36C26319B0010-0001001.pdf
PDF 920 KB Posted
- Attached to
- REPLACE BOILER PLANT (437-14-112)
- Solicitation number
- 36C26319B0010
About this file
36C26319B0010 0001 437-14-112 Replace Boiler Plant Structural Drawings (4 pages).pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26319C0205-000.docx | DOCX document | |
| 36C26319B0010-0004000.docx | DOCX document | |
| 36C26319B0010-0003000.docx | DOCX document | |
| 36C26319B0010-0003001.pdf | ||
| 36C26319B0010-0003002.pdf | ||
| 36C26319B0010-0002000.docx | DOCX document | |
| 36C26319B0010-0002001.pdf | ||
| 36C26319B0010-0001000.docx | DOCX document | |
| 36C26319B0010-012.pdf | ||
| 36C26319B0010-010.pdf | ||
| 36C26319B0010-004.pdf | ||
| 36C26319B0010-011.pdf | ||
| 36C26319B0010-001.docx | DOCX document | |
| 36C26319B0010-008.pdf | ||
| 36C26319B0010-005.pdf | ||
| 36C26319B0010-002.pdf | ||
| 36C26319B0010-007.pdf | ||
| 36C26319B0010-006.pdf | ||
| 36C26319B0010-003.pdf | ||
| 36C26319B0010-009.pdf | ||
| 36C26319B0010-000.docx | DOCX document |
Show all 21
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STANDARD NON-COATED BARS
NOTES:
REINFORCING STEEL SPLICE LENGTHS
TYPE #3 SPLICE
CLASS B SPLICE
SPACING LESS THAN 6 Bd - ADJUSTMENT FACTOR = 1.5
E. EPOXY COATED REINFORCING W/ COVER LESS THAN Bd OR CLEAR
D. TYPICAL EPOXY COATED REINFORCING - ADJUSTMENT FACTOR = 1.2
C. FOR LIGHT WEIGHT CONCRETE - ADJUSTMENT FACTOR = 1.3
B. FOR Fy OTHER THAN 60 ksi - ADJUSTMENT FACTOR = Fy (USED)/ 60
ADJUSTMENT FACTORS = 1.0 IF NONE BELOW APPLY
1. MIN. LAP: 18" FOR TYPE #1 THRU TYPE #3 & 12" FOR TYPE #4 SPLICES.
A. FOR HORIZ. REINFORCING W/ MORE THAN 12" OF FRESH CONCRETE
2. REQ'D. SPLICE LENGTH = LISTED SPLICE LENGTH x ADJUSTMENT FACTORS
PLACED BELOW BAR - ADJUSTMENT FACTOR = 1.3
F'c
4000 psi
5000 psi
3500 psi
3000 psi
34 Bd 42 Bd
Bd = BAR DIAMETER
55 Bd44 Bd 66 Bd
41 Bd
38 Bd
51 Bd
47 Bd
#6 AND
44 Bd 55 Bd
66 Bd
62 Bd
53 Bd
49 Bd
79 Bd
74 Bd
71 Bd57 Bd 85 Bd
STRENGTH
CONCRETE TYPE #1 SPLICE
CLASS A SPLICE CLASS B SPLICE
TYPE #2 SPLICE
83 Bd 30 Bd
99 Bd
92 Bd
30 Bd
30 Bd
107 Bd 30 Bd
COMPRESSION SPLICE
TYPE #4 SPLICE
SMALLER LARGER
#7 AND #6 AND
SMALLER
#7 AND
LARGER
#7 AND
SMALLER
#6 AND
LARGER
#4 AND LARGER
3. ALL ADJUSTMENT FACTORS THAT APPLY SHALL BE USED TO CALCULATE
SPACING LESS THAN 6 Bd - ADJUSTMENT FACTOR = 1.5
REQUIRED SPLICE LENGTH.
6000 psi 31 Bd 38 Bd 50 Bd40 Bd 60 Bd 76 Bd 30 Bd
GENERAL CONSTRUCTION NOTES:
1. THE INTENT OF THESE PLANS AND NOTES IS TO PRESENT THE PROJECT REQUIREMENTS
FOR THE VA REPLACE BOILER PLANT IN FARGO, ND.
2. THESE STRUCTURAL DRAWINGS INTENDED TO BE USED IN CONJUCTION WITH THE
ARCHITECTURAL DRAWINGS. SOME DIMENSIONS, SECTIONS, AND FRAMING DETAILS MAY
BE SHOWN ON THE ARCHITECTURAL DRAWINGS.
3. DURING CONSTRUCTION, THE CONTRACTOR MAY ENCOUNTER EXISTING CONDITIONS THAT
ARE UNKNOWN OR THAT DIFFER THAN AS DEPICTED IN THESE DRAWINGS. SUCH
EXISTING CONDITIONS MAY INTERFERE WITH THE NEW CONSTRUCTION OR REQUIRED
PROTECTION DURING CONSTRUCTION.
4. CONTRACTOR SHALL NOTIFY ARCHITECT/ENGINEER OF ALL ENCOUNTERED EXISTING
CONDITIONS THAT INTERFERE WITH THE PROPER EXECUTION OF NEW WORK OR
COMPRIMISE THE STRUCTURAL INTEGRITY OF THE EXISTING STRUCTURE.
5. ALL WORK SHALL COMPLY WITH THE 2015 INTERNATIONAL BUILDING CODE,
AS APPROVED BY THE STATE OF NORTH DAKOTA / CITY OF FARGO.
6. REFERENCE STANDARDS: UNLESS OTHERWISE NOTED (U.O.N.), ALL STANDARDS
SHALL BE CURRENT EDITION, WITH LATEST ADDENDA, IF APPLICABLE.
7. THE CONTRACTOR SHALL VERIFY ALL CONTRACT DOCUMENTS, SITE ELEVATIONS,
DIMENSIONS AND CONDITIONS PRIOR TO STARTING WORK AND SHALL NOTIFY THE
OWNER/ARCHITECT/ENGINEER OF ANY DISCREPANCIES OR INCONSISTENCIES.
8. SPECIFIC NOTES AND DETAILS SHALL TAKE PRECEDENCE OVER GENERAL NOTES.
9. THE CONTRACT STRUCTURAL DRAWINGS AND SPECIFICATIONS REPRESENT THE
FINISHED STRUCTURE. UNLESS OTHERWISE INDICATED, THEY DO NOT INDICATE THE
MEANS, METHODS, TIMING, OR PROCEDURES USED TO COMPLETE THE CONSTRUCTION.
TEMPORARY BRACING, SHORING, OR PROTECTION OF THE STRUCTURE AGAINST WIND,
ERECTION AND OTHER SITE CONDITIONS DURING CONSTRUCTION OF THE BUILDING
SHALL BE THE RESPONSIBILITY OF CONTRACTOR. THE CONTRACTOR IS SOLELY
RESPONSIBLE FOR THE PROTECTION OF THE STRUCTURE DURING ALL PHASES OF
DEMOLITION, CONSTRUCTION, AND INSTALLATION.
10 NO AREA OF THE STRUCTURE SHALL BE LOADED WITH CONSTRUCTION MATERIALS
OR EQUIPMENT THAT EXCEEDS FINAL DESIGN CRITERIA.
11. SEE MECHANICAL, ELECTRICAL, AND ARCHITECTURAL DRAWINGS FOR ALL OPENINGS
AND INSERTS NOT SHOWN ON THE STRUCTURAL DRAWINGS.
12. VERIFY LOCATION OF BOX OUTS AND OPENINGS WITH MECHANICAL AND ELECTRICAL
CONTRACTORS. OPENING SIZES AND LOCATIONS SHOWN FOR PIPES, DUCTS ETC. ARE
FOR GENERAL INFORMATION ONLY AND SHALL BE VERIFIED WITH THE MECHANICAL
CONTRACTOR BEFORE COMMENCING THE WORK.
13. VERIFY SIZE, NUMBER, AND LOCATION OF ALL MECHANICAL AND ELECTRICAL
EQUIPMENT. IF EQUIPMENT SIZES, WEIGHTS, OR LOCATIONS DO NOT COINCIDE WITH
EQUIPMENT SHOWN ON PLANS, COORDINATE ADJUSTMENTS WITH THE STRUCTURAL
ENGINEER.
14. HOLES, PIPES, SLEEVES, ETC. NOT SHOWN ON THE DRAWINGS MUST BE APPROVED BY
THE STRUCTURAL ENGINEER BEFORE PLACEMENT THROUGH STRUCTURAL MEMBERS.
15. CONTRACTOR SHALL PROVIDE A CAST-IN SLEEVE FOR ALL HORIZONTAL ELEMENTS
THAT EXTEND THROUGH FOOTING. IE: DRAIN TILE, ELECTRICAL CONDUIT, MECHANICAL
PIPING, ETC. ALL SLEEVES SHALL BE COORDINATED WITH ARCHITECT/ENGINEER.
16. SHOP DRAWINGS PREPARED BY SUPPLIERS, SUB CONTRACTORS, ETC., SHALL BE
DIMENSIONED, REVIEWED, COORDINATED, AND SIGNED/STAMPED BY THE GENERAL
CONTRACTOR PRIOR TO SUBMITTING TO THE OWNER/ARCHITECT/ENGINEER. MANUFACTURED
COMPONENTS SUCH AS TRUSSES OR PRECAST CONCRETE SHALL BE ENGINEERED
AND STAMPED PRIOR TO SUBMISSION
17. FABRICATOR SHALL CLEARLY NOTE CHANGES MADE IN THE SHOP DRAWINGS WHICH
DO NOT COMPLY WITH THE CONTRACT DOCUMENTS. REVIEWED APPROVAL SHOP
DRAWINGS SHOWING ENGINEERS COMMENTS ACCOMPANIED WITH RECORD SET
SHOP DRAWINGS, SHALL BE AVAILABLE FOR REFERENCE AT THE CONSTRUCTION SITE.
18. EXPANION ANCHORS (EXP. ANC.) SHALL BE HILTI "KWIK BOLT TZ" OR EQUIVALENT
(U.O.N.). INSTALL ANCHORS IN STRUCTURAL CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
19. ADHESIVE ANCHORS (A.A.) SHALL BE HILTI "HIT HY-200 USING 'HAS' STANDARD RODS"
OR EQUIVALENT (U.O.N.). USE HILTI HIT-ICE FOR COLD WEATHER APPLICATIONS,
SEE SPECIFICATIONS FOR USAGE. INSTALL ANCHORS IN STRUCTURAL CONFORMANCE
WITH THE MANUFACTURER'S RECOMMENDATIONS.
20. CONCRETE SCREW ANCHORS (S.A.) SHALL BE SIMPSON STRONG-TIE TITEN HD OR
EQUIVALENT (U.O.N.). INSTALL ANCHORS IN STRUCTURAL CONFORMANCE
WITH THE MANUFACTURER'S RECOMMENDATIONS.
21 DESIGN LOADS:
FLOOR LIVE LOADS:
CATWALKS....................................................................... 40 psf MEZZANINE..................................................................... 125 psf CORRIDORS & STAIRS................................................... 100 psf STORAGE......................................................................... 125 psf
ROOF LIVE LOADS:
FLAT ROOF SNOW.......................................................... Pf = 51 psf
EXPOSURE FACTOR........................................ Ce = 1.0 IMPORTANCE FACTOR.................................... Is = 1.2 THERMAL FACTOR........................................... Ct = 1.0 GROUND SNOW LOAD..................................... Pg = 50 psf
DEAD LOADS:
TYPICAL FLOOR.............................................................. 10 psf (SUPERIMPOSED) TYPICAL ROOF................................................................ 15 psf (SUPERIMPOSED)
LATERAL LOADS (WIND-MWFRS)
ULTIMATE DESIGN WIND SPEED (3 SEC. GUST)............. Vult = 120 mph NOMINAL DESIGN WIND SPEEDBBBBBBB............... Vasd = 93 mph WIND EXPOSURE............................................................... " B "
INTERNAL PRESSURE COEFFICIENT................................ ±0.18
RISK CATEGORY................................................................ IV
COMPONENTS AND CLADDINGBBBBBBBBBB.... 13.2 psf (qh BASE PRESSURE)
LATERAL LOADS (SEISMIC-MSFRS):
RISK CATEGORY............................................................. IV
IMPORTANCE FACTOR................................................... Ie = 1.50 MAPPED SPECTURAL RESPONSE................................ Ss = 5.3 %g
S1 = 2.0 %g SITE CLASS...................................................................... " D " (ASSUMED)
DESIGN SPECTRAL RESPONSE.................................... SDS = 0.057
SD1 = 0.032
SEISMIC DESIGN CATEGORY........................................ " A "
BASIC SEISMIC FORCE-RESISTING SYSTEMBBBB ORD. PLAN MAS. SHEAR WALL
DESIGN BASE SHEAR..................................................... V = 0.057 W SEISMIC RESPONSE COEFFICIENT............................. Cs = 0.057
RESPONSE MODIFICATION FACTOR............................ R = 1.5
ANALYSIS PROCEDURE................................................. E.L.F.A.
EXCAVATION AND BACKFILL NOTES:
1. EXCAVATION AND BACKFILL SHALL BE EXECUTED IN ACCORDANCE WITH THE
PROJECT SPECIFICATIONS.
2. BACKFILL AND COMPACTION SHALL BE INSPECTED AND CERTIFIED BY A LICENSED
GEOTECHNICAL ENGINEER. REPORTS ARE TO BE SUBMITTED TO THE OWNER/ ARCHITECT/
ENGINEER.
3. FOOTING EXCAVATIONS SHALL BE EXCAVATED TO PROPER LINE AND LEVEL TO
ENSURE MINIMUM CONCRETE COVER OF FOOTING REINFORCEMENT FOR FOOTING
DEPTH.
4. BACKFILL SHALL BE COMPACTED BY MECHANICAL MEANS. FLOODING OR WATER
INUNDATION SHALL NOT BE PERMITTED.
5. BACKFILL SHALL BE PLACED IN ALTERNATING LIFTS ON EACH SIDE OF THE
FOUNDATION WALLS TO MAINTAIN STABILITY OF FOUNDATION WALLS.
6. BACKFILL SHALL NOT BE PLACED AGAINST BASEMENT FOUNDATION WALLS UNLESS
WALLS ARE ADEQUATELY BRACED TOP AND BOTTOM. FINAL WALL BRACING IS
BASEMENT SLAB AND 1ST FLOOR STRUCTURE. IF THESE ELEMENTS ARE NOT IN
PLACE AT TIME OF BACKFILL. CONTRACTOR SHALL PROVIDE AN ENGINEERED,
TEMPORARY BRACING SYSTEM. THE TEMPORARY BRACING SYSTEM PROPOSED
SHALL BE SUBMITTED TO THE OWNER/ARCHITECT/ENGINEER FOR REVIEW PRIOR TO
BACKFILLING.
7. THE CONTRACT STRUCTURAL DOCUMENTS AND SPECIFICATIONS REPRESENT THE
FINISHED STRUCTURE. THE MEANS AND METHODS USED TO PERFORM THE EXCAVATION
IS AT THE SOLE DISCRETION OF THE CONTRACTOR, INCLUDING THE DESIGN AND
INSTALLATION OF TEMPORARY BRACING OR SHORING. CONTRACTOR IS RESPONSIBLE
FOR ALL CODE AND REGULATORY SAFETY REQUIREMENTS.
FOUNDATION NOTES:
1. FOOTING ELEVATIONS ARE TO TOP OF FOOTING (T.O. FTG.), UNLESS OTHERWISE NOTED.
2. FOOTINGS ARE DESIGNED FOR AN ASSUMED NET ALLOWABLE SOIL BEARING
PRESSURE OF 1500 psf. THIS VALUE SHALL BE VERIFIED BY A GEOTECHNICAL ENGINEER, SUBMIT REPORT OF OBSERVATION TO OWNER/ARCHITECT/ENGINEER PRIOR TO POURING
FOOTINGS.
3. FOOTINGS SHALL BEAR ON NATURAL UNDISTURBED SOIL OR ENGINEERED FILL.
SOILS SHALL BE OBSERVED AND APPROVED BY A GEOTECHNICAL ENGINEER PRIOR
TO PLACEMENT OF FOOTING CONCRETE. IF NATURAL UNDISTURBED SOILS ARE NOT
ENCOUNTERED AND/OR INADEQUATE SOILS ARE NOTED AT FOOTING BEARING LEVEL.
OWNER/ARCHITECT/ENGINEER SHALL BE NOTIFIED PRIOR TO PROCEEDING WITH FURTHER
WORK AT THOSE FOOTING LOCATIONS.
4. PROTECT FOOTINGS FROM THE ACTION OF WATER OR FREEZING.
5. FOOTINGS ARE CENTERED UNDER WALLS ABOVE - UNLESS OTHERWISE NOTED.
6. PRIOR TO PLACEMENT OF FOOTING CONCRETE, CLEAN FOOTING EXCAVATIONS OF
SNOW, WATER, MUD, DIRT, AND DEBRIS.
7. FOOTINGS SHALL NOT BE EARTH FORMED.
CONCRETE NOTES:
1. CONCRETE CONSTRUCTION SHALL CONFORM TO AMERICAN CONCRETE INSTITUTE
(ACI) CODES AND SPECIFICATIONS, LATEST EDITION.
ACI 301 "SPECIFICATIONS FOR STRUCTURAL CONCRETE"
ACI 315 "DETAILS & DETAILING OF CONCRETE REINFORCEMENT"
ACI 318-14 "BUILDING CODE REQUIREMENTS FOR REINFORCED CONCRETE"
2. CAST-IN-PLACE CONCRETE SHALL HAVE A 28 DAY COMPRESSIVE STRENGTH IS
AS FOLLOWS:
3000 psi - FOOTINGS 3000 psi - EXTERIOR FOUNDATION WALLS 3000 psi - INTERIOR FOUNDATION WALLS 4000 psi - INTERIOR SLABS ON GRADE 4000 psi - EXTERIOR SLABS ON GRADE - AIR ENTRAINED 4000 psi - EXTERIOR SLABS ON DECK - AIR ENTRAINED
3. CONCRETE MIX DESIGNS SHALL BE BY AN INDEPENDENT TESTING LABORATORY.
4. CAST-IN-PLACE CONCRETE SHALL BE SUBJECT TO TESTING BY AN INDEPENDENT
TESTING LABORATORY. SEE PROJECT SPECIFICATIONS FOR REQUIREMENTS.
5. NON-WELDED REINFORCING STEEL SHALL BE GRADE 60 DEFORMED, BILLET-STEEL,
ASTM A615, U.O.N. ALL WELDED WIRE FABRIC (WWF) SHALL BE PLAIN ASTM A185.
6. WELDED REINFORCING STEEL SHALL BE GRADE 60, LOW CARBON, ASTM A706.
7. CLEAR CONCRETE COVER FOR ALL REINFORCING SHALL BE AS FOLLOWS, UNLESS
OTHERWISE NOTED ON THE DRAWING:
CONCRETE ON SOIL.................................................................... 3" SLAB ON GRADE.......................................................................... MIDHEIGHT
WALLS, STRUCTURAL SLABS
FORMED AND EXPOSED TO EARTH OR WEATHER:
#6 THROUGH #18................................................................. 2" #5 AND SMALLER................................................................. 1 1/2"
NOT EXPOSED TO EARTH AND WEATHER:
#11 AND SMALLER............................................................... 3/4"
BEAMS AND COLUMNS (COVER TO STIRRUPS OR TIES)....... 1 1/2"
8. PROVIDE EXTRA REINFORCEMENT AROUND ALL OPENINGS GREATER THAN 12" SQUARE
OR 12" IN DIAMETER, INCLUDING DOOR OPENINGS, IN CONCRETE WALLS & SLABS.
PROVIDE TWO (2) #5 BARS @ 3" O.C., ON EACH SIDE OF THE OPENING EXTENDING 24"
BEYOND THE CORNER OF THE OPENING & TWO (2) #5 BARS AT 3" O.C. BY 3'-0" LONG
DIAGONAL BARS AT EACH CORNER. PLACE DIAGONAL BARS CENTERED ON CORNER
@ 2" CLEAR OF CORNER. ADDITIONAL REINFORCEMENT SHALL BE PROVIDED AT EACH
LAYER OF REINFORCING.
9. REINFORCING STEEL SHALL BE BENT, SPLICED, AND PLACED IN ACCORDANCE WITH
ACI 301 (LATEST EDITION).
10. PROVIDE LAP SPLICE FOR REINFORCING STEEL AS INDICATED IN THE FOLLOWING
SCHEDULE.
11. UNLESS OTHERWISE NOTED ON PLAN OR DETAILS, LAP THE FOLLOWING BARS AS
DEFINED IN LAP SPLICE TABLE ABOVE.
A. VERTICAL HOOKED OR STRAIGHT BARS EXTENDING FROM FOOTINGS:
TYPE #4 SPLICE.
B. HORIZONTAL BARS IN SLABS ON GRADE, GRADE BEAMS, FOOTINGS, & FOUNDATIONS:
TYPE #2 SPLICE.
C. VERTICAL BARS IN COLUMNS & PIERS: TYPE #4 SPLICE.
D. WHERE SPECIFICALLY NOTED ON PLANS OR DETAILS:
TYPE #3 SPLICE.
12. PROVIDE ADEQUATE SUPPORT BARS AND ACCESSORIES TO HOLD REINFORCING
BARS FIRMLY IN PLACE TO SPECIFIED COVERAGES.
13. UNLESS SHOWN SPECIFICALLY ON PLAN, CONTROL JOINTS SHALL BE PLACED IN A
SQUARE PATTERN WITH A MAXIMUM SPACING OF 36 TIMES THE SLAB THICKNESS.
WHERE A SQUARE PATTERN IS NOT POSSIBLE, THE MAXIMUM LONG SIDE TO SHORT
SIDE OF THE JOINT PATTERN SHALL NOT EXCEED A RATIO OF 1.25:1. CONSTRUCTION
JOINTS SHALL BE LOCATED BY THE CONTRACTORS AS REQUIRED FOR CONSTRUCTION
WITH A MAXIMUM OF 3,000 SQUARE FEET. CONTRACTOR SHALL SUBMIT A JOINT
PLACEMENT PLAN TO OWNER/ARCHITECT/ENGINEER FOR REVIEW PRIOR TO POURING
CONCRETE.
14. CAST DOWELS, WITH STD 90°HOOK, IN FOOTINGS FOR CONCRETE PIERS AND WALLS
ABOVE DOWELS SHALL BE THE SAME SIZE AND NUMBERS AS THE VERTICAL
REINFORCING. (U.O.N.)
SPECIAL INSPECTIONS:
1. THE CONTRACTOR SHALL COORDINATE THE TESTING AND INSPECTION SERVICES
IN ACCORDANCE WITH THE PROGRESS OF THE WORK. THE CONTRACTOR SHALL
PROVIDE SUFFICIENT NOTICE TO THE TESTING OR INSPECTION AGENCY OF THE
REQUIRED WORK TO ALLOW ALLOCATION OF PERSONNEL. THE COST OF ANY
RETESTING OR ADDITIONAL INSPECTIONS AS A RESULT OF UNINSPECTED WORK,
FAILED TESTS, OR REJECTED WORK, SHALL BE BORNE BY THE CONTRACTOR.
2. THE FOLLOWING TABLE INCLUDES ITEMS REQUIRING SPECIAL INSPECTION PROVIDED
BY THE CONTRACTOR. SPECIAL INSPECTIONS LISTED IN THIS TABLE MAY NOT INCLUDE ALL
INSPECTIONS AND/OR TESTING THAT IS REQUIRED FOR THE PROJECT PER IBC CHAPTER
17. ADDITIONAL TESTING MAY BE REQUIRED BY THE CONTRACTOR, AS PART OF THEIR
CONTRACT.
REQUIRED SPECIAL INSPECTION
12. SPEC. GRADING
11. SHOTCRETE
9. INSULATING-CONC.
8. REINF. GYPSUM
7. STRUCTURAL MASONRY
3. DUCTILE MOMENT-RES.
6. HIGH STRENGTH
5. WELDING
4. REINF. STEEL AND
2. BOLTS INSTALLED
1. CONCRETE
EXC. AND FILLING
FILL
CONCRETE
BOLTING
PRESTRESSING STEEL
CONCRETE FRAME
IN CONCRETE
TESTING
YES
IBC CHAPTER 17
DESCRIPTION OF WORK INSPECTION
YES NO NO
REMARK
10. PILING, DRILLED PIERS
AND CAISSONS
13. WOOD FRAMING
TRUSSES
14. STRUCTURAL PRECAST
15. SPECIAL CASES
X
NA
X X
X X X
X X X X X X X X X
X X X
X
MASONRY NOTES:
1. CONCRETE BLOCK MASONRY UNITS SHALL CONFORM TO GRADE 'N', MOISTURE
CONTROLLED TYPE I REQUIREMENTS OF ASTM C90, WITH AN ASSUMED COMPRESSIVE
STRENGTH F'm - 1900 PSI. MORTAR SHALL CONFORM TO ASTM C270 AND SHALL BE
TYPE 'M' OR TYPE 'S', WITH TYPE 'M' BELOW GRADE.
2. ALL MASONRY LINTEL BEAMS AND BOND BEAMS WHERE NOTED SHALL BE A “U” BLOCK
TYPE UNIT.
3. CONCRETE GROUT FOR UNIT MASONRY CORES AND BOND BEAMS SHALL HAVE A 28
DAY COMPRESSIVE STRENGTH OF 3000psi.
4. MASONRY WALLS ARE TO BE SUPPORTED LATERALLY UNTIL THE ENTIRE ROOF
AND/OR FLOOR IS IN PLACE AS DETAILED.
5. WIRE REINFORCING FOR CMU WALLS SHALL BE CORROSION RESISTANT 9 GA
HORIZONTAL JOINT REINFORCING CONFORMING TO ASTM A951. REINFORCING SHALL
BE INSTALLED AS PER MANUFACTURER'S RECOMMENDATIONS WITH MAXIMUM SPACING
OF 1’-4" OC (UON)
6. MASONRY REINFORCING SHALL BE LAPPED AS FOLLOWS:
#3 BAR = 1’-6" #6 BAR = 3’-0"
#4 BAR = 2’-0" #7 BAR = 3’-6"
#5 BAR = 2’-6" #8 BAR = 4’-0"
7. VERTICAL REINFORCING BARS SHALL BE HELD IN POSITION AT TOP AND BOTTOM AND
AT 192 (REINF) DIAMETER INTERVALS MAXIMUM. LENGTH OF REINFORCING BARS TO
BE COORDINATED WITH GENERAL CONTRACTOR AND MASONRY CONTRACTOR.
8. WHERE CELLS ARE TO BE FILLED W/ CONCRETE GROUT, PROVIDE ADDITION FULL
MORTAR BED AT CROSS WEBS ENCLOSING GROUTED CELL.
9. CONSOLIDATE ALL CONCRETE GROUT BY PUDDLING OR VIBRATING.
10. BLOCK COURSING SHOWN ON STRUCTURAL PLANS MAY NOT BE REPRESENTATIVE OF
ACTUAL COURSING. SEE ARCHITECTURAL PLANS AND SECTIONS FOR ACTUAL LAYOUT
OF BLOCK COURSING.
11. FIRST COURSE OF ALL HOLLOW MASONRY SHALL BE PLACED ON A FULL BED OF
MORTAR.
12. CAST DOWELS, WITH STANDARD HOOKS, IN FOOTINGS FOR PIERS AND WALLS ABOVE.
DOWELS SHALL BE THE SAME SIZE AND SPACING OF VERTICAL REINFORCING. (UON)
STRUCTURAL STEEL NOTES:
1. STRUCTURAL STEEL WORK SHALL BE PER AMERICAN INSTITUTE OF STEEL
CONSTRUCTION (AISC) SPECIFICATION, 14TH EDITION, MATERIAL:
ASTM A992 W, S, AND M SHAPES Fy = 50 ksi ASTM A53 GRADE B - STANDARD PIPES Fy = 35 ksi ASTM A500 GRADE B - HSS PIPES Fy = 42 ksi ASTM A500 GRADE B - HSS TUBES Fy = 46 ksi ASTM A36 PLATES, BARS, MISC. SHAPES Fy = 36 ksi
(ANGLES), CHANNELS, & RODS
ASTM F1554 GRADE 36 – ANCHOR RODS Fy = 36 ksi
GRADE 55 – ANCHOR RODS Fy = 55 ksi GRADE 105 – ANCHOR RODS Fy = 105 ksi
ASTM F3125 GRADE A325 - CONNECTION BOLTS
GRADE A490 - CONNECTION BOLTS
ASTM A563 CONNECTION NUTS
ASTM F436 WASHERS
ASTM A108 HEADED STUD ANCHORS Fy = 65 ksi E70XX ELECTRODES Fy = 70 ksi
2. WELDED CONNECTIONS SHALL BE MADE IN ACCORDANCE W/ THE LATEST
RECOMMENDATIONS OF:
AISC - AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AWS - AMERICAN WELDING SOCIETY
3. COLUMN BASE AND CAP PLATES TO BE WELDED AROUND ALL SIDES.
4. BOTTOM PLATE OF STEEL LINTELS SHALL BE WELDED TO THE BEAM WITH 3/16" FILLET
WELD (BOTH SIDES) 3" LONG @ 1'-0" OC (UON) L3 1/2 X 3 1/2 X 1/4
5. WELDS NOT SPECIFIED SHALL BE A FILLET WELD, CONTINUOUS AND/OR ALL AROUND
WITH MINIMUM THROAT DIMENSION AS REQUIRED FOR MATERIAL THICKNESS PER AWS.
6. STRUCTURAL FABRICATORS SHALL SHOW ALL FIELD WELDING REQUIREMENTS ON
SHOP DRAWINGS SUBMITTED TO THE ENGINEER.
7. BEAMS AND COLUMNS SHALL BE ERECTED TRUE AND PLUMB WITHIN AISC TOLERANCE.
PROVIDE TEMPORARY BRACING AS REQUIRED.
8. BEARING PLATES FOR STEEL COLUMNS SHALL BE DRY PACKED WITH A NON-SHRINK,
NON-METALLIC GROUT AS SPECIFIED.
9. PROVIDE DOUBLE ANGLE CONNECTIONS AS DESCRIBED IN PART 10 OF THE AISC.
MANUAL OF STEEL CONSTRUCTION (14TH ED-ASD)
• CONNECTIONS SHALL BE SELECTED TO SUPPORT BEAM END REACTIONS INDICATED
ON THE CONTRACT DRAWINGS.
• IF BEAM END REACTIONS ARE NOT INDICATED, CONNECTIONS SHALL BE SELECTED
TO SUPPORT 1/2 THE TOTAL UNIFORM LOAD CAPACITY GIVEN IN THE ALLOWABLE
UNIFORM LOAD TABLES, PART 3- 14TH ED-ASD, FOR THE SPECIFIED BEAM SIZE,
SPAN, AND STEEL GRADE (UON). OTHER RATIONAL ENGINEERING CONNECTION
DESIGN AND STARDARD CONNECTION PRACTICES MAY BE USED WITH APPROVAL
OF THE ENGINEER.
• CONNECTIONS SHALL HAVE MINIMUM ROWS OF BOLTS FOR BEAM DEPTHS AS
INDICATED IN PART 10.
10. FRAMED STEEL BEAM CONNECTIONS SHALL BE "BEARING TYPE", (UON).
11. STEEL BEAM KEY:
NUMBER OF HEADED STUDS (EQUALLY SPACED)
CAMBER
ELEVATION FROM T.O. STEEL
W16x40 (15) (3/4") (-0'-0") (BEAM SIZE)
20 20 (BEAM END REACTION/MOMENT)
12. LINTELS SHALL HAVE A BEARING OF 1" PER FOOT OF SPAN AT EACH END, 8" MIN.
LINTELS ANGLES WHICH HAVE NOT BEEN SHOWN OTHERWISE, TO BE AS FOLLOWS
FOR EACH 4" OF WALL THICKNESS:
SPANS TO 4'-0" - L3 1/2" x 3 1/2" x 1/4" 4'-0" TO 6'-0" - L4 x 3 1/2" 1/4" 6'-0" TO 8'-0" - L5 x 3 1/2" x 1/4"
• FOR SPANS GREATER THAN 8'-0" CONTACT STRUCTURAL ENGINEER.
13. DO NOT PAINT STEEL SURFACES TO BE FIELD WELDED.
14. DO NOT PAINT STEEL SURFACES THAT HEADED STUD ANCHORS WILL BE WELDED TO.
15. ALL HEADED STUD ANCHORS TO BE ATTACHED TO STEEL SECTION USING ELECTRIC ARC WELDING GUN.
16. FOR STEEL TO RECEIVE SPRAY APPLIED FIREPROOFING, VERIFY STEEL SURFACE PREPARATION
REQUIREMENTS MANUFACTURER.
17. METAL DECK TO BE MANUFACTURED AND ERECTED IN ACCORDANCE WITH STEEL
DECK INSTITUTE SPECIFICATIONS.
ROOF DECK - 1 1/2" DEEP, TYPE B, 20 GA.,
AS MADE BY VULCRAFT OR EQUAL
18. VERIFY LOCATION OF ROOF OPENINGS WITH MECHANICAL CONTRACTOR. ROOF
OPENINGS SHALL BE FRAMED WITH L3x3x3/8" ON FOUR SIDES (UON). SEE STANDARD DETAILS.
19. ROOF PERIMETER STEEL ELEMENTS SUCH AS ANGLES OR BENT PLATES, NOTED TO
BE CONTINUOUS, SHALL BE FIELD SPLICED WITH A FULL LENGTH SQUARE GROOVE
FULL PENETRATION WELD UTILIZING A MINIMUM 3/16" ROOT OPENING.
ABBREVIATIONS AND SYMBOLS:
AA ADHESIVE ANCHOR
AR ANCHOR ROD
APA AMERICAN PLYWOOD ASSOCIATION
ASTM AMERICAN SOCIETY OF TESTING MATERIALS
ARCH ARCHITECT/ARCHITECTURAL
BB BOND BEAM
BLDG BUILDING
BLK BLOCK
BM BEAM
B.O. BOTTOM OF
BOT BOTTOM
BTWN BETWEEN
BRG BEARING
CIP CAST IN PLACE
CL CENTER LINE
CJ CONTROL JOINT
CCJ CONSTRUCTION CONTROL JOINT
CLR CLEAR/CLEARANCE
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CRC COLD-ROLLED CHANNEL
DBL DOUBLE
DET DETAIL
DEG DEGREES
DIA DIAMETER
DIM DIMENSION
DL DEAD LOAD
DT DRAIN TILE
DWL DOWEL
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEV ELEVATOR
EQ EQUAL
EW EACH WAY
(E) EXISTING
EXC EXCAVATION
EXP EXPANSION
EXT EXTERIOR
FD FLOOR DRAIN
FDN FOUNDATION
FTG FOOTING
FT FOOT/FEET
GALV GALVANIZE
GA GAUGE
GC GENERAL CONTRACTOR
GT GIRDER TRUSS
HC HOLLOWCORE
HORIZ HORIZONTAL
HSA HEADED STUD ANCHOR
HSS HOLLOW STRUCTURAL SECTION
IF INSIDE FACE
INT INTERIOR
JST JOIST
K KIPS
KLF KIPS PER LINEAR FOOT
KSI KIPS PER SQUARE INCH
L ANGLE
LL LIVE LOAD
LB LEDGER BEAM
LBS POUNDS
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONG LONGITUDINAL
MAS MASONRY
MAX MAXIMUM
MECH MECHANICAL
MFG MANUFACTURER
MIN MINIMUM
MIR MIRROR
MISC MISCELLANEOUS
MTL METAL
MO MASONRY OPENING
N NORTH
NTS NOT TO SCALE
NS NON-SHRINK
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OH OVERHEAD
OPNG OPENING
ORIG ORIGINAL
OSB ORIENTED STRAND BOARD
PAF POWDER ACTUATED FASTENER
PART PARTITION
PC PRECAST CONCRETE
PLF POUND PER LINEAR FOO
PL PLATE
PWD PLYWOOD
PNL PANEL
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
RAD RADIUS
RD ROOF DRAIN
REINF REINFORCING
REM REMOVE
RQD REQUIRED
RFG ROOFING
RO ROOF OPENING
SA SCREW ANCHOR
SB SOIL BORING
SCHED SCHEDULE
SD SEE DETAIL
SDL SUPERIMPOSED DEAD LOAD
SLL SUPERIMPOSED LIVE LOAD
SER STRUCTURAL ENGINEER OF RECORD
SHT SHEET
SIM SIMILAR
SQ SQUARE
SJ STEEL JOIST
SL SNOW LOAD
SPA SPACE/SPACING
SPECS SPECIFICATIONS
SS STAINLESS STEEL
STD STANDARD
STL STEEL
TEMP TEMPORARY
T & B TOP & BOTTOM
T & G TONGUE AND GROOVE
THK THICK OR THICKENED
T.O. TOP OF
TRANS TRANSVERSE
TRTD TREATED
TS TUBE STEEL
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VER VERIFY
VERT VERTICAL
WF WIDE FLANGE
WD WOOD
WL WIND LOAD
W/ WITH
W/O WITH OUT
WT WEIGHT
WWF WELDED WIRE FABRIC
@ AT
+/- PLUS OR MINUS
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
V e te ra n s A ff a ir s
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
D e p a rt m e n t o f
Dwg. of 6910 - BOILER PLANT
FARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218
EAG EAG SWVA263
Project Phase www.jlgarchitects.com copyright © 2015
Fargo 214 Broadway
Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
HE 039.0072.2015 EAG/SW
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
C.D. 5 (100% SIGNED) SUBMITTAL 10/26/2018
/3
/2
:1 :5
P
M 1/8" = 1'-0"
S001 437-14-112
REPLACE BOILER PLANT 10.26.18
GENERAL STRUCTURAL NOTES
100% CONSTRUCTION DOCUMENTS
S001.DWG 4
S101
4 4 4
S101
S101
EXIST. FTG. (V.) EXIST. FDN. WALL (V.)
EXIST. FTG. (V.)
EXIST. FDN. WALL (V.)
EXIST. FTG. (V.)
EXIST. FDN. WALL (V.)
EXIST. FTG. (V.)
EXIST. FDN. WALL (V.)
6' - 0" 8"
3' - 4" 8"
(V
(E) TRENCH DRAIN
T.O. EXIST SLAB EL=100'-0" (V)
CONCRETE SLAB OVER 6" FREE DRAINING
GRANULAR FILL OVER VAPOR BARRIER
(SEE SPEC). REINF. W/ #4 @ 1'-4" OC.
T.O. SLAB EL= 93'-0" (VERIFY/MATCH EXIST)
EXISTING BOILER FDN
EXISTING BOILER FDN
KEY NOTES
DEMO EXISTING PIT WALL AS NECESSARY TO INSTALL NEW PIT EXTENSION.1
#5 x 2'-6" DWLS @ 1'-0" O.C. INTO EXIST. PIT WALLS. DRILL & EPOXY INTO
EXIST. FDN. WALLS, 6" EMBED DEPTH.
DEMO EXIST STRUCTURE SEE ARCH FOR DEMO PLANS. DO NOT DAMAGE
EXIST. STRUCTURE. CONTRACTOR TO PATCH EXIST. STRUCTURE THAT
REMAINS AS NECESSARY.
DEMO EXIST. MECH. PAD SEE MECH. FOR DEMO PLANS. INFILL AFTER DEMO
IS COMPLETE W/ NEW CONC. SLAB ON GRADE. DRILL & EPOXY NEW #4 DWLS
@ 1'-0" O.C. INTO EXIST. SLAB, S.D. 3/S101.
INFILL EXIST. PIT W/ GRANULAR FILL & PLACE NEW CONC. SLAB ON GRADE,
DRILL & EPOXY NEW #4 DWLS @ 1'-0" INTO EXIST. SLAB/PIT WALL.
DEMO EXIST. SLAB AS NECESSARY TO INSTALL NEW PIT EXTENSION.
REPLACE W/ NEW 6" CONCRETE SLAB ON GRADE W/ #4 @ 1'-0" O.C.
NEW MECH. PAD. SEE MECHANICAL DRAWINGS FOR NEW PAD SIZE &
CONSTRUCTION (VERIFY SIZE AND LOCATION OF PADS).
DEMO AND REMOVE EXIST GENERATOR PAD. DEMO EXIST. SLAB
AS NECESSARY TO INSTALL NEW GENERATOR PAD, S.D. 4/S101.
#5 X 2'-6" DOWELS @ 1'-0" OC INTO EXIST PIT SLAB (VERIFY), DRILL & EPOXY
INTO EXIST SLAB. 6" EMBED DEPTH.
DEMO & REPLACE EXIST BASEMENT SLAB.10
2 - #5 X 2'-6" DOWEL, DRILL & EPOXY INTO EXIST FOOTING. 6" EMBED DEPTH.11
1' - 4"
EL.= 93'-0" (V)
T.O. SLAB
EL.= 90'-0" (V.)
T.O. SLAB
#4 DWL @ 1'-0" O.C.
DEMO EXIST. PIT WALL
& SLAB AS NECESSARY
SIKA SWELL WATER
STOP OR EQUAL
EXIST. PIT SLAB (V.)
#5 x 2'-6" DWL @ 1'-0" O.C. DRILL
& EPOXY INTO EXIST. SLAB(V.),
6" EMBED DEPTH
(2) #4
#5 @ 1'-0" O.C. E.W.
#4 DWL. @ 1'-0" O.C.
#4 @ 1'-0" O.C. E.W.8" MIN.
PVC WATERSTOP
TO BE INSTALLED
2" CLR.
#4 BENT BARS @ 1'-0" O.C.
CONCRETE SLAB
SEE PLAN
21"
9"
12"
24"
3" VOID
9"
SLAB BY OTHERS (V.)
CONC. SLAB OVER 1 1/2", TYPE "C", 20 GA.
(GALV.) FORM DECK W/ #4 @ 1'-0" EA. WAY
O.C. W/ 3" BRG. @ EA. END
EXTERIOR SLAB EXTENDS BEYOND STOOP
HOLD STOOP SLAB EDGE BACK 2" WHERE
PREMOLDED FILLER
EXIST. CONC. SLABVER.
(M
IN
/2
C
L R
EL.= SEE PLAN
T.O. SLAB
EXIST. FDN. WALL(V.)
EXIST. FTG. (V.)
8"
SEE PLAN
2 - #5 CONT.
1' - 8"
DWL. TO MATCH
@ EA. VERT.
#4 @ 1'-0" O.C.
EA. WAY
#4 DWL. @
1'-4" O.C. - TYP.
/4
F
T
S L
O P
E
/2
EL.= MATCH EXIST.
T.O. FTG.
6"
#4 DWL @ 1'-4" OC. DRILL &
EPOXY INOT EXIST WALL.
5" EMBED DEPTH.
1" 1"
E X
IS
T
S
L A
B
V
#4 x 2'-0" DWLS @ 1'-0" O.C.
DRILL & EPOXY INTO EXIST.
SLAB 5" EMBED DEPTH
EL.=SEE MECH.
T.O. PAD
SEE MECH.
DEMO EXIST. SLAB & PAD AS
NECESSARY TO INSTALL NEW
GENERATOR PAD
SEE ELECTRICAL FOR GENERATOR CONN.
TO FDN INCLUDING VIBRATION
ISOLATION PAD
#4 @ 1'-0" O.C. E.W.
TOP & BOT.
C L
R
EXIST. SLAB (V.)
/2
C L
R
SHEET NOTES
1. VERIFY ALL DIMENSION W/ ARCHITECTURE DRAWINGS
2. CONTRACTOR TO VERIFY ALL EXISTING CONDITIONS AND DIMENSIONS.
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
V e te ra n s A ff a ir s
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
D e p a rt m e n t o f
Dwg. of 6910 - BOILER PLANT
FARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218
EAG EAG SWVA263
Project Phase www.jlgarchitects.com copyright © 2015
Fargo 214 Broadway
Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
HE 039.0072.2015 EAG/SW
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
C.D. 5 (100% SIGNED) SUBMITTAL 10/26/2018
/3
/2
:1 :5
P
M As indicated
S101 437-14-112
REPLACE BOILER PLANT 10.26.18
SLAB/FOUNDATION PLAN
100% CONSTRUCTION DOCUMENTS
S101.DWG
N
1/4" = 1'-0"
FOUNDATION/SLAB PLAN
1/2" = 1'-0"S101
1 PIT EXTENSION DETAIL
1/2" = 1'-0"S101
2 STOOP DETAIL
1/2" = 1'-0"S101
3 SLAB INFILL DETAIL
1/2" = 1'-0"S101
4 GENERATOR FDN. DETAIL
T.O. (E) FTG. = (V.)
M C
X
.6
C
X
.7
C12X20.7
C
X
.7
C
X
.7
C
X
.7
C
X
.7
C12X20.7
C12X20.7C
X
.7
C12X20.7
L3X3X1/4L3 X3X
1/
L3X3X1/4
L3 X3X
1/
L3X3X1/4
EXIST. CATWALK
EXIST. CATWALK
S201
C
X
.2
C
X
.2
C6X8.2
C
X
.2
S201
C
X
.2
L3 X3X
1/
S201
S201
(TYP.)
(TYP.)
(TYP.)
L3 X3X
1/
L3 X3X
1/
S201(TYP.)
C
X
.2
2 EQ. SPACES
EXISTING DOOR OPENING
(V
T.O. CATWALK EL=115'-0" (V.)]
(V
4' - 6" (V)
(V
(V
(V
(V
12' - 10" (V)
/1
(V
5' - 10" (V)3' - 0" (V)
5' - 0" (V)4' - 5" (V)
KEY NOTES
1 DEMO EXIST. CATWALK FRAMING & GRATING AS NECESSARY TO INSTALL
NEW OR EXPANDED PLATFORM FRAMING.
2 CUT AND SHORE EXIST. CATWALK C6 BEAM AS NECESSARY TO INSTALL
NEW C12 CATWALK BEAM. S.D. 2 & 3/S202 FOR CONN. DETAIL.
3 PROVIDE & INSTALL NEW 1" BAR GRATING. MATCH EXIST. DEPTH
AND ELEVATION (VERIFY).
4 DEMO EXIST PORTION OF CATWALK FOR NEW BOILERS, SEE MECH.
REPAIR EXIST HANDRAIL & GRATING AS NECESSARY.
SHEET NOTES
1. MATCH TOP OF STEEL WITH EXIST. CATWALK FRAMING.
3/16 3-12
STEEL BEAM
SEE PLAN
1" BAR GRATING
CONT. L2x2x1/4
1" BAR GRATING
L3x3x1/4 CLIP ANGLE
STEEL BEAM
SEE PLAN
3/16
3/16
EXIST. 1" BAR GRATING (VER.)
EXIST. C6 CHANNEL (VER.)
STEEL BEAM
SEE PLAN
EXIST. 1/4x4" KICK PL VERIFY
DEMO AS NECESSARY FOR
NEW GRATING
3/16
3/16
L3x3x1/4 CLIP ANGLE
STEEL BEAM
SEE PLAN
U.O.N.
8"
EMBED PL 3/8"x6"x10" W/ (2) 1/2" DIA. x 4" H.S.A. DEMO AS
NECESSARY & GROUT SOLID
INTO POCKET IN EXIST.
MASONRY WALL
EXIST. MASONRY
WALL (VER.)
1/4 64
1" BAR GRATING
CONT. L2x2x1/4
STEEL BEAM
SEE PLAN
1/4" STIFF PL
STEEL COL.
SEE PLAN
3/16 3
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
V e te ra n s A ff a ir s
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
D e p a rt m e n t o f
Dwg. of 6910 - BOILER PLANT
FARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218
EAG EAG SWVA263
Project Phase www.jlgarchitects.com copyright © 2015
Fargo 214 Broadway
Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
HE 039.0072.2015 EAG/SW
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
C.D. 5 (100% SIGNED) SUBMITTAL 10/26/2018
/3
/2
:1 :5
P
M As indicated
S201 437-14-112
REPLACE BOILER PLANT 10.26.18
CATWALK FRAMING PLAN
100% CONSTRUCTION DOCUMENTS
S201.DWG
N
1/4" = 1'-0"
CATWALK FRAMING PLAN
1" = 1'-0"S201
1 GRATING BRG. DETAIL
1" = 1'-0"S201
2 CONNECTION DETAIL
1" = 1'-0"S201
3 CONNECTION DETAIL
1" = 1'-0"S201
4 CONNECTION DETAIL @ EXIST.
1" = 1'-0"S201
5 CONNECTION DETAIL
W16x31
S202
W x2
W x2
L3 X3X
1/
L3 X3X
1/
L3 X3X
1/
L3 X3X
1/
L3 X3X
1/
W6X15
W6X15
W6X15
W6X15
W6X15
W6X15
W6X15
W6X15
E X
IS
T
T
R U
S S
V
E R
IF
Y
E X
IS
T
T
R U
S S
V
E R
IF
Y
E X
IS
T
T
R U
S S
V
E R
IF
Y
E X
IS
T
T
R U
S S
V
E R
IF
Y
E
IX
S T
S
T E
E L
J O
IS
T
S
'-0
O
.C
3 3 3
(V
S202
(TYP.)
W
X
W
X
W6X25
W6X25
HSS3X
0.
HSS3X
0.
HSS3X
0.
HSS3X
0.
HSS3X
0.
HSS3X
0.
HSS3X
0.
HSS3X
0.
S202
(TYP.)
W6X15 W6X15
4 4
CO
L.
U P
L3X3X1/4
EXIST. STEEL JOISTS @ 4'-6" O.C.
CO
L.
U P
L3 x3 x1 /4
CO
L.
U P
L3 x3 x1 /4
CO
L. UP
L3x3x1/4
S202
EXIST DOOR
OPENING
T.O. STEEL EL= 112'-0" (V.)T.O. STEEL EL= 128'-6" (V.)
" 4
3/16
3/16
3/16
EL.= SEE ARCH.
ROUGH OPENING
3 SIDES
1/2 RETURN
L6x6x1/2x8" W/ (2) 1/2" DIA. x 6" HSA
DEMO POCKET INTO EXIST. PILASTER
ONLY AS NECESSARY TO INSTALL
EMBED PL, GROUT SOLID
L3x3x5/16 CLIP ANGLE
LINTEL BEAM
SEE PLAN
3/8" LINTEL PL VERIFY
WIDTH REQ'D
PL 1/2"x8"x1'-2" W/ (2) 3/4" DIA.
ANCHOR RODS (4" GAGE)
DRILL & EPOXY INTO EXIST.
PILASTER 8" EMBED
EXIST. PILASTER(V.)
1/4" LINTEL PL VERIFY WIDTH
W/ EXIST. WALL THICKNESS
NEW LINTEL BEAM
SEE PLAN
EXIST. MASONRY WALL(VER.)
1' - 0" C.M.U.
1/2" 1/2"
EL=SEE ARCH
CONTRACTOR TO DEMO AND
PATCH EXIST. MASONRY AS
NECESSARY TO INSTALL NEW
LINTEL3/16
TYP.
3-12
STEEL LINTEL
SEE PLAN
1/4" LINTEL PL x R.O.
U.O.N.
8"
EMBED PL 3/8"x8"x7" W/ (2) 1/2" DIA. x
4" H.S.A. DEMO AS NECESSARY &
GROUT SOLID INTO POCKET IN EXIST.
MASONRY WALL
EXIST. MASONRY
WALL (VER.)
3/16 3-12 1/4 6
KEY NOTES
CONTRACTOR TO SHORE EXIST. MASONRY WALL AS NECESSARY TO
INSTALL NEW LINTEL FOR NEW BOILER INSTALLATION. S.D. 1/S202 FOR
LINTEL CONNECTION DETAIL.
CONTRACTOR TO INSTALL NEW LINTEL FOR MECH. OPENING IN
EXIST. MASONRY WALL. VERIFY REQUIRED ROUGH OPENING
SIZE W/ MECHANICAL, S.D. 2 & 3/S202.
VERIFY SIZE & LOCATION OF NEW ECONOMIZER MECH. UNITS. PLACE
NEW W6 SUPPORT TO SUPPORT UNITS.
NEW W6 SUPPORT BEAM AS NECESSARY TO SUPPORT NEW L3x3x1/4
DROP COLUMN VERIFY LOCATION IN FIELD W/ MECH. EPQUIPMENT &
CATWALK LAYOUTS.
NEW MECH. UNIT TO BE SUPPORTED BY NEW STEEL FRAME,
S.D. 5/S202. VERIFY SIZE & LOCATION W/ MECH.
CONTRACTOR TO PATCH AND INFILL EXIST. LOW ROOF OPENING.
CONTRACTOR TO VERIFY SIZE & LOCATION OF OPENING TO BE
FILLED. S.D. 6/S202 FOR OPENING PATCH DETAIL.
7 CONTRACTOR TO INFILL & ROOF OVER EXIST ROOF OPENING
VERIFY NUMBER & SIZE WITH ARCH & MECH DRAWINGS.
SHEET NOTES
1. CONTRACTOR TO PATCH AND INFILL EXIST. ROOF OPENINGS THAT WILL
BE ABANDONED AS PART OF THIS PROJECT. CONTRACTOR TO VERIFY
QUANTITY & SIZE OF OPENING TO BE IN FILLED.
STEEL BEAM
SEE PLAN
EXIST. STEEL
JOIST
1/4
TYP.
EL.= 122'-0" (V.)
T.O. STEEL
ADD 3/8" STIFF PL
CENTER ON
STEEL BEAM 3/16
TYP.
STEEL BEAM
SEE PLAN
HSS3.0x.25
PL 1/4"x6"x6"
EXIST. STEEL JOIST
@ 4'-0" O.C. (VER.)
EL.= MECH VERIFY
T.O. STEEL
1/8 3
EXIST. STEEL JOISTS
@ 4'-0" OC
(V.) (V.)
EQ EQ EQ EQ
EXIST. CONC. INFILL TO MATCH EXIST.
CONC. DEPTH
EXIST. CONC.
L2X2X1/4
3/163/16
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
V e te ra n s A ff a ir s
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
D e p a rt m e n t o f
Dwg. of 6910 - BOILER PLANT
FARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218
EAG EAG SWVA263
Project Phase www.jlgarchitects.com copyright © 2015
Fargo 214 Broadway
Fargo, ND 58102 phone 7 0 1.3 6 4.0 2 3 7 facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
HE 039.0072.2015 EAG/SW
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
C.D. 5 (100% SIGNED) SUBMITTAL 10/26/2018
/3
/2
:1 :5
P
M As indicated
S202 437-14-112
REPLACE BOILER PLANT 10.26.18
ROOF FRAMING PLAN
100% CONSTRUCTION DOCUMENTS
S202.DWG
N
1/4" = 1'-0"
ROOF FRAMING PLAN
1" = 1'-0"S202
1 CONNECTION DETAIL
1" = 1'-0"S202
2 LINTEL DETAIL
1" = 1'-0"S202
3 LINTEL BRG. DETAIL
1" = 1'-0"S202
4 CONNECTION DETAIL @ EXIST.
1" = 1'-0"S202
5 JOIST BRG. DETAIL
1" = 1'-0"S202
6 LOW ROOF OPENING PATCH DETAIL
File details come from the government source that posted it.