36C26319B0010-009.pdf

PDF 4 MB Posted

Attached to
REPLACE BOILER PLANT (437-14-112)
Solicitation number
36C26319B0010
Issued by

About this file

36C26319B0010 437-14-112 Replace Boiler Plant Electrical Drawings (14 pages).pdf

View the file

Other files

File Type Posted
36C26319C0205-000.docx DOCX document
36C26319B0010-0004000.docx DOCX document
36C26319B0010-0003000.docx DOCX document
36C26319B0010-0003001.pdf PDF
36C26319B0010-0003002.pdf PDF
36C26319B0010-0002000.docx DOCX document
36C26319B0010-0002001.pdf PDF
36C26319B0010-0001001.pdf PDF
36C26319B0010-0001000.docx DOCX document
36C26319B0010-012.pdf PDF
36C26319B0010-010.pdf PDF
36C26319B0010-004.pdf PDF
36C26319B0010-011.pdf PDF
36C26319B0010-001.docx DOCX document
36C26319B0010-008.pdf PDF
36C26319B0010-005.pdf PDF
36C26319B0010-002.pdf PDF
36C26319B0010-007.pdf PDF
36C26319B0010-006.pdf PDF
36C26319B0010-003.pdf PDF
36C26319B0010-000.docx DOCX document
Show all 21

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

48"

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

SINGLE POLE (HORSE POWER RATED WHEN USED AS MOTOR DISCONNECT)

PC

DESCRIPTION

CEILING SURFACE MOUNTED LIGHT FIXTURE, CAPITAL LETTER IDICATES

FIXTURE TYPE, SMALL LETTER INDICATES SWITCHING

RECESSED CEILING MOUNTED LIGHT FIXTURE

SUSPENDED LIGHT FIXTURE

TRACK AND TRACK LIGHT

SURFACE FLUORESCENT FIXTURE

EMERGENCY BATTERY LIGHT

PENDANT LIGHT FIXTURE

SYMBOL

A

7' - 6"

MOUNTING

HEIGHT

ELECTRICAL SYMBOL LEGEND

a

WALL MOUNTED LIGHT FIXTURE

CEILING EXIT SIGN, SHADED SIDE INDICATES LIGHTED FACE, ARROWS

INSTALLED AS SHOWN

WALL EXIT SIGN

RECESSED FLUORESCENT

6" ABOVE

DOOR

FRAME TO

BOTTOM

WALL MOUNT OCCUPANCY SENSOR SWITCH

EMERGENCY REMOTE LAMP 7' - 6"

DOUBLE POLE 48"

3 - WAY 48"

4 - WAY 48"

LV

LOW VOLTAGE 48"

M

DIMMER SWITCH 48"

D

KEY OPERATED SWITCH 48"

K

PILOT LIGHT (MAY BE USED WITH OTHER SWITCH TYPES) 48"

P

MOMENTARY CONTACT 48"

MC

PHOTOCELL 9' - 0"

POLE MOUNTED FIXTURE

CEILING MOUNT OCCUPANCY SENSOROS

TIME CONTROL SWITCH 48"

T

M MOTION SENSOR SWITCH POWER PACKPP

C CONTACTOR (NUMBER INDICATES NUMBER OF POLES)2

DESCRIPTIONSYMBOL

18"

18"

DOUBLE DUPLEX RECEPTACLE 18"

TYPE L14-30 RECEPTACLE 18"A

TYPE L14-50 RECEPTACLE 6"B

SR

CIRCUIT BREAKER PANEL

WALL HEATER

HATCHED SYMBOL INDICATES REMOVED

DASHED SYMBOL INDICATES EXISTING

T

T1

BASEBOARD HEATER

LINE VOLTAGE THERMOSTAT

COMB. MOTOR STARTER

VARIABLE FREQUENCY DRIVE

DISCONNECT SWITCH.

CEILING MOUNTED VERTICAL MULTIPLE OUTLET ASSEMBLY

POWER OR DISTRIBUTION PANEL

MOTOR (SEE SCHEDULE)

TRANSFORMER

SPECIAL CABINET

CONDUIT TRANSITION DOWN

CONDUIT TRANSITION UP

BRANCH CIRCUIT HOME RUN

CONDUIT EXPOSED

SURFACE RACEWAY

CONDUIT STUBBED OUT

CONDUIT CONCEALED BELOW FLOOR

CONDUIT CONCEALED IN WALL OR OVERHEAD

SMOKE DETECTOR ('E' INDICATES DEVICE WITH ELEVATOR RECALL)

DUCT SMOKE DETECTOR

FLOORBOX COMMUNICATIONS OUTLET

1 KEYED NOTE

MULTIOUTLET ASSEMBLY , PROVIDE DEVICES AS SHOWN ON PLANS

GFCI RECEPTACLE 18"G

SPECIAL RECEPTACLE

FOURPLEX RECEPTACLE

SWITCHED DUPLEX RECEPTACLE

ISOLATED GROUND RECEPT (DUPLEX SHOWN)

FLOOR RECEPTACLE (DUPLEX SHOWN)

FOURPLEX RECEPTACLE WITH (1) DUPLEX SWITCHED AND (1)

UNSWITCHED.

18"

18"

18"

18"

DUPLEX RECEPTACLE - HALF SWITCHED 18"

MOUNTING

HEIGHT

J

J CEILING MOUNTED JUNCTION BOX

WALL MOUNTED JUNCTION BOX

PUSH BUTTON, SEE DWG FOR TYPE 48"

48"

SF-1

DESCRIPTIONSYMBOL

MOUNTING

HEIGHT

72"*

72"*

72"*

72"*

72"*

72"*

AUDIO/VISUAL INPUT JACK - 'V' INDICATES VIDEO/HDMI WALLPLATE

CEILING MOUNTED RECESSED SPEAKER

SURFACE MT SPEAKER

S

MICROPHONE OUTLET

CEILING MOUNTED HORN SPEAKER

VOLUME CONTROL

S

S

S

S

WALL MOUNTED SPEAKER

WALL MOUNTED HORN SPEAKER

WIRELESS CLOCK (120V POWERED)

90"

90"

* DISTANCE TO THE TOP OF THE EQUIPMENT OR DEVICE ** DISTANCE TO THE BOTTOM OF THE EQUIPMENT OR DEVICE

84"

V

M

48"

18"

A 18"

COMPUTER OUTLET (NUMBER INDICATES QUANTITY OF CABLES, NO NUMBER

INDICATES ONE)

WALL TELEPHONE OUTLET

TELEPHONE OUTLET

W

TELEVISION/ FLAT PANEL MONITOR LOCATIONTV

WIRELESS ACCESS POINT OUTLET - QTY OF (2) CABLES AND JACKS AT EACH

18"

48"

18"

76"

CARD READER

KEYPAD

CR 48"

48"

BALANCED DOOR POSITION SWITCH

ELECTRIC STRIKEES

P

MAGNETIC LOCKML

12'AFF

IP CCTV CAMERA

DESCRIPTIONSYMBOL

MOUNTING

HEIGHT

F MANUAL FIRE ALARM PULL STATION

H

FIXED TEMPERATURE DETECTOR

48"

S

FIRE ALARM HORN WITH STROBE

FIRE ALARM SPEAKER WITH STROBES 80"**

80"**

H

COMBINATION FIRE/SMOKE DAMPER OR SMOKE DAMPER BY DIVISION 23

DS

FIRE ALARM STROBE LIGHT 80"**

FIRE ALARM CHIME WITH STROBEC 80"**

FR FIRE ALARM MODULE/RELAY

MAGNETIC DOOR HOLD OPEN

SPRINKLER VALVE TAMPER SWITCH, NUMBER INDICATES QUANTITY

SPRINKLER FLOW SWITCH, NUMBER INDICATES QUANTITY

SPRINKLER PRESSURE SWITCH

FIRE ALARM REMOTE ANNUNCIATOR

FA ANNUN

72"*

FIRE ALARM CONTROL PANEL

FACP

72"*

CABLE TRAY

CONDUIT SLEEVE (SIZE DENOTED)

UE UNDERGROUND ELECTRICAL

ABBREVATIONS

A AMPERE

AC ABOVE COUNTER

AFF ABOVE FINISHED FLOOR

AHU AIR HANDLING UNIT

AL ALUMINUM

AMP AMPERE

ATS AUTOMATIC TRANSFER SWITCH

AV AUDIO VISUAL

BC BELOW COUNTER

C CONDUIT

CU COPPER

CUH CABINET UNIT HEATER

EF EXHAUST FAN

EWC ELECTRIC WATER COOLER

ANN ANNUNCIATOR

FA FIRE ALARM

FACP FIRE ALARM CONTROL PANEL

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GR GROUND

HP HORSEPOWER

JBOX JUNCTION BOX

KV KILOVOLT

KW KILOWATT

PH PHASE

TV TELEVISION

W WIRE

WP WEATHERPROOF

WH WATERHEATER

V VOLT

VFD VARIABLE FREQUENCY DRIVE

UE UNDERGROUND ELECTRICAL

RTU ROOF TOP UNIT

SWBD SWITCHBOARD

LIGHT FIXTURE WITH EMERGENCY BALLAST

1. NOT ALL SYMBOLS OR ABBREVATIONS ARE APPLICABLE TO THESE DRAWIANGS. 2. MOUNTING HEIGHT IS TO THE CENTER OF DEVICE UNLESS NOTED OTHERWISE. 3. FOR DEVICES SHOWN AS 48 INCHES MOUNTING HEIGHT, WHEN INSTALLED IN MASONRY BLOCK WALLS, MOUNTING AT 48 INCHES TO THE TOP OF THE OUTLET BOX IS ACCEPTABLE.

AREA OF RESCUE STATIONAR

L

P

PUSH BUTTONPB 48"

C

ELECTRIFIED LOCKEL

AP

DH

FS

TS

KP

ALARM SIRENA 12'AFF

TELEPHONE RINGER - EMERGENCY FIRE PHONETR

LUMINAIRE SCHEDULE

TYPE MANUFACTURERS

CATALOG

INFORMATION

FIXTURE DESCRIPTION

LAMP DATA DRIVER DATA INPUT

WATTS

VOLTAGE MOUNTING REMARKS

NO. TYPE NO. TYPE

A1

METALUX 2GR SERIES 2' X 4' RECESSED LED TROFFER, REGRESSED ALUMINUM DOOR FRAME HINGED AND LATCHED

WITH 0.125 INCH THICK PATTERN #12 DIFFUSER. 4900 LUMENS

LED 0-10V DIMMING DRIVER 38 277 RECESSED

OR EQUAL

A2

METALUX 2GR SERIES SAME AS TYPE 'A1', 2'X2' VERSION, 4300 LUMENS.

LED 0-10V DIMMING DRIVER 33 277 RECESSED

OR EQUAL

C1

HALO H4 LED 4 INCH LED RECESSED DOWNLIGHT. ALUMINUM CONSTRUCTION, 4000 DEGREE COLOR

TEMPERATURE,80 CRI, INITIAL LUMEN OUTPUT OF 600. WET LISTED. WHITE REFLECTOR WITH

WHITE TRIM RING. LED LED DRIVER 30 277 RECESSED

OR EQUAL SERIES

E1

LITHONIA LV SERIES SINGLE FACE LED EXIT LUMINAIRE, DIE CAST ALUMINUM HOUSING, WHITE BODY AND CANOPY, POLYCARBONATE COVER, STENCIL FACE, RED LETTERS, AC ONLY.

LED LED DRIVER 1.5 277 UNIVERSAL

OR EQUAL

EM

LITHONIA INDX SERIES INDUSTRIAL BATTERY PACK LIGHT, 90 MIN ILLUMINATION, HIGH TEMPERATURE BATTERY, POLYCARBONATE HOUSING AND LENS, GASKETED.

LED LED DRIVER 1.5 277 UNIVERSAL

OR EQUAL

F1

METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL

FINISH, 4000K, 5400 LUMENS, 80 CRI.

LED LED DRIVER 43 277 SURFACE

OR EQUAL

F2

LITHONIA LBLED SERIES 4 FOOT LED CURVED BASKET WRAPAROUND LIGHT, #12 PRISMATIC DIFFUSER, NARROW HOUSING, 4000K, 4800 LUMENS.

LED LED DRIVER 32 277 SURFACE

OR EQUAL

F3

METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL

FINISH, 4000K, 7400 LUMENS, 80 CRI.

LED LED DRIVER 64 277 SUSPENDED

PROVIDE WITH STEM MOUNT KIT

OR EQUAL

H1

HOLOPHANE PHUZION PHS LED, HIGH BAY LUMINAIRE, CAST ALUMINUM HOUSING, PRISMATIC GLASS LENS, PENDANT

MOUNTING, UPLIGHT, 4000K, 80 CRI, WIDE OPTIC, WHITE FINISH, 18000 LUMENS, HOOK

MOUNT WITH SAFETY CHAIN LED LED DRIVER 166 277 SUSPENDED

SUSPEND 24'AFF TYPICAL.

OR EQUAL SERIES

U1

FAIL SAFE UCL SERIES 2 FOOT LED UNDERCABINET FIXTURE, SOLID FACE, ACRYLIC LENS, WHITE FINISH, 3500K, 750 LUMENS/FT, INTEGRAL TOGGLE SWITCH.

LED LED DRIVER 9 120 SURFACE

OR EQUAL

V1

TERON VICEROY SERIES 2 FOOT LED VANITY FIXTURE WITH (2) 6W LED STRIPS, SOLID FACE, ACRYLIC LENS, UP/DOWNLIGHT HOUSING, STEEL TEXTURED WHITE HOUSING, 4000K

LED LED DRIVER 20 277 SURFACE

OR EQUAL

W1

LITHONIA D SERIES SIZE 0 EXTERIOR WALL MOUNTED AREA FIXTURE, P1 VERSION, FORWARD THROW

DISTRIBUTION.SINGLE PIECE DIE-CAST ALUMINUM HOUSING,DARK BRONZE FINISH, 4000K,

BI-LEVEL 50% MOTION SENSOR, GLARE SHIELD. LED LED-DRIVER 50 277 WALL

SEE DRAWINGS FOR MOUNTING HEIGHT

OR EQUAL

W2

LITHONIA DSXW SERIES SIZE 1 EXTERIOR WALL PACK, 10 LED, TYPE II DISTRIBUTION SINGLE PIECE DIE-CAST

ALUMINUM HOUSING, SINGLE PIECE DIE CAST ALUMINUM HOUSING, DARK BRONZE FINISH,

4000K. LED LED-DRIVER 14 277 WALL

SEE DRAWINGS FOR MOUNTING HEIGHT

OR EQUAL

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :2

P

M

E1 437-14-112

REPLACE BOILER PLANT 10.26.18

ELECTRICAL SYMBOLS AND

ABBREVIATIONS

100% CONSTRUCTION DOCUMENT

5615-193 E1.DWG

AS NOTED

SEE DRAWINGS AND ONE-LINE

FOR EXACT QUANTITY AND

SIZE OF WIRING AND

CONDUITS

15-193 E2.DWG

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

10 - BOILER PLANT

CH MB CH

Project Phase www.jlgarchitects.com copyright © 2015

214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

KEY PLAN

437-14-112

REPLACE BOILER PLANT 10.26.18

100% CONSTRUCTION DOCUMENT

Dwg. of 69

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

DATE 10-26-18

ELECTRICAL SITE PLAN AND DETAILS

AS NOTED

0' 30'15' 60'

0' 30'15' 60'

E2

0' 4'2' 8'

0' 4'2' 8'

15-193 E3.DWG

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

10 - BOILER PLANT

CH MB CH

Project Phase www.jlgarchitects.com copyright © 2015

214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

KEY PLAN

437-14-112

REPLACE BOILER PLANT 10.26.18

100% CONSTRUCTION DOCUMENT

Dwg. of 69

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

DATE 10-26-18

ELECTRICAL DEMOLITION PLANS

AS NOTED

E3

4 3

3 3

BOILER ROOM

ELECTRICAL

VESTIBULE

SHOP

GENERATOR

ROOM

STORAGE

CLOSET

HOUSEKEEPING

CLOSET

OFFICE/CONTROL

LOCKER ROOM

LOWER LEVEL

SHOP ALCOVE

105A

F1 F1

F1 F1

F1 F1

F1 F1

F1 F1

F1

F1

F1 F1 F1 F1

F1F1F1F1

F1

F1

F1

F1

F1 F1

F1

F1

E1

A1

B1

A1

A2

EB101N1 EB101N2 EB101N3

TO MEZZANINE

LEVEL LIGHTS,

SEE SHEET E5

E1

F1

E1

TO TUNNEL

LIGHTS

E1

E

M

M

V1

U1

C1 B1

W1 W2

W2

W1

W1

W1

W1

E1

U1

U1

D

EB101N3-5

EB101N3-3

EB101N3-9

EB101N3-7

B1

B1B1

D

TO UPPER LEVEL LIGHTING

SEE SHEET E5

TO UPPER LEVEL LIGHTING

SEE SHEET E5

W1

W1

W1 W1 W2

W1

W1

W1

54444

EB101N1-28

F1 F1 F1 F1 F1 F1 F1 F1

EM

EM

EM EM

EM

F1 F1 F1 F1

F1 F1 F1 F1 F1 F1

EM

EM

EM

EM

EM

EB101N3-11

EB101N3-13

EB101N3-15

VIA PHOTOCELL

VIA PHOTOCELL

PC 9

EM

EM

EM

nl

F1

F1

TO UPPER LEVEL LIGHTING

SEE SHEET E5

7 7 7 77

8 8 8

2 HOUR RATED WALL

1 HOUR RATED WALL

C

EXTERIOR LIGHTING CONTACTOR

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :2

P

M

E4 437-14-112

REPLACE BOILER PLANT 10.26.18

MAIN LEVEL REMODELING

PLAN - LIGHTING

100% CONSTRUCTION DOCUMENT

1/4" = 1'-0"1

MAIN LEVEL REMODELING PLAN - LIGHTING

PLAN NOTES:

TO NEAREST AVAILABLE 120V RECEPTACLE

CIRCUIT.

WALL MOUNT AT 7' AFF.

CONNECT VESTIBULE LIGHT TO OUTDOOR LIGHTING

FOR CONTROL VIA PHOTOCELL.

MOUNT CENTER OF FIXTURE AT 16'-4".

MOUNT CENTER OF FIXTURE AT 9'-0".

MOUNT CENTER OF FIXTURE AT 12'-0".

MOUNT FIXTURE BELOW PIPE RACKING, COORDINATE

WITH MECHANICAL CONTRACTOR.

MOUNT FIXTURE TO BOTTOM OF CATWALK SYSTEM.

PROVIDE PHOTOCELL TO CONTROL OUTDOOR LIGHTING

AND OTHER FIXTURES AS NOTED.

COORDINATE EXACT PLACEMENT OF LIGHT FIXTURES WITH

MECHANICAL SYSTEMS IN THIS ROOM.

15-193 E4.DWG

N

OS

F2 V1

F3 F3

A1

A1

BOILER ROOM

BATHROOM

OFFICE

BOILER ROOM

H1 H1 H1 H1 H1

H1

H1 H1H1H1H1H1

H1 H1 H1 H1 H1

H1

D

TO SWITCH BELOW,

SEE SHEET E4

EB101N3-2

EB101N3-4

EM

EM

EM EM

EM

EM

4 4

EM

F3 F3

UPPER LEVEL

F3 F3

F3 F3

16'AFF (TYP)

2 HOUR RATED WALL

UPPER

MEZZANINE

F1F1

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :2

P

M

E5 437-14-112

REPLACE BOILER PLANT 10.26.18

UPPER LEVEL REMODELING

PLAN - LIGHTING

100% CONSTRUCTION DOCUMENT

1/4" = 1'-0"1

UPPER LEVEL REMODELING PLAN - LIGHTING

1/4" = 1'-0"2

UPPER MEZZANINE REMODELING PLAN - LIGHTING

PLAN NOTES:

TO UPPER MEZZANINE LIGHTING, SEE 2/E5 FOR CONTINUATION.

TO LIGHTING ON MEZZANINE BELOW, SEE 1/E5 FOR CONTINUATION.

TO SWITCH BELOW, SEE 1/E5 FOR CONTINUATION.

MOUNT TO CEILING STRUCTURE ABOVE CATWALK.

15-193 E5.DWG

N

48"

J

J

G

WP

48"

48"

32 33

EX

48"

1 2 3

EX

G

G G

48" 48"

G

WP

AC

G

J

AC

G

G

G

WP

G

WP

G

WP

G

WP

G

WP

G

WP

G

WP

G

WP

EWC

G

G

WP

48" 48"

G

WP

G

WP

G

WP

J

J

J

EX

22 23 24

G

WP

G

WP

48"

J

BOILER ROOM

ELECTRICAL

VESTIBULE

SHOP

GENERATOR

ROOM

STORAGE

CLOSET

HOUSEKEEPING

CLOSET

OFFICE/CONTROL

LOCKER ROOM

LOWER LEVEL

SHOP ALCOVE

105A

EB101N1EB101N2EB101N3

FACP

T10-LV1

EXISTING EMERGENCY

DOMESTIC WATER PUMPS

EXISTING

FAN

CHEMICAL

PUMPS

EXISTING

TRANSFER

PUMPS

BOILER B-1 BOILER B-2 BOILER B-3

ANN

EXISTING GENSET

ANNUNCIATORS

AC

MOA

AC

MOA

REF

MICRO

NEW DAY

TANK AND

PUMPS

10-SWBD

ANN

NEW GENSET

ANNUNCIATOR

EB101N1-13,15

EB101N1-20,22

EB101N1-33

EB101N1-16,18

EB101N1-4

EB101N1-10,12,14

EB101N1-8

EB101N1-27

EB101N1-21,23,25

21 2123 2325 25 21

EB101N1-2

EB101N1-45

EB101N1-47

EB101N1-1,3

EB101N1-6

EB101N1-35,37

EB101N1-19

48" 48" 48"

48" 48"

48" 48"

SALVAGED

FEEDWATER

PUMPS

P-1 AND P-2

EB101N1-49,51

48"

48"

48"

TK-01

SP-1

HTP-01

WH-2

UNDER COUNTER

ST-1

IN PIT BELOW

WH-3

WH-4

DA-1

BATTERY

CHARGER

EB101N2-11

EB101N2-13,15,17

EB101N3-19,21,23 (3)#10,#10G IN 3/4"C.

ANNANNANN

EB101N1-7,9,11

EB101N1-43

11 2

4949 51

37 35

EXHAUST FAN VFDS

AC

AC

EB101N2-35

EXISTING

VFD

EXISTING

VFD

EF-1 EF-2 EF-3

EB101N1-5

3 1

1616 1818

EF-5

BOILER COMPRESSR BC-1 BOILER COMPRESSR BC-2 BOILER COMPRESSR BC-3

P1 P2

P1

P2

EB101N2-39

EB10N1-34

EB101N1-36

DP-01

16 16

P-3

P-4

P-6 P-7

EB101N1-38

GENERATOR

REMOTE

E-STOP BUTTON

P-8

P-9

EF-6

BELOW LANDING

AC

SEE SHEET E2 FOR CONTINUATION

SEE SHEET E2 FOR CONTINUATION

400KW GENERATOR

EXHAUST FAN EF-5

ECM CONTROLLER

EB101N1-38

EB101N1-40

EB101N1-48

1 HOUR RATED WALL

2 HOUR RATED WALL

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :2

P

M

E6 437-14-112

REPLACE BOILER PLANT 10.26.18

MAIN LEVEL REMODELING PLAN

- POWER

100% CONSTRUCTION DOCUMENT

1/4" = 1'-0"1

MAIN LEVEL REMODELING PLAN - POWER

PROVIDE NEW MOA, SEE SECTION 26 27 26 WIRING

DEVICES.

PROVIDE 3/4" PLYWOOD BACKBOARD FROM FLOOR

TO 8'AFF, PAINT WITH TWO COATS FIRE RETARDANT

PAINT. DO NOT PAINT OVER UL LABEL.

PROVIDE SEPARATE 120V CIRCUIT FOR AIR

COMPRESSOR CONTROL RELAYS AND ADJACENT AIR

DRYER.

NEW UNDERGROUND FEEDER CONDUITS, SEE SHEET

E2 AND DETAIL 2/E10 FOR REQUIREMENTS.

CUT AND PATCH EXISTING CONCRETE FLOOR AS

REQUIRED FOR INSTALLATION OF NEW CONDUITS,

ROUTE SHOWN IS APPROXIMATE, COORDINATE WITH

HOLDOUTS ON ELECTRICAL EQUIPMENT.

NEW 400 KW GENERATOR, SEE ONE LINE DIAGRAM

ON E13 FOR WIRING REQUIREMENTS. MAXIMUM

DIMENSIONS ON GENERATOR ARE 138 INCHES LONG

BY 65 INCHES WIDE. BASIS OF DESIGN IS

CATERPILLAR E13 SERIES.

CIRCUIT BREAKERS REQUIRED TO BE MOUNTED ON

NORTH SIDE OF GENSET.

WATER JACKET HEATER, FIELD COORDINATE EXACT

LOCATION ON GENSET.

PROVIDE 120V CONNECTION TO MASTER CONTROL

PANEL, COORDINATE WITH MECHANICAL.

RECONNECT EXISTING COMPRESSOR THROUGH NEW

DISCONNECT TO CIRCUIT INDICATED.

RECONNECT EXISTING AIR DRYER THROUGH NEW

DISCONNECT TO CIRCUIT INDICATED.

PROVIDE 120V CONNECTION FOR REINSTALLATION

OF EXISTING UNDERGROUND TANK MONITORING

SYSTEM CONTROL PANEL, RECONNECT EXISTING

ALARMS AND MONITORING DEVICES AND REINSTALL

ALL EQUIPMENT.

ALL ELECTRICAL CONDUIT TO BE CONCEALED IN THIS

ROOM, CUT AND PATCH EXISTING WALLS AS

REQUIRED FOR INSTALLATION OF NEW DEVICES.

PROVIDE EQUAL TO ASCO MTS SERIES MANUAL

TRANSFER SWITCH WITH TEMPORARY GENERATOR

CONNECTIONS, SWITCHED NEUTRAL, NEMA 3R

ENCLOSURE,INTEGRAL QUICK CONNECT CAMLOCK

CONNECTIONS. SEE 2/E10 FOR WIRING

REQUIREMENTS.

15-193 E6.DWG

N

AS NOTED

PLAN NOTES:

1 PROVIDE 120V CONNECTION ON DEDICATED

20A CIRCUIT TO ELECTRIC DOOR LOCKING

HARDWARE POWER SUPPLIES, COORDINATE

WITH HARDWARE SUPPLIER FOR EXACT

QUANTITY OF POWER SUPPLIES TO BE USED.

PROVIDE 120V CONNECTION ON DEDICATED

20A CIRCUIT TO INTRUSION DETECTION

SYSTEM EQUIPMENT.

PROVIDE NEW STARTER/DISCONNECTS AND RECONNECT

SALVAGED PUMPS, SEE MOTOR AND EQUIPMENT SCHEDULE

FOR ADDITIONAL INFORMATION.

PROVIDE 120V CONNECTION WITH

DISCONNECT TO ELECTRIC COOKTOP.

PROVIDE RECEPTACLE AT SHELF LOCATION

FOR MICROWAVE, COORDINATE EXACT

MOUNTING HEIGHT WITH CASEWORK

ELEVATIONS.

PROVIDE 120V CONNECTION TO MEDGAS

ALARM PANEL, COORDINATE WITH MECHANICAL

CONTRACTOR.

PROVIDE DEDICATED 20 CIRCUIT FOR FIRE ALARM

CONTROL PANEL.

CONNECT EXISTING RELOCATED FUEL OIL PUMPS, PROVIDE

WITH NEW STARTERS, SEE MOTOR AND EQUIPMENT

SCHEDULE FOR ADDITIONAL INFORMATION.

PROVIDE 120V CONNECTION OF DEDICATED CIRCUIT

FOR CARD ACCESS SYSTEM CONTROL PANELS.

(3)#6,#10G IN 1" CONDUIT.

PROVIDE 120V CONNECTION TO DANGEROUS

GAS DETECTION SYSTEM CONTROL PANEL, COORDINATE

WITH MECHANICAL CONTRACTOR.

RECIRCUIT EXISTING PUMPS THROUGH EXISTING WALL

MOUNTED DISCONNECTS TO NEW PANEL SHOWN.

PROVIDE SINGLE POINT 208V/1 PHASE CONNECTION TO

SUMP CONTROL PANEL PER MOTOR AND EQUIPMENT

SCHEDULE. PROVIDE SEPARATE 120V CIRCUUIT FOR

AUDIBLE ALARM AS NOTED ON THE PLANS.

RECIRCUIT EXISTING PUMPS THROUGH EXISTING FLOOR

MOUNTED VFDS TO NEW PANEL, SEE MOTOR AND

EQUIPMENT SCHEDULE FOR PANEL AND CIRCUIT NUMBER.

AC

G

J

BOILER ROOM

UPPER LEVEL

BATHROOM

OFFICE

EXISTING

DATA

RACK

EXISTING

VISN

METERS

EB101N1-27,29,31

PAGING

RACK

EB101N1-39,41

EB101N1-53

EB101N1-37

EF-1

EF-2

EF-3

AH-1

EF-4

AH-2

48"

48"

EB101N1-26

SS-2

2 HOUR RATED WALL

TO PLATFORM ABOVE

48"

VIDEO SURVELLANCE

RACK

UPPER

MEZZANINE

SS-1

WH-1

TO OFFICE BELOW

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :2

P

M

E7 437-14-112

REPLACE BOILER PLANT 10.26.18

UPPER LEVEL PLAN - POWER

100% CONSTRUCTION DOCUMENT

1/4" = 1'-0"1

UPPER LEVEL REMODELING PLAN - POWER

1/4" = 1'-0"2

UPPPER MEZZANINE LEVEL REMODELING PLAN - POWER

PLAN NOTES:

1 WIRING BETWEEN CONDENSING UNIT AND EVAPORATOR

UNITS BY MECHANICAL CONTRACTOR.

PROVIDE (2) 20A/120V CIRCUITS FOR EXISTING VISN METERS,

RECONNECT (7) EXISTING METER DISCONNECTS, ALTERNATE CIRCUIT

BETWEEN EACH DISCONNECT.

15-193 E7.DWG

N

S

S F

S

CR

F S

CR

CR

S

F

S

S

FA ANNUN

S

S

S F

S

CR

H

A

A

A

A

F

S

GENERATOR

ROOM

SHOP

LOCKER ROOM

OFFICE/CONTROL

BOILER ROOM

LOWER LEVEL

ELECTRICAL

16' AFF

16' AFF

CARD ACCESS PANEL

INTRUSION DETECTION PANEL

8' AFF

(LOWER

LEVEL)

9' AFF

9' AFF

9' AFF

P P

9' AFF

9' AFF

P

P

A

9' AFF

9' AFF

A

A

IC

M3

16' AFF

AC

AC

MS

W

A

A

A

A

IC

P

EXISTING TELEPHONE

BLOCKS

A

A

9' AFF

P

16' AFF

A

FIRE SPRINKLER TAMPER

AND FLOW SWITCHES

MS

MS

MS

MS

MS

A

A

P

A

A

A6

EXISTING FIBER PULLBOX

AP

AP

AP

AP

TO MEZZANINE LEVEL

9' AFF

FS TS 5

WP

12' AFF

CLG

TS

W

S

S

S

S

S

FACP

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12' AFF

12'

12'

W

W

K

K

K

K

K

S

S

12' AFF 13

12' AFF

TR

TR

TR

TR

TR

8'AFF

8'AFF

TR

TR

KP

KP

KP

KP

WALLS IN GENERATOR ROOM

HAVE A 1 HOUR RATING

1 HOUR RATED WALL

2 HOUR RATED WALL

9'AFF

A

CLG

A

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :3

P

M

E8 437-14-112

REPLACE BOILER PLANT 10.26.18

MAIN LEVEL REMODELING PLAN

- SYSTEMS

100% CONSTRUCTION DOCUMENT

1/4" = 1'-0"1

MAIN LEVEL REMODELING PLAN - SYSTEMS

REINSTALL EXISTING ACCESS POINT IN NEW CEILING GRID.

PROVIDE NEW PAGING HORN, CONNECT TO EXISTING BOILER

PAGING ZONE.

PROVIDE ADDRESSABLE FIRE ALARM MODULE AND

ASSOCIATED CONNECTIONS TO EXTERIOR POST INDICATOR

VALVE TO MONITOR VALVE POSITION, PROGRAM TO

GENERATE TROUBLE CONDITION ON FACP WHEN VALVE IS

CLOSED.

INSTALL SALVAGED FIRE PHONE, AND CONNECT TO NEW FIRE

PHONE ALERT SPEAKER.

PROVIDE TELEPHONE AUDIOV/VISUAL SOUNDER EQUAL TO

WHEELOCK UTA SERIES REMOTE RINGER, CONNECT TO FIRE

PHONE FOR REMOTE ANNUCIATION OF RINGER, PROVIDE

REMOTE POWER SUPPLY AS REQUIRED.

PROVIDE NEW SIMPLEX FIRE ALARM PANEL PER SECTION 28

3100, CONNECT TO EXISTING VA CAMPUS SIMPLEX MAPNET

NETWORK CONNECTION IN THIS BUILDING.

PROVIDE KEYED SWITCH WITH CYLINDER TO MATCH VA

MASTER KEYING SYSTEM, CONNECT TO CARD ACCESS

SYSTEM TO SHUNT DOOR POSITION SWITCH TO ALLO

EXTENDED HOLD OPEN.

PROVIDE INTRUSION DETECTION SYSTEM KEYPAD, SEE

DETAIL 10/E12 FOR ADDITIONAL INFORMATION.

15-193 E8.DWG

N

AS NOTED

GENERAL NOTES:

1. ALL PAGING SYSTEM WIRING, SECURITY SYSTEM WIRING, AND

CAMERA WIRING TO BE IN MINIMUM 3/4" CONDUIT, ORANGE IN

COLOR.

2. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN MINIMUM 3/4"

CONDUIT, RED IN COLOR.

3. ALL DATA/TELEPHONE WIRING SHALL BE IN MINIMUM 3/4"

CONDUIT, ORANGE IN COLOR, WHERE EXPOSED TO VIEW OR

ROUTED ACROSS OPEN SPACES.

PLAN NOTES:

1 PROVIDE EQUAL TO AIPHONE JP-DV SERIES SURFACE

MOUNTED. VANDAL PROOF VIDEOINTERCOM SYSTEM.

PROVIDE WITH EXTERNALSIGNALING RELAY TO ACTIVATE

INTERNAL

DOORBELL SOUNDERS.

PROVIDE EQUAL TO AIPHONE JPS SERIES 7 INCH VIDEO

INTERCOM MASTER STATION, DESKTOP MOUNTING, CONNECT

TO EXTERIORDOOR INTERCOM STATION, SEE PLAN NOTE #1.

PROVIDE CONNECTION FROM MASTERSTATION TO RELEASE

ELECTRIC DOORHARDWARE ON EXTERIOR DOOR ADJACENT

TO THE EXTERIOR INTERCOM.

PROVIDE CARD ACCESS AND DOOR MONITORING EQUIPMENT,

SEE DETAIL 9/E12 FOR TYPICAL ROUGH IN AND WIRING

REQUIREMENTS.

PROVIDE DOOR POSITION MONITORING AT THIS DOOR,

CONNECT TO ALARM ANNUNCIATOR PANEL IN CONTROL

ROOM 103.

INTRUSION DETECTION ALARM .DOOR ALARM TO SOUND UPON

DOOR FORCE OR DOOR PROP ALARM, VALID CARD SWIPE OR

KEYPAD CODE ENTRY SHALL DEACTIVATE ALARM.

PROVIDE 3/4” CONDUIT FROM CAMERA TO VIDEO

SURVEILLANCE SYSTEM RACK ON MEZZANINE LEVEL FOR

VIDEO SURVEILLANCE CAMERA. MOUNT CAMERA AT HEIGHT

INDICATED OR TO CEILING STRUCTURE BOTTOM WHERE

NOTED.

REINSTALL AND RECONNECT SALVAGED SPEAKER TO

EXISTING SPEAKER WIRING.

PROVIDE CEILING MOUNTED MOTION SENSOR,

CONNECT TO INTRUSION DETECTION SYSTEM PANEL IN 3/4"

CONDUIT.

PROVIDE DATA JACK AT BOILER PLANT MASTER CONTROL

PANEL, COORDINATE WITH MECHANICAL CONTRACTOR.

PROVIDE CABLING IN 3/4" CONDUIT TO MEZZANINE DATA

RACK.

INSTALL DEVICE IN LOWER LEVEL UNDERNEATH STAIR

STRUCTURE NEAR STEAM TUNNEL ENTRANCE.

PROVIDE WEATHERPROOF FIRE ALARM HORN/STROBE ABOVE

FIRE DEPARTMENT CONNECTION. PROGRAM TO ACTIVATE

UPON SPRINKLER SYSTEM FLOW.

S S S

F

BATHROOM

OFFICE

UPPER LEVEL

IC

M

9' AFF

EXISTING

DATA RACK

2 2

AP

A

TO LOWER LEVEL

J

A

CLG CLG

CLG

CLG

CLG

DS

DS

DS

DS

S

S S S

S

J

J

S

2 HOUR RATED WALL

PAGING RACK

VIDEO SURV. RACK

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :3

P

M

E9 437-14-112

REPLACE BOILER PLANT 10.26.18

UPPER LEVEL REMODELING

PLAN - SYSTEMS

100% CONSTRUCTION DOCUMENT

1/4" = 1'-0"1

UPPER LEVEL REMODELING PLAN - SYSTEMS

PLAN NOTES:

1 PROVIDE EQUAL TO AIPHONE JPS SERIES 7 INCH VIDEO INTERCOM

STATION, DESKTOP MOUNTING, CONNECT TO EXTERIOR DOOR

STATION. PROVIDE CONNECTION TO RELEASE ELECTRIC DOOR

LOCK FROM MASTER STATION.

REINSTALL SALVAGED PUBLIC ADDRESS SYSTEM SPEAKER.

INSTRUSION DETECTION SYSTEM AUDIBLE ALARM. DOOR ALARM TO

SOUND UPON DOOR FORCE OR DOOR PROP ALARM, VALID CARD

SWIPE OR KEYPAD CODE SHALL DEACTIVATE ALARM.

PROVIDE (2) 2" CONDUITS FOR NEW COMMUNICATIONS CABLING,

ROUTE ADJACENT TO MECHANICAL PIPING.

ROUTE COMMUNICATIONS CONDUITS DOWN WALL INTO EXISTING

DATA CABINET.

ROUTE COMMUNICATIONS CONDUIT DOWN WALL AND STUB INTO

ACCESSIBLE CEILING SPACE IN CONTROL OFFICE BELOW.

MOUNT REMOTE TEST SWITCH FOR DUCT DETECTORS IN

ACCESSIBLE SPACE ABOVE CATWALK, FIELD COORDINATE EXACT

LOCATION.

PROVIDE TELEPHONE AUDIOV/VISUAL SOUNDER EQUAL TO

WHEELOCK UTA SERIES REMOTE RINGER, CONNECT TO FIRE

PHONE FOR REMOTE ANNUCIATION OF RINGER, PROVIDE REMOTE

POWER SUPPLY AS REQUIRED.

PROVIDE DUCT SMOKE DETECTOR IN SUPPLY AND RETURN WITH

CONNECTION TO FAN SHUTDOWN RELAY.

15-193 E9.DWG

N

AS NOTED

GENERAL NOTES:

1. ALL PAGING SYSTEM WIRING, SECURITY SYSTEM WIRING,

AND CAMERA WIRING TO BE IN MINIMUM 3/4" CONDUIT,

ORANGE IN COLOR.

2. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN MINIMUM 3/4"

CONDUIT, RED IN COLOR.

3. ALL DATA/TELEPHONE WIRING SHALL BE IN MINIMUM 3/4"

CONDUIT, ORANGE IN COLOR, WHERE EXPOSED TO VIEW OR

ROUTED ACROSS OPEN SPACES.

J

A -3

P

EXISTING BUILDING 10

SWITCHGEAR MAIN SWITCH

480V

BUILDING 10

GENERATOR

300 kVA

BUILDING 10

SWITCHBOARD

480V, 800A

BUILDING

10 ATS

XFMR

101C2,

45.0 kVA

PANEL

101C2

WELDING

XFMR,

15.0 kVA

WELDING

PANEL

240V

PANEL

101W2

G

500A-3P

A -3

P

A -3

P

PANEL

101W1 480V

MCC10

480V

A -3

P

XFMR

T-101C1

30 kVA

A -3

P

A -3

P

A -3

P

BLDG

PANEL

AIR COOLED CHILLER ACCH-4

SWITCH

SECTIONALIZINGSECTIONALIZING

SWITCH

EXISTING

SAC-2SAC-1

23.9KV

XCEL SOURCE #3

150E 150E

23.9KV

XCEL SOURCE #4

M

- EPDM STRESS

CONE TERMINATIONS

- ELBOW TERMINATIONS

- FUSE

- SWITCH

- TRANSFORMER

- METER

- CURRENT TRANSFORMER

- POTENTIAL TRANSFORMER

EXISTING

25KV SERVICE

DISCONNECT

SWITCHGEAR

WITH METERING

SS-SOUTH

25E

SWITCH

SECTIONALIZING

S56-1

50E50E

PULL BOX

CHILLER PLANT FEED#1 CHILLER PLANT FEED#2

ADD FUSE

EXISTING VAULT

EXISTING

50E

T10-1

BOILER PLANT FEED #1 -SEE 2/E10

T10-2

BOILER PLANT FEED #2 -SEE 2/E10

50E

SWITCH

SECTIONALIZING

S10-1

NEW

TO SPARE OUTPUT

800A-3P

KIRK KEY

INTERLOCK

SEE

1/E12

K K KDRAW OUT

800A-3P

LSIG

DRAW OUT

800A-3P

LSIG

T10-LV1

150 KVA-480V

KV-PRI 120/208-SEC

A

-3 P

PANEL

EB101N3

(4 )3

/0

G

N D

I N

"C

SPD

A

-3 P

KIRK KEY

INTERLOCK

LSIG 2

A -3

P

A

-3 P

A -3

P

A

-3 P

A

-3 P

A -3

P

PANEL

EB101N1

PANEL

EB101N2

SPD

BOILER

A

-3 P

BOILER

INTEGRAL ATS -

OPEN TRANSITION

(4) 3/0+#6 GND

IN 2"C.

BLDG

PANEL

(4

G N

D I N

C

A -3

P

A -3

P

INTEGRAL ATS -

OPEN TRANSITION

G

DETAIL NOTES:

(4) 3/0+#6 GND

IN EACH OF (2)

2"C.

DETAIL NOTES:

(4) 300MCM IN EACH OF (3) 3 "

C.

(4) 300MCM +1/0G

IN EACH

OF(3) 2 1/2"

C.

(4

G

N D

I N

C

T10-LV2

30 KVA-480V

KV-PRI

120/208-SEC

BOILER

A

-3 P

ST-1

A

-3 P

A

-3 P

A -3

P

A

-3 P

A

-3 P

A

-3 P

AH-1

A

-3 P

AH-2

A

-3 P

A

-3 P

A -3

P

EF-1EF-2

A

-3 P

EF-3

A

-3 P

- DASHED INDICATES EXISTING EQUIPMENT OR WIRING

- SOLID LINE INDICATES NEW EQUIPMENT OR WIRING

#1 #3 #2WH-3

A -3

P

WH-4

DA-1

HPT-01

S P

A R

E

BOILER PLANT

FEED #1

SEE 3/E10 FOR

CONTINUATION

S P

A R

E

SEE1/E12

SWBD-10

KIRK KEY

INTERLOCK

800 AMPERES, 480/277V, 3 PH, 4 WIRE, 65,000 AIC

S P

A R

E

BOILER PLANT

FEED #2

SEE 3/E10 FOR

CONTINUATION

S P

A R

E

SWITCH

SECTIONALIZING

S56-2

EXISTING

A

-3 P

S P

A R

E

A

-3 P

S P

A R

E

A

-3 P

S P

A R

E

A

-3 P

S P

A R

E

PROVIDE TEMPORARY POWER TO BUILDING 50 PANEL

VIA EXISTING BURIED CONDUIT DURING CONSTRUCTION

OF NEW BUILDING 10 SERVICE. RETAIN EXISTING

TRANSFORMER T-101C1 AND PANEL 101C1 DURING

CONSTRUCTION FOR TEMPORARY CONNECTION OFF OF

EXISTING BUILDING #10 SWITCHGEAR. REMOVE WHEN

NEW SYSTEM IS OPERATIONAL.

DISCONNECT THE EXISTING 25KV FEEDER THAT IS

CURRENTLY CONNECTED TO S56-2, PULL BACK INTO

THE ADJACENT VAULT, AND RECONNECT INTO NEW

SWITCH S10-1.

PROVIDE NEW 25KV FEED INTO S56-2 FROM NEW

SWITCHGEAR S10-1, QUANTITY (3) 4/0 CU 25KV ,

4/0 CU 600V NEUTRAL IN 4" CONDUIT.

QTY (3) 4/0 CU 25 KV, 4/0 CU 600V NEUTRAL IN

EXISTING 4" CONDUIT

480V/277

3-PHASE

T10-1

750 KVA

23.9 KV-PRI

277/480-SEC

(3

G N

D

IN

/4

C

SEE MOTOR AND EQUIPMENT SCHEDULE FOR WIRING AND

CONDUIT REQUIREMENTS.

DETAIL NOTES:

T10-2

750 KVA

23.9 KV-PRI

277/480-SEC

(4) 300MCM IN EACH

OF (3) 3 " C.

(3

G N

D

IN

/4

C

(4

G

N D

IN

C

(4

/0

G N

D I N

"C

EXISTING 25KV SERVICE

DISCONNECT SWITCHGEAR

WITH METERING

SS-NORTH

1. PROVIDE CONTINUOUS RUNS OF 25 KV WIRING,

SPLICING IN VAULTS IS NOT ALLOWED.

DETAIL GENERAL NOTES:

(4) 300MCM IN EACH

OF (3) 3 " C.

(4) 300MCM IN EACH

OF (3) 3 " C.

EXISTING

PULLBOX

TO 5 KV

SERVICE

T10

BOILER

PLANT

500 KVA

PANEL

101C1

400KW GENERATOR

EXISTING BUILDING #10 TRANSFORMER TO REMAIN

OPERATIONAL DURING CONSTRUCTION TO PROVIDE

POWER TO TEMPORARY BOILERS, PUMPS, BUILDING

#50, AND OTHER TEMPORARY CONSTRUCTION

POWER REQUIREMENTS. REMOVE TRANSFORMER AND

PAD AFTER INSTALLATION AND TESTING OF

PERMANENT SYSTEMS. SEE DETAIL 4/E2.

(4) 300MCM +1/0G

IN EACH OF (3) 2 1/2"

C.

TEMP

GENSET

INLET

TEMP

GENSET

MANUAL

SWITCH

S P

A R

E

(4) 300MCM +1/0G

IN EACH

OF(3) 2 1/2"

C.

PROVIDE EQUAL TO ASCO MTS SERIES MANUAL TRANSFER

SWITCH FOR TEMPORARY GENERATOR CONNECTIONS,

SWITCHED NEUTRAL, NEMA 3R ENCLOSURE,INTEGRAL QUICK

CONNECT CAMLOCK CONNECTIONS. MOUNT ON EXTERIOR

WALL PER FLOORPLANS.

L S

I

L S

I

THE EXISTING GENERATOR AND ATS MAY STAY IN PLACE

TO PROVIDE EMERGENCY POWER TO THE TEMPORARY

BOILER DURING CONSTRUCTION. CONTRACTOR SHALL

PROVIDE A TEMPORARY OUTDOOR GENERATOR WHEN THE

EXISTING GENSET IS REMOVED UNTIL THE NEW BOILER

SYSTEM IS OPERATIONAL.

1 3 2

BUILDING 10 ELECTRICAL ONE-LINE DIAGRAM- DEMOLITION

NO SCALE

E1025 KV ONE LINE DIAGRAM - REVISED

NO SCALE

E10

BUILDING 10 ELECTRICAL ONE-LINE DIAGRAM

NO SCALE

E10

411 1226179 18

105 13

11111 1 1 1 1 1 1 1 1

T56-1

M

25E 25E 25E

M

25E

T56-2 T56-3

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :3

P

M

E10 437-14-112

REPLACE BOILER PLANT 10.26.18

ELECTRICAL ONE-LINE

DIAGRAMS

100% CONSTRUCTION DOCUMENT

6515-193 E10.DWG

EB101N1 MCB 400A NEMA 1 107

208Y/120, 3 PH., 4W.

400 AMP 10,000 SURFACE SWBD

CKT

TRIP

AMPS

POLE

LOAD IN VOLT-AMPERES LOAD

DESCRIPTION

PH LOAD DESCRIPTION

LOAD IN VOLT-AMPERES TRIP

AMPS

POLE

CKT

#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING

1 20 1 1000 EXT.REC A LOCKER ROOM 400 20 1 2

3 20 1 600 EXT.REC B 103 1000 20 1 4

5 20 1 800 102 REC C 103 1200 20 1 6

7 20 1 1600 CARD ACCESS A MICROWAVE 1600 *20 1 8

9 20 1 1600 PWR SUPPLY B REF 1200 *20 1 10

11 20 1 1600 IDS SYSTEM C COOKTOP 1600 20 1 12

13 20 1 400 SHOP REC A 103 200 20 1 14

15 20 1 400 SHOP REC B WEST EXT.REC 400 20 1 16

17 20 1 400 SHOP REC C WEST EXT.REC 400 20 1 18

19 20 1 400 SHOP REC A 001 REC 600 20 1 20

21 20 1 400 SHOP REC B 101 REC 800 20 1 22

23 20 1 400 SHOP REC C DAY TANK PUMPS 1600 20 1 24

25 20 1 400 SHOP REC A CATWALK REC 800 20 1 26

27 20 1 800 OFFICE 202 B TUNNEL LIGHTS 1400 20 1 28

29 20 1 1200 IT RACK C SUMP PUMP 1664 15 30

31 20 1 1200 PAGING RACK A 2 32

33 20 1 1000 101 REC B SUMP ALARM 600 20 1 34

35 20 1 1000 MEDGAS C EXT. RECEPT 600 20 1 36

37 20 1 1000 GAS DET. A MASTER CONTROL 1200 20 1 38

39 20 1 400 VISN METERS B TANK MONITORING 1200 20 1 40

41 20 1 400 VISN METERS A SPARE 15 42

43 20 1 1600 FACP B 44

45 20 1 1200 106,107 C 3 46

47 20 1 1200 001 REC A AIR DRYER 20 1 48

49 20 1 400 CHEM.PUMPS B PANEL 101N2 16525 200 50

51 30 SPARE C 19885 52

53 2 A 18505 3 54

55 20 1 SPARE B SPARE 20 50

57 20 1 SPARE C 52

59 20 1 SPARE A 3 54

61 20 1 SPARE B SPARE 20 1 50

63 20 1 SPARE C SPARE 20 1 52

65 20 1 SPARE A SPARE 20 1 54

LOAD TYPE

VA / PHASE TOTAL

VA

DEMAND

FACTOR

DIVERSIFIED

LOAD

NOTES:

A B C 1. BREAKERS NOTED WITH * TO BE GFCI

LIGHTING 0 1400 0 1400 1.00 1400

RECEPTACLES 10200 9400 8200 27800 0.50 13900

MOTORS & EQUIP 19125 22085 24369 65579 0.90 59021

KITCHEN EQUIP. 0 0 0 0 0.65 0

HEAT / AC 0 0 0 0 0.90 0

LARGEST MOTOR 0.25 0

TOTAL AMPS: 206 TOTAL VA: 74,321

PANELBOARD LOAD SCHEDULE

PANEL: MAIN: ENCLOSURE: LOCATION:

VOLTS:

RATING: AIC RATING: MOUNTING: FED FROM:

LOAD CALCULATIONS

EB101N2 MLO NEMA 1 107

208Y/120, 3 PH., 4W.

225 AMP 10,000 SURFACE 101N1

CKT

TRIP

AMPS

POLE

LOAD IN VOLT-AMPERES LOAD

DESCRIPTION

PH LOAD DESCRIPTION

LOAD IN VOLT-AMPERES TRIP

AMPS

POLE

CKT

#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING

1 20 1 400 EF-4 A SS-1 2080 30 2

3 40 3000 WH-1 B 2080 2 4

5 2 3000 C SS-2 2080 30 6

7 40 3000 WH-2 A 2080 2 8

9 2 3000 B SUMP PUMP 1300 30 10

11 20 1 1500 BATT.CHARGER C 1300 2 12

13 60 4800 JACKET HTR A HTP-01 2105 15 14

15 4800 B 2105 16

17 3 4800 C 2105 3 18

19 15 830 EX.PUMP P-1 A SPARE 40 20

21 830 B 22

23 3 830 C 3 24

25 15 830 EX.PUMP P-2 A SPARE 15 26

27 830 B 28

29 3 830 C 3 30

31 20 1 720 EF-5 A SPARE 15 32

33 20 1 600 DP-01 B 34

35 20 1 1600 EX. AIR DRYER C 3 36

37 20 1 REC -101 A SPARE 15 38

39 20 1 1600 EX. EXHAUST B 40

41 20 1 720 EF-6 A 3 42

43 20 1 SPARE B SPARE 20 44

45 20 1 SPARE C 2 46

47 20 1 SPARE A SPARE 20 48

49 20 1 SPARE B 2 50

51 20 1 SPARE C SPARE *20 1 52

53 20 1 SPARE C SPARE *20 1 54

LOAD TYPE

VA / PHASE TOTAL

VA

DEMAND

FACTOR

DIVERSIFIED

LOAD

NOTES:

A B C 1. BREAKERS NOTED WITH * TO BE GFCI

LIGHTING 0 0 0 0 1.00 0

RECEPTACLES 0 0 0 0 0.50 0

MOTORS & EQUIP 16845 20145 18765 55755 0.90 50180

KITCHEN EQUIP. 0 0 0 0 0.65 0

HEAT / AC 0 0 0 0 0.90 0

LARGEST MOTOR 0.25 0

TOTAL AMPS: 139 TOTAL VA: 50,180

PANELBOARD LOAD SCHEDULE

PANEL: MAIN: ENCLOSURE: LOCATION:

VOLTS:

RATING: AIC RATING: MOUNTING: FED FROM:

LOAD CALCULATIONS

EB101N3 MLO NEMA 1 107

480Y/277, 3 PH., 4W.

225 AMP 25,000 SURFACE SWBD-10

CKT

TRIP

AMPS

POLE

LOAD IN VOLT-AMPERES

LOAD DESCRIPTION PH LOAD DESCRIPTION

LOAD IN VOLT-AMPERES TRIP

AMPS

POLE

CKT

#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING

1 20 1 1992 MAIN LVL LTG A 101 LTG -HIGH BAY 2988 20 1 2

3 20 1 539 001 LTG B MEZZ LEVEL LTG 1240 20 1 4

5 20 1 294 102 LTG C SPARE 20 1 6

7 20 1 735 LTG -S. INT A EXISTING WTR.PUMP 3047 15 8

9 20 1 392 EXT. LTG B 3047 10

11 20 1 882 101 LTG C 3047 3 12

13 20 1 343 EXT. LTG A SPARE 20 1 14

15 20 1 LTG - OFFICE/LOCK. B SPARE 20 1 16

17 20 1 SPARE C SPARE 20 1 18

19 30 3878 EX.AIR COMP A EXISTING TRAN.PUMP 2100 15 20

21 3878 B 2100 22

23 3 3878 C 2100 3 24

25 15 830 EX.FUEL PUMP P-6 A EXISTING TRAN.PUMP 15 26

27 830 B 28

29 3 830 C 3 30

31 15 EX.FUEL PUMP P-7 A EX.DOMES.WTR PUMP 2100 15 32

33 B 2100 34

35 3 C 2100 3 36

37 15 1216 BOILER COMPRESSOR A EX.DOMES.WTR PUMP 15 38

39 1216 B 40

41 3 1216 C 3 42

43 15 1216 BOILER COMPRESSOR A SPARE 30 44

45 1216 B 46

47 3 1216 C 3 48

49 15 1216 BOILER COMPRESSOR A SPARE 25 50

51 1216 B 52

53 3 1216 C 3 54

LOAD TYPE

VA / PHASE TOTAL

VA

DEMAND FACTORDIVERSIFIED LOAD

NOTES:

A B C 1. BREAKERS NOTED WITH * TO BE GFCI

LIGHTING 6058 2171 1176 9405 1.00 9405

RECEPTACLES 0 0 0 0 0.50 0

MOTORS & EQUIP 15603 15603 15603 46809 0.90 42128

KITCHEN EQUIP. 0 0 0 0 0.65 0

HEAT / AC 0 0 0 0 0.90 0

LARGEST MOTOR 0.25 0

TOTAL AMPS: 62 TOTAL VA: 51,533

PANELBOARD LOAD SCHEDULE

PANEL: MAIN: ENCLOSURE: LOCATION:

VOLTS:

RATING: AIC RATING: MOUNTING: FED FROM:

LOAD CALCULATIONS

M O T O R

N O

L O C A T I O N

R O O M

N O

L O A D

I N

H O R S E P O W E R

H P

O R

F U L L

L O A D

A M P S

F L A

V O L T A G E

P H A S E

P A N E L

A N D

C I R C U I T

N U M B E R

O R

M C C

N U M B E R

C O N D U C T O R

S I Z E

A N D

Q U A N T I T Y

G R O U N D

C O N D U C T O R

S I Z E

C O N D U I T

S I Z E

CONTROLLER DISCONNECT CONTROL OR AUXILIARY DEVICE (SEE

NOTES)

M A G N E T I C

S T A R T E R D I S C O N N E C T

S T A R T E R

S I Z E

V A R I A B L E

F R E Q U E N C Y

D R I V E

M A N U A L

M O T O R

C O N T R O L L E R

L O W

V O L T A G E

S W I T C H

O C C

S E N S O R

C O N T R O L L E R

B Y

D I V

N O

C O N T R O L L E R

L O C A T I O N

R O O M

N O O R

A S

N O T E D

D I S C O N N E C T

S I Z E

F U S I B L E

N O N

F U S I B L E

N E M A

R A T I N G

D I S C O N N E C T

B Y

D I V

N O

V F D

D E F I N I T E

P U R P O S E

R E L A Y

T I M E

S W I T C H

T H E R M O S T A T

L O W

V O L T A G E

S W I T C H

O C C

S E N S O R

F I R E

A L A R M

C O N T R O L

R E L A Y

F I R E

A L A R M

D U C T

D E T E C T O R S

S U P P L Y

A N D

R E T U R N

I N T E R L O C K

W I T H

1 BOILER B-1 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26

2 BOILER B-2 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26

3 BOILER B-3 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26

4 ST-1 101 3 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 ON UNIT ON UNIT

5 DA-1 101 10 HP 480, 3 SWBD-10 3 #10 #10 3/4" 23 ON UNIT ON UNIT

6 DAY TANK KIT TK-01 107 .5 HP 120, 1 EB101N1-24 2 #12 #12 3/4" 20A NF 1 26

7 WH-1 MEZZ 301 6 KW 208, 1 EB101N2-3,5 2 #8 #10 3/4" 23 BAS 60A NF 1 26

8 WH-2 105 6 KW 208, 1 EB101N2-7,9 2 #8 #10 3/4" 23 BAS 60A NF 1 26

9 WH-3 101 144 KW 480, 3 SWBD-10 3 #3/0 #6 2" 23 BAS ON UNIT

10 WH-4 105 144 KW 480, 3 SWBD-10 3 #3/0 #6 2" 23 BAS ON UNIT

11 AH-1 101 15 MCA 480, 3 SWBD-10 3 #10 #10 3/4" 23 BAS 30A F 30 1 26 3 1

12 AH-2 101 15 MCA 480, 3 SWBD-10 3 #10 #10 3/4" 23 BAS 30A F 30 1 26 3 1

13 HPT-01 101 5 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 BAS 30A NF 1 26

14 SPLIT SYSTEM SS-1 (CONDENSING UNIT) MEZZ 301 20 MCA 208, 1 EB101N2-2,4 2 #10 #10 3/4" ON UNIT

15 SPLIT SYSTEM SS-2 (CONDENSING UNIT) 101-UPPER LVL 20 MCA 208, 1 EB101N2-6,8 2 #10 #10 3/4" ON UNIT

16 M-EF-1 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 30A NF 1 26 3

17 M-EF-2 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 30A NF 1 26 3

18 M-EF-3 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 ON UNIT 3

19 M-EF-4 108- ROOF FRAC 120, 1 EB101N2-1 3 #12 #12 3/4" 23 BAS 20A NF 1 26

20 M-EF-5 102 -ROOF 1/2 HP 120, 1 EB101N2-31 3 #12 #12 3/4" 23 BAS ON UNIT

21 M-EF-6 107 1/4 HP 120, 1 EB10N2-41 2 #12 #12 3/4" 23 BAS 20A NF 1 26

22 BOILER COMPRESSOR BC-1 101 5 HP 480, 3 EB101N3-37,39,41 3 #12 #12 3/4" 23 ON UNIT ON UNIT

23 BOILER COMPRESSOR BC-2 101 5 HP 480, 3 EB101N3-43,45,47 3 #12 #12 3/4" 23 ON UNIT ON UNIT

24 BOILER COMPRESSOR BC-3 101 5 HP 480, 3 EB101N3-49,51,53 3 #12 #12 3/4" 23 ON UNIT ON UNIT

25 EXISTING FEEDWATER PUMP P-1 101 1.5 HP 208, 3 EB101N2-19,21,23 3 #12 #12 3/4" 1 26 101 ON STRT

26 EXISTING FEEDWATER PUMP P-2 101 1.5 HP 208, 3 EB101N2-25,27,29 3 #12 #12 3/4" 1 26 101 ON STRT

27 DIESEL PUMP DP-1 EXTERIOR. 4.9 AMP 120, 1 EB101N2-33 2 #12 #12 3/4" 26 101 20A NF 3R 26

28 EXISTING TRANSFER PUMP P-3 RM 001 3 HP 480, 3 EB101N3-20,22.24 3 #12 #12 3/4" EXISTING

29 EXISTING TRANSFER PUMP P-4 RM 001 3 HP 480, 3 EB101N3-26,28,30 3 #12 #12 3/4" EXISTING

30 EXISTING DOMESTIC WATER PUMP P-8 RM 001 7.5 HP 480, 3 EB101N3-32,34,36 3 #12 #12 3/4" EXISTING

31 EXISTING DOMESTIC WATER PUMP P-9 RM 001 7.5 HP 480, 3 EB101N3-38,40,42 3 #12 #12 3/4" EXISTING

32 EXISTING FUEL PUMP P-6 101 1.5 HP 480, 3 EB101N3-25,27,29 3 #12 #12 3/4" 1 26 101 ON STRT

33 EXISTING FUEL PUMP P-7 101 1.5 HP 480, 3 EB101N3-31,33,35 3 #12 #12 3/4" 1 26 101 ON STRT

34 SUMP PUMP SP-1 001-PIT 2 HP 208, 1 EB101N2-10,12 2 #10 #10 3/4" 23 ON UNIT 30A F 30 1 26

1. ELECTRICAL CONTRACTOR TO FURNISH, SET, AND WIRE AUXILIARY CONTROL DEVICE

2. ELECTRICAL CONTRACTOR TO SET, AND WIRE AUXILIARY CONTROL DEVICE FURNISHED BY OTHERS

3. ELECTRICAL CONTRACTOR TO WIRE AUXILIARY CONTROL DEVICE FURNISHED AND SET BY OTHERS

4. PROVIDE DUCT DETECTOR IN SUPPLY AND RETURN DUCTS AND CONNECT TO FA SYSTEM

MOTOR AND EQUIPMENT SCHEDULE

X

X

X

X

X

X

X

X

X

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :3

P

M

E11 437-14-112

REPLACE BOILER PLANT 10.26.18

ELECTRICAL SCHEDULES

100% CONSTRUCTION DOCUMENT

6615-193 E11.DWG

SPD

NOTE:

#6

48"

91.5"

36" 42" 36"42" 42"

DATA PHONE

DATA DATA

DATA-CLOSET#-ROOM#-PLATE#

NOTES:

PHONE-CLOSET#-PLATE#

1 2

3 4

3/4" CONDUIT

48"

CARD

READER

48"

NOTES:

TYPICAL SINGLE

DOOR

TYPICAL DOUBLE

DOOR

3/4" CONDUIT

SEE NOTE

#3

LAN

200W/CH-70V

DATAPORT

200W/CH-70V

DATAPORT

SPEAKER

SPEAKER

DATAPORT

SPEAKER #18/2

GPIO

DOOR INTERCOM CONTACT

SPEAKER

SEE NOTE #2

SEE NOTE

#1

1. ALL EQUIPMENT SHOWN AS DASHED IS EXISTING.

1.

2.

3.

4.

"DATA CLOSET#-ROOM#-PLATE#-JACK#"

4-POLE

TRANSFER

SWITCH

480V/277, 3 PH, 4 WIRE

LOAD

EGC

N G

SERVICE

EQUIPMENT

BONDING

JUMPER

CONDUCTOR

ELECTRODE NEARBY,

PREFERABLY THE

STRUCTURAL STEEL

N

GROUNDING

GROUNDING ELECTRODE

SEPARATELY

DERIVED SYSTEMGEN.

NOTE:

KP

MS

A

NOTES:

120V

PROVIDE OTHER GROUND CONNECTIONS AS

SPECIFIED IN N.E.C. ARTICLE 250-64

TO MOUNTING

STEEL

NEUTRAL BUS IN

DISCONNECT

GROUND BUS

TO DISCONNECT

FRAME GROUNDING ROD

(LOCATED NEAR

DISCONNECT

MOUNTING BASE)

PROVIDE A GROUNDING CONDUCTOR

IN ALL BRANCH CIRCUIT AND

FEEDER CONDUITS, SEE

SPECIFICATION SECTION 26 05 26

GANG

OPERATED

SWITCH

GANG

OPERATED

SWITCH

BUSSING

(TYPICAL)

FUSIBLE

SWITCH

FUSIBLE

SWITCH

GANG

OPERATED

SWITCH

COMPARTMENT

GANG

OPERATED

SWITCH

COMPARTMENT

FUSIBLE

INDIVIDUALLY

OPERATED

SWITCH

COMPARTMENT

FUSIBLE

INDIVIDUALLY

OPERATED

SWITCH

COMPARTMENT

GANG

OPERATED

SWITCH

OPERATING

HANDLE

BEHIND

PADLOCKED

COVER

GANG

OPERATED

SWITCH

OPERATING

HANDLE

BEHIND

PADLOCKED

COVERDOOR

HANDLE

W/PADLOCK

DATA JACK#

ROOM#-PLATE#

D2

101-1

2. SEE SECTION 27 10 05 FOR PLATE AND JACK REQUIREMENTS.

5. LABEL ALL VOICE AND DATA CABLES AT BOTH ENDS WITH

7. DATA JACKS ARE NUMBERED LEFT TO RIGHT, TOP TO BOTTOM.

6. ALL (4) JACKS TO BE CATEGORY 6e CABLES.

4. PLATES ARE LABELED AS SHOWN, NUMBER PLATES ARE CLOCKWISE FROM THE DOOR.

3. DATA JACKS TO BE ORANGE COLOR, PHONE JACKS TO BE IVORY.

1. = (3) DATA, (1) PHONE JACK.

GENERAL NOTES

DETAIL NOTES:

1. CONFIGURE DOOR INTERCOM TO TRIGGER DRY CONTACT

INPUTS ON EXISTING QSC Q-SYS DSP GPIO INPUT. PROGRAM

TO INITIATE DOOR CHIME OVER PA SPEAKERS IN BOILER

PLANT ZONE

2. BOILER PLANT SPEAKERS CURRENTLY CONNECTED TO ZONE

#13, DISCONNECT SPEAKER LINES AND RECONNECT TO SPARE

OUTPUT ON EXISTING QSC DAB-801 SPEAKER MODULE.

REPROGRAM BOILER PLANT AS A SEPARATE PUBLIC ADDRESS

ZONE

SOUND EQUIPMENT

CABINET 10

BOILER PLANT

MEZZANINE

DATAPORT

EXISTING REDUNDANT

AMPLIFIER

EXISTING AUDIO

NETWORK SIGNAL

EXISTING QSC CORE 110F

SERIES DSP/ IO FRAME EXISTING

AMPLIFIER

QSC DAB-801

ZONE #13 BLDG 11/12/13

ZONE #14 BLDG 51

ZONE #15 BLDG 10 (BOILER PLANT)

CONFIGURE CARD ACCESS SYSTEM TO DISABLE AUDIBLE

ALARM SIGNAL UPON VALID CARD SWIPE OR FROM IDS

KEYPAD NUMERIC CODE ENTRY.

CONFIGURE CARD ACCESS SYSTEM TO ACTIVATE IDS

SYSTEM AUDIBLE ALARMS UPON DOOR PROP SIGNAL,

PROVIDE 30 SECOND TIMER FUNCTION.

EACH DEVICE SHALL BE GIVEN AN INDEPENDENT ADDRESS

ON THE IDS SYSTEM, AND ASSIGNED TO PARTITION NOTED.

IDS

POWER

SUPPLY

IDS

CONTROL

PANEL

ELECTRIC LATCH

RETRACTION OR

VERTICAL ROD DEVICE

BY DIVISION 08

ELECTRIC HINGE

OR POWER TRANSFER

BY DIVISION 08

BALANCED

DOOR

POSITION

SWITCH

BALANCED

DOOR

POSITION

SWITCH

REQUEST TO

EXIT SENSOR

3/4"

CONDUIT

3/4"

CONDUIT

TO ACCESS CONTROL

SYSTEM PANELS IN

ELECTRICAL ROOM 102

3/4" CONDUIT

TYPICAL

JUNCTION BOX

ELECTRIC STRIKE

BY DIVISION 08

CARD

READER

ELECTRIC HINGE

OR POWER TRANSFER

BY DIVISION 08

DOOR

POSITION

SWITCH

REQUEST TO

EXIT SENSOR

3/4"

CONDUIT

TO ACCESS CONTROL SYSTEM

PANELS IN ELECTRICAL ROOM 102

3/4" CONDUIT

PROVIDE MINIMUM 4" CONCRETE HOUSEKEEPING PAD

REINFORCE WITH #3 BARS AT 12 INCHES ON CENTER

PROVIDE WITH 3/4" CHAMFER EDGE

I1

I202

I2

I1

I3

I4

I2

I1

SEE NOTE #1

SEE NOTE #2

DOOR PROP SIGNAL

I/0 MODULE

THIS DETAIL IS A TYPICAL INSTALLATION, COORDINATE EXACT WIRING AND DOOR

HARDWARE REQUIREMENTS WITH DIVISION 08 AND ACCESS CONTROL SYSTEM SUPPLIER.

DOOR HARDWARE POWER SUPPLIES SHALL BE CENTRALLY LOCATED IN THE MAIN

ELECTRICAL ROOM, SEE POWER DRAWINGS FOR CIRCUIT REQUIREMENTS.

SURFACE MOUNTED CONDUIT IS ALLOWED WITHIN BOILER PLANT, ROUTE CONDUIT DOWN

SECURED SIDE OF DOOR AND STUB CONDUIT THROUGH TO EXTERIOR CARD READER.

DISARM SIGNAL

MS

MS

MS

KP

ALL WIRING IN EMT CONDUIT, 3/4" MINIMUM.

KP

KEYED

BYPASS

SWITCH

KP

4.

SEE NOTE #5 SEE NOTE #5

SEE NOTE #5

IDS MASTER KEYPAD

OFFICE 103

SEE DWG

IDS MOTION SENSORS

PARTITION #1

BOILER PLANT

PARTITION #2

GENERATOR ROOM 107

PARTITION #3

ELECTRICAL ROOM 102

PARTITION #4

STEAM TUNNEL ENTRY

IDS AUDIBLE ALARM

SEE DWG FOR LOCATION

SEE NOTE#6

SEE NOTE #3

1.

2.

3.

4.

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPEAKER

SPD

TRANSFER SWITCH TRANSFER SWITCH

- KEY INTERLOCK

K

A P

P R

O X

IM

A

T E

L Y

I N

C H

E S

APPROXIMATELY 60 INCHES

OPERATOR

K

K

K

OPERATOR

K

K

K

SYSTEM GROUNDING DETAIL

NO SCALE

E12

DISCONNECT GROUNDING DETAILS

NO SCALE

E12

SWITCHBOARD SWBD-10 ELEVATION

NO SCALE

E12

S10-1 CIRCUIT DIAGRAM

NO SCALE

E12

S10-1 ENCLOSURE TOP VIEW

NO SCALE

E12

S10-1 SIDE VIEW

NO SCALE

E12

PATCH PANEL SAMPLE LABELS

NO SCALE

E12

TYPICAL COMMUNICATIONS PLATE DETAIL

NO SCALE

E12

TYPICAL CARD ACCESS WIRING DETAIL

NO SCALE

E12

PAGING AND DOORBELL SYSTEM ONE-LINE DIAGRAM

NO SCALE

E12

TYPICAL INTRUSION DETECTION SYSTEM WIRING DETAIL

NO SCALE

E12

AUDIBLE ALARM SHALL SOUND IF DOOR HAS BEEN PROPPED

FOR MORE THAN 30 SECONDS UNLESS BYPASSED WITH

KEYED SWITCH ADJACENT TO DOOR.

AUDIBLE ALARM SHALL SOUND IF DOOR HAS BEEN PROPPED

FOR MORE THAN 30 SECONDS UNLESS BYPASSED WITH

KEYED SWITCH ADJACENT TO DOOR.

5. BALANCED MAGNETIC SWITCH FURNISHED

UNDER SECTION 28 16 00.

6. KEYED SWITCH PROVIDED IN SECTION 28 13 16.

PROVIDE WITH RED/GREEN LIGHTS TO INDICATED

DOOR BYPASS STATUS, MATCH VA KEY TYPE.

KEY PLAN

Fargo, ND 58102

2101 Elm Street

Medical Center

Dept. of Veterans Affairs

Building No.

VA Project No.

Drawing Title

Contract No.

V e te ra n s A ff a ir s

Location

Drawn ByChecked ByDesigned By

Project Title

Drawing No.

Date

Scale:

D e p a rt m e n t o f

Dwg. of 6910 - BOILER PLANT

FARGO VA HEALTH CARE SYSTEM

FARGO, NORTH DAKOTA

VA263-P-1218

CH MB CHVA263

Project Phase www.jlgarchitects.com copyright © 2017

Fargo 214 Broadway

Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8

Elec. dwg name:

Submittal Date

S.D. 1 SUBMITTAL 12/30/2015

D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016

D.D. 1 (35%) SUBMITTAL 09/30/2016

D.D. 2 (50%) SUBMITTAL 03/03/2017

D.D. 3 (99%) SUBMITTAL 10/20/2017

C.D. 4 (100%) SUBMITTAL 06/01/2018

/2

/2

:3 :3

P

M

E12 437-14-112

REPLACE BOILER PLANT 10.26.18

ELECTRICAL DETAILS

100% CONSTRUCTION DOCUMENT

6715-193 E12.DWG

(1

M

IN

(1

M

IN

CONDUIT ROOF PENETRATION DETAIL

NO SCALE

E13

ROOF

EMERGENCY GENERATOR EXHAUST

NO SCALE

E13

4"

4"

PROVIDE EXOTHERMIC

WELDING FOR ALL

CONNECTIONS (TYPICAL)GROUND

ROD

(TYPICAL)

2"

TRANSFORMER PAD AND GROUNDING DETAIL

NO SCALE

E13

EMERGENCY GENERATOR WITH INTEGRAL RADIATOR

NO SCALE

E13

VIBRATION ISOLATORS

TO STRUCTURE ( TYP)

CONDUIT, TYP.

BATT INSULATION

PREFABRICATED FORMED 0.06"

THICK ALUMINUM FLASHING ROUND COLLAR

WITH MIN. 3" WIDE FLANGE. ATTACH TO ROOF

PER MANUFACTURER'S INSTRUCTIONS

MULTIPLE MEMBRANE STRIPPING PLIES FEATHERED

AT FIELD OF ROOF BY ROOFING CONTRACTOR.

PRIME FLANGE BEFORE STRIPPING.

SEAL-OFF FITTING, TYP.

STAINLESS CLAMP, TYP.

PREFABRICATED RUBBER BOOT CAP

WITH GRADUATED STEPS &

WEATHER-PROOF PRESSURE SEAL

TO COLLAR

SEALANT AT PENETRATION

TO MEMBRANE JUNCTURE

BY ROOFING CONTRACTOR

ROOF MEMBRANE

METAL ROOF

WATER CUT-OFF MASTIC

COMPATIBLE WITH ROOF

MEMBRANE

CONDUIT CLAMP,

SIZE AS REQUIRED

INTEGRAL GALVANIZED

LIPPED STEEL MOUNTING

CHANNEL, ATTACH TO

STRUCTURE BELOW

DECK

GENERAL NOTES:

1. MAINTAIN A MINIMUM CLEARANCE OF 12 INCHES ON ALL SIDES OF ROOF PENETRATION FROM WALLS, CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.

2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.

3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.

4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE PROPER METHODS

& MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.

ENGINE EXHAUST PIPE SIZE

AS RECOMMENDED BY

MANUFACTURER

MUFFLER, SIZE AS

RECOMMENDED BY

MANUFACTURER,

PROVIDE VIBRATION ISOLATORS

12" LONG DRIP LEG WITH DRAIN VALVE

EXHAUST PIPE, SIZE AS RECOMMENDED BY

MANUFACTURER.

THIMBLE OUTER SLEEVE

CLEARANCE AS REQUIRED BY THIMBLE

MANUFACTURER

FLASHING & ROOF OPENING BY GENERAL

CONTRACTOR

THIMBLE INNER SLEEVE

RAIN SHIELD

RAIN CAP

CONDUIT OPENING,

VERIFY SIZE AND

LOCATION WITH

TRANSFORMER

MANUFACTURER

PRIMARY SERVICE

CONDUITS

TO TRANSFORMER

NEUTRAL, #4/0.

SECONDARY

SERVICE CONDUITS

#4 REBAR WITH TIES

12 INCHES ON CENTER

EACH WAY

TRANSFORMER PAD,

VERIFY SIZE WITH

MANUFACTURER. PAD

SHALL EXTEND A MINIMUM

OF 8 INCHES BEYOND

TRANSFORMER

CONCRETE, SEE

SECTION 03 30 00.

FINISHED

GRADE

COMPACTED

GRAVEL BASE

SECONDARY

CONDUIT

PRIMARY

CONDUIT

GROUND

ROD

GROUND

ROD

HOT AIR

EXHAUST PIPING, ROOF THIMBLE AND

INSTALLATION PROVIDED BY DIVISION 26

INSTALL MUFFLER AND

FLEXIBLE CONNECTION.

INSULATE MUFFLER

INTEGRAL

RADIATOR

THERMOSTATIC AIR

RECIRCULATING

DAMPER PROVIDED BY

DIVISION 23

FLEXIBLE DUCT CONNECTOR

AND DUCTWORK PROVIDED BY

DIVISION 23

PROVIDE

VIBRATION

ISOLATORSPROVIDE FLEXIBLE FUEL

LINES FOR INSTALLATION

BY DIVISION 23

BLOCK

HEATER

EXTEND EXISTING

CONCRETE PAD

NOTE:

1.

CONDUIT

FLOOR

FIRESTOP…