSS-2 (BUS A) 32 1

-- 29 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 30 --

-- 27 EXISTING LOAD 30 A 2 -- -- -- 0 1.17 -- -- -- -- -- -- -- 28 --

-- 25 -- -- -- -- -- -- -- 0 1.17 0.49 12 12 12 3 20 A FDSS-1 (BUSA) 26 1

-- 23 EXISTING LOAD 30 A 2 -- -- -- 0 1.17 -- -- -- -- -- -- -- 24 --

-- 21 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 22 --

-- 19 EXISTING LOAD 30 A 2 -- -- -- 0 1.17 0.56 12 12 12 3 20 A SPARE (BUS A) 20 1

-- 17 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 18 --

-- 15 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 16 --

-- 13 EXISTING LOAD 60 A 3 -- -- -- 0 1.17 0.52 12 12 12 3 20 A SEC/JBA (BUS A) 14 1

-- 11 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 12 --

-- 9 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 10 --

-- 7 EXISTING LOAD 60 A 3 -- -- -- 0 1.17 0.48 12 12 12 3 20 A MDA A-1 (BUS A) 8 1

-- 5 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- -- 0 1.17 -- -- -- -- -- -- -- 4 --

-- 1 EXISTING LOAD 60 A 3 -- -- -- 0 1.17 0.44 12 12 12 3 20 A MDA A-2 (BUS A) 2 1

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: MATCH EXISTING SCCR.

ISC UNKNOWN 0.00 kA

SCCR: EXISTING

LOCATION: COMPUTER ROOM BA120 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE SINGLE TUB MAIN: 225 A MLO

EXIST. PNL: PDU-B/D

CIRCUIT KEY NOTES:

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 0 A

TOTAL CONNECTED AMPS: 0.00 A

TOTAL ESTIMATED DEMAND LOAD: 0 kVA

TOTAL CONNECTED LOAD: 0.00 kVA

Power 0 kVA 0.00% 0 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 0.00 0.00 0.00

Total Load: 0.00 kVA 0.00 kVA 0.00 kVA

-- 41 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 42 --

-- 39 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 40 --

37 FDSS-2 (BUS B) 20 A 3 12 12 12 0 0 12 12 12 3 20 A FDSS-1 (BUS B) 38

-- 35 -- -- -- -- -- -- -- 0 -- -- -- -- 1 -- SPACE 36 --

-- 33 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 34 --

31 MDA B-1 (BUS B) 20 A 3 12 12 12 0 0 -- -- -- 2 0 A SPARE 32 --

-- 29 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 30 --

-- 27 -- -- -- -- -- -- -- 0 0 -- -- -- 2 30 A SPARE 28 --

25 MDA B-1 (BUS B) 20 A 3 12 12 12 0 0 -- -- -- -- -- -- -- 26 --

-- 23 -- -- -- -- -- -- -- 0 0 -- -- -- 2 30 A SPARE 24 --

-- 21 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 22 --

19 SPARE (BUS B) 20 A 3 12 12 12 0 0 -- -- -- 2 30 A SPARE 20 --

-- 17 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 18 --

-- 15 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 16 --

13 SEC/JBA (BUS B) 20 A 3 12 12 12 0 0 -- -- -- 3 60 A SPARE 14 --

-- 11 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 12 --

-- 9 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 10 --

7 MDA A-1 (BUS B) 20 A 3 12 12 12 0 0 -- -- -- 3 60 A SPARE 8 --

-- 5 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- -- 0 0 -- -- -- -- -- -- -- 4 --

1 MDA A-2 (BUS B) 20 A 3 12 12 12 0 0 -- -- -- 3 60 A SPARE 2 --

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: MATCH EXISTING SCCR.

ISC UNKNOWN 0.00 kA

SCCR: EXISTING

LOCATION: COMPUTER ROOM BA120 WIRE: 4

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 SOLID NEUTRAL VOLTS: 120/208 Wye

MOUNTING: SURFACE SINGLE TUB MAIN: 225 A MLO

EXIST. PNL: PDU-D/D

Revisions: Date:

BID RFI 06/25/2026

ADDENDA DATA CENTER COOLING, Q.56 07/24/2026

CIRCUIT KEY NOTES: 1 - PROVIDE NEW BREAKER

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 185.8 A

TOTAL CONNECTED AMPS: 185.82 A

TOTAL ESTIMATED DEMAND LOAD: 154.488 kVA

TOTAL CONNECTED LOAD: 154.49 kVA

HVAC Cooling Only 154.488 kVA 100.00% 154.488 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 185.82 185.82 185.82

Total Load: 51.50 kVA 51.50 kVA 51.50 kVA

-- 41 -- -- -- -- -- -- -- 0 -- -- -- -- -- -- -- -- 42 --

-- 39 -- -- -- -- -- -- -- 0 -- -- -- -- -- -- -- -- 40 --

-- 37 EXISTING LOAD 15 A 3 -- -- -- 0 -- -- -- -- 3 -- SPACE 38 --

-- 35 -- -- -- -- -- -- -- 0 1.25 -- -- -- -- -- -- -- 36 --

-- 33 -- -- -- -- -- -- -- 0 1.25 -- -- -- -- -- -- -- 34 --

-- 31 EXISTING LOAD 25 A 3 -- -- -- 0 1.25 0.36 12 -- 12 3 15 A ACCU-6 32 1

-- 29 -- -- -- -- -- -- -- 0 9.56 -- -- -- -- -- -- -- 30 --

-- 27 -- -- -- -- -- -- -- 0 9.56 -- -- -- -- -- -- -- 28 --

-- 25 EXISTING LOAD 35 A 3 -- -- -- 0 9.56 0.89 10 -- 8 3 50 A CRAC-6 26 1

-- 23 -- -- -- -- -- -- -- 0 2.47 -- -- -- -- -- -- -- 24 --

-- 21 -- -- -- -- -- -- -- 0 2.47 -- -- -- -- -- -- -- 22 --

-- 19 EXISTING LOAD 15 A 3 -- -- -- 0 2.47 0.84 12 -- 12 3 20 A ACCU-4 20 1

-- 17 -- -- -- -- -- -- -- 0 17.87 -- -- -- -- -- -- -- 18 --

-- 15 -- -- -- -- -- -- -- 0 17.87 -- -- -- -- -- -- -- 16 --

-- 13 EXISTING LOAD 125 A 3 -- -- -- 0 17.87 1.03 8 -- 3 3 90 A CRAC-4 14 1

-- 11 -- -- -- -- -- -- -- -- 2.47 -- -- -- -- -- -- -- 12 --

-- 9 -- -- -- -- -- -- -- -- 2.47 -- -- -- -- -- -- -- 10 --

-- 7 SPACE -- 3 -- -- -- -- 2.47 0.53 12 -- 12 3 20 A ACCU-1 8 1

-- 5 -- -- -- -- -- -- -- -- 17.87 -- -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- -- -- 17.87 -- -- -- -- -- -- -- 4 --

-- 1 SPACE -- 3 -- -- -- -- 17.87 0.45 8 -- 3 3 90 A CRAC-1 2 1

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: MATCH EXISTING SCCR.

ISC UNKNOWN 0.00 kA

SCCR: EXISTING

LOCATION: ACTIVE STORAGE BA117 WIRE: 3

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 VOLTS: 480 Delta

MOUNTING: SURFACE SINGLE TUB MAIN: 400 A MCB

EXIST. PNL: A1

CIRCUIT KEY NOTES: 1 - PROVIDE NEW BREAKER.

*TOTAL DEMAND CALCS SUBTRACT ANY REDUNDANT LOAD AND THE SMALLER OF ANY NONCOINCIDENT HVAC LOADS. THIS CALC IS DONE AT EACH PANEL.

TOTAL ESTIMATED DEMAND AMPS: 185.8 A

TOTAL CONNECTED AMPS: 185.82 A

TOTAL ESTIMATED DEMAND LOAD: 154.488 kVA

TOTAL CONNECTED LOAD: 154.49 kVA

HVAC Cooling Only 154.488 kVA 100.00% 154.488 kVA

LOAD CLASSIFICATION CONNECTED LOAD DEMAND FACTOR ESTIMATED DEMAND

TOTALS*

LOAD SUMMARY

Total Amps: 185.82 185.82 185.82

Total Load: 51.50 kVA 51.50 kVA 51.50 kVA

-- 41 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 42 --

-- 39 -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- -- 40 --

-- 37 SPACE -- 3 -- -- -- -- -- -- -- -- 3 -- SPACE 38 --

-- 35 -- -- -- -- -- -- -- -- 2.47 -- -- -- -- -- -- -- 36 --

-- 33 -- -- -- -- -- -- -- -- 2.47 -- -- -- -- -- -- -- 34 --

-- 31 SPACE -- 3 -- -- -- -- 2.47 0.81 12 -- 12 3 20 A ACCU-5 32 1

-- 29 -- -- -- -- -- -- -- 0 17.87 -- -- -- -- -- -- -- 30 --

-- 27 -- -- -- -- -- -- -- 0 17.87 -- -- -- -- -- -- -- 28 --

-- 25 EXISTING LOAD 15 A 3 -- -- -- 0 17.87 0.73 8 -- 3 3 90 A CRAC-5 26 1

-- 23 -- -- -- -- -- -- -- 0 2.47 -- -- -- -- -- -- -- 24 --

-- 21 -- -- -- -- -- -- -- 0 2.47 -- -- -- -- -- -- -- 22 --

-- 19 EXISTING LOAD 0 A 3 -- -- -- 0 2.47 0.69 12 -- 12 3 20 A ACCU-3 20 1

-- 17 -- -- -- -- -- -- -- 0 17.87 -- -- -- -- -- -- -- 18 --

-- 15 -- -- -- -- -- -- -- 0 17.87 -- -- -- -- -- -- -- 16 --

-- 13 SPARE 125 A 3 -- -- -- 0 17.87 0.71 8 -- 3 3 90 A CRAC-3 14 1

-- 11 -- -- -- -- -- -- -- 0 1.25 -- -- -- -- -- -- -- 12 --

-- 9 -- -- -- -- -- -- -- 0 1.25 -- -- -- -- -- -- -- 10 --

-- 7 EXISTING LOAD 15 A 3 -- -- -- 0 1.25 0.32 12 -- 12 3 15 A ACCU-2 8 1

-- 5 -- -- -- -- -- -- -- 0 9.56 -- -- -- -- -- -- -- 6 --

-- 3 -- -- -- -- -- -- -- 0 9.56 -- -- -- -- -- -- -- 4 --

-- 1 EXISTING LOAD 25 A 3 -- -- -- 0 9.56 0.56 10 -- 8 3 50 A CRAC-2 2 1

K E Y

CKT

NO. LOAD DESCRIPTION

OCPD

AMPS P

WIRE

SIZE

H N G

VD

A B C VD

WIRE

SIZE

G N H

OCPD

P AMPS LOAD DESCRIPTION

CKT

NO.

K E Y

NOTES: MATCH EXISTING SCCR.

ISC UNKNOWN 0.00 kA

SCCR: EXISTING

LOCATION: ACTIVE STORAGE BA117 WIRE: 3

FED FROM: 0 A/0P @ GROUND BUS PHASE: 3

ENCLOSURE: NEMA 1 VOLTS: 480 Delta

MOUNTING: SURFACE SINGLE TUB MAIN: 400 A MCB

EXIST. PNL: B1

Sheets
32-EN100 - BASEMENT PLAN - ELECTRICAL
32-EN302 - ELECTRICAL SCHEDULES

File details come from the government source that posted it. Updated .