Attachment H _ 846770 Report _ Hyko Solutions _ Fargo VA _ Signed.pdf
PDF 5 MB Posted
- Attached to
- Y1DZ--437-25-103, 3 Year Electrical Testing & Maintenance Federal contract opportunity
- Solicitation number
- 36C26325B0012
About this file
This document is a comprehensive electrical testing and maintenance report for the Fargo VA Medical Center, prepared by CE Power on August 9, 2022, under VA Contract 36C26322P0343. The report details extensive electrical system testing across multiple buildings and components, including automatic transfer switches, circuit breakers, motor control centers, switchboards, transformers, and disconnect switches.
The testing revealed several key deficiencies and recommendations, including: a failed vacuum contactor in Building 11's automatic transfer switch requiring replacement, circuit breakers in multiple locations with high contact resistance that need monitoring, and specific breakers in Building 9 that require complete replacement due to tripping failures. The report provides detailed technical measurements for each tested component, including resistance readings, insulation tests, and performance evaluations across various electrical systems. While most systems passed initial testing, the document highlights multiple areas requiring maintenance, repair, or potential equipment replacement to ensure continued reliable electrical infrastructure at the Fargo VA Medical Center.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C26325B0012 0003.docx | DOCX document | |
| 36C26325B0012 0002.docx | DOCX document | |
| Attachment A - Statement of Work - Revised 6-26-2025.pdf | ||
| 36C26325B0012 0001.docx | DOCX document | |
| Attachment J - 437-25-103 Electrical Testing Questions and Answers Responses.pdf | ||
| Attachment I - Site Visit Sign In Sheets 6-12-2025.pdf | ||
| Attachment D - Bid Drawings - 33 pages.pdf | ||
| Attachment B - Appendix A - Example Schedule - 3 pages.pdf | ||
| 36C26325B0012_1.docx | DOCX document | |
| Attachment F - Questions Request Form - 1 page.pdf | ||
| Attachment C - Specifications - 438 pages.pdf | ||
| Attachment A - SOW 12 pages.pdf | ||
| Attachment G - VAAR 852.219-75 Limitations on Subcontracting-Cert of Compliance_JAN 2023 [DEVIATION] - 2 pages.pdf | ||
| Attachment E - Wage Rate determination - 8 pages.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CE Power ‐ Minnesota
August 9, 2022
Hyko Solutions
Attn: Jon Wilkinson – 808-679-1892 – jon@hykosolutions.com
Re: Hyko Solutions Fargo VA CE Power Job Number: 846770 cc: J. Foster R. Wiegand J. Nielsen M. Dziadosz K. Primozich
Attachments:
Project Summary Test Report Details
360-463-0060 Senior Service Technician, NETA III Delbert Parrish
Sincerely, you for the opportunity to perform this service.
If you have any questions, or if we can be of further assistance, please feel free to call our office. Thank
Please refer to the individual test result sheets for additional details.
Numerous breaker issues were discovered and some thermal deficiencies.
Please see the attached testing results from the firast phase of testing at the Fargo VA Medical Center.
In conjunction with the execution of the project, we have provided the attached report documentation.
36C26322P0343 that was performed at Fargo Veterans Affairs Medical Center.
Attached is the report on conducting electrical testing and maintenance in accordance with VA Contract
Jon;
CE Power – NETA Member
Conduct electrical testing and maintenance in accordance with VA Contract 36C26322P0343 at
Fargo Veterans Affairs Medical Center
846770
For
Hyko Solutions
Attention: Jon Wilkinson
August 9, 2022 Submitted By: Delbert Parrish
Senior Service Technician, NETA III
CE Power – NETA Member
CE Power ‐ Minnesota
WORK SCOPE
Conduct electrical testing and maintenance in accordance with VA Contract 36C26322P0343.
*NOTE: In certain instances, due to site conditions, outage constraints, weather and other unexpected circumstances, the exact quoted scope of work may not have been fully accomplished, or additional equipment may have been added. In those instances, the detailed report documentation will be noted accordingly.
Table of Contents Job #846770
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
1 of 179PAGE
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
2054100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 1 ATS Critical Branch
2154100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 1 ATS Equipment Branch
2254100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 1 ATS Life Safety
2354100 - AUTOMATIC TRANSFER SWITCH TEST - Fail (Needs Attention) Fargo VA Medical Center ATS/MTS Building 11 ATS
2454100 - AUTOMATIC TRANSFER SWITCH TEST
Fargo VA Medical Center ATS/MTS Building 40 ATS MCC-1
2554100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 46 ATS 3B-EBE
2654100 - AUTOMATIC TRANSFER SWITCH TEST
Fargo VA Medical Center ATS/MTS Building 46 ATS FIRE PUMP
2754100 - AUTOMATIC TRANSFER SWITCH TEST (2)
Fargo VA Medical Center ATS/MTS Building 46 ATS SURGERY CHILLER
2854100 - AUTOMATIC TRANSFER SWITCH TEST (2)
Fargo VA Medical Center ATS/MTS Building 9 ATS LIFE SAFETY
2954100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 ATS-CR
3054100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 ATS-EB1
3154100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 ATS-EB2
3254100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 MTS-1
3354100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 MTS-2
3454100 - AUTOMATIC TRANSFER SWITCH TEST (2)
Fargo VA Medical Center ATS/MTS Building 9 MTS-3
3654100 - AUTOMATIC TRANSFER SWITCH TEST
Fargo VA Medical Center ATS/MTS Building 9 MTS-EB 90N1
3754100 - AUTOMATIC TRANSFER SWITCH TEST
Fargo VA Medical Center ATS/MTS Building 9 MTS-EB 90N3
3815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY CB
3915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY EB
4015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY GEN MAIN
4115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY LIFE SAFETY
4215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL CB
4315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL EB
4415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL FEEDER 1
4515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL FEEDER 2
4615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL LIFE SAFETY
2 of 179PAGE
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
4715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 1 NORMAL SWBD-1 SHOPS MAIN
4815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL TIE
4915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY EE CBE
5015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY EE EBE EBE2
5115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY EE FIRE PUMP
5215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY GENERATOR BREAKER
5315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY LSE
5415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY SPARE
5515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY SURGURY CHILLER
5615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL FLOOR SPARE 2400
5715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL FLOOR SPARE 800
5815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 10E6P
5915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 460C2
6015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 460C3
6115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 460N1
6215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 461C1/461C2
6315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 462C1/462N1
6415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 462C2
6515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 462C3
6615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 463C1/464C2
6715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 463C2/464C1
6815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 464C3/464C4
6915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 465C2
7015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 46OS2
7115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD CBE
7215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD EBE2
3 of 179PAGE
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
7315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD FIRE PUMP
7415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD LIFE SAFETY
7515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD MCC-46
7615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD MDS NO. 1
7715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD MDS NO. 2
7815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 1
7915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 2
8015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 3
8115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 4
8215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SURGCHILLER
8315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD TIE
8415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (5) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-1
8515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-2
8615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-3
8715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 56 CHLR-4
8815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-5
8915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 56 FUTURE
9015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 56 MAIN A
9115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 56 MAIN B
9215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 56 TIE
9315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 EB EMERGENCY ELEV 1, 2, 3
9415800 - MOLDED CASE CIRCUIT BREAKER INSP
Fargo VA Medical Center Circuit Breaker Building 9 EB MCC3B RM BA-01
9515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 9 EB2 EB90W1
9615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 9 EB2 EB90W2
9715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY CB ATS
9815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY EB1 ATS
4 of 179PAGE
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
9915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY EB2 ATS
10015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY GENERATOR
10115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL CRITICAL BRANCH
10215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL EB1 ATS
10315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL EB2 ATS
10415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 NORMAL EB90W1
10515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL PNL 95C2
10615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL SWBD FEEDER 1 MAIN
10715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 NORMAL SWBD FEEDER 2 MAIN
10815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL SWBD TIE
10915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 X-Ray Panel Main
11015510 - LOW VOLTAGE AIR SWITCH
Fargo VA Medical Center LV Disconnect ACCH-4 Disconnect
11130000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 1 MCCEB-1 (Sec. A-B)
11230000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 1 MCCEB-1 (Sec. C-D)
11330000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 40 MCC 1 (RM 112B)
11430000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 40 MCC 2 (RM 212)
11530000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 46 MCC-3B (Sec. A-B)
11630000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 46 MCC-3B (Sec. C)
11730000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 46 MCC-3B (Sec. D )
11830000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 46 MCCB-46 SWBD (RM BA-01)
11930000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 46 MCC-EB462C1 (RM 2D-12)
12030000 - MOTOR CONTROL CENTER INSPECTION
Fargo VA Medical Center MCC BLDG 46 MCC-ES464C1 (RM 4C-27)
12115601 - FUSE DISCONNECT INSP. TEST
Fargo VA Medical Center S&C Switches Elm Stret 26KV Switches
12229100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-1 Feeder 7 SW-1
12329100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-1 Feeder 7 SW-2
12429100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-2 Feeder 6 SW-1
5 of 179PAGE
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
12529100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-2 Feeder 6 SW-2
12629100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-56-1 SW-1
12729100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-56-1 SW-2
12829100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-56-2 (Boiler Plant XFMR 10-1)
12929100 - DISCONNECT SELECTOR SWITCH
Fargo VA Medical Center S&C Switches SAC-56-2 (XFMR T56-3)
13050400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY CB
13150100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY CB
13250400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY EB
13350100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY EB
13450400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY LS
13550100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY LS
13650100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 1
13750400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 1
13850100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 2
13950400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 2
14050400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 NORMAL SWBD 2
14150100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 NORMAL SWBD 2
14250400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 1 SWBD-1 Shops
14350100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 1 SWBD-1 Shops
14450100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Main (RM 111)
14550400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Main (RM 111)
14650400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Sec #1 (RM 111)
14750400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Sec #2 (RM 111)
14850400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 56 MAIN
14950100 - LV SWITCHBOARD INSULATION
Fargo VA Medical Center Switchboard BLDG 56 MAIN
15050100 - LV SWITCHBOARD INSULATION (2)
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY CB
6 of 179PAGE
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
15150400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY CB
15250100 - LV SWITCHBOARD INSULATION (2)
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB1
15350400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB1
15450100 - LV SWITCHBOARD INSULATION (2)
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB2
15550400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB2
15650100 - LV SWITCHBOARD INSULATION (2)
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY GENERATOR
15750400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY GENERATOR
15850400 - SWITCHBOARD BUS CONNECTION TEST (2)
Fargo VA Medical Center Switchboard BLDG 9 NORMAL FDR 2
15950400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 9 NORMAL POWER FDR 1
16050400 - SWITCHBOARD BUS CONNECTION TEST
Fargo VA Medical Center Switchboard BLDG 9 X-RAY PANEL
16156700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-1 Shops
16256700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-10 (Boiler Plant)
16365500 - LIGHTNING ARRESTER TEST
Fargo VA Medical Center Transformer Transformer T-10 (Boiler Plant)
16456700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-11 (BLDG 11-12-13)
16565500 - LIGHTNING ARRESTER TEST
Fargo VA Medical Center Transformer Transformer T-13
16656700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-13
16756700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-1-EAST
16856700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-1-WEST
16956700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-40
17065500 - LIGHTNING ARRESTER TEST
Fargo VA Medical Center Transformer Transformer T-40
17156700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T56-1 (Chiller Plant)
17256700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T56-2 (Chiller Plant)
17365500 - LIGHTNING ARRESTER TEST
Fargo VA Medical Center Transformer Transformer T56-2 (Chiller Plant)
17456700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T56-3 (Chiller Plant)
17565500 - LIGHTNING ARRESTER TEST
Fargo VA Medical Center Transformer Transformer T56-3 (Chiller Plant)
17656700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T9 (X-Ray)
7 of 179PAGE
REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com
Family of companies
PAGE
NO.Asset
Circuit_IDSubstationPlant
Hyko SolutionsCustomer
Fargo Veterans Affairs Medical CenterOwner
17756700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T9-East (BLDG 9, Feeder 2)
17856700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T9-West (BLDG 9, Feeder 1)
17956700 - TRANSFORMER MAINTENANCE TEST
Fargo VA Medical Center Transformer Transformer T-NW
OIL ANALYSIS 4/27/2022 (SEE THESE PAGES FOR DEFICIENCIES) 183 THRU 185 OF 241
OIL ANALYSIS AND PCB 5/10 & 5/11/2022 (SEE THESE PAGES FOR DEFICIENCIES) 186 THRU 193 OF 241 OIL ANALYSIS 6/6 & 6/7/2022 (SEE THESE PAGES FOR DEFICIENCIES) 194 THRU 202 OF 241
INFRARED (SEE THESE PAGES FOR DEFICIENCIES) 203 THRU 241 OF 241
8 of 179PAGE
Customer Hyko Solutions
Owner Fargo Veterans Affairs Medical Center
Comment and Deficiency Summary Job #846770
6/6/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: ATS/MTS
Circuit_ID: Building 11 ATS
Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST - Fail (Needs Attention)
DEFICIENCIES: The "emergency" side vacuum contactor Failed the contact resistance test.
Recommend replacing all three vacuum bottles for this contactor.
4/27/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: ATS/MTS
Circuit_ID: Building 46 ATS FIRE PUMP
Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST
COMMENTS: This is a three pole ATS. The Zero for Neutral contact resistance signifies not present.
6/7/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: ATS/MTS
Circuit_ID: Building 9 MTS-3
Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST (2)
COMMENTS: Emergency power side fuse resistance as follows:
A:299 B:317 C:307 MicroOhms Normal Power side fuse resistance as follows:
A:322 B:308 C:313 MicroOhms Fuses installed are BUSS class T fuses IR 200KA HRCI-T 200A
6/7/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: ATS/MTS
Circuit_ID: Building 9 MTS-EB 90N1
Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST
COMMENTS: Due to restrictions of facility we were unable to test this
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 EMERGENCY CB
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
Comment and Deficiency Summary
9 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 EMERGENCY EB
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 EMERGENCY GEN MAIN
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
COMMENTS: Due to limitation of test equipment tested Instantaneous trip at lower settings.
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 NORMAL CB
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 NORMAL EB
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 NORMAL FEEDER 1
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
10 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 NORMAL FEEDER 2
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 NORMAL SWBD-1 SHOPS MAIN
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/26/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 1 NORMAL TIE
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 46 EMERGENCY EE EBE EBE2
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 46 EMERGENCY LSE
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/11/2022Date:
Page:
11 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
5/11/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 46 NORMAL SWBD MDS NO. 1
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
4/28/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 46 NORMAL SWBD MDS NO. 2
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
4/28/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 46 NORMAL SWBD SPARE 2
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: Due to limitation of test equipment tested Instantaneous trip at lower settings.
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 56 CHLR-3
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)
DEFICIENCIES: Breaker failed to reset during testing. Replaced this breaker with the Future breaker by facilities.
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 56 FUTURE
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: This breaker was swapped to the CHLR-3 position due to a failure of that breaker.
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
12 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
Circuit_ID: Building 56 TIE
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 EB2 EB90W1
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)
DEFICIENCIES: Breaker does not trip on overcurrent nor does it trip on short circuit. Recommend replacing breaker.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 EB2 EB90W2
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
DEFICIENCIES: Breaker does not trip on overcurrent nor does it trip on short circuit. It tripped once on A Phase and then no longer tripped. Recommend replacing breaker.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 EMERGENCY EB1 ATS
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 EMERGENCY EB2 ATS
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/24/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 EMERGENCY GENERATOR
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
13 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 NORMAL CRITICAL BRANCH
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
DEFICIENCIES: During testing the trip unit failed to operate on C Phase. After this we attempted testing A and B phases again and they did not trip. Indicates a failed trip unit.
Recommend replacing trip unit or breaker.
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 NORMAL EB1 ATS
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 NORMAL EB2 ATS
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 NORMAL SWBD TIE
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)
COMMENTS: Due to limitation of test equipment tested Long time, Short time and Instantaneous trips at lower settings.
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Circuit Breaker
Circuit_ID: Building 9 X-Ray Panel Main
Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST
14 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
DEFICIENCIES: Breaker does not trip nor does the trip unit status light come on. Recommend replacing breaker.
4/28/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: MCC
Circuit_ID: BLDG 46 MCCB-46 SWBD (RM BA-01)
Equipment: 30000 - MOTOR CONTROL CENTER INSPECTION
COMMENTS: M-CWP-9, 2 AWG, 100A MCCB, Magnetic M-CWP-8, 2 AWG, 100A MCCB, Magnetic
5/27/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: Elm Stret 26KV Switches
Equipment: 15601 - FUSE DISCONNECT INSP. TEST
COMMENTS: Unable to perform insulation resistance test due to installed metering transformers.
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-1 Feeder 7 SW-1
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3.
"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4.
All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-1 Feeder 7 SW-2
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3.
"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4.
All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-2 Feeder 6 SW-1
15 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3.
"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4.
All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-2 Feeder 6 SW-2
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3.
"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4.
All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-56-1 SW-1
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3.
"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4.
All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-56-1 SW-2
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3.
"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4.
All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open, Some Tests could not be completed due to cables being attched.
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-56-2 (Boiler Plant XFMR 10-1)
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3 (Boiler Plant XFMR 10-1).
"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4 (T56-3 XFMR).
All Switch Insulation Resistance values were > 2T?.
16 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: S&C Switches
Circuit_ID: SAC-56-2 (XFMR T56-3)
Equipment: 29100 - DISCONNECT SELECTOR SWITCH
COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3 (Boiler Plant XFMR 10-1).
"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4 (T56-3 XFMR).
All Switch Insulation Resistance values were > 2T?.
4/27/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Switchboard
Circuit_ID: BLDG 40 SWBD LDS Sec #1 (RM 111)
Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST
DEFICIENCIES: Numerous breakers have high contact resistance. Recommend monitoring. IR scan did not reveal any hot spots.
4/27/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Switchboard
Circuit_ID: BLDG 40 SWBD LDS Sec #2 (RM 111)
Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST
DEFICIENCIES: Numerous breakers have high contact resistance. Recommend monitoring. IR scan did not reveal any hot spots.
5/25/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Switchboard
Circuit_ID: BLDG 56 MAIN
Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST
DEFICIENCIES: Numerous breakers have high contact resistance. Recommend monitoring. IR scan did not reveal any hot spots.
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Switchboard
Circuit_ID: BLDG 9 NORMAL FDR 2
Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST (2)
DEFICIENCIES: Contact resistance on B phase on 92W2 breaker for is high out of tollerance.
17 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
5/12/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Switchboard
Circuit_ID: BLDG 9 X-RAY PANEL
Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST
DEFICIENCIES: The conductors on breaker for X-Ray Panel 1st Floor are too large for lugs. Some conductors have been trimmed off.
6/6/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-1 Shops
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in m?
Primary side measurements are in ?.
5/11/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-10 (Boiler Plant)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in m?
Primary side measurements are in m?.
6/6/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-11 (BLDG 11-12-13)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in m?
Primary side measurements are in ?.
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-13
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
18 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
COMMENTS: Low side winding resistance in MiliOhms.
6/6/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-1-WEST
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance High side in Milli-Ohms, Low side in Micro-Ohms.
4/27/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-40
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance Low side in Micro Ohms high side in Milli Ohms.
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T56-1 (Chiller Plant)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in m?
Primary side measurements are in ?.
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T56-2 (Chiller Plant)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in µ?
Primary side measurements are in ?.
5/10/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T56-3 (Chiller Plant)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
19 of 179PAGE
TEST EQUIPMENT USED: TESTED BY:
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
COMMENTS: Winding resistance:
Secondary side imeasurements are in µ?
Primary side measurements are in ?.
6/7/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T9 (X-Ray)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Primary & Secondary measurements are in m?
6/7/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T9-East (BLDG 9, Feeder 2)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in µ?
Primary side measurements are in m?.
6/7/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T9-West (BLDG 9, Feeder 1)
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Winding resistance:
Secondary side imeasurements are in µ?
Primary side measurements are in m?.
4/27/2022Date:
Page:Plant: Fargo VA Medical Center
Substation: Transformer
Circuit_ID: Transformer T-NW
Equipment: 56700 - TRANSFORMER MAINTENANCE TEST
COMMENTS: Single Phase Transformer, Primary internally bonded to ground. Only performed insulation test on Low side of transformer.
SEE OIL ANALYSIS AND INFRARED PAGES FOR THOSE DEFICIENCIES
EQUIPMENT TEMPERATURE
R T = R M K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 923 TESTED BY: TR-5059
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 5/25/22
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
PassTEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 1 ATS Critical Branch
%45 PLANT20 °C
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
310 310 310
333 333 333
318 318 318
357 357 357
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C
C
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
Cummins Power Generation SERIAL NO. C130467583 TYPE OTPCC-1322786
208/120 400
3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
0306-5030-03CATALOG NO.
Description
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
COMMENTS:
DEFICIENCIES:
K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 923 TESTED BY: TR-5059
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 5/25/22
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
PassTEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 1 ATS Equipment Branch
%45 PLANT20 °C
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
72 72 72
76 76 76
74 74 74
75 75 75
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C
C
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
Cummins Power Generation SERIAL NO. C130467580 TYPE OTPCD-1322788
208/120 800
3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
0306-5052-03CATALOG NO.
Description
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 923 TESTED BY: TR-5059
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 5/25/22
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
PassTEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 1 ATS Life Safety
%45 PLANT20 °C
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
142 142 142
139 139 139
144 144 144
156 156 156
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C
C
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
Cummins Power Generation SERIAL NO. C130467587 TYPE OTPCD-1322789
208/120 225
3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
0306-5030-03CATALOG NO.
Description
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 1233 TESTED BY: B ONeil
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 6/6/22
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
Fail (Needs Attention)TEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 11 ATS
%28 PLANT69 °F
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
27 27 27
40 40 40
2,990 2,978 2,990
0 0 0
2,978
POLE 20°C POLE
21 0.996086°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C
C
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
Asco Delta SERIAL NO. 12150-01 TYPE Indoor
4.16kV 450
UNKN CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
N/ACATALOG NO.
Description
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
COMMENTS:
DEFICIENCIES: The "emergency" side vacuum contactor Failed the contact resistance test.
Recommend replacing all three vacuum bottles for this contactor.
K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 1083 TESTED BY: Delbert Parrish
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 4/27/2022
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
PassTEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 40 ATS MCC-1
%45 PLANT20 °C
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
338 338 338
437 437 437
328 328 328
306 306 306
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
N/A
N/A
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
N/A
N/A
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
GE SERIAL NO. 1656643-1 TYPE ZENITH ZTS
208/120 225
1656643 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
ZBTS00B00022FCATALOG NO.
Description
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 923 TESTED BY: TR-5059
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 5/24/22
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
PassTEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 46 ATS 3B-EBE
%45 PLANT20 °C
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
287 287 287
294 294 294
305 305 305
298 298 298
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
C
C
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
ASCO SERIAL NO. 536648 RE TYPE 7000 SERIES
208/120 600
3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR
INSTALLED OPTIONS
J07ATSB30600C5X0CATALOG NO.
Description
POLE RESISTANCE
= AMBIENT TEMPERATURE
MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD
K
K
ST
T
+ T
+ TM
TEST EQUIPMENT USED: 1083 TESTED BY: Delbert Parrish
Family of companies
COPYRIGHT © 2015-2017 CE POWER HOLDING, INC
www.powerdb.com
HUMIDITY Fargo VA Medical CenterDATE 4/27/2022
AUTOMATIC TRANSFER SWITCH TEST
TS UNIT
Address
ASSET ID
CUSTOMER
JOB # 846770 CUSTOMER PO
PAGE
OWNER
PassTEST STATUS
Fargo Veterans Affairs Medical Center
Hyko Solutions
ATS/MTS
AMBIENT TEMPERATURE
Building 46 ATS FIRE PUMP
%45 PLANT20 °C
SUBSTATION CIRCUIT_ID
OVERALL CLEANLINESS
INSULATING MEMBERS
MECHANICAL CONNECTIONS
STRUCTURAL MEMBERS
CUBICLE
RACKING DEVICES
CONTACT FINGERS
MAIN CONTACTS
ARCING CONTACTS
ARC CHUTES
OPERATING MECHANISM
CONTACT SEQUENCE
GROUND CONNECTION
AUXILIARY DEVICES
INSPECTED CONDITION CLEAN/LUBE
LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:
R
R M
S
K
= TOTAL POLE RESISTANCE AT 85°C
T
= TOTAL POLE RESISTANCE AT TEST TEMPERATURE
= TEMP. RESISTANCE CONSTANT (°C)
COPPER = 234.5°C
M
= TEMPERATURE FOR DESIRED RESISTANCE (20°C)
T
T
T
AS LEFT 20°C
NORMAL
A
B
C
N
AS FOUND AS FOUND 20°C AS LEFT 20°C
A
B
C
N
EMERGENCY
469 469 469
448 448 448
584 584 584
0 0 0
POLE 20°C POLE
20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
Acceptable
N/A
N/A
Acceptable
Acceptable
Acceptable
Acceptable
C
C
C
C
C
C/L
C
C
N/A
N/A
C
N/A
C
N/A
MANUFACTURER
NAMEPLATE DATA
WIRING NO.
SYSTEM VOLTAGE AMPACITY
GE SERIAL NO. 1545466-1 TYPE ZENITH ZTS
208/120 225
1656643 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE…
This is the start of the file's text. The full file is on GovTribe.