Amendment 0003 - Nurse_Call_System_Responses_to_Questions.pdf
PDF 152 KB Posted
- Solicitation number
- 36C26326Q0435
About this file
Summary of Nurse Call System Questions and Answers (36C26326Q0435-0003)
This document is a Questions and Answers (Q&A) file for a VA nurse call system procurement solicitation 36C26326Q0435. The solicitation is an Open Market procurement under FAR 12, not a GSA Schedule (FAR 8) procurement. All shaded areas in the provided floor plans represent clinical rooms and patient exam spaces requiring nurse call system connections; bidders should assume each shaded room will require nurse call buttons at minimum and code blue functionality at maximum due to anticipated room designation changes from ongoing construction projects. The Government will provide the VA TIL 27 52 23 nurse call code blue specification document and will extend the solicitation due date. Licensing costs, if required for system operation, must be included in the contractor's proposed price with no separate Government reimbursement. More detailed drawings and CAD files will not be provided; the shaded drawings are considered sufficient for bidding purposes.
Key technical and compliance requirements include: CAT-6A cabling is required; above-ceiling work is mandatory; conduit requirements will be based on VA standards and applicable fire codes, with existing pathways acceptable where compliant; ICRA (Infection Control Risk Assessment), HEPA carts, fire stopping, and core drilling are required as specified; and proposed systems must be compatible with the current Vocera system if brand-name-or-equal products are offered. Warranty periods, device specifications, and phasing/installation schedules will be detailed in the Statement of Work and specifications. Bidders must meet BAA (Buy American Act) compliance. Material quantity estimates provided are estimates only and should be used as such. The Government requires clarification on the definition of "Software Assurance" before determining its applicability, and self-service repair training is not required.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26326Q0435 0003.docx | DOCX document | |
| NURSE CALL SYSTEM QUESTIONS ANSWERED.docx | DOCX document | |
| 36C26326Q0435 0002.docx | DOCX document | |
| DRAWINGS - IC nurse call locations _ floor plans.pdf | ||
| P09 SOW V4 - Nurse Call System Replacement.docx | DOCX document | |
| S06 - AMENDMENT - Nurse Call System - IC - 36C26326Q0435 0001 - FINAL.pdf | ||
| Buy American Certificate - 52.225-2 - Tailored - ALL SUPPLIES 02.docx | DOCX document | |
| 36C26326Q0435.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
NURSE CALL SYSTEM QUESTIONS
36C26326Q0435 - 0003
1. Licensing requirement question.
If the system proposed requires licensing to operate, such licensing shall be included within the contractor’s proposed price. The Government will not provide separate reimbursement for licensing costs.
2. GSA Schedule procurement question.
Solicitation 36C26326Q0435 is Open Market (RFO FAR 12) and not FAR 8.
3. Clause CL-120 missing.
See pages 32 and 33 of the Solicitation
4. What rooms require nurse call?
The areas shaded in the drawings represent all clinical rooms and spaces requiring connection to the nurse call system.
5. What devices are required?
Refer to the Statement of Work (SOW) for required system functions, which will guide device requirements for each room.
6. Will more detailed drawings be provided?
No.
7. Is 5-year warranty required?
Refer to specifications for required warranty periods.
8. Software Assurance required?
The VA requires clarification on the definition of 'Software Assurance' before determining applicability.
9. Self-service repair training?
No.
10. Use Rauland material estimates?
The provided quantities are estimates and should be used as such.
11. CAT-6A required?
Yes.
12. Rooms per day conversion?
This will be based on contractor means and methods and mutually agreed-upon phasing (see
SOW).
13. CAD drawings provided?
No.
14. Drawings detail sufficient?
The shaded drawings are considered sufficient.
15. Provide legend?
The shaded drawings are considered sufficient.
16. Count of Rauland vs Ascom?
The shaded drawings are considered sufficient.
17. Brand name or equal?
Brand name or equal products will be accepted if compatibility with the current Vocera system is demonstrated.
18. Replace entire hospital?
Brand name or equal products will be accepted if compatibility with the current Vocera system is demonstrated.
19. Extend Solicitation due date?
Yes
20. BAA compliance?
Must meet BAA compliance.
21. TIL: Does the Government intend to provide the required VA TIL 27 52 23 nurse call code blue specification document?
Yes, we will provide that.
22. Conduit requirement?
Conduit requirements will be determined based on VA standards and applicable fire code(s).
Use of existing pathways may be acceptable where compliant.
23. Above ceiling work required?
Yes.
24. Other requirements:
ICRA – Yes
HEPA Carts – Yes
Core drilling – Contractor means and methods
Fire Stop – Yes
25. FLOOR PLANS - Are these the only floor plans you have? Are there life safety plans with all rooms labeled? I need to know what the rooms are on the drawing to quote nurse call.
There are a few areas like in purple below where rooms are labeled but most are not.
The areas shaded in the floor plans are clinic and patient exam rooms. Due to current construction projects going on some of these rooms will change designation in the future.
As such please bid based on each of them being a current patient room that will need nurse call buttons at minimum and code blue at maximum.