This document is a comprehensive electrical testing and maintenance report for the Fargo VA Medical Center, prepared by CE Power on August 9, 2022, under VA Contract 36C26322P0343. The report details extensive electrical system testing across multiple buildings and components, including automatic transfer switches, circuit breakers, motor control centers, switchboards, transformers, and disconnect switches.

The testing revealed several key deficiencies and recommendations, including: a failed vacuum contactor in Building 11's automatic transfer switch requiring replacement, circuit breakers in multiple locations with high contact resistance that need monitoring, and specific breakers in Building 9 that require complete replacement due to tripping failures. The report provides detailed technical measurements for each tested component, including resistance readings, insulation tests, and performance evaluations across various electrical systems. While most systems passed initial testing, the document highlights multiple areas requiring maintenance, repair, or potential equipment replacement to ensure continued reliable electrical infrastructure at the Fargo VA Medical Center.

View the file

Other files for this federal contract opportunity

Show all 14

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CE Power ‐ Minnesota

August 9, 2022

Hyko Solutions

Attn: Jon Wilkinson – 808-679-1892 – jon@hykosolutions.com

Re: Hyko Solutions Fargo VA CE Power Job Number: 846770 cc: J. Foster R. Wiegand J. Nielsen M. Dziadosz K. Primozich

Attachments:

Project Summary Test Report Details

360-463-0060 Senior Service Technician, NETA III Delbert Parrish

Sincerely, you for the opportunity to perform this service.

If you have any questions, or if we can be of further assistance, please feel free to call our office. Thank

Please refer to the individual test result sheets for additional details.

Numerous breaker issues were discovered and some thermal deficiencies.

Please see the attached testing results from the firast phase of testing at the Fargo VA Medical Center.

In conjunction with the execution of the project, we have provided the attached report documentation.

36C26322P0343 that was performed at Fargo Veterans Affairs Medical Center.

Attached is the report on conducting electrical testing and maintenance in accordance with VA Contract

Jon;

CE Power – NETA Member

Conduct electrical testing and maintenance in accordance with VA Contract 36C26322P0343 at

Fargo Veterans Affairs Medical Center

846770

For

Hyko Solutions

Attention: Jon Wilkinson

August 9, 2022 Submitted By: Delbert Parrish

Senior Service Technician, NETA III

CE Power – NETA Member

CE Power ‐ Minnesota

WORK SCOPE

Conduct electrical testing and maintenance in accordance with VA Contract 36C26322P0343.

*NOTE: In certain instances, due to site conditions, outage constraints, weather and other unexpected circumstances, the exact quoted scope of work may not have been fully accomplished, or additional equipment may have been added. In those instances, the detailed report documentation will be noted accordingly.

Table of Contents Job #846770

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

1 of 179PAGE

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

2054100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 1 ATS Critical Branch

2154100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 1 ATS Equipment Branch

2254100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 1 ATS Life Safety

2354100 - AUTOMATIC TRANSFER SWITCH TEST - Fail (Needs Attention) Fargo VA Medical Center ATS/MTS Building 11 ATS

2454100 - AUTOMATIC TRANSFER SWITCH TEST

Fargo VA Medical Center ATS/MTS Building 40 ATS MCC-1

2554100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 46 ATS 3B-EBE

2654100 - AUTOMATIC TRANSFER SWITCH TEST

Fargo VA Medical Center ATS/MTS Building 46 ATS FIRE PUMP

2754100 - AUTOMATIC TRANSFER SWITCH TEST (2)

Fargo VA Medical Center ATS/MTS Building 46 ATS SURGERY CHILLER

2854100 - AUTOMATIC TRANSFER SWITCH TEST (2)

Fargo VA Medical Center ATS/MTS Building 9 ATS LIFE SAFETY

2954100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 ATS-CR

3054100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 ATS-EB1

3154100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 ATS-EB2

3254100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 MTS-1

3354100 - AUTOMATIC TRANSFER SWITCH TEST - Pass Fargo VA Medical Center ATS/MTS Building 9 MTS-2

3454100 - AUTOMATIC TRANSFER SWITCH TEST (2)

Fargo VA Medical Center ATS/MTS Building 9 MTS-3

3654100 - AUTOMATIC TRANSFER SWITCH TEST

Fargo VA Medical Center ATS/MTS Building 9 MTS-EB 90N1

3754100 - AUTOMATIC TRANSFER SWITCH TEST

Fargo VA Medical Center ATS/MTS Building 9 MTS-EB 90N3

3815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY CB

3915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY EB

4015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY GEN MAIN

4115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 1 EMERGENCY LIFE SAFETY

4215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL CB

4315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL EB

4415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL FEEDER 1

4515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL FEEDER 2

4615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL LIFE SAFETY

2 of 179PAGE

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

4715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 1 NORMAL SWBD-1 SHOPS MAIN

4815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 1 NORMAL TIE

4915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY EE CBE

5015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY EE EBE EBE2

5115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY EE FIRE PUMP

5215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY GENERATOR BREAKER

5315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY LSE

5415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY SPARE

5515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 EMERGENCY SURGURY CHILLER

5615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL FLOOR SPARE 2400

5715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL FLOOR SPARE 800

5815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 10E6P

5915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 460C2

6015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 460C3

6115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 460N1

6215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 461C1/461C2

6315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 462C1/462N1

6415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 462C2

6515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 462C3

6615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 463C1/464C2

6715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 463C2/464C1

6815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 464C3/464C4

6915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 465C2

7015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD 46OS2

7115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD CBE

7215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD EBE2

3 of 179PAGE

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

7315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD FIRE PUMP

7415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD LIFE SAFETY

7515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD MCC-46

7615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD MDS NO. 1

7715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD MDS NO. 2

7815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 1

7915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 2

8015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 3

8115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SPARE 4

8215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD SURGCHILLER

8315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 46 NORMAL SWBD TIE

8415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (5) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-1

8515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-2

8615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-3

8715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 56 CHLR-4

8815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 56 CHLR-5

8915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 56 FUTURE

9015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 56 MAIN A

9115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 56 MAIN B

9215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 56 TIE

9315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 EB EMERGENCY ELEV 1, 2, 3

9415800 - MOLDED CASE CIRCUIT BREAKER INSP

Fargo VA Medical Center Circuit Breaker Building 9 EB MCC3B RM BA-01

9515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4) Fargo VA Medical Center Circuit Breaker Building 9 EB2 EB90W1

9615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 9 EB2 EB90W2

9715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY CB ATS

9815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY EB1 ATS

4 of 179PAGE

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

9915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY EB2 ATS

10015055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 EMERGENCY GENERATOR

10115055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL CRITICAL BRANCH

10215055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL EB1 ATS

10315055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL EB2 ATS

10415055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 NORMAL EB90W1

10515055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL PNL 95C2

10615055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL SWBD FEEDER 1 MAIN

10715055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 NORMAL SWBD FEEDER 2 MAIN

10815055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2) Fargo VA Medical Center Circuit Breaker Building 9 NORMAL SWBD TIE

10915055 v1 - LOW VOLT. PWR. CKT. BKR. TEST Fargo VA Medical Center Circuit Breaker Building 9 X-Ray Panel Main

11015510 - LOW VOLTAGE AIR SWITCH

Fargo VA Medical Center LV Disconnect ACCH-4 Disconnect

11130000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 1 MCCEB-1 (Sec. A-B)

11230000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 1 MCCEB-1 (Sec. C-D)

11330000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 40 MCC 1 (RM 112B)

11430000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 40 MCC 2 (RM 212)

11530000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 46 MCC-3B (Sec. A-B)

11630000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 46 MCC-3B (Sec. C)

11730000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 46 MCC-3B (Sec. D )

11830000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 46 MCCB-46 SWBD (RM BA-01)

11930000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 46 MCC-EB462C1 (RM 2D-12)

12030000 - MOTOR CONTROL CENTER INSPECTION

Fargo VA Medical Center MCC BLDG 46 MCC-ES464C1 (RM 4C-27)

12115601 - FUSE DISCONNECT INSP. TEST

Fargo VA Medical Center S&C Switches Elm Stret 26KV Switches

12229100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-1 Feeder 7 SW-1

12329100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-1 Feeder 7 SW-2

12429100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-2 Feeder 6 SW-1

5 of 179PAGE

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

12529100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-2 Feeder 6 SW-2

12629100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-56-1 SW-1

12729100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-56-1 SW-2

12829100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-56-2 (Boiler Plant XFMR 10-1)

12929100 - DISCONNECT SELECTOR SWITCH

Fargo VA Medical Center S&C Switches SAC-56-2 (XFMR T56-3)

13050400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY CB

13150100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY CB

13250400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY EB

13350100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY EB

13450400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY LS

13550100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 EMERGENCY LS

13650100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 1

13750400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 1

13850100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 2

13950400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 NORMAL FDR 2

14050400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 NORMAL SWBD 2

14150100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 NORMAL SWBD 2

14250400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 1 SWBD-1 Shops

14350100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 1 SWBD-1 Shops

14450100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Main (RM 111)

14550400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Main (RM 111)

14650400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Sec #1 (RM 111)

14750400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 40 SWBD LDS Sec #2 (RM 111)

14850400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 56 MAIN

14950100 - LV SWITCHBOARD INSULATION

Fargo VA Medical Center Switchboard BLDG 56 MAIN

15050100 - LV SWITCHBOARD INSULATION (2)

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY CB

6 of 179PAGE

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

15150400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY CB

15250100 - LV SWITCHBOARD INSULATION (2)

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB1

15350400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB1

15450100 - LV SWITCHBOARD INSULATION (2)

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB2

15550400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY EB2

15650100 - LV SWITCHBOARD INSULATION (2)

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY GENERATOR

15750400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 9 EMERGENCY GENERATOR

15850400 - SWITCHBOARD BUS CONNECTION TEST (2)

Fargo VA Medical Center Switchboard BLDG 9 NORMAL FDR 2

15950400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 9 NORMAL POWER FDR 1

16050400 - SWITCHBOARD BUS CONNECTION TEST

Fargo VA Medical Center Switchboard BLDG 9 X-RAY PANEL

16156700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-1 Shops

16256700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-10 (Boiler Plant)

16365500 - LIGHTNING ARRESTER TEST

Fargo VA Medical Center Transformer Transformer T-10 (Boiler Plant)

16456700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-11 (BLDG 11-12-13)

16565500 - LIGHTNING ARRESTER TEST

Fargo VA Medical Center Transformer Transformer T-13

16656700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-13

16756700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-1-EAST

16856700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-1-WEST

16956700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-40

17065500 - LIGHTNING ARRESTER TEST

Fargo VA Medical Center Transformer Transformer T-40

17156700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T56-1 (Chiller Plant)

17256700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T56-2 (Chiller Plant)

17365500 - LIGHTNING ARRESTER TEST

Fargo VA Medical Center Transformer Transformer T56-2 (Chiller Plant)

17456700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T56-3 (Chiller Plant)

17565500 - LIGHTNING ARRESTER TEST

Fargo VA Medical Center Transformer Transformer T56-3 (Chiller Plant)

17656700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T9 (X-Ray)

7 of 179PAGE

REVISED 5/28/2010COPYRIGHT © 2015-2017 CE POWER HOLDING, INC www.powerdb.com

Family of companies

PAGE

NO.Asset

Circuit_IDSubstationPlant

Hyko SolutionsCustomer

Fargo Veterans Affairs Medical CenterOwner

17756700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T9-East (BLDG 9, Feeder 2)

17856700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T9-West (BLDG 9, Feeder 1)

17956700 - TRANSFORMER MAINTENANCE TEST

Fargo VA Medical Center Transformer Transformer T-NW

OIL ANALYSIS 4/27/2022 (SEE THESE PAGES FOR DEFICIENCIES) 183 THRU 185 OF 241

OIL ANALYSIS AND PCB 5/10 & 5/11/2022 (SEE THESE PAGES FOR DEFICIENCIES) 186 THRU 193 OF 241 OIL ANALYSIS 6/6 & 6/7/2022 (SEE THESE PAGES FOR DEFICIENCIES) 194 THRU 202 OF 241

INFRARED (SEE THESE PAGES FOR DEFICIENCIES) 203 THRU 241 OF 241

8 of 179PAGE

Customer Hyko Solutions

Owner Fargo Veterans Affairs Medical Center

Comment and Deficiency Summary Job #846770

6/6/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: ATS/MTS

Circuit_ID: Building 11 ATS

Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST - Fail (Needs Attention)

DEFICIENCIES: The "emergency" side vacuum contactor Failed the contact resistance test.

Recommend replacing all three vacuum bottles for this contactor.

4/27/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: ATS/MTS

Circuit_ID: Building 46 ATS FIRE PUMP

Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST

COMMENTS: This is a three pole ATS. The Zero for Neutral contact resistance signifies not present.

6/7/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: ATS/MTS

Circuit_ID: Building 9 MTS-3

Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST (2)

COMMENTS: Emergency power side fuse resistance as follows:

A:299 B:317 C:307 MicroOhms Normal Power side fuse resistance as follows:

A:322 B:308 C:313 MicroOhms Fuses installed are BUSS class T fuses IR 200KA HRCI-T 200A

6/7/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: ATS/MTS

Circuit_ID: Building 9 MTS-EB 90N1

Equipment: 54100 - AUTOMATIC TRANSFER SWITCH TEST

COMMENTS: Due to restrictions of facility we were unable to test this

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 EMERGENCY CB

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

Comment and Deficiency Summary

9 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 EMERGENCY EB

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 EMERGENCY GEN MAIN

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

COMMENTS: Due to limitation of test equipment tested Instantaneous trip at lower settings.

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 NORMAL CB

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 NORMAL EB

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 NORMAL FEEDER 1

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

10 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 NORMAL FEEDER 2

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 NORMAL SWBD-1 SHOPS MAIN

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/26/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 1 NORMAL TIE

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: Due to limitation of test equipment tested Short time and Instantaneous trips at lower settings.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 46 EMERGENCY EE EBE EBE2

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 46 EMERGENCY LSE

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/11/2022Date:

Page:

11 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

5/11/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 46 NORMAL SWBD MDS NO. 1

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

4/28/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 46 NORMAL SWBD MDS NO. 2

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

4/28/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 46 NORMAL SWBD SPARE 2

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: Due to limitation of test equipment tested Instantaneous trip at lower settings.

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 56 CHLR-3

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)

DEFICIENCIES: Breaker failed to reset during testing. Replaced this breaker with the Future breaker by facilities.

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 56 FUTURE

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: This breaker was swapped to the CHLR-3 position due to a failure of that breaker.

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

12 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

Circuit_ID: Building 56 TIE

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 EB2 EB90W1

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (4)

DEFICIENCIES: Breaker does not trip on overcurrent nor does it trip on short circuit. Recommend replacing breaker.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 EB2 EB90W2

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

DEFICIENCIES: Breaker does not trip on overcurrent nor does it trip on short circuit. It tripped once on A Phase and then no longer tripped. Recommend replacing breaker.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 EMERGENCY EB1 ATS

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 EMERGENCY EB2 ATS

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/24/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 EMERGENCY GENERATOR

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

13 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 NORMAL CRITICAL BRANCH

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

DEFICIENCIES: During testing the trip unit failed to operate on C Phase. After this we attempted testing A and B phases again and they did not trip. Indicates a failed trip unit.

Recommend replacing trip unit or breaker.

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 NORMAL EB1 ATS

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (3)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 NORMAL EB2 ATS

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Short time trip at lower settings.

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 NORMAL SWBD TIE

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST (2)

COMMENTS: Due to limitation of test equipment tested Long time, Short time and Instantaneous trips at lower settings.

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Circuit Breaker

Circuit_ID: Building 9 X-Ray Panel Main

Equipment: 15055 v1 - LOW VOLT. PWR. CKT. BKR. TEST

14 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

DEFICIENCIES: Breaker does not trip nor does the trip unit status light come on. Recommend replacing breaker.

4/28/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: MCC

Circuit_ID: BLDG 46 MCCB-46 SWBD (RM BA-01)

Equipment: 30000 - MOTOR CONTROL CENTER INSPECTION

COMMENTS: M-CWP-9, 2 AWG, 100A MCCB, Magnetic M-CWP-8, 2 AWG, 100A MCCB, Magnetic

5/27/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: Elm Stret 26KV Switches

Equipment: 15601 - FUSE DISCONNECT INSP. TEST

COMMENTS: Unable to perform insulation resistance test due to installed metering transformers.

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-1 Feeder 7 SW-1

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3.

"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4.

All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-1 Feeder 7 SW-2

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3.

"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4.

All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-2 Feeder 6 SW-1

15 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3.

"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4.

All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-2 Feeder 6 SW-2

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3.

"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4.

All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-56-1 SW-1

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3.

"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4.

All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-56-1 SW-2

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3.

"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4.

All Switch Insulation Results are with Cables Attached Source Isnt Grounded Switch Open, Some Tests could not be completed due to cables being attched.

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-56-2 (Boiler Plant XFMR 10-1)

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #2 to Compartment #3 (Boiler Plant XFMR 10-1).

"B" side measurement refer to the current path and fuses from Compartment #2 to Compartment #4 (T56-3 XFMR).

All Switch Insulation Resistance values were > 2T?.

16 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: S&C Switches

Circuit_ID: SAC-56-2 (XFMR T56-3)

Equipment: 29100 - DISCONNECT SELECTOR SWITCH

COMMENTS: "A" side measurement refer to the current path and fuses from Compartment #1 to Compartment #3 (Boiler Plant XFMR 10-1).

"B" side measurement refer to the current path and fuses from Compartment #1 to Compartment #4 (T56-3 XFMR).

All Switch Insulation Resistance values were > 2T?.

4/27/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Switchboard

Circuit_ID: BLDG 40 SWBD LDS Sec #1 (RM 111)

Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST

DEFICIENCIES: Numerous breakers have high contact resistance. Recommend monitoring. IR scan did not reveal any hot spots.

4/27/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Switchboard

Circuit_ID: BLDG 40 SWBD LDS Sec #2 (RM 111)

Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST

DEFICIENCIES: Numerous breakers have high contact resistance. Recommend monitoring. IR scan did not reveal any hot spots.

5/25/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Switchboard

Circuit_ID: BLDG 56 MAIN

Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST

DEFICIENCIES: Numerous breakers have high contact resistance. Recommend monitoring. IR scan did not reveal any hot spots.

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Switchboard

Circuit_ID: BLDG 9 NORMAL FDR 2

Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST (2)

DEFICIENCIES: Contact resistance on B phase on 92W2 breaker for is high out of tollerance.

17 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

5/12/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Switchboard

Circuit_ID: BLDG 9 X-RAY PANEL

Equipment: 50400 - SWITCHBOARD BUS CONNECTION TEST

DEFICIENCIES: The conductors on breaker for X-Ray Panel 1st Floor are too large for lugs. Some conductors have been trimmed off.

6/6/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-1 Shops

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in m?

Primary side measurements are in ?.

5/11/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-10 (Boiler Plant)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in m?

Primary side measurements are in m?.

6/6/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-11 (BLDG 11-12-13)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in m?

Primary side measurements are in ?.

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-13

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

18 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

COMMENTS: Low side winding resistance in MiliOhms.

6/6/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-1-WEST

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance High side in Milli-Ohms, Low side in Micro-Ohms.

4/27/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-40

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance Low side in Micro Ohms high side in Milli Ohms.

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T56-1 (Chiller Plant)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in m?

Primary side measurements are in ?.

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T56-2 (Chiller Plant)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in µ?

Primary side measurements are in ?.

5/10/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T56-3 (Chiller Plant)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

19 of 179PAGE

TEST EQUIPMENT USED: TESTED BY:

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

COMMENTS: Winding resistance:

Secondary side imeasurements are in µ?

Primary side measurements are in ?.

6/7/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T9 (X-Ray)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Primary & Secondary measurements are in m?

6/7/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T9-East (BLDG 9, Feeder 2)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in µ?

Primary side measurements are in m?.

6/7/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T9-West (BLDG 9, Feeder 1)

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Winding resistance:

Secondary side imeasurements are in µ?

Primary side measurements are in m?.

4/27/2022Date:

Page:Plant: Fargo VA Medical Center

Substation: Transformer

Circuit_ID: Transformer T-NW

Equipment: 56700 - TRANSFORMER MAINTENANCE TEST

COMMENTS: Single Phase Transformer, Primary internally bonded to ground. Only performed insulation test on Low side of transformer.

SEE OIL ANALYSIS AND INFRARED PAGES FOR THOSE DEFICIENCIES

EQUIPMENT TEMPERATURE

R T = R M K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 923 TESTED BY: TR-5059

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 5/25/22

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

PassTEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 1 ATS Critical Branch

%45 PLANT20 °C

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

310 310 310

333 333 333

318 318 318

357 357 357

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C

C

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

Cummins Power Generation SERIAL NO. C130467583 TYPE OTPCC-1322786

208/120 400

3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

0306-5030-03CATALOG NO.

Description

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

COMMENTS:

DEFICIENCIES:

K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 923 TESTED BY: TR-5059

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 5/25/22

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

PassTEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 1 ATS Equipment Branch

%45 PLANT20 °C

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

72 72 72

76 76 76

74 74 74

75 75 75

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C

C

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

Cummins Power Generation SERIAL NO. C130467580 TYPE OTPCD-1322788

208/120 800

3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

0306-5052-03CATALOG NO.

Description

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 923 TESTED BY: TR-5059

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 5/25/22

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

PassTEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 1 ATS Life Safety

%45 PLANT20 °C

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

142 142 142

139 139 139

144 144 144

156 156 156

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C

C

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

Cummins Power Generation SERIAL NO. C130467587 TYPE OTPCD-1322789

208/120 225

3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

0306-5030-03CATALOG NO.

Description

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 1233 TESTED BY: B ONeil

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 6/6/22

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

Fail (Needs Attention)TEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 11 ATS

%28 PLANT69 °F

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

27 27 27

40 40 40

2,990 2,978 2,990

0 0 0

2,978

POLE 20°C POLE

21 0.996086°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C

C

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

Asco Delta SERIAL NO. 12150-01 TYPE Indoor

4.16kV 450

UNKN CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

N/ACATALOG NO.

Description

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

COMMENTS:

DEFICIENCIES: The "emergency" side vacuum contactor Failed the contact resistance test.

Recommend replacing all three vacuum bottles for this contactor.

K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 1083 TESTED BY: Delbert Parrish

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 4/27/2022

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

PassTEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 40 ATS MCC-1

%45 PLANT20 °C

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

338 338 338

437 437 437

328 328 328

306 306 306

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

N/A

N/A

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

N/A

N/A

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

GE SERIAL NO. 1656643-1 TYPE ZENITH ZTS

208/120 225

1656643 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

ZBTS00B00022FCATALOG NO.

Description

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 923 TESTED BY: TR-5059

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 5/24/22

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

PassTEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 46 ATS 3B-EBE

%45 PLANT20 °C

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

287 287 287

294 294 294

305 305 305

298 298 298

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

C

C

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

ASCO SERIAL NO. 536648 RE TYPE 7000 SERIES

208/120 600

3/4 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE MICROPROCESSOR

INSTALLED OPTIONS

J07ATSB30600C5X0CATALOG NO.

Description

POLE RESISTANCE

= AMBIENT TEMPERATURE

MICRO-OHMS LINE TO LOAD MICRO-OHMS LINE TO LOAD

K

K

ST

T

+ T

+ TM

TEST EQUIPMENT USED: 1083 TESTED BY: Delbert Parrish

Family of companies

COPYRIGHT © 2015-2017 CE POWER HOLDING, INC

www.powerdb.com

HUMIDITY Fargo VA Medical CenterDATE 4/27/2022

AUTOMATIC TRANSFER SWITCH TEST

TS UNIT

Address

ASSET ID

CUSTOMER

JOB # 846770 CUSTOMER PO

PAGE

OWNER

PassTEST STATUS

Fargo Veterans Affairs Medical Center

Hyko Solutions

ATS/MTS

AMBIENT TEMPERATURE

Building 46 ATS FIRE PUMP

%45 PLANT20 °C

SUBSTATION CIRCUIT_ID

OVERALL CLEANLINESS

INSULATING MEMBERS

MECHANICAL CONNECTIONS

STRUCTURAL MEMBERS

CUBICLE

RACKING DEVICES

CONTACT FINGERS

MAIN CONTACTS

ARCING CONTACTS

ARC CHUTES

OPERATING MECHANISM

CONTACT SEQUENCE

GROUND CONNECTION

AUXILIARY DEVICES

INSPECTED CONDITION CLEAN/LUBE

LOAD CONDUCTOR NO./ PHASE: CU ALSIZE: 3/0 KCM:

R

R M

S

K

= TOTAL POLE RESISTANCE AT 85°C

T

= TOTAL POLE RESISTANCE AT TEST TEMPERATURE

= TEMP. RESISTANCE CONSTANT (°C)

COPPER = 234.5°C

M

= TEMPERATURE FOR DESIRED RESISTANCE (20°C)

T

T

T

AS LEFT 20°C

NORMAL

A

B

C

N

AS FOUND AS FOUND 20°C AS LEFT 20°C

A

B

C

N

EMERGENCY

469 469 469

448 448 448

584 584 584

0 0 0

POLE 20°C POLE

20 1°C TEMPERATURE CORRECTION FACTOR 20°C, TCF

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

Acceptable

N/A

N/A

Acceptable

Acceptable

Acceptable

Acceptable

C

C

C

C

C

C/L

C

C

N/A

N/A

C

N/A

C

N/A

MANUFACTURER

NAMEPLATE DATA

WIRING NO.

SYSTEM VOLTAGE AMPACITY

GE SERIAL NO. 1545466-1 TYPE ZENITH ZTS

208/120 225

1656643 CONTROLS TYPE: ELECTROMECHANICAL SOLID STATE…