S06 Revised Atch A.2 SOW Atch 1 Drawings - 35 pages.pdf

PDF 9 MB Posted

Attached to
PN: 636A8-24-003, Correct Lightning Protection and Grounding Federal contract opportunity
Solicitation number
36C26326B0008
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 23

About this file

This is a set of construction documents for a Lightning Protection and Grounding System project at Iowa City VA Medical Center in Iowa City, Iowa. The project number is 636A8-24-003 with an issue date of August 15, 2025. The documents are prepared by enviros, an Architect/Engineer of Record located at 220 Ramsey Street, Hastings, Minnesota, and are submitted as a Construction Documents - Bid Set for the U.S. Department of Veterans Affairs Office of Construction and Facilities Management.

The scope of work includes the installation of a complete lightning protection and grounding system across multiple buildings at the medical center campus. The work encompasses demolition of existing lightning protection systems in Buildings 1, 8, 16, 50, and 7, followed by new installation of Class I and Class II lightning protection conductors, air terminals, and grounding electrodes in compliance with UL 96A standards. Key buildings receiving new systems include Buildings 1, 2, 7, 8, 16, 20, 40, 41, 42, 45, 49, and 50. The documents specify that all work must be performed by a UL-listed installer with final inspection and certification by a UL representative. The contractor must provide a UL Master Label Certificate upon completion. Installation details include air terminal placement, conductor routing and bonding requirements, grounding bus bar locations, and interior grounding connections. The documents contain comprehensive electrical details, grounding floor plans, riser diagrams, one-line diagrams for multiple buildings, and specifications for materials including copper and aluminum conductors, various connector types, and surge protective devices at main service entrances.

View the file

Other files for this federal contract opportunity

Other files attached to PN: 636A8-24-003, Correct Lightning Protection and Grounding, newest first.
File Type Posted
36C26326B0008 0007.docx DOCX document
S06 36C26326B0008 - Amendment 0006.pdf PDF
S06 Revised Atch A.1 SOW - 4 pages.pdf PDF
S06 Addendum Number 1 - 10 pages.pdf PDF
S06 Revised Atch A.2 SOW Atch 2 Specs - 141 pages.pdf PDF
S06 36C26326B0008 - Amendment 0005.pdf PDF
S06 36C26326B0008 - Amendment 0004.pdf PDF
S06 Atch D Revised Wage Determination IA20260068 1-2-26 - 6 pages.pdf PDF
S06 36C26326B0008 - Amendment 0003.pdf PDF
S06 Pre-Bid Site Visit Agenda - 2 pages.pdf PDF
S04 Pre-Bid Site Visit Sign-In - Second Site Visit - 1 page.pdf PDF
S06 36C26326B0008 - Amendment 0002.pdf PDF
S06 Pre-Bid Site Visit Sign-In - First Site Visit - 1 page.pdf PDF
S06 36C26326B0008 - Amendment 0001.pdf PDF
S02 Atch D Revised Wage Determination IA20250068 11-21-25 - 3 pages.pdf PDF
S02 Atch C Safety or Environmental Violations and EMR Information - 2 pages.pdf PDF
S02 Atch A.2 SOW Atch 1 Drawings - 43 pages.pdf PDF
S02 Atch A.1 SOW - 4 pages.pdf PDF
S02 Atch B VAAR 852.219-75 Limitations on Subcontracting Cert of Compliance - 2 pages.pdf PDF
S02 Atch A.2 SOW Atch 3 TMS 20939 - 4 pages.pdf PDF
S02 Atch A.2 SOW Atch 2 Specs - 141 pages.pdf PDF
S02 36C26326B0008.pdf PDF
S02 Atch D Wage Determination IA20250068 9-5-25 - 7 pages.pdf PDF
S02 Atch A.2 SOW Atch 4 NARA Contract Language - 2 pages.pdf PDF
Show all 24

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

G-001

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

Cover Sheet

BUILDING 16

BUILDING 1

BUILDING 50

BUILDING 2

BUILDING 1

BUILDING 36

NEWTON ROAD

W O

O L

F A

V E

N U

E

U.S. HIGHWAY 6

BUILDING 51

LO

T

M

NEW

TO

N RO

AD

BLDG 24

BUILDING 45

BUILDING 43

BUILDING 44

BUILDING 9

STRUCTURE 23

BLDG 7

STRUCTURE 33

BUILDING 20

BUILDING 40

BUILDING 41 BUILDING 42

BUILDING 11

BLD

G

PARKING RAMP

STRUCTURE 49

LOT I

LOT H

LOT G

LOT FBUILDING 32

STRUCTURE 37

LOT E

BUILDING 47

BUILDING 46

LOT B

LOT A

STRUCTURE 48

LOT CSTRUCTURE 17

STRUCTURE 18

LOT D

LOT J

LOT K

LOADING

DOCK

LOT N

LOT O

BUILDING 16

BUILDING 1

BUILDING 50

BUILDING 2

BUILDING 1

BUILDING 36

NEWTON ROAD

W O

O L

F A

V E

N U

E

U.S. HIGHWAY 6

BUILDING 51

LO

T

M

NEW

TO

N RO

AD

BLDG 24

BUILDING 45

BUILDING 43

BUILDING 44

BUILDING 9

STRUCTURE 23

BLDG 7

STRUCTURE 33

BUILDING 20

BUILDING 40

BUILDING 41 BUILDING 42

BUILDING 11

BLD

G

PARKING RAMP

STRUCTURE 49

LOT I

LOT H

LOT G

LOT FBUILDING 32

STRUCTURE 37

LOT E

BUILDING 47

BUILDING 46

LOT B

LOT A

STRUCTURE 48

LOT CSTRUCTURE 17

STRUCTURE 18

LOT D

LOT J

LOT K

LOADING

DOCK

LOT N

LOT O

IOWA CITY VA MEDICAL CENTER

AE CORRECT LIGHTNING PROTECTION AND GROUNDING SYSTEM

601 US-6 IOWA CITY, IA 52246

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-001

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

ELECTRICAL GENERAL NOTES AND

LEGENDS

CLASS I OR CLASS II AIR TERMINAL DEVICE. "X" DENOTES THE AIR TERMINAL

TYPE, SEE ELECTRICAL DETAILS FOR TYPE INFORMATION.

CLASS I OR CLASS II CONDUCTOR CONNECTOR. COORDINATE CONNECTOR

REQUIREMENTS WITH LOCATION/MATERIAL TYPES.

CLASS I OR CLASS II MAIN CONDUCTOR. INSTALL PER UL 96A.

CLASS I OR CLASS II DOWN CONDUCTOR. INSTALL PER UL 96A.

GROUNDING ELECTRODE. INSTALL PER UL 96A.

GROUND BAR. SIZE AND TYPE SHOULD BE FIELD COORDINATED.

NEW DEVICES/CONNECTIONS

EXISTING DEVICES/CONNECTIONS TO BE REMOVED

EXISTING DEVICES/CONNECTIONS TO BE REMAIN

SYMBOL LEGEND

PHASING LEGEND

A. ALL WORK SHALL BE PERFORMED BY A UL LISTED INSTALLER AND SHALL COMPLY WITH UL96A

AND VA LIGHTNING PROTECTION SPECS.

B. ALL WORK SHALL BE INSPECTED BY A UL REPRESENTATIVE. A UL LETTER FINDINGS FOR THE

AREA OF WORK SHALL BE PROVIDED TO THE OWNER AFTER INSPECTION.

C. CONDUCTOR BEND SHALL NOT FORM A SHARPER ANGLE THAN 90 DEGREES OR HAVE A RADIUS

LESS THAN 8".

D. ISOLATED METAL BODIES THAT SHOW NO CONDUCTANCE TO GROUND SHALL NOT REQUIRE

BONDING. A GROUNDED METAL BODY WITHIN THE SIX FOOT RULE HAS TO BE BONDED TO THE

SYSTEM.

E. CONNECTIONS TO GROUND AND/OR COUNTERPOISE MUST BE MADE AT A POINT NOT LESS THAN

1'-0" BELOW GRADE, AND 2'-0" AWAY FROM FOUNDATION WALL.

F. AIR TERMINAL SHALL BE PLACED AT THE LOCATIONS INDICATED, NOT MORE THAN 2'-0" FROM THE

EDGES OF RIDGES, OUTSIDE CORNERS, OR OUTSIDE EDGES OF MAIN ROOFS AND MUST EXTEND

A MINIMUM OF 10" ABOVE OBJECT TO BE PROTECTED.

G. MID ROOF AIR TERMINALS SHALL BE SPACED AT 50'-0" O.C. MAXIMUM SPACING.

H. JOB CONDITIONS MAY DICTATE VARIATIONS IN AIR TERMINAL, CONDUCTORS, AND GROUND ROD

LOCATIONS.

I. CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD PATH FREE FROM "U" AND "V"

POCKETS. ANY RISE IN HORIZONTAL CONDUCTOR SHALL NOT EXCEED 8".

J. CONDUCTOR SHALL RISE UPWARDS AT A RATE OF NO MORE THAN 3" OF RISE PER 1'-0" RUN.

K. COPPER LIGHTNING PROTECTION MATERIALS SHALL NOT BE PLACED ON ALUMINUM, GALVANIZED

STEEL, GALVALUME SURFACES OR ANY OTHER DISSIMILAR METAL SURFACES.

L. (PAINTED OR NOT) NOR SHALL ALUMINUM MATERIALS BE PLACED ON COPPER SURFACES.

M. WE HAVE NOT CALLED OUT EACH INDIVIDUAL ITEM OF LIGHTNING PROTECTION MATERIALS ON

THE ROOF PLAN. THESE MATERIAL TYPES SHALL BE FIELD COORDINATED AND MATCHED WITH

THE APPROPRIATE MATERIALS PER UL96A.

N. ELECTRIC, TELEPHONE AND ANTENNA SYSTEM GROUNDS SHALL BE CONNECTED WITH MAIN SIZE

CONDUCTOR TO ONE LIGHTNING PROTECTION GROUND OR METAL WATER PIPE. COORDINATE

SCOPE OF THIS EQUIPMENT WITH COR BEFORE BEGINNING WORK.

O. A LIGHTNING ARESTOR, PROTECTOR, OR ANTENNA-DISCHARGE UNIT MUST BE INSTALLED ON

EACH ELECTRIC AND TELEPHONE SERVICE ENTRANCE RADIO AND TELEVISION ANTENNA LEAD.

FIELD COORDINATE FINAL POLYPHASOR REQUIRED FOR EACH INSTALLATION AREA.

P. ALL ADHESIVE FIXTURES SHALL BE SET WITH AN ADHESIVE COMPOUND COMPATIBLE WITH THE ROOFING MATERIAL. ADHESIVES SHALL BE APPROVED IN ADVANCED BY THE ROOFING SUPPLIER

THAT HOLDS THE WARRENTY FOR THE ROOF WHERE THE SYSTEM IS BEING INSTALLED.

Q. BOND ALL METAL PIPES SUCH AS WATER, GAS, FIRE, STORM, SEWER, ECT., WHICH ENTER THE

STRUCTURE TO NEAREST DOWN-LEAD, GROUND ROD OR COUNTERPOISE.

R. CONDUCTOR WILL BE FASTENED EVERY 3'-0" ON CENTER MAXIMUM.

S. PERIMETER AND RIDGE AIR TERMINALS 10" TO 23" SHALL BE SPACED UP TO 20' MAXIMUM.

T. AIR TERMINALS 24" AND OVER WILL BE SPACED 25' MAXIMUM.

U. LIGHTNING PROTECTION SYSTEMS SHALL BE INSTALLED IN A NEAT, AND PROFESSIONAL MANNER, V. WHEN ANCHORING IN MASONRY, HOLES MADE TO RECEIVE THE BODY OF THE ANCHOR SHALL BE

MADE IN BRICK, STONE, OR OTHER MASONRY UNIT. (RATHER THAN IN MORTAR JOINTS)

W. THE EXISTING FACILITY IS PROVIDED WITH A LIGHTNING PROTECTION SYSTEM. TYPICALLY, THE

SYSTEM CONSIST GROUNDED METAL OBJECTS BONDED TO THE LIGHTNING PROTECTION

SYSTEM, INCLUDING, BUT NOT LIMITED TO STRUCTURAL STEEL SUPPORTS, RAILINGS, LADDERS, ROOF HATCHES, FLAGPOLES, HVAC FLASHING, GRAVEL STOPS, LOUVERS, DOOR FRAMES, ANTENNAS, HAND RAILS PER UL 96A, ETC.

X. UTILIZE CLASS I MATERIALS ON 5TH FLOOR ROOF AND BELOW (A50 AND C50 CABLE) AND UTILIZE

CLASS II MATERIALS ON THE 6TH FLOOR AND ABOVE (A55 AND C55 CABLE).

GENERAL LIGHTNING PROTECTION NOTES

G-001 COVER SHEET

E-001 ELECTRICAL GENERAL NOTES AND LEGENDS

E-002 ZONE OF PROTECTION PLAN

E-003 CAMPUS ROOF ELEVATION PLAN

ED-101 LIGHTNING PROTECTION PLAN - DEMOLITION

ED-102 LIGHTNING PROTECTION PLAN - DEMOLITION

ED-103 LIGHTNING PROTECTION PLAN - DEMOLITION

ED-104 LIGHTNING PROTECTION PLAN - DEMOLITION

E-100 LIGHTNING PROTECTION PLAN - SITE

E-101 LIGHTNING PROTECTION PLAN - NEW

E-102 LIGHTNING PROTECTION PLAN - NEW

E-103 LIGHTNING PROTECTION PLAN - NEW

E-104 LIGHTNING PROTECTION PLAN - NEW

E-105 LIGHTNING PROTECTION PLAN - NEW

E-106 LIGHTNING PROTECTION PLAN - NEW

E-107 LIGHTNING PROTECTION PLAN - NEW

E-108 LIGHTNING PROTECTION PLAN - NEW

E-109 LIGHTNING PROTECTION PLAN - NEW

E-110 LIGHTNING PROTECTION PLAN - NEW

E-201 INTERIOR GROUNDING PLAN

E-202 INTERIOR GROUNDING PLAN

E-203 INTERIOR GROUNDING PLAN

E-204 INTERIOR GROUNDING PLAN

E-205 INTERIOR GROUNDING PLAN

E-206 INTERIOR GROUNDING PLAN

E-207 INTERIOR GROUNDING PLAN

E-208 INTERIOR GROUNDING PLAN

E-209 INTERIOR GROUNDING PLAN

E-210 INTERIOR GROUNDING PLAN

E-211 INTERIOR GROUNDING PLAN

E-212 INTERIOR GROUNDING PLAN

E-213 GROUNDING FLOOR PLAN - BASEMENT & SECOND

E-214 GROUNDING FLOOR PLAN

E-501 ELECTRICAL DETAILS

E-502 ELECTRICAL DETAILS

E-601 GROUNDING RISER DIAGRAM

E-701 ONE-LINE DIAGRAM

E-702 ONE-LINE DIAGRAM

E-703 ONE-LINE DIAGRAM

E-704 ONE-LINE DIAGRAM

E-705 ONE-LINE DIAGRAM

E-706 ONE-LINE DIAGRAM

E-707 ONE-LINE DIAGRAM

SHEET LIST

A. CONTRACTOR TO MEET THE INSTALLATION REQUIREMENTS OF UL 96A AND COORDINATE FINAL

INSPECTION TO PROVIDE A UL MASTER LABEL CERTIFICATE.

B. IT IS THE CONTRACTORS RESPONSIBILITY TO PROVIDE ALL INSPECTIONS NEEDED TO RECEIVE A

UL MASTER LABEL CERTIFICATION FOR THE SITE.

PROJECT NOTES

FIRE BARRIER LEGEND

3-HOUR FIRE BARRIER

2-HOUR FIRE BARRIER

1-HOUR FIRE BARRIER

30-MINUTE FIRE BARRIER

GENERAL NOTES:

1. ALL FIRE RATED BARRIERS PENETRATIONS SHALL BE SEALED USING THE APPROPRIATE

MATERIAL PER SPECIFICATION SECTION 07 84 00 FIRESTOPPING.

2. FIRE RATED BARRIERS WERE NOT PREVIOUSLY SHOWN IN BID SET. THE FOLLOWING SHEETS

WERE UPDATED PER ADDENDUM 1 TO INCLUDE THE LOCATION OF ALL EXISTING FIRE RATED

BARRIERS.

E-201 INTERIOR GROUNDING PLAN

1 LIGHTNING PROTECTION PLAN - ZONE OF PROTECTION

SCALE: 1/32" = 1'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-002

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

ZONE OF PROTECTION PLAN

BUILDING 16

BUILDING 1

BUILDING 50

BUILDING 2

BUILDING 1

BUILDING 36

NEWTON ROAD

W O

O

LF

A V

E N

U E

U.S. HIGHWAY 6

BUILDING 51

LO

T

M

BLDG 24

BUILDING 45

BUILDING 43

BUILDING 44

BUILDING 9

STRUCTURE 23

BLDG 7

STRUCTURE 33

BUILDING 20

BUILDING 40

BUILDING 41

BUILDING 42

BUILDING 11

BLD

G

PARKING RAMPSTRUCTURE 49

LOT I

LOT H

LOT G

LOT F

BUILDING 32

STRUCTURE 37

LOT E

BUILDING 47

BUILDING 46

LOT B

LOT A

STRUCTURE 48LOT C

STRUCTURE 17

STRUCTURE 18

LOT D

LOT J

LOT K

LOADINGDOCK

LOT N

LOT O

HATCH DENOTES CALCULATED ZONE OF

PROTECTION AREA.

1 CAMPUS ROOF ELEVATION PLANS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-003

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

CAMPUS ROOF ELEVATION PLANS

BUILDING 16

BUILDING 1

BUILDING 50

BUILDING 2

BUILDING 1

BUILDING 36

W O

O

LF

A V

E N

U E

U.S. HIGHWAY 6

BUILDING 51

LO

T

M

N E

W

TO

N R

O A

D

BLDG 24

BUILDING 45

BUILDING 43

BUILDING 44

BUILDING 9

STRUCTURE 23

BLDG 7

STRUCTURE 33

BUILDING 20

BUILDING 40

BUILDING 41

BUILDING 42

BUILDING 11

BLD

G

PARKING RAMPSTRUCTURE 49

LOT I

LOT H

LOT G

LOT F

BUILDING 32

STRUCTURE 37

LOT E

BUILDING 47

BUILDING 46

LOT B

LOT A

STRUCTURE 48LOT C

STRUCTURE 17

STRUCTURE 18

LOT D

LOT J

LOT K

LOADINGDOCK

LOT N

LOT O

874FT

865 FT

847 FT847 FT 833 FT

843 FT

830 FT AFG

819 FT AFG

726FT

726FT

725FT

842 FT

828 FT

726FT

726FT

764FT

773FT

787FT

764FT

766FT

776FT

750FT

771FT

819FT

855FT

843FT

833FT

819FT

832FT

833FT

762FT

726FT

739FT

763FT

750FT

761FT

776FT

714FT

726FT

714FT

712FT

716 FT

698 FT

711 FT

723 FT

698 FT

698 FT

735 FT

736 FT

711 FT

710 FT

686 FT

723 FT

739FT

740FT

697FT

745FT

1 BUILDING 01 - LIGHTNING PROTECTION PLAN - DEMOLITION

SCALE: 1/16" = 1'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

ED-101

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

DEMOLITION

ALL EXISTING LIGHTNING PROTECTION CONDUCTORS, CONNECTORS, AIR TERMINALS AND OTHER DEVICES SHALL BE REMOVED IN IT'S ENTIRETY. ALL GROUNDING SYSTEM EQUIPMENT SHALL BE RESTORED TO PROPER FUNCTION IF REMOVAL OF LIGHTNING PROTECTION DEVICES AFFECTS THE

EXISTING SYSTEM.

EXISTING ROOF, WALL, OR EQUIPMENT SURFACE DAMAGED BY THE REMOVAL OF THE EXISTING

LIGHTNING PROTECTION SYSTEM SHALL BE REPAIRED/RESTORED TO THE CONDITION (OR BETTER

THAN) PRIOR TO DEMOLITION.

A.

B.

GENERAL SHEET DEMO NOTES

DOWN CONDUCTOR IS ROUTED THROUGH ROOF 1F PARAPET DOWN TO ROOF 1T. DOWN CONDUCTOR

IS TAPPED AND EXTENDED OVER TO SERVE ROOF 1R.

DOWN CONDUCTOR IS ROUTED THROUGH ROOF 1G PARAPET DOWN TO THE GROUND.

DOWN CONDUCTOR IS ROUTED THROUGH ROOF 1F PARAPET DOWN TO THE GROUND.

DOWN CONDUCTOR IS ROUTED THROUGH ROOF 1A PARAPET DOWN TO THE ROOF 1F PERIMETER

CONDUCTOR.

DOWN CONDUCTOR IS ROUTED THROUGH ROOF 1A PARAPET DOWN TO ROOF 1E. DOWN CONDUCTOR

IS TAPPED AND EXTENDED OVER TO SERVE ROOF 1F.

DOWN CONDUCTOR IS ROUTED THROUGH ROOF 1F PARAPET DOWN TO ROOF 1I PERIMETER

CONDUCTOR.

DOWN CONDUCTOR IS ROUTED OVER THE SIDE OF ROOF 1Z DOWN TO BUILDING 2 ROOF PERIMETER

CONDUCTOR.

DOWN CONDUCTOR IS ROUTED OVER THE SIDE OF ROOF 1Z DOWN TO GROUND. DOWN CONDUCTOR

IS NOT PROPERLY CONNECTED TO THE ROOF.

EXISTING LIGHTNING PROTECTION SYSTEM IN THE AREA IS WITHIN ZONE OF PROTECTION. LIGHTNING

PROTECTION SYSTEM SHALL BE REMOVED.

1.

2.

3.

4.

5.

6.

7.

8.

9.

KEYED ELECTRICAL SHEET NOTES

LIGHTNING PROTECTION

FOR TELECOM EQUIPMENT

BY OTHERS

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING LIGHTNING PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTIONNO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

NO EXISTING

LIGHTNING

PROTECTION

4 5

1 BUILDING 08, 16 - LIGHTNING PROTECTION PLAN - DEMOLITION

SCALE: 3/16" = 1'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

ED-102

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

DEMOLITION

ALL EXISTING LIGHTNING PROTECTION CONDUCTORS, CONNECTORS, AIR TERMINALS AND OTHER DEVICES SHALL BE REMOVED IN IT'S ENTIRETY. ALL GROUNDING SYSTEM EQUIPMENT SHALL BE RESTORED TO PROPER FUNCTION IF REMOVAL OF LIGHTNING PROTECTION DEVICES AFFECTS THE

EXISTING SYSTEM.

EXISTING ROOF, WALL, OR EQUIPMENT SURFACE DAMAGED BY THE REMOVAL OF THE EXISTING

LIGHTNING PROTECTION SYSTEM SHALL BE REPAIRED/RESTORED TO THE CONDITION (OR BETTER

THAN) PRIOR TO DEMOLITION.

A.

B.

GENERAL SHEET DEMO NOTES

BUILDING 16

BLD

G

GROUNDING WIRE WITH NO CONNECTION

GROUNDING WIRE WITH NO CONNECTION

NO EXISTING LIGHTNING PROTECTION

EXISTING LIGHTING PROTECTION ON BUILDING IN POOR

SHAPE AND SHALL BE REMOVED IN IT'S ENTIRETY.

1 BUILDING 50 - LIGHTNING PROTECTION PLAN- DEMOLITION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

ED-103

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

DEMOLITION

ALL EXISTING LIGHTNING PROTECTION CONDUCTORS, CONNECTORS, AIR TERMINALS AND OTHER DEVICES SHALL BE REMOVED IN IT'S ENTIRETY. ALL GROUNDING SYSTEM EQUIPMENT SHALL BE RESTORED TO PROPER FUNCTION IF REMOVAL OF LIGHTNING PROTECTION DEVICES AFFECTS THE

EXISTING SYSTEM.

EXISTING ROOF, WALL, OR EQUIPMENT SURFACE DAMAGED BY THE REMOVAL OF THE EXISTING

LIGHTNING PROTECTION SYSTEM SHALL BE REPAIRED/RESTORED TO THE CONDITION (OR BETTER

THAN) PRIOR TO DEMOLITION.

A.

B.

GENERAL SHEET DEMO NOTES

BUILDING 50

EXISTING LIGHTING PROTECTION ON BUILDING NOT

COMPLETE AND END OF LIFE. EXISTING WILL BE

REMOVED IN IT'S ENTIRETY.

1 BUILDING 7 - LIGHTNING PROTECTION PLAN - DEMOLITION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

ED-104

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

DEMOLITION

ALL EXISTING LIGHTNING PROTECTION CONDUCTORS, CONNECTORS, AIR TERMINALS AND OTHER DEVICES SHALL BE REMOVED IN IT'S ENTIRETY. ALL GROUNDING SYSTEM EQUIPMENT SHALL BE RESTORED TO PROPER FUNCTION IF REMOVAL OF LIGHTNING PROTECTION DEVICES AFFECTS THE

EXISTING SYSTEM.

EXISTING ROOF, WALL, OR EQUIPMENT SURFACE DAMAGED BY THE REMOVAL OF THE EXISTING

LIGHTNING PROTECTION SYSTEM SHALL BE REPAIRED/RESTORED TO THE CONDITION (OR BETTER

THAN) PRIOR TO DEMOLITION.

A.

B.

GENERAL SHEET DEMO NOTES

BLDG 7

EXISTING LIGHTING PROTECTION ON BUILDING NOT

COMPLETE AND END OF LIFE. EXISTING WILL BE

REMOVED IN IT'S ENTIRETY.

1 LIGHTNING PROTECTION PLAN - SITE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-100

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

SITE

BUILDING 16

BUILDING 1

BUILDING 50

BUILDING 2

BUILDING 1

BUILDING 36

NEWTON ROAD

W O

O L

F A

V E

N U

E

U.S. HIGHWAY 6

BUILDING 51

LO

T

M

NEW

TO

N RO

AD

BLDG 24

BUILDING 45

BUILDING 43

BUILDING 44

BUILDING 9

STRUCTURE 23

BLDG 7

STRUCTURE 33

BUILDING 20

BUILDING 41 BUILDING 42

BUILDING 11

BLD

G

PARKING RAMP

STRUCTURE 49

LOT I

LOT H

LOT G

LOT FBUILDING 32

STRUCTURE 37

LOT E

BUILDING 47

BUILDING 46

LOT B

LOT A

STRUCTURE 48

LOT CSTRUCTURE 17

STRUCTURE 18

LOT D

LOT J

LOT K

LOADING

DOCK

LOT N

LOT O

BUILDING 40

HATCH DENOTES BUILDING WITH NO EXISTING

LIGHTNING PROTECTION SYSTEM

BUILDING 51 OUT OF SCOPE

1 BUILDING 1 - LIGHTNING PROTECTION PLAN - NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-101

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

PROVIDE DOWN CONDUCTOR FROM UPPER ROOM SYSTEM TO LOWER ROOF SYSTEM FOR ROOF

SYSTEM CONNECTION.

EXISTING PERIMETER RAILING ON ROOF MAY BE USED AS MAIN CONDUCTOR AND STRIKE

TERMINATION DEVICE. THIS WILL REQUIRE FIELD VERIFICATION OF RAILING THICKNESS TO BE USED

AS A MAIN CONDUCTOR OR TO BE USED AS A MAIN CONDUCTOR AND TERMINATION DEVICE.

UTILIZE EXISTING METAL FRAMING AS MAIN CONDUCTOR. FIELD COORDINATE COATING AND

THICKNESS FOR CONNECTION REQUIREMENTS NEEDED.

PROVIDE CONNECTION OF EXISTING LADDER/STAIR TO NEW LIGHTNING PROTECTION SYSTEM.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

4.

5.

6.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

AREA OUT OF SCOPE

NO EXISTING

LIGHTNING

PROTECTIONNO EXISTING

LIGHTNING

PROTECTION

EXISTING PERIMETER RAILING ON ROOF '1F' SHALL

BE USED AS MAIN CONDUCTOR. FIELD COORDINATE

RAILING THICKNESS IS GREATER THAN .064".

1 BUILDING 2 - LIGHTNING PROTECTION PLAN -NEW

SCALE: 3/32" = 1'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-102

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

PROVIDE DOWN CONDUCTOR FROM UPPER ROOM SYSTEM TO LOWER ROOF SYSTEM FOR ROOF

SYSTEM CONNECTION.

EXISTING PERIMETER RAILING ON ROOF MAY BE USED AS MAIN CONDUCTOR AND STRIKE

TERMINATION DEVICE. THIS WILL REQUIRE FIELD VERIFICATION OF RAILING THICKNESS TO BE USED

AS A MAIN CONDUCTOR OR TO BE USED AS A MAIN CONDUCTOR AND TERMINATION DEVICE.

PROVIDE CONNECTION OF EXISTING LADDER/STAIR TO NEW LIGHTNING PROTECTION SYSTEM.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

4.

5.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

EXISTING PERIMETER RAILING IS GREATER THAN

24" FROM ROOF EDGE. BOND TO MAIN

CONDUCTOR AT LOCATIONS INDICATED

BUILDING 2

1 BUILDING 07 - LIGHTNING PROTECTION PLAN -NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-103

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

PROVIDE DOWN CONDUCTOR FROM UPPER ROOM SYSTEM TO LOWER ROOF SYSTEM FOR ROOF

SYSTEM CONNECTION.

EXISTING PERIMETER RAILING ON ROOF MAY BE USED AS MAIN CONDUCTOR AND STRIKE

TERMINATION DEVICE. THIS WILL REQUIRE FIELD VERIFICATION OF RAILING THICKNESS TO BE USED

AS A MAIN CONDUCTOR OR TO BE USED AS A MAIN CONDUCTOR AND TERMINATION DEVICE.

PROVIDE CONNECTION OF EXISTING LADDER/STAIR TO NEW LIGHTNING PROTECTION SYSTEM.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

4.

5.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

BLDG 7

1 BUILDING 08, 16, 45 - LIGHTNING PROTECTION PLAN -NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-104

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

BUILDING 16

BLDG 8

BUILDING 45

1 BUILDING 20 - LIGHTNING PROTECTION PLAN - NEW

SCALE: 1/4" = 1'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-105

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

BUILDING 20

1 BUILDING 40 - LIGHTNING PROTECTION PLAN - NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-106

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

EXISTING PERIMETER RAILING ON ROOF MAY BE USED AS MAIN CONDUCTOR AND STRIKE

TERMINATION DEVICE. THIS WILL REQUIRE FIELD VERIFICATION OF RAILING THICKNESS TO BE USED

AS A MAIN CONDUCTOR OR TO BE USED AS A MAIN CONDUCTOR AND TERMINATION DEVICE.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

BUILDING 40

BUILDING 47

1 BUILDING 41 - LIGHTNING PROTECTION PLAN - NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-107

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

EXISTING PERIMETER RAILING ON ROOF MAY BE USED AS MAIN CONDUCTOR AND STRIKE

TERMINATION DEVICE. THIS WILL REQUIRE FIELD VERIFICATION OF RAILING THICKNESS TO BE USED

AS A MAIN CONDUCTOR OR TO BE USED AS A MAIN CONDUCTOR AND TERMINATION DEVICE.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

A.

B.

1.

2.

3.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

BUILDING 41

1 BUILDING 42 - LIGHTNING PROTECTION PLAN - NEW

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-108

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

LIGHTNING PROTECTION PLAN -

NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

EXISTING PERIMETER RAILING ON ROOF MAY BE USED AS MAIN CONDUCTOR AND STRIKE

TERMINATION DEVICE. THIS WILL REQUIRE FIELD VERIFICATION OF RAILING THICKNESS TO BE USED

AS A MAIN CONDUCTOR OR TO BE USED AS A MAIN CONDUCTOR AND TERMINATION DEVICE.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

BUILDING 42

1 BUILDING 49 - LIGHTNING PROTECTION PLAN - NEW

GENERAL SHEET NOTES

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

KEYED ELECTRICAL SHEET NOTES

PROVIDE DOWN CONDUCTOR FROM UPPER ROOM SYSTEM TO LOWER ROOF SYSTEM FOR ROOF

SYSTEM CONNECTION.

EXISTING PERIMETER RAILING/FENCING ON ROOF SHALL BE TIED INTO THE NEW MAIN CONDUCTOR.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

4.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-109

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

NEW

PARKING RAMP

STRUCTURE 49

COORDINATE NEW AIR TERMINALS WITH

EXISTING LIGHT POLES MOUNTED IN

THE MIDDLE OF PARKING STRUCTURE.

1 BUILDING 50 - LIGHTNING PROTECTION PLAN - NEW

NEW LIGHTNING PROTECTION CONDUCTOR AND DEVICE LOCATIONS SHALL BE FIELD COORDINATED

WITH EXISTING CONDITIONS AND INSTALLED PER UL 96A.

FIELD COORDINATE ALL ROOF EQUIPMENT AND DEVICE AND PROVIDE LIGHTING PROTECTION

CONNECTIONS AS REQUIRED PER UL 96A.

A.

B.

PROVIDE DOWN CONDUCTOR FROM UPPER ROOM SYSTEM TO LOWER ROOF SYSTEM FOR ROOF

SYSTEM CONNECTION.

PROVIDE NEW DOWN CONDUCTORS TO NEW GROUND RODS. EQUIPMENT SHOWN ARE FOR

REFERENCE AND FINAL LOCATIONS COORDINATED WITH SITE CONDITIONS AND INSTALLED PER UL 96A.

PROVIDE LIGHTNING PROTECTION CONNECTION TO MAIN GROUNDING BUS BAR. SEE GROUNDING

PLANS FOR ADDITIONAL INFORMATION AND REQUIREMENTS.

1.

2.

3.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-110

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

LIGHTNING PROTECTION PLAN -

NEW

GENERAL SHEET NOTES

KEYED ELECTRICAL SHEET NOTES

GROUP OF VENT STACKS.

BUILDING 50

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-201

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

GROUNDING FLOOR PLAN -

BASEMENT AND SUB BASEMENT 01

SCALE: 1/16" = 1'-0"1 BUILDING 01 - GROUNDING FLOOR PLAN - BASEMENT

SCALE: 1/16" = 1'-0"2 BUILDING 01 - GROUNDING FLOOR PLAN - SUB BASEMENT

LOCATION OF ROOM CONTAINING GROUNDING WITHIN SCOPE.

EXISTING GROUNDING CONNECTIONS IN WIREWAY. RE-ROUTE GROUNDS TO NEW MAIN GROUND

BARS. PROVIDE #3/0 BARE COPPER FROM NEW BUSBAR TO EXISTING WIREWAY

PROVIDE NEW MAIN SERVICE GROUND BUSBAR. NEW GROUND BAR TO INCLUDE ALL UL 96A AND NFPA 70 (NEC) REQUIRED GROUND CONNECTIONS. SEE DETAIL 1/E601 FOR ADDITIONAL INFORMATION.

EXISTING AC EQUIPMENT GROUND BAR.

LOCATION OF EXISTING #3/0 GROUND CONDUCTOR ROUTED THROUGH THE BUILDING. FIELD

COORDINATE THE EXACT LOCATION OF GROUND CONDUCTOR IN BUILDING SHAFT.

PROVIDE NEW GROUNDING BUS BAR PER SPECIFICATIONS AND BOND TO EXISTING ELECTRICAL

SYSTEM BAR SAME LOCATION. PROVIDE A 3/0 BARE BONDING JUMPER TO BONDING CONDUCTORS

SOUTHWEST CORNER OF ROOM. SEE PLAN NOTE 2 THIS SHEET

PROVIDE NEW GROUNDING BUS BAR PER SPECIFICATIONS AND BOND TO EXISTING ELECTRICAL

SYSTEM BAR WITH 3/0 BONDING JUMPER

PROPOSED PATHWAY FOR GROUNDING. LINES ARE INDICATIVE OF PATHWAY TO ROOMS ONLY AND

SHALL TERMINATE AT EACH ROOM'S GROUND BAR AS SHOWN ON SHEET E-601. CONTRACTOR TO

VERIFY FIELD CONDITIONS AND FEASIBILITY OF PATHWAY WITH COR BEFORE INSTALLATION.

1.

2.

3.

4.

5.

6.

7.

8.

KEYED ELECTRICAL SHEET NOTES

ENG MECH

ENG MECH

UP

BS04D

BW12A

BSTO9

BW25

SHAFT

B C

BE24A

BST03

BST10

BE19A

BST12

BST02

BC08A BW108C

BW05A

BW05C

BW05B

SH

AF

T

SH

AF

T

LADDER HATCH

TO 1ST FLOOR

BW108B109 110

1C02 1C01

1STO1

101B

E

BW202

BCP03

BW201

A D

BCN01

BC

N0

BN03

BN01

BN02

BN03A

BN04

BCE01

BE01

BE01A

MEZZANINE

BE02

BE02BBE02A

BE04 BE03

BE05

BE06

BE07BE09

BE08

BE14

BCE02

BE12ABE12

BE11

BE12D

BE12C

BE12B

BE16

BE18

BE17

BE23

BCS01

BC

E0

BE24

BCS04

BC

S0

BE20

BE13

BE15

BCS03B

BC

S0

BCS03

BCS03A

BE22

BE21

BCS05

BE19

BS04B BS04C

BS04E

BS04

BS04G

BS04F

BS04A

BS04D

BS01

BS03

BS02

BCS01A

BS06

BS

ABS11

BC01

BS10BS10B

BS10A

BS07

BS05B

BS05

BS05A

BST05

BS13BS12

BS

BS

A

BS05C

BW08A

BW03

BW05

DW-1

BC

BC08

BC

BCW01A

BW02A

BW02

BC02

BCW01

BC05BC06

BST07

BCW04BCW03

BC03

BCW01

BC

W

BW

BW08

BW02B

BW02

BCW01

BW08C BW08DBW08B

BW04

BW08E

BW11A

BW22

BW23

BW12

BW10

BW21

BW16

BW13

BW19

BW

BW15

BW11

BW

09 BW17

BW26BW24

BW15A

BC

W0

3A

BW100

BW102B

BW102A

BW102C

BW101B

BW102F

BW101

BW101

BST08

BW101A

BW110BBW110A

BW110D

BW

BW112

BW115BW114 BW116

BW104

BW107

BW108

BW110C

BW108A

BW

BW102E

BW110

BW111

BW116A

BW118

BW117

BW119

BW120

BW119A

BW119B

BW120B

BW

0A

BW119C

BW120C

BST06

BC

P0

BC

P0

BS

T0

BW

D

BE01B

GRATING

DN BW02C

BST13BCW05

SUMP

PANEL B23L

PANEL B07A

PANEL B27H

PANEL B24

PANEL B25

PANEL B26

PANEL B20H

PANEL B22

PANEL B05-1H

XFMR TB05

PANEL B15

PANEL B10

PANEL B28H

XFMR TB12

B-MCC

PANEL B12

PANEL B-EFP

PANEL B-03

PANEL B01H

PANEL LB01H

PANEL B06-4

PANEL B06-3

SECT. 2

PANEL B06-2

PANEL 1E

PANEL B06-3

SECT. 1PANEL

B06-1H

600A BUS

PANEL B06-5

PANEL AB31

TRANSFORMER

T-AB31

PANEL CB31L

PANEL CB31R

PANEL CB31H

PANEL NB33R

PANEL NB33L

PANEL NB33H

PANEL CB-1

PANEL B01PANEL B21

PANEL TBD

BUILDING

NO.8

BLDG

NO.36

PANEL CB32

(VERIFY LOCATION)

BST04

A2

A3A1

A4

A5

B3

B2

B1

C2

C1

BW20

BCW05A

BLDG 2

BW01

SB01A

SB12B

SB05C

SB06A

SBST01

A5

SB12A

SB12

SB13

SB11

SB10

SB08

SB04

SB09 SB01

SB02A

SB02

SB03

SB05

SB06C

SB05A

SB05B

SB06

SB06B

SBST11

TYP.

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-210

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

GROUNDING FLOOR PLAN -

FIRST 02

SCALE: 1/8" = 1'-0"1 BUILDING 02 - GROUNDING FLOOR PLAN - FIRST

LOCATION OF EXISTING BUILDING ELECTRICAL SYSTEM GROUND BAR. PROVIDE CONNECTION TO NEW

LIGHTNING PROTECTION SYSTEM PER SPECIFICATIONS AND UL96A REQUIREMENTS.

1.

KEYED ELECTRICAL SHEET NOTES1

DN

DN

DN

UP

UP

BS10BS10BBS10A BS06BCS03

114F

109 110

BCS05

BS15

BS14 BS16

BS17

1C021C01

113A114A114B114C114D

114E

114G

1C03

BC08

BCS04

BC

A1STO1

OFFICE

HSKPG

BREAKROOM

ELEC

CLST

ELEV.

EQUIP.

ROOM

IT

CLOSET

SAFETY

EQUIPMENT

STORAGE

CORRIDOR

UNIV

WASTE

HOLDING

MEN'S

TOILET

WOMEN'S

TOILET

IV

STORAGE

LOBBYVESTIBULE

OFFICEOFFICEOFFICEOFFICEOFFICE

OFFICE

TRAINING

ROOM

ELEC.

CO

RR

ID

OR

LIQUID

NITROGEN

STORAGE

101B

103B

103C

103A

103E

103D

103G

103F

BLDG 1

P1

OFFICES

113B

OFFICE

113C

OFFICE

113D

OFFICE

130B

HUMAN

RESOURCES

1ST02

WAREHOUSE

PANEL 101DP2

PANEL C101H

MECHANICAL

EQUIPMENT

ROOM

ELECTRICAL

EQUIPMENT

ROOM

130A

RECEIVING

1C04

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-211

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

GROUNDING FLOOR PLAN

07 & 16

SCALE: 3/16" = 1'-0"1 BUILDING 07 - GROUNDING FLOOR PLAN

SCALE: 3/16" = 1'-0"

BUILDING 16 - GROUNDING FLOOR PLAN

1. LOCATION OF EXISTING BUILDING ELECTRICAL SYSTEM GROUND BAR. PROVIDE CONNECTIONS

TO NEW LIGHTNING PROTECTION SYSTEM PER SPECIFICATIONS AND UL96A REQUIREMENTS

2. PROVIDE NEW ELECTRICAL SYSTEM GROUNDING BUS BAR IN ELECTRICAL ROOM B25.

3. PROVIDE 3/0 BARE CONDUCTOR FROM NEW GROUNDING BUS BAR TO GROUND IN MAIN

PANELBOARD LOCATED IN MEZZANINE DIRECTLY ABOVE BUS BAR LOCATIONS.

4. NEW LIGHTNING SYSTEM INTERCONNECTION.

KEYED ELECTRICAL SHEET NOTES1

SCALE: NOT TO SCALE3 BUILDING 16 - GROUNDING ONE LINE

AUX MAIN

DISTRB

PANEL N12

MCC-7N11

01-7

04-7 06-7

05-7

07-7

03-7 02-7

FLOOR PLAN

TRANSFORMER T-C

CONTROLLER 95-1R

PANEL 7-1-2

08-16

03-16 04-16 06-16

05-16

01ST-16

01-16

01ST-16

PULL BOX

PULL BOX

PANEL

HVAC MINI SPLIT

JUNCTION BOX

BUILDING

EXISTING

MDPH

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-212

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

GROUNDING FLOOR PLAN

20 & 40

SCALE: 3/16" = 1'-0"1 BUILDING 40 - GROUNDING FLOOR PLAN

SCALE: 3/16" = 1'-0"3 BUILDING 20 - GROUNDING FLOOR PLAN

1. PROVIDE NEW ELECTRICAL SYSTEM GROUNDING BUS BAR IN ELECTRICAL ROOM 1M04

2. PROVIDE 3/0 BARE CONDUCTOR FROM NEW GROUNDING BUS BAR TO GROUND IN MAIN

PANELBOARD SAME ROOM.

3. NEW LIGHTNING SYSTEM INTERCONNECTION

4. PROVIDE NEW ELECTRICAL SYSTEM GROUNDING BUS BAR IN ELECTRICAL ROOM NEAR PANEL

EDPH

KEYED ELECTRICAL SHEET NOTES1

SCALE: NOT TO SCALE4 BUILDING 20 - GROUNDING ONE LINE

SCALE: NOT TO SCALE2 BUILDING 40 - GROUNDING ONE LINE

1 1

1M03 1A02

1M02 1M04B

1M01

1M04 1A05

1A04

1A01

1A03A

1A03

1B05

1B08

1B08A

1B04

1B06

1B07

1B04A

1A01A

M1-21

PANEL PNL-B

MEN

1B02

WOMEN

1B03

ELECT.

CLOSET

1B01 H.A.C.

1B01A

RESTROOM

1M04A

PANEL PNL-A

BUILDING

EXISTING

PANEL-A

PANEL DPL

PANEL EDPH

PANEL B03

BUILDING

EXISTING

EDPH

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-213

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

GROUNDING FLOOR PLAN -

BASEMENT & SECOND 41

SCALE: 1/8" = 1'-0"1 BUILDING 41 - GROUNDING FLOOR PLAN - BASEMENT

PROVIDE NEW ELECTRICAL SYSTEM GROUNDING BUS BAR IN ELECTRICAL ROOM B25.

PROVIDE 3/0 BARE CONDUCTOR FROM NEW GROUNDING BUS BAR IN ELECTRICAL ROOM B25 TO 3/0 GROUNDING CONDUCTOR IN SAME ROOM FROM MAIN PANELBOARD. PROVIDE 3/0-3/0 TAPING CRIMP

SPLICE PER SPECIFICATIONS.

NEW LIGHTNING SYSTEM INTERCONNECTION.

EXISTING TELECOMMUNICATIONS GROUNDING BAR TO REMAIN.

1.

2.

3.

4.

KEYED ELECTRICAL SHEET NOTES1

SCALE: NOT TO SCALE2 BUILDING 41 - GROUNDING ONE LINE

STAIR

FREEZER

ROOM

MAGNETIC

IMAGING TELECOM

CUSTODIAL

ROOM ELEV.

MACHINE RM.

FILM

LOAD

AUTOCLAVE

MECHANICAL

TUNNEL

VESTIBULE

PANEL MDPH

TRANSFORMER T-1TRANSFORMER T-2

TRANSFORMER T-3

HALLWAY

ELECTRICAL

EXISTING TELECOM

GROUND BAR

LOCATION OF NEW

GROUND BAR

MDPH

ROOM B27 - TELECOM ROOM B27 - TELECOM

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-214

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

GROUNDING FLOOR PLAN

42 & 50

SCALE: 1/8" = 1'-0"1 BUILDING 42 - GROUNDING FLOOR PLAN

SCALE: 1/8" = 1'-0"2 BUILDING 50 - GROUNDING FLOOR PLAN

SCALE: NOT TO SCALE3 BUILDING 42 - GROUNDING ONE LINE

SCALE: NOT TO SCALE4 BUILDING 50 - GROUNDING ONE LINE

1. PROVIDE NEW ELECTRICAL SYSTEM GROUNDING BUS BAR IN ELECTRICAL ROOM B41.

2. PROVIDE 3/0 BARE CONDUCTOR FROM NEW GROUNDING BUS BAR IN ELECTRICAL ROOM B41 TO

MAIN PANELBOARD MDPH SAME ROOM.

3. NEW LIGHTNING SYSTEM INTERCONNECTION.

KEYED ELECTRICAL SHEET NOTES1

B102

ELECTRICAL

ROOM

MECHANICAL

(ELEV PIT)

MECHANICAL

ROOM

MECHANICAL

TUNNEL

MECHANICAL

ROOM

0ST01

STAIR

PANEL MDPH

EXISTING GROUND

BAR LOCATION

BC08

STAIRS

BST01

STORAGE

B62

CLEAN CAGING

B63

BEDDING

B49

CAGE WASHING

B48

CAGE WASH

B47

WASTE

B44B45

B46

CORRIDOR

BC04

MULTI-PURPOSE

B43

CORRIDOR

BC03

VESTIBULE

B39

B41A

BC01

ELEVATOR

B40 B41B

STAFF

B42

TOILET

B42B

B42A

HOUSEKEEPING

B51

PROCEDURE

B53

CORRIDOR

BC06

B52

B50

CORRIDOR

BC05

CORRIDOR

BC09

B56 CORRIDOR

BC07

B55

B59B58

B60

PROCEDURE

B61

VESTIBULE

MECHANICAL

B41B54

HOLDING ROOM (MICE)

B59

HOLDING ROOM

(RAT)

HOLDING ROOM

(RAT)

ISOLATION

HOLDING ROOM

RECEIVING

QUARANTINE

SHOWER/

CHANGE

ELEVATOR

LOBBY

HOLDING ROOM

(MICE)

HOLDING ROOM

(MICE)

HOLDING ROOM

(HAMPSTER)

HOLDING ROOM

(RAT)

ELEVATOR

MECHANICAL

HOLDING ROOM

(GUINEA PIG)

ELECTRICAL

TRANSFORMER T-1

MULTI-

PURPOSE

NEW GROUND BAR

LOCATION (BELOW

FIRE ALARM PANEL)

BUILDING

EXISTING

PANEL-A

EXISTING

EXISTING

BUILDING

EXISTING

PANEL-A

4 AIR TERMINAL BASE DETAIL - TYPE C

SCALE: NTS

5 DOWNLEAD AND GROUND TERMINAL

SCALE: NTS 6

DOWN CONDUCTOR PENETRATION OF THE

PARAPET WALL DETAIL

2 AIR TERMINAL BASE DETAIL - TYPE B1

SCALE: NTS 3 AIR TERMINAL BASE DETAIL - TYPE B2

SCALE: NTS1 AIR TERMINAL BASE DETAIL - TYPE A

SCALE: NTS

7 PARAPET AIR TERMINAL DETAIL

SCALE: NTS 8 CONDUIT AIR TERMINAL DETAIL

SCALE: NTS

9 HAND RAIL AIR TERMINAL DETAIL

SCALE: NTS 10 VENT AIR TERMINAL DETAIL

SCALE: NTS 11 LIGHT POLE AIR TERMINAL DETAIL

SCALE: NTS

SCALE: NTS

12 CPC - APC - UPC - STYLE PIPE CLAMPS

SCALE: NTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-501

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

ELECTRICAL DETAILS

CUAT / ALAT - STYLE GENTLY

TAPERED AIR TERMINAL

160 - STYLE RIDGE SADDLE

AIR TERMINAL BASE

CCC / ACC - SERIES

CABLE FASTENER

COPPER OR ALUMINUM, CLASS I OR

CLASS II LIGHTNING PROTECTION

CONDUCTOR

LIGHTNING CABLE

USE NON-FERROUS

CLAMPS ONLY

CADWELD TYPE GR

GROUND ROD

FINISH. GRADE

TO LIGHTNING PROTECTION

SYSTEM ROOF CONDUCTOR

(LEAD 22)

(18" MAXIMUM)

DOWNLEAD AND GROUND TERMINAL

ROUTE LIGHTNING DOWNLEAD CONDUCTOR

IN SCHEDULE 40 PVC CONDUIT TO A HEIGHT

OF 10 FEET ABOVE GRADE.

12" MIN.

SEALER (TYP)

HORIZONTAL RUN OF

LIGHTNING CONDUCTOR

ALONG ROOF.SEALER

SLEEVE

ROUTE DOWNLEAD CONDUCTOR

EXPOSED ALONG STRUCTURE

SURFACE FROM ROOF TO

BELOW GRADE

#2/0 COPPER LIGHTNING DOWNLEAD

CONDUCTOR FROM ROOF

DOWN CONDUCTOR PENETRATION

OF THE PARAPET WALL DETAIL

CUAT / ALAT - STYLE GENTLY

TAPERED AIR TERMINAL

262 - SERIES ADHESIVE

CABLE FASTENER

COPPER OR ALUMINUM,

CLASS I OR CLASS II

LIGHTNING PROTECTION

CONDUCTOR

UBU - STYLE UNIVERSAL

FLAT SURFACE AIR

TERMINAL BASE

MOUNTED HORIZONTALLY

CUAT / ALAT - STYLE GENTLY

TAPERED AIR TERMINAL

262 - SERIES ADHESIVE

CABLE FASTENER

COPPER OR ALUMINUM,

CLASS I OR CLASS II

LIGHTNING PROTECTION

CONDUCTOR

UBS - STYLE UNIVERSAL

SWIVAL AIR TERMINAL BASE

CUAT / ALAT - STYLE GENTLY

TAPERED AIR TERMINAL

UBU - STYLE UNIVERSAL

FLAT SURFACE AIR

TERMINAL BASE

MOUNTED VERTICALLY

CCC / ACC - SERIES

CABLE FASTENER

COPPER OR ALUMINUM,

CLASS I OR CLASS II

LIGHTNING PROTECTION

CONDUCTOR

COPPER OR ALUMINUM 1

BOLT PARALLEL

CONNECTOR

262 SERIES ADHESIVE

CABLE FASTENER

COPPER OR ALUMINUM, CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

UBU STYLE UNIVERSAL FLAT

SURFACE AIR TERMINAL BASE

MOUNTED HORIZONTALLY

CUAT / ALAT STYLE GENTLY

TAPERED AIR TERMINAL

CUFATM STYLE COPPER AIR

TERMINAL WITH FIBERGLASS

MAST ASSEMBLY

SSATMSC STYLE AIR

TERMINAL MAST MOUNTING

ASSEMBLY

COPPER LIGHTNING

CONDUCTOR TAIL (INCLUDED

WITH MAST ASSEMBLY)

CPC / APCBM STYLE U-BOLT

PIPE CLAMP

RGS CONDUIT

BY OTHERS

CUAT / ALAT STYLE

GENTLY TAPERED

AIR TERMINAL

CCC / ACC STYLE CABLE

FASTENER

157 STYLE VERTICAL AIR

TERMINAL BASE

B1BC / A1BC PARALLEL

CABLE CONNECTOR

COPPER OR ALUMINUM CLASS I

OR CLASS II LIGHTNING

PROTECTION CONDUCTOR

262 / A262 ADHESIVE CABLE

HOLDER

COPPER OR ALUMINUM, CLASS I OR

CLASS II LIGHTNING PROTECTION

CONDUCTOR

CURS / ALRS STYLE 1/2 RIDGE SADDLE

AIR TERMINAL BASE

CUAT / ALAT STYLE GENTLY TAPERED

AIR TERMINAL

CUAT / ALAT STYLE GENTLY

TAPERED AIR TERMINAL

PRB STYLE PIPE AIR

TERMINAL BASE

COPPER OR ALUMINUM

CLASS I OR CLASS II

LIGHTNING PROTECTION

CONDUCTOR

CPC - APC 1/1.25 - STYLE PIPE

CLAMP

CPC - APC - STYLE PIPE

CLAMP

UPC - STYLE PIPE CLAMP

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-502

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/20261

ELECTRICAL DETAILS

1 EXHAUST FAN HOOD PROTECTION DETAIL

SCALE: NTS 2 ROOFTOP A/C UNIT PROTECTION DETAIL

SCALE: NTS

3 ROOFTOP A/C UNIT PROTECTION DETAIL

SCALE: NTS 4 TYPICAL - ACCEPTABLE CABLE BENDS

SCALE: NTS

5 TYPICAL - ROOF EQUIPMENT BONDS

SCALE: NTS 6 TYPICAL - SECONDARY BONDS

SCALE: NTS

7 TYPICAL - ADHESIVE AIR TERMINAL

SCALE: NTS 8 TYPICAL -GRADUAL RISE CABLE RUN

SCALE: NTS

3/8"∅, 18" LONG ALUMINUM AIR

TERMINAL

COPPER MAIN

CONDUCTOR

CONDUCTOR

ALUMINUM BONDING

CONDUCTOR

FAN/EXHAUST HOOD

BIMETAL

CONNECTOR

MINIMUM BEND

RADIUS SHALL BE 8"

FAN/EXHAUST

HOOD

BOLT TYPE

BONDING PLATE

EXOTHERMIC

CABLE SPLICE

USE BI-METALLIC

CONNECTORS (TYPICAL).

COPPER ON ROOF

ROOF

ALUMINUM

OVER UNITS

AIR TERMINALS ON

TOP OF ROOF TOP

UNIT, PER UL 96A.

EXTEND NEW LIGHTNING

PROTECTION CONDUCTORS

TO EXISTING LIGHTNING

PROTECTION SYSTEM ROOF

CONDUCTORS AND BOND.

PER UL 96A, WHERE ONLY ONE STRIKE TERMINATION

DEVICE IS REQUIRED ON A CHIMNEY OR VENT, AT LEAST

ONE MAIN SIZED CONDUCTOR SHALL CONNECT THE

STRIKE TERMINATION DEVICE TO A MAIN CONDUCTOR AT

THE LOCATION WHERE THE VENTS MEETS THE ROOF

SURFACE AND PROVIDE TWO OR MORE PATHS TO

GROUND FROM THAT LOCATION IN ACCORDANCE WITH

SECTION 3-9 AND 3-9.2.

CAST ALUMINUM PARALLEL COMBINATION CABLE

SPLICER.

GREATER THAN 1 220 (4'-0") NOT TO EXCEED 6 100 (20'-0").

410 (1'-4"), MAX

410 (1'-4"), MAX

410 (1'-4"), MAX

410 (1'-4"), MAX

1.

2.

3.

KEYED DETAIL NOTES:

SEE GENERAL LIGHTNING PROTECTION NOTE "P"

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved

VA FORM 08 - 6231

E-601

A

Fi le

P at h

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

IOWA CITY, IA

636A8-24-003

Revisions: Date: 08/15/2025 BA DG220 Ramsey Street, Hastings, MN 55033 | 651.319.0170 enviros.co

IOWA CITY VAMC CORRECT

LIGHTNING PROTECTION AND

GROUNDING

CONSTRUCTION

DOCUMENTS - BID SET

ADDENDUM 1 01/30/2026

GROUNDING…