Amendment 0003 - Attachment 18. Grating and Fall Protection Railing Criteria.pdf

PDF 300 KB Posted

Attached to
Modernize Pathology Department, Bldg. 1 (VA-24-00001439)
Solicitation number
36C26223B0016_1
Issued by

About this file

This document provides criteria for fiberglass grating and fall protection railing to be installed as part of a federal contract opportunity with the Department of Veterans Affairs. The criteria specify that the grating shall be 2-inch square mesh fiberglass grating with a maximum span of 48 inches. The grating and support system must be engineered and stamped by a registered professional engineer to support a 50 psf live load plus a 300 lb concentrated load. Deflections must be limited to L/240 under loading. Beam connections require a minimum of two 1/2-inch bolts and anchors to concrete shall be 5/8-inch diameter Hilti Kwik Bolt TZ2 or Hilti HIT RE-500 V3 adhesive anchors. A minimum of two holddown clips per section are required at each support point and abutment clips must be installed at midspan of unsupported edges.

View the file

Other files

File Type Posted
Contract Award Notice_36C26223C0282.pdf PDF
Amendment 0003 - Attachment 9. 1XA.pdf PDF
Amendment 0003 - Attachment 21. DWGFINALSUBMITTAL.pdf PDF
Amendment 0003 - Attachment 16. Structural Drawings.pdf PDF
Amendment 0003 - Attachment 7. 1CEXM.pdf PDF
Amendment 0003 - Attachment 12. MCC.pdf PDF
Amendment 0003 - Attachment 22. Building 1 Fire Spinkler Valves 8.5x11.pdf PDF
Amendment 0003 - Attachment 3. 1CEXC Rev1.pdf PDF
Amendment 0003 - Attachment 20. MH-6.03 Rev01.pdf PDF
Amendment 0003 - Attachment 1. 1A Rev1.pdf PDF
Amendment 0003 - Attachment 2. 1CEXB Rev1.pdf PDF
Amendment 0003 - RFI Notice.pdf PDF
Amendment 0003 - Attachment 5. 1CEXG Rev1.pdf PDF
Amendment 0003 - Attachment 19. VA SD Master Finish Legend.pdf PDF
Amendment 0003 - Attachment 4. 1CEXF Rev1.pdf PDF
Amendment 0003 - Attachment 14. Comprehensive Hazardous Materials Survey.pdf PDF
Amendment 0003 - Attachment 10. 1XAA Rev1.pdf PDF
Amendment 0003 - Attachment 11. 1XR Rev1.pdf PDF
Amendment 0003 - Attachment 13. Panel Photos.pdf PDF
Solicitation Amendment 0003 (SF30)_36C26223B0016 0003.pdf PDF
Amendment 0003 - Attachment 17. Record Drawings.pdf PDF
Amendment 0003 - Attachment 6. 1CEXGA Rev1.pdf PDF
Amendment 0003 - Attachment 15. 1st Floor PA.pdf PDF
Amendment 0003 - Attachment 8. 1CEXN.pdf PDF
S06 - Amendment 0002_ Att J. Pre-Bid Conference Site Visit Sign-in Sheet.pdf PDF
S06 - Solicitation Amendment 0002 (SF30)_36C26223B0016 0002.pdf PDF
S06 - Solicitation Amendment (SF30)_36C26223B0016 0001.pdf PDF
S02 - Att F. IFC Drawings 3.pdf PDF
S02 - Att A. Statement of Work_VASD Modernize Pathology.pdf PDF
S02 - Att H. Site Visit Map.pdf PDF
S02 - Att C. Specifications - VASD Modernize Pathology Project Manual_Vol 2.pdf PDF
S02 - Att E. IFC Drawings 2.pdf PDF
S02 - Att G. DB Wage Rates_GDN CA20230001 06.09.2023.pdf PDF
S02 - Att D. IFC Drawings 1.pdf PDF
S02 - Solicitation (SF1442)_36C26223B0016.pdf PDF
S02 - Att B. Specifications - VASD Modernize Pathology Project Manual_Vol 1.pdf PDF
Show all 36

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GRATING CRITERIA

1. Contractor shall be responsible for layout and engineering of the complete grating support system and its connections and anchorage. Calculations and drawings shall be submitted for review and approval and shall be stamped by a registered Professional

Engineer (PE).

2. Grating shall be a commercial grade 2‐inch deep by 2‐inch square mesh open molded fiberglass grating. Maximum grating span shall be 48‐inches.

3. Fiberglass shall be manufactured from a premium grade Isophthalic Polyester Resin system with Class I fire retardancy per ASTM E‐84.

4. Grating support system shall consist of fiberglass structural shapes and ledge angles and their design shall conform to the following requirements:

a. Support beams shall be designed for a 50 psf uniform live load over the entire tributary grated area plus concurrently a 300 lb. concentrated load applied at the center of the beam span.

b. Deflections of support members and ledge angles shall be limited to L/240 under the above loading conditions.

5. Beam to beam structural connections shall be a minimum of two (2) 1/2‐inch diameter bolts.

6. Anchorage to concrete shall be with minimum 5/8‐inch diameter anchors. Acceptable anchors are Hilti Kwik Bolt TZ2 or adhesive anchors using Hilti HIT RE-500‐ V3 adhesive anchoring system.

7. A minimum of two hold‐down clips shall be installed on each fiberglass grating section at each support point. Install abutment clips at midspan of all unsupported grating edges to tie the adjacent grating sections together.