The amendment extends the quote submission deadline to October 9, 2026, at 4:00 PM PST and provides a revised price schedule that offerors must use for their proposals. The solicitation is a 100% set-aside for Service-Disabled Veteran-Owned Small Business (SDVOSB) concerns and covers fire alarm and protection system inspection and preventive maintenance in accordance with a Performance Work Statement. The inspection certificates document comprehensive annual testing completed on January 28-30, 2026, for two buildings (PA5 and PA7) at 3801 Miranda Ave, Palo Alto, CA 94304, performed by scDataCom (Inspector: Derrick Tillman) in compliance with NFPA 101 (Life Safety Code, 2024 Edition), NFPA 72 (Fire Alarm Systems, 2022 Edition), and NFPA 90A (Air Conditioning/Ventilating Systems, 2022 Edition). The testing included 326 devices at PA5 (all passed, zero failures) and 329 devices at PA7 (all passed, zero failures), encompassing tamper switches, waterflow switches, duct detectors, heat detectors, pull stations, smoke detectors, speakers, strobes, releasing devices, control panels, batteries, power supplies, elevators, and related fire suppression and life safety equipment. The work was performed in compliance with The Joint Commission/VHA Standards and latest VHA clarification memoranda on engineering and life safety standards. The contracting agency is the Department of Veterans Affairs Veterans Health Administration, Veterans Integrated Service Network 21 (VISN 21).
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate
For
PA5
3801 Miranda Ave
Palo Alto, CA 94304
This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR
CONDITIONING/VENTILATING SYSTEMS.
This inspection and testing service has been performed in compliance with The Joint Commission/VHA
Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.
Annual Inspection
Inspection Completion Date
Jan 30, 2026
Building: PA5 Company: scDataCom
Contact: Anthony Losito Contact: Derrick Tillman
Title: Electronics Shop Supervisor Title: Technician scDataCom 1 Download Date: 02/04/2026
Executive Summary
Generated by: BuildingReports.com
Building Information
Building: PA5 Contact: Anthony Losito
Address: 3801 Miranda Ave Phone: 6508523437
Address: Fax:
City/State/ZIP Code: Palo Alto, CA 94304 Mobile:
Country: United States of America Email:
Inspection Performed By
Company: scDataCom Inspector: Derrick Tillman
Address: 2700 Gregory St Ste 180 Phone: (669) 333-6375
Address: Fax:
City/State/ZIP Code: Savannah, GA 31404 Mobile:
Country: United States of America Email: dtillman@pavion.com
System Control Unit
Manufacturer: Notifier Inspection Date: 01/30/2026 IDC Style:
Model Number: NFS-3030D Install Date: 05/10/2017 SLC Style:
Software Version: Version Date: 05/10/2017 NAC Style:
Location: 1st Floor Electrical Room Bldg 5 FACP Current Protection:
scDataCom 2 Download Date: 02/04/2026
Inspection Completion Date: Jan 30, 2026
Building: PA5
EC 02.03.05 EP 01
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; room temperature supervisory and other supervisory initiating devices.
Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2
(17)(10)(b-g)
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
(2026) Total Quantity
Tamper Switch 22 22 0 22 0 22
EC 02.03.05 EP 02
Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2
(17)(10)(a) & (17)(11)
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
Waterflow Switch 14 14 0 14 0 14
EC 02.03.05 EP 03
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72
(2022) Table 14.4.3.2 (17)
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
(2026) Total Quantity
Duct Detector 23 23 0 23 0 23
Heat Detector 24 24 0 24 0 24
Pull Station 28 28 0 28 0 28
Smoke Detector 33 33 0 33 0 33
EC 02.03.05 EP 04
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72
(2022) Table 14.4.3.2 (22)
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
(2026) Total Quantity
Releasing Device 8 8 0 8 0 8
Speaker 16 16 0 16 0 16
Speaker/Strobe 114 114 0 114 0 114
Strobe 12 12 0 12 0 12
Voice Evacuation 3 3 0 3 0 3
EC 02.03.05 EP 05
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2
(4)
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
Monitor Device 6 6 0 6 0 6
EC 02.03.05 EP 11
For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
Fire Pump Auto 1 1 0 1 0 1
EC 02.03.05 EP 19
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024)
6.4.1
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
(2026) Total Quantity
Duct Detector 23 23 0 23 0 23
Fan Shutdown 1 1 0 1 0 1
LS 02.01.34 EP 02
Protected master fire alarm control panel
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
Control Panel 1 1 0 1 0 1 scDataCom 3 Download Date: 02/04/2026
LS 02.01.34 EP 10
All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
(2026) Total Quantity
Annunciator 2 2 0 2 0 2
Battery 10 10 0 10 0 10
Power Supply 3 3 0 3 0 3
Programmable Relay 1 1 0 1 0 1
LS 02.01.50 EP 07
Annual - Elevators are fully equipped and protected
Devices
Tested This
Quarter Pass Fail
Tested YTD
(2026)
Untested YTD
(2026) Total Quantity
Elevator 4 4 0 4 0 4
Total Device Count: 326 scDataCom 4 Download Date: 02/04/2026
Certification
Company: scDataCom Building: PA5
Inspector: Derrick Tillman Contact: Anthony Losito scDataCom 5 Download Date: 02/04/2026
Inspection & Testing
The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.
Passed=P, Failed=F, Replaced=R
Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;
water temperature supervisory; room temperature supervisory and other supervisory initiating devices.
Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2
(17)(10)(b-g)
Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a))
Devices Tested Q1/26 Pass Q1/26 Fail Q1/26 Tested YTD (2026) Total Quantity
Tamper Switch 22 22 0 22 22
Device Type Location ScanID Address Q1/25 Q1/26
Tamper Switch 1st Floor Area B Stair Riser 12535329 1-L1 M07 03/11-P 01/29-P
Tamper Switch 4th Floor Stair 1 12535550 1-L002 M019 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211863 1-L1 M059 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211870 1-L1 M055 / PIV 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211873 1-L1 M057 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211869 1-L1 M057 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211872 1-L1 M057 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211874 1-L1 M057 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211875 1-L1 M057 03/12-P 01/29-P
Tamper Switch Outside Fire Pump 45211871 1-L1 M057 03/12-P 01/29-P
Tamper Switch 1st Stair C 12535350 1-L1 M04 03/12-P 01/29-P
Tamper Switch 1st Stair 1 12535345 1-L1 M09 03/12-P 01/29-P
Tamper Switch 1st Stair 3 12535302 1-L1 M11 03/12-P 01/29-P
Tamper Switch 2nd Stair 1 12535371 1-L1 M29 03/12-P 01/29-P
Tamper Switch 2nd South Fire Exit Stairwell 12535406 1-L1 M27 03/12-P 01/29-P
Tamper Switch 2nd North Stair 3 12535376 1-L1 M31 03/12-P 01/29-P
Tamper Switch 3rd Stairs Exit Near Police 12535525 1-L2 M07 03/12-P 01/29-P
Tamper Switch 3rd Stairs 1 12535418 1-L2-M09 03/12-P 01/29-P
Tamper Switch 3rd Stair 3 45210220 1-L2 11 03/13-P 01/29-P
Tamper Switch 4th North Stair 3 12535542 1-L2 M21 03/12-P 01/29-P
Tamper Switch 4th Area B Stair Riser 12535554 1-L2 M17 03/12-P 01/29-P
Tamper Switch Roof Area A Stair Riser Penthouse 12535536 1-L002 M030 03/13-P 01/29-P
Device Total: 22 scDataCom 6 Download Date: 02/04/2026
(17)(10)(a) & (17)(11)
Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11))
Waterflow Switch 14 14 0 14 14
Waterflow Switch 1st Floor Area B Stair Riser 12535330 1-L1 M06 03/11-P 01/29-P
Waterflow Switch 1st Stair C 12535351 1-L1 M03 03/12-P 01/29-P
Waterflow Switch 1st Stair 1 12535346 1-L1 M08 03/12-P 01/29-P
Waterflow Switch 1st Stair 3 12535303 1-L1 M10 03/12-P 01/29-P
Waterflow Switch 2nd Stair 1 12535372 1-L1 M28 03/12-P 01/29-P
Waterflow Switch 2nd South Fire Exit Stairwell 12535405 1-L1 M26 03/12-P 01/29-P
Waterflow Switch 2nd North Stair 3 12535377 1-L1 M30 03/12-P 01/29-P
Waterflow Switch 3rd Stairs Exit Police 12535526 1-L2 M06 03/12-P 01/29-P
Waterflow Switch 3rd Stairs 1 12535419 1-L2-M08 03/12-P 01/29-P
Waterflow Switch 3rd Stair 3 Stairs Exit 45210219 1-L2 10 03/13-P 01/29-P
Waterflow Switch 4th North Stair 3 12535543 1-L2 M20 03/12-P 01/29-P
Waterflow Switch 4th Stair 1 12535551 1-L002 M018 03/12-P 01/29-P
Waterflow Switch 4th Area B Stair Riser 12535555 1-L2 M16 03/12-P 01/29-P
Waterflow Switch Roof Area A Stair Riser Penthouse 12535537 1-L002 M029 03/13-P 01/29-P
Device Total: 14 scDataCom 7 Download Date: 02/04/2026
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72
(2022) Table 14.4.3.2 (17)
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))
Duct Detector 23 23 0 23 23
Duct Detector Basement Area C 45212593 1-L1 D36 03/17-P 01/29-P
Duct Detector Basement Boiler Room B-113 45210824 1-L1 D24 03/17-P 01/29-P
Duct Detector 1st Men's Restroom Area A 45212765 1-L1 D11 03/17-P 01/30-P
Duct Detector 1st Women's Restroom Area A 45212764 1-L1 D23 03/13-P 01/29-P
Duct Detector 1st Men's Restroom Area A 84048757 1-L1 D11
01/29-P
Duct Detector 1st Outside By Room A-117A Elevator
Lobby
45212766 1-L1 D9 03/13-P 01/29-P
Duct Detector 1st Room A-117A 45212767 1-L1 D8 03/13-P 01/29-P
Duct Detector 2nd In Room B-232 12535367 1-L1 D12 03/13-P 01/29-P
Duct Detector 2nd In Room B-226 12535368 1-L1 D13 03/13-P 01/29-P
Duct Detector 2nd Back Counter In Room A252 12535397 1-L1 D17 03/13-P 01/29-P
Duct Detector 2nd Women's Restroom Area A 45212759 1-L1 D35 03/17-P 01/29-P
Duct Detector 2nd Men's Restroom A-241 45212757 1-L01 D34 03/13-P 01/29-P
Duct Detector 3rd In Office B322 in Hatch 45212595 1-L02 D02 03/17-P 01/29-P
Duct Detector 3rd Women's Locker Room B323 45212594 1-L02 D03 03/17-P 01/29-P
Duct Detector 3rd Men's Restroom Area A 45212756 1-L02 D09 03/13-P 01/29-P
Duct Detector 3rd Women's Rest Room Area A 45212755 1-L02 D10 03/13-P 01/29-P
Duct Detector 3rd Elevator Corridor Area A 45212758 1-L02 D07 03/13-P 01/29-P
Duct Detector 4th Corner of rm Inside Room B-429 45212760 1-L2 D12 03/13-P 01/29-P
Duct Detector 4th Men's Restroom Area A 45212761 1-L2 D14 03/13-P 01/29-P
Duct Detector 4th Women's Restroom Area A 45212762 1-L2 D18 03/13-P 01/29-P
Duct Detector 4th Reception Area A-432 ABOVE COPIER
MACH.
45212763 1-L2 D17 03/13-P 01/29-P
Duct Detector Roof Roof AHU.4 ROOF mounted outside unit
45208351 1-L2 D023 03/17-P 01/29-P
Duct Detector Roof Roof AHU-3 45210815 1-L2 D24 03/13-P 01/29-P
Device Total: 23 scDataCom 8 Download Date: 02/04/2026
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72
(2022) Table 14.4.3.2 (17)
Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.
Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))
Heat Detector 24 24 0 24 24
Heat Detector Roof Roof ROOF Penthouse Heat 84049416 1-L02 D55
Heat Detector Roof Roof ROOF Penthouse Heat 84049415 1-L02 D54
Heat Detector Roof Roof ROOF Penthouse Heat 84049413 1-L02 D43
Heat Detector Roof Roof ROOF Penthouse Heat 84049412 1-L02 D55
Heat Detector Roof Roof ROOF Penthouse Heat 84049411 1-L02 D56
Heat Detector Roof Roof ROOF Penthouse Heat 84049410 1-L02 D57
Heat Detector Roof Roof ROOF Penthouse Heat 84049409 1-L02 D58
Heat Detector Roof Roof ROOF Penthouse Heat 84049408 1-L02 D60
Heat Detector Roof Roof ROOF Penthouse Heat 84049407 1-L02 D59
Heat Detector Roof Roof ROOF Penthouse Heat 84049406 1-L02 D48
Heat Detector Roof Roof ROOF Penthouse Heat 84049425 1-L02 D51
Heat Detector Roof Roof ROOF Penthouse Heat 84048770 1-L02 D47
Heat Detector Roof Roof ROOF Penthouse Heat 84048769 1-L02 D46
Heat Detector Roof Roof ROOF Penthouse Heat 84048768 1-L02 D45
Heat Detector Roof Roof ROOF Penthouse Heat 84048767 1-L02 D49
Heat Detector Roof Roof ROOF Penthouse Heat 84048766 1-L02 D50
Heat Detector Roof Roof ROOF Penthouse Heat 84048765 1-L02 D44
Heat Detector Roof Roof ROOF Penthouse Heat 84048764 1-L02 D66
Heat Detector Roof Roof ROOF Penthouse Heat 84048763 1-L02 D65
Heat Detector Roof Roof ROOF Penthouse Heat 84048762 1-L02 D64
Heat Detector Roof Roof ROOF Penthouse Heat 84048761 1-L02 D63
Heat Detector Roof Roof ROOF Penthouse Heat 84048760 1-L02 D61
Heat Detector Roof Roof ROOF Penthouse Heat 84048759 1-L02 D61
Heat Detector Roof Roof ROOF Penthouse Heat 84048758 1-L02 D67
Device Total: 24 scDataCom 9 Download Date: 02/04/2026
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72
(2022) Table 14.4.3.2 (17)
Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5))
Pull Station 28 28 0 28 28
Pull Station 1st Floor Elevator Area C 45207772 1-L001 M020 03/11-P 01/29-P
Pull Station 1st Floor Area B Stair Exit 45207743 1-L001 M041 03/11-P 01/29-P
Pull Station 1st Floor Prosthetic Storage Room C-166 45208174 1-L001 M021 03/11-P 01/29-P
Pull Station 1st Floor Radiology Sciences Laboratory
Room C-181
45208176 1-L01 03/11-P 01/29-P
Pull Station 1st Floor Room A117B 45208185 1-L001 M018 03/11-P 01/29-P
Pull Station 1st Floor FACP ROOM Exit A 114 45207733 1-L001 M005 03/11-P 01/29-P
Pull Station 1st Floor Area B Stair Exit 45207742 1-L001 M012 03/11-P 01/29-P
Pull Station 4th Floor Area B Stair Exit 12535557 1-L002 M015 03/12-P 01/29-P
Pull Station 1st STAIRWELL 1 84048756 1-L1 M40
Pull Station 1st Wheel Chair Repair Room Area A 45208193 1-L01 M15 03/11-P 01/29-P
Pull Station 1st Wheel Chair Repair Room Area A 45208192 1-L001 M014 03/11-P 01/29-P
Pull Station 1st Amputee SVC Room B136 45208189 1-L01 M22 03/11-P 01/29-P
Pull Station 1st Amputee SVC A236 45208191 1-L01 M43 03/11-P 01/29-P
Pull Station 1st Room A-117A 45212768 1-L1 M19 03/12-P 01/29-P
Pull Station 1st Exit Near A-100 45210806 1-L1 M16 03/11-P 01/29-P
Pull Station 1st Area B Stair Exit 840656 1-L001 M040
Pull Station 1st Entrance 45210805 1-L1 M17 03/11-P 01/29-P
Pull Station 1st By Room A-116 12535347 1-L1 M13 03/11-P 01/29-P
Pull Station 2nd North Entrance To Fire Exit Stairs 45210646 1-L1 M36 03/11-P 01/29-P
Pull Station 2nd South Outside Entrance To Fire Exit
Stairs
45210610 1-L1 M32 03/13-P 01/29-P
Pull Station 2nd Entrance To Central Fire Exit Stairs 45210623 1-L1 M34 03/13-P 01/29-P
Pull Station 3rd Stairs Exit 45210245 1-2 5 03/13-P 01/29-P
Pull Station 3rd Stairs Exit 45210236 1-2 M12 03/11-P 01/29-P
Pull Station 3rd Stairs Exit 45210218 1-L02 M13 03/13-P 01/29-P
Pull Station 4th North Entrance To Fire Exit Stairs 45210654 1-L2 M23 03/13-P 01/29-P
Pull Station 4th Central Entrance To Fire Exit Stairs 45210672 1-L2 M22 03/13-P 01/29-P
Pull Station Roof South Exit Penthouse 45208211 1-L02 M32 03/13-P 01/29-P
Pull Station Roof Penthouse North Exit To Roof 45210675 1-L2 M31 03/12-P 01/29-P
Device Total: 28 scDataCom 10 Download Date: 02/04/2026
Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72
(2022) Table 14.4.3.2 (17)
Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2
(17)(7)(a))
Smoke Detector 33 33 0 33 33
Smoke Detector 1st Floor Telecom Rm A186 45208187 1-L001 D032 03/11-P 01/30-P
Smoke Detector 1st Floor Telecom Rm A 308 45207740 1-L001 D027 03/12-P 01/30-P
Smoke Detector 1st Floor Room B-427F Area B Above
Ceiling
12535559 1-L002 D013 03/12-P 01/30-P
Smoke Detector 1st Floor Corridor At B 109 45207751 1-L001 D28 03/11-P 01/29-P
Smoke Detector 1st Floor STAIRWELL 2 Elevator Area C
NORTH
45207770 1-L001 D010 03/12-P 01/29-P
Smoke Detector 1st Floor Corridor At C 159 45207767 1-L001 D031 03/11-P 01/29-P
Smoke Detector 1st Floor Elevator S7 LOBBY 45207762 1-L001 D004 03/13-P 01/29-P
Smoke Detector 1st Floor Corridor At C 181 45207766 1-L001 D007 03/11-P 01/29-P
Smoke Detector 1st Floor Corridor At A 183 45207765 1-L001 D006 03/11-P 01/29-P
Smoke Detector 1st Floor Elevator P-5 & P-6 45207761 1-L001 D005 03/13-P 01/29-P
Smoke Detector 1st Floor Corridor At B 105 45207756 1-L001 D003 03/11-P 01/29-P
Smoke Detector 1st Floor Corridor At B 106 45207755 1-L001 D002 03/11-P 01/29-P
Smoke Detector 1st Floor Corridor At B 108 45207749 1-L001 D029 03/11-P 01/29-P
Smoke Detector 1st Floor Corridor At Area B 45207741 1-L001 D026 03/11-P 01/29-P
Smoke Detector 1st Floor FACP Room B 114 45207734 1-L001 D001 03/11-P 01/29-P
Smoke Detector 1st Corridor By C-176 45210811 1-L1 D-30 03/11-P 01/29-P
Smoke Detector 2nd B-311 44230235 1-L001 D01 03/12-P 01/30-P
Smoke Detector 2nd North Ceiling Of Waiting Room C 45210637 1-L1 D21 03/13-P 01/29-P
Smoke Detector 2nd North Entrance To Waiting Room C 45210636 1-L1 D20 03/13-P 01/29-P
Smoke Detector 2nd South Waiting Room B 45210618 1-L1 M14 03/13-P 01/29-P
Smoke Detector 2nd South Entrance To Waiting Room B 45210621 1-L1 M15 03/11-P 01/29-P
Smoke Detector 2nd Central Hallway Elevator Lobby ELEV.
S7 LOBBY
45210631 1-L1 D16 03/13-P 01/29-P
Smoke Detector 2nd Central Hallway Elevator Lobby P5 &
P6 ELEV..
45210630 1-L1 D18 03/13-P 01/29-P
Smoke Detector 2nd North Stairwell 2 Elevator AREA C
ELEV. S8
45210648 1-L1 D22 03/13-P 01/29-P
Smoke Detector 3rd LOBBY Elevator S7 45210230 1-2 D008 03/13-P 01/29-P
Smoke Detector 3rd Lobby Elevator P5 & P6 45210231 1-2 D006 03/13-P 01/29-P
Smoke Detector 3rd ELEV. S8 LOBBY STAIR 2 45210221 1-2 D11 03/13-P 01/29-P
Smoke Detector 4th North RM 425 45212097 1-L2 D19 03/13-P 01/29-P
Smoke Detector 4th North Stairwell 2 Elevator ELEV. S8 45210656 1-L2 D20 03/13-P 01/29-P
Smoke Detector 4th S7 Elevator LOBBY ALCOVE 45210668 1-L2 D15 03/13-P 01/29-P
Smoke Detector 4th Central Hallway Elevator Lobby Lobby
Elevator P5 & P6
45210669 1-L2 D16 03/13-P 01/29-P
Smoke Detector Roof P6 And P5 Elevator Machinery
Enclosure PENTHOUSE
45210677 1-L2 D21 03/17-P 01/29-P
Smoke Detector Roof Mechanical ELEVATOR P5/P6
PENTHOUSE MECH.
45210814 1-L2 D22 03/17-P 01/29-P
Device Total: 33 scDataCom 11 Download Date: 02/04/2026
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72
(2022) Table 14.4.3.2 (22)
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Releasing Device 8 8 0 8 8
Releasing Device 1st Corridor By C-181 45212096 1 03/12-P 01/29-P
Releasing Device 1st Corridor By C-181 45212095 1 03/12-P 01/29-P
Releasing Device 1st Corridor By C-176 45212094 1 03/12-P 01/29-P
Releasing Device 1st Corridor By B-108 45208349 1 03/12-P 01/29-P
Releasing Device 1st Corridor By B-108 45208348 1 03/12-P 01/29-P
Releasing Device 1st Corridor By A-116 45208347 1 03/12-P 01/29-P
Releasing Device 2nd Outside Men's Bathroom Ceiling
A-241
45208346 1 03/12-P 01/29-P
Releasing Device 2nd Outside Men's Bathroom Ceiling
A-241
45208345 1 03/12-P 01/29-P
Device Total: 8 scDataCom 12 Download Date: 02/04/2026
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72
(2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2))
Speaker 16 16 0 16 16
Speaker 1st Floor Elevator P-5 & P-6 45207760 1-SP1 8-Feb 03/12-P 01/29-P
Speaker 1st Floor Corr Near B-114 45207747 1-SP1 4-Jan 03/12-P 01/29-P
Speaker 4th Floor Corr Near B-411 45208206 1-SP4 8-Jan 03/12-P 01/29-P
Speaker 4th Floor Corr Near B-429 45208203 1-SP4 7-Jan 03/12-P 01/29-P
Speaker 4th Floor Corr Near Area B Stair 45208198 1-SP4 3-Jan 03/12-P 01/29-P
Speaker 1st Corridor By C-150 45210812 1-SP1. 7-Mar 03/12-P 01/29-P
Speaker 2nd North Hallway Outside Room C-282 45210649 1-SP2.3 10 03/13-P 01/29-P
Speaker 2nd North Hallway Outside Room C-262 45210643 1-SP2.3 4 03/13-P 01/29-P
Speaker 2nd Central Hallway Elevator Lobby 45210627 1-SP2.2 8 03/13-P 01/29-P
Speaker 2nd South Hallway Ceiling Outside RM
B-226
45210614 1-SP2.1 4 03/13-P 01/29-P
Speaker 2nd South Hallway Ceiling Outside RM
B-208
45210608 1-SP2.1 7 03/13-P 01/29-P
Speaker 3rd Hallway Near B308 45210246 1-SP 3.1-2 03/13-P 01/29-P
Speaker 3rd Hallway Near A-349 45210233 1-SP 3.2-5 03/13-P 01/29-P
Speaker 3rd Hallway Near C-380 45210224 1-SP 3.3-2 03/13-P 01/29-P
Speaker 3rd Hallway Near C-380 45210217 1-SP 3.3-6 03/13-P 01/29-P
Speaker 4th Central Elevator Lobby 45210670 1-SP4.2 5 03/13-P 01/29-P
Device Total: 16 scDataCom 13 Download Date: 02/04/2026
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72
(2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2))
Speaker/Strobe 114 114 0 114 114
Speaker/Strobe 1st Floor Simulation Center Room C-181 45208178 1-ST1/SP1 03/12-P 01/29-P
Speaker/Strobe 1st Floor Simulation Center Room C-181 45208179 1-ST1/SP1
3-1/3-1
03/12-P 01/29-P
Speaker/Strobe 1st Floor Room A-118 45208180 1-ST1/SP1
2-10/2-11
03/12-P 01/29-P
Speaker/Strobe 1st Floor Room A-184 45208181 1-ST1/SP1
2-9/2-10
03/12-P 01/29-P
Speaker/Strobe 1st Floor Room A-101 45208182 1-ST1/SP1
2-7/2-7
03/12-P 01/29-P
Speaker/Strobe 1st Floor Simulation Center Room C-181 45208177 1-ST1/SP1
3-2/3-2
03/12-P 01/29-P
Speaker/Strobe 1st Floor Simulation Center Room C-181 45208175 1-ST1/SP1 03/12-P 01/29-P
Speaker/Strobe 1st Floor Physical Therapy Room C-166 45208173 1-ST1/SP1
3-13/3-13
03/12-P 01/29-P
Speaker/Strobe 1st Floor Physical Therapy Room C-166 45208172 1-ST1/SP1
3-11/3-12
03/12-P 01/29-P
Speaker/Strobe 1st Floor Optometry Conf Room C-172 45208171 1-ST1/SP1
3-8/3-9
03/12-P 01/29-P
Speaker/Strobe 1st Floor Occupational Health Program
Room C-149
45208170 1-ST1/SP1
3-4/3-4
03/12-P 01/29-P
Speaker/Strobe 1st Floor Elevator Area C 45207771 1-ST1/SP1
3-9/3-10
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corridor At C 171 45207769 1-ST1/SP1
3-7/3-8
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corridor At C Stair 45207768 1-ST1/SP1
3-10/3-11
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corridor At A 183 45207764 1-ST1/SP1
2-11/2-12
03/12-P 01/29-P
Speaker/Strobe 1st Floor Elevator S7 45207763 1-ST1/SP1
2-8/2-9
03/12-P 01/29-P
Speaker/Strobe 1st Floor West Exit Area A 45207759 1-ST1/SP1
2-4/2-4
03/12-P 01/29-P
Speaker/Strobe 1st Floor Men's Rest Room Near A-116 45207758 1-ST1/SP1
2-2/2-2
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corr At Room A-116 45207757 1-ST1/SP1
2-3/2-3
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corr At Room B-106 45207754 1-ST1/SP1
1-2/1-2
03/12-P 01/29-P
Speaker/Strobe 1st Floor Room B-106 45207753 1-ST1/SP1
1-3/1-3
03/12-P 01/29-P
Speaker/Strobe 1st Floor Near Room B-109A 45207752 1-ST1/SP1
1-9/1-9
03/12-P 01/29-P
Speaker/Strobe 1st Floor Near Room B-109D 45207750 1-ST1/SP1
1-5/1-6
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corr Near Room B-107 45207748 1-ST1/SP1 1-4/1-
03/11-P 01/29-P
Speaker/Strobe 1st Floor Room B-111 45207746 1-ST1/SP1
1-13/1- 16
03/12-P 01/29-P
Speaker/Strobe 1st Floor Corr Area B Stair 45207744 1-ST1/SP1
1-14/1- 12
03/12-P 01/29-P
Speaker/Strobe 1st Floor Conf Room B -110D 45207739 1-ST1/SP1
1-10/1-11
03/12-P 01/29-P
Speaker/Strobe 1st Floor Room B-110 45207738 1-ST1/SP1 03/12-P 01/29-P scDataCom 14 Download Date: 02/04/2026
1-11/1- 10
Speaker/Strobe 1st Floor FACP Room B 114 45207732 1-ST1/SP1
1-1/1-1
03/12-P 01/29-P
Speaker/Strobe 4th Floor Room B-421C 45208195 1-ST4/SP4
1-1/1-1
03/12-P 01/29-P
Speaker/Strobe 4th Floor Corr Near Room B-422 45208196 1-ST4/SP4
1-2/1-2
03/12-P 01/29-P
Speaker/Strobe 4th Floor Corr Near Room B-414 45208200 1-ST4/SP4
1-6/1-5
03/12-P 01/29-P
Speaker/Strobe 4th Floor Room B-414 45208202 1-ST4/SP4
1-5/1-4
03/12-P 01/29-P
Speaker/Strobe 4th Floor Room B-427 45208204 1-ST4/SP4
1-7/1-6
03/12-P 01/29-P
Speaker/Strobe 4th Floor Room B-430 45208207 1-ST4/SP4
1-9/1-9
03/12-P 01/29-P
Speaker/Strobe 4th Floor Men's Restroom Across A-431 45208209 1-ST4/SP4
2-1/2-1
03/12-P 01/29-P
Speaker/Strobe 4th Floor Corr Near A-431 45208210 1-ST4/SP4
2-2/2-2
03/12-P 01/29-P
Speaker/Strobe Basement Boiler Room B-113 45210819 1-ST1/SP1
1-18/1-15
03/12-P 01/29-P
Speaker/Strobe Basement Boiler Room B-113 45210823 1-ST1/SP1
1-17/1-14
03/12-P 01/29-P
Speaker/Strobe 1st Room A-117B 45208184 1-ST1/SP1
2-5/2-5
03/12-P 01/29-P
Speaker/Strobe 1st Amputee SVC Room B136 45208188 1-ST1/SP1
1-7/1-8
03/12-P 01/29-P
Speaker/Strobe 1st Wheel Chair Repair Room 45208194 1-ST1/SP1
2-1/2-1
03/12-P 01/29-P
Speaker/Strobe 1st Lobby Area Of A-100 45210807 1-ST1/SP1
2-6/2-6
03/12-P 01/29-P
Speaker/Strobe 1st Women's Restroom 45210808 1-ST1/SP1
2-12/2-13 EOL
03/12-P 01/29-P
Speaker/Strobe 1st Corridor By C-180 45210809 1-ST1/SP1
3-3/3-3
03/12-P 01/29-P
Speaker/Strobe 1st Corridor By C-176 45210810 1-ST1/SP1
3-5/3-5
03/12-P 01/29-P
Speaker/Strobe 1st Corridor By C-151 45210813 1-ST1/SP1
3-6/3-6
03/12-P 01/29-P
Speaker/Strobe 2nd Ceiling Room A-250 45208410 1-ST2.2.3 / SP2. 03/12-P 01/29-P
Speaker/Strobe 2nd South Hallway Ceiling Outside RM
B-202
45210607 1-ST2.1 / SP2.1 8
/ 9 EOL
03/12-P 01/29-P
Speaker/Strobe 2nd South Ceiling Inside Room B-209 45210609 1-ST2.1 / SP2.1
8-Jul
03/13-P 01/29-P
Speaker/Strobe 2nd South Ceiling Main Hallway
Intersection
45210612 1-ST2.1 / SP2.1
6-May
03/13-P 01/29-P
Speaker/Strobe 2nd South Ceiling Hallway Outside RM
B-225
45210613 1-ST2.1 / SP2.1
5-Apr
03/13-P 01/29-P
Speaker/Strobe 2nd South Hallway Ceiling Outside RM
B-222
45210615 1-ST2.1 / SP2.1
2-Feb
03/13-P 01/29-P
Speaker/Strobe 2nd South Hallway Ceiling Outside Room
B-232
45210617 1-ST2.1 / SP2.1
1-Jan
03/13-P 01/29-P
Speaker/Strobe 2nd South Waiting Room B West End 45210619 1-ST2.2 / SP2.2
1-Jan
03/13-P 01/29-P
Speaker/Strobe 2nd South Waiting Room B East End 45210620 1-ST2.2 / SP2.2
2-Feb
03/13-P 01/29-P
Speaker/Strobe 2nd Men's Bathroom Ceiling A-241 45210622 1-ST2.2 / SP2.2
4-Apr
03/13-P 01/29-P
Speaker/Strobe 2nd Central Hallway Outside Entrance To
Fire Exit
45210624 1-ST2.2 / SP2.2
5-May
03/13-P 01/29-P scDataCom 15 Download Date: 02/04/2026
Speaker/Strobe 2nd Resource Room Ceiling A-244 45210625 1-ST2.2 / SP2.2
6-Jun
03/13-P 01/29-P
Speaker/Strobe 2nd Ceiling Room A-240 45210626 1-ST2.2 / SP2.2
3-Mar
03/13-P 01/29-P
Speaker/Strobe 2nd Ceiling Woman's Resource Center
A-247
45210628 1-ST2.2 / SP2.2
7-Aug
03/13-P 01/29-P
Speaker/Strobe 2nd Ceiling Room A-250 45210632 1-ST2.2 / SP2.2
10-Oct
03/13-P 01/29-P
Speaker/Strobe 2nd Ceiling Room A-250 45210633 1-ST2.2 / SP2.2
9-Sep
03/13-P 01/29-P
Speaker/Strobe 2nd Check-In Room A-252 45210634 1-ST2.2 / SP2.2
12-Dec
03/13-P 01/29-P
Speaker/Strobe 2nd Central Hallway Outside RM A-252 45210635 1-ST2.2 / SP2.2
11-Nov
03/13-P 01/29-P
Speaker/Strobe 2nd Waiting Room C 45210638 1-ST2.3 / SP2.3
1-Jan
03/13-P 01/29-P
Speaker/Strobe 2nd Waiting Room C 45210639 1-ST2.3 / SP2.3
2-Feb
03/13-P 01/29-P
Speaker/Strobe 2nd North Women's Bathroom 45210640 1-ST2.2 / SP2.2
13 / 13 EOL
03/13-P 01/29-P
Speaker/Strobe 2nd North Hallway Outside Room C-258 45210641 1-ST2.3 / SP2.3
3-Mar
03/13-P 01/29-P
Speaker/Strobe 2nd North Hallway Intersection Outside
Nurses Station
45210642 1-ST2.3 / SP2.3
3-Mar
03/13-P 01/29-P
Speaker/Strobe 2nd North Hallway Outside C-270 45210644 1-ST2.3 / SP2.3
6-May
03/13-P 01/29-P
Speaker/Strobe 2nd North Hallway Outside C-267 45210645 1-ST2.3 / SP2.3
8-Jul
03/13-P 01/29-P
Speaker/Strobe 2nd North Stairwell Elevator Alcove 45210647 1-ST2.3 / SP2.3
9-Sep
03/13-P 01/29-P
Speaker/Strobe 2nd North Hallway Outside Room C-288 45210650 1-ST2.3 / SP2.3
12-Nov
03/13-P 01/29-P
Speaker/Strobe 2nd North Conference Room A-281 45210651 1-ST2.3 / SP2.3
11-Oct
03/13-P 01/29-P
Speaker/Strobe 3rd Room A-349 45210234 1-ST/SP
3.2-4/3.2-4
03/13-P 01/29-P
Speaker/Strobe 3rd Staff Break Room 45210232 1-ST/SP
3.2-5/3.2-6
03/13-P 01/29-P
Speaker/Strobe 3rd In Front of Elevator 45210229 1-ST/SP
3.2-6/3.2-7
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near C-377 45210216 1-ST/SP 3.3-5
EOL/3.3-7
03/13-P 01/29-P
Speaker/Strobe 3rd Room A-352 45210228 1-ST/SP
3.2-7/3.2-8
03/13-P 01/29-P
Speaker/Strobe 3rd Center Elevator 45210222 1-ST/SP 3.3-4
/3.3-5
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near C-387 45210223 1-ST/SP
3.3-3/3.3-4
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near A-354 45210227 1-ST/SP
3.2-8/3.2-9
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near C-362 45210225 1-ST/SP
3.3-2/3.3-3
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near C-391 45210226 1-ST/SP
3.3-1/3.3-1
03/13-P 01/29-P
Speaker/Strobe 3rd Near Room A-349C 45210235 1-ST/SP
3.2-3/3.2-3
03/13-P 01/29-P
Speaker/Strobe 3rd Bathroom Men's 45210237 1-ST/SP
3.2-1/3.2-1
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near Room A-328 45210238 1-ST/SP
3.2-2/3.2-2
03/13-P 01/29-P scDataCom 16 Download Date: 02/04/2026
Speaker/Strobe 3rd Bathroom Women's 45210239 1-ST/SP
3.2-9/3.2-10
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near B-325 45210240 1-ST/SP 3.1-8
EOL/3.1-5
03/13-P 01/29-P
Speaker/Strobe 3rd Women's Locker Room B-323 45210241 1-ST/SP
3.1-5/3.1-5
03/13-P 01/29-P
Speaker/Strobe 3rd Room B-324 45210242 1-ST/SP
3.1-7/3.1-7
03/13-P 01/29-P
Speaker/Strobe 3rd Near Room B-312 45210243 1-ST/SP
3.1-6/3.1-6
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near Room B321 45210244 1-ST/SP
3.1-4/3.1-4
03/13-P 01/29-P
Speaker/Strobe 3rd Hallway Near Room B302 45210247 1-ST/SP
3.2-1/3.1-1
03/13-P 01/29-P
Speaker/Strobe 3rd Employee Fitness Room 45210249 1-ST/SP
3.1-3/3.1-3
03/13-P 01/29-P
Speaker/Strobe 4th North Room C-443 45210652 1-ST4.3 / SP4.3 9
EOL / 8
03/13-P 01/29-P
Speaker/Strobe 4th North Hallway Outside Room C-444 45210653 1-ST4.3 / SP4.3
7-Aug
03/13-P 01/29-P
Speaker/Strobe 4th North Fire Exit Stairwell Elevator
Alcove
45210655 1-ST4.3 / SP4.3
6-Jul
03/13-P 01/29-P
Speaker/Strobe 4th North Room C-449 45210657 1-ST4.3 / SP4.3
3-Apr
03/13-P 01/29-P
Speaker/Strobe 4th North Hallway Intersection Outside
RM C-435
45210658 1-ST4.3 / SP4.3
3-Apr
03/13-P 01/29-P
Speaker/Strobe 4th North Inside Room C-347 45210659 1-ST4.3 / SP4.3
4-May
03/13-P 01/29-P
Speaker/Strobe 4th North Inside Room C-347 45210660 1-ST4.3 / SP4.3
5-Jun
03/13-P 01/29-P
Speaker/Strobe 4th North Hallway Outside RM-454 45210662 1-ST4.3 / SP4.3
1-Jan
03/13-P 01/29-P
Speaker/Strobe 4th North Inside Women's Bathroom 45210663 1-ST4.3 / SP4.3
10 EOL / 10 EOL
03/13-P 01/29-P
Speaker/Strobe 4th North Hallway Outside Women's
Bathroom
45210664 1-ST4.2 / SP4.2
9-Sep
03/13-P 01/29-P
Speaker/Strobe 4th North Inside Room A-432 45210665 1-ST4.2 / SP4.2
8-Aug
03/13-P 01/29-P
Speaker/Strobe 4th North Inside Room A-432 Back
Hallway
45210666 1-ST4.2 / SP4.2
7-Jul
03/13-P 01/29-P
Speaker/Strobe 4th S7 Elevator Alcove 45210667 1-ST4.2 / SP4.2
6-May
03/13-P 01/29-P
Speaker/Strobe 4th Inside Room A-431 45210673 1-ST4.2 / SP4.2
4-May
03/13-P 01/29-P
Speaker/Strobe 4th Inside Room A-431 45210674 1-ST4.2 / SP4.2
3-Apr
03/13-P 01/29-P
Speaker/Strobe Roof South Exit Penthouse 45208212 1-ST4/SP4
4-1/4-1
03/13-P 01/29-P
Speaker/Strobe Roof Penthouse ENTRANCE ON COLUMN
AHU Room
12535534 1-ST4.4 / SP4.4
2-Feb
03/13-P 01/29-P
Speaker/Strobe Roof Penthouse North Exit To Roof 45210676 1-ST4.4 / SP4.4
2-Feb
03/12-P 01/29-P
Device Total: 114 scDataCom 17 Download Date: 02/04/2026
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72
(2022) Table 14.4.3.2 (22)
For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3))
Strobe 12 12 0 12 12
Strobe 1st Floor Amputee SVC Room B136
Restroom
45208190 1-ST1 8-Jan 03/12-P 01/29-P
Strobe 1st Floor Men's Restroom Near Area B
Stair
45207745 1-ST1 15-Jan 03/12-P 01/29-P
Strobe 1st Floor By Room B-109C 45207737 1-ST1 10-Jan 03/12-P 01/29-P
Strobe 1st Floor Women's Restroom Near B-110 45207736 1-ST1 13-Jan 03/12-P 01/29-P
Strobe 4th Floor Restroom Near B-411 45208208 1-ST4 8-Jan 03/12-P 01/29-P
Strobe 4th Floor Kitchen B-415 45208201 1-ST4 4-Jan 03/12-P 01/29-P
Strobe 4th Floor B-Wing Restroom 45208199 1-ST4 3-Jan 03/12-P 01/29-P
Strobe 2nd Ceiling Woman's Resource Center
A-247H
45210629 1-ST2.2 7 03/13-P 01/29-P
Strobe 2nd Resource Room A-244 12535373 1 03/12-P 01/29-P
Strobe 3rd Bathroom Men's Police 45210248 1-ST 3.1-2 03/13-P 01/29-P
Strobe 4th Unisex Bathroom RM A-404 45210671 1-ST4.3 2 03/13-P 01/29-P
Strobe 4th North Unisex Bathroom RM C-451 45210661 1-ST4.3 2 03/13-P 01/29-P
Device Total: 12 scDataCom 18 Download Date: 02/04/2026
Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72
(2022) Table 14.4.3.2 (22)
For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2))
Voice Evacuation 3 3 0 3 3
Voice Evacuation 1st Floor Electrical Room Bldg 5 DAA 4 45207723 1 03/12-P 01/29-P
Voice Evacuation 1st Floor Electrical Room Bldg 5 DAA 3 45207722 1 03/12-P 01/29-P
Voice Evacuation 1st Floor Electrical Room Bldg 5 DAA 2 45207721 1 03/12-P 01/29-P
Device Total: 3 scDataCom 19 Download Date: 02/04/2026
Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2
(4)
Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4))
Monitor Device 6 6 0 6 6
Monitor Device 1st Floor Electrical Room Power Supply
Monitor Module
45207731 1-L001 M002 03/12-P 01/30-P
Monitor Device 1st Floor Electrical Room Power Supply
Relay Module
45207730 1-L001 M039 03/12-P 01/29-P
Monitor Device 1st Lower inside elec rm B-116 MC-RM
INSIDE FCPS 24S
44231100 2-1 M01 03/12-P 01/29-P
Monitor Device 3rd B-311 44230232 1-2 m02 03/13-P 01/29-P
Monitor Device 4th B-425 house keeping closet left battery
44230230 2-2 m51 03/13-P 01/29-P
Monitor Device Roof Roof AHU.5 AHU Room 45208350 1-L2 M56 03/13-P 01/30-P
Device Total: 6 scDataCom 20 Download Date: 02/04/2026
EC 02.03.05 EP 11
For automatic sprinkler systems: Every 12 months, the hospital tests fire pumps under flow. Fire pump supervisory signals for pump running and pump power loss are tested annually. NFPA 25 (2023) 8.3.3
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions
(outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Fire Pump Auto 1 1 0 1 1
Fire Pump Auto Outside Fire Pump 45211868 1-L1 M057 03/12-P 01/29-P
Device Total: 1 scDataCom 21 Download Date: 02/04/2026
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024)
6.4.1
Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))
Duct Detector 23 23 0 23 23
Duct Detector Basement Area C 45212593 1-L1 D36 03/17-P 01/29-P
Duct Detector Basement Boiler Room B-113 45210824 1-L1 D24 03/17-P 01/29-P
Duct Detector 1st Men's Restroom Area A 45212765 1-L1 D11 03/17-P 01/30-P
Duct Detector 1st Women's Restroom Area A 45212764 1-L1 D23 03/13-P 01/29-P
Duct Detector 1st Men's Restroom Area A 84048757 1-L1 D11
Duct Detector 1st Outside By Room A-117A Elevator
Lobby
45212766 1-L1 D9 03/13-P 01/29-P
Duct Detector 1st Room A-117A 45212767 1-L1 D8 03/13-P 01/29-P
Duct Detector 2nd In Room B-232 12535367 1-L1 D12 03/13-P 01/29-P
Duct Detector 2nd In Room B-226 12535368 1-L1 D13 03/13-P 01/29-P
Duct Detector 2nd Back Counter In Room A252 12535397 1-L1 D17 03/13-P 01/29-P
Duct Detector 2nd Women's Restroom Area A 45212759 1-L1 D35 03/17-P 01/29-P
Duct Detector 2nd Men's Restroom A-241 45212757 1-L01 D34 03/13-P 01/29-P
Duct Detector 3rd In Office B322 in Hatch 45212595 1-L02 D02 03/17-P 01/29-P
Duct Detector 3rd Women's Locker Room B323 45212594 1-L02 D03 03/17-P 01/29-P
Duct Detector 3rd Men's Restroom Area A 45212756 1-L02 D09 03/13-P 01/29-P
Duct Detector 3rd Women's Rest Room Area A 45212755 1-L02 D10 03/13-P 01/29-P
Duct Detector 3rd Elevator Corridor Area A 45212758 1-L02 D07 03/13-P 01/29-P
Duct Detector 4th Corner of rm Inside Room B-429 45212760 1-L2 D12 03/13-P 01/29-P
Duct Detector 4th Men's Restroom Area A 45212761 1-L2 D14 03/13-P 01/29-P
Duct Detector 4th Women's Restroom Area A 45212762 1-L2 D18 03/13-P 01/29-P
Duct Detector 4th Reception Area A-432 ABOVE COPIER
MACH.
45212763 1-L2 D17 03/13-P 01/29-P
Duct Detector Roof Roof AHU.4 ROOF mounted outside unit
45208351 1-L2 D023 03/17-P 01/29-P
Duct Detector Roof Roof AHU-3 45210815 1-L2 D24 03/13-P 01/29-P
Device Total: 23 scDataCom 22 Download Date: 02/04/2026
Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024)
6.4.1
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Fan Shutdown 1 1 0 1 1
Fan Shutdown Basement Boiler Room B-113 45210818 1-L1 D24 03/17-P 01/30-P scDataCom 23 Download Date: 02/04/2026
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions
(outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Control Panel 1 1 0 1 1
Control Panel 1st Floor Electrical Room Bldg 5 FACP 45207719 1 03/13-P 01/30-P scDataCom 24 Download Date: 02/04/2026
Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11))
Annunciator 2 2 0 2 2
Annunciator 1st Floor Lobby A-101 45208183 1 03/11-P 01/30-P
Annunciator 1st Floor Electrical Room Bldg 5 Digital
Voice Commands Center
45207720 1 03/12-P 01/30-P
Device Total: 2 scDataCom 25 Download Date: 02/04/2026
With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9))
Battery 10 10 0 10 10
Battery 1st Floor Electrical Room DAA Battery
Left
45207724 1 03/12-P 01/30-P
Battery 1st Floor Electrical Room DAA Battery
Right
45207725 1 03/12-P 01/30-P
Battery 1st Floor Electrical Room FACP Battery
Left
45207726 1 03/12-P 01/30-P
Battery 1st Floor Electrical Room FACP Battery
Right
45207727 1 03/12-P 01/30-P
Battery 1st Floor Electrical Room Power Supply
Battery Left
45207728 1 03/12-P 01/30-P
Battery 1st Floor Electrical Room Power Supply
Battery Right
45207729 1 03/12-P 01/30-P
Battery 3rd B-311 right battery 44230234 1 03/13-P 01/30-P
Battery 3rd B-311 left battery 44230233 1 03/13-P 01/30-P
Battery 4th Electrical Room B-425 Right battery 45212099 1 03/13-P 01/30-P
Battery 4th B-425 house keeping closet left battery
45212098 1 03/13-P 01/30-P
Device Total: 10 scDataCom 26 Download Date: 02/04/2026
Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions
(outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))
Power Supply 3 3 0 3 3
Power Supply 1st Floor Electrical Room 45207735 1 03/12-P 01/30-P
Power Supply 3rd B-311 44230231 1 03/13-P 01/30-P
Power Supply 4th B-425 house keeping closet left battery
44230229 1 03/13-P 01/30-P
Device Total: 3 scDataCom 27 Download Date: 02/04/2026
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Programmable Relay 1 1 0 1 1
Programmable Relay Roof AHU 1 45210250 1-2 57 03/12-P 01/29-P scDataCom 28 Download Date: 02/04/2026
LS 02.01.50 EP 07
Annual - Elevators are fully equipped and protected
Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))
Elevator 4 4 0 4 4
Elevator Roof Roof 45210817 1-L2 M27 03/17-P 01/30-P
Elevator Roof Roof 45210816 1-L2 M28 03/17-P 01/30-P
Elevator Roof P6 And P5 Elevator Machinery
Enclosure
45210680 1-L2 M26 03/17-P 01/29-P
Elevator Roof P6 And P5 Elevator Machinery
Enclosure
45210678 1-L2 M25 03/17-P 01/29-P
Device Total: 4 scDataCom 29 Download Date: 02/04/2026
Service Summary
The Service Summary section provides an overview of the services performed in this report.
Device Type Service Quantity
Passed
Annunciator Tested 2
Battery Tested 10
Control Panel Tested 1
Duct Detector Tested 23
Elevator Tested 4
Fan Shutdown Tested 1
Fire Pump Auto Tested 1
Heat Detector Tested 24
Monitor Device Tested 6
Power Supply Tested 3
Programmable Relay Tested 1
Pull Station Tested 28
Releasing Device Tested 8
Smoke Detector Tested/Cleaned 33
Speaker/Strobe Tested 114
Speaker Tested 16
Strobe Tested 12
Tamper Switch Tested 22
Voice Evacuation Tested 3
Waterflow Switch Tested 14
Total 326
Grand Total 326 scDataCom 30 Download Date: 02/04/2026
Auxiliary Functions Testing
Building: PA5 Control Panel: 1 - Notifier NFS-3030D
The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.
Type Location Comment ScanID Simulated
Passed
Elevator
Roof P6 And P5 Elevator Machinery Enclosure Passed 45210678
Roof P6 And P5 Elevator Machinery Enclosure Passed 45210680
Roof Roof Passed 45210816
Roof Roof Passed 45210817
Fan Shutdown
Basement Boiler Room B-113 Passed 45210818
Programmable Relay
Roof AHU 1 Passed 45210250
Releasing Device
1st Corridor By A-116 Passed 45208347
1st Corridor By B-108 Passed 45208348
1st Corridor By B-108 Passed 45208349
1st Corridor By C-176 Passed 45212094
1st Corridor By C-181 Passed 45212095
1st Corridor By C-181 Passed 45212096
2nd Outside Men's Bathroom Ceiling A-241 Passed 45208345
2nd Outside Men's Bathroom Ceiling A-241 Passed 45208346 scDataCom 31 Download Date: 02/04/2026
Time, Temperature & Level Testing
Control Panel: 1 - Notifier
NFS-3030D
The Time, Temperature, & Level Testing section details the measurements taken from various devices that are designed to respond in a certain amount of time, respond at a certain temperature, or respond within the acceptable range of volume or level. Items are grouped by Passed or Failed/Other.
Type Location Comment Sec Deg Lvl ScanID
Passed
Waterflow Switch
1st Floor Area B Stair Riser Passed 45 n/a n/a 12535330
1st Stair 1 Passed 45 n/a n/a 12535346
1st Stair 3 Passed 45 n/a n/a 12535303
1st Stair C Passed 46 n/a n/a 12535351
2nd Stair 1 Passed 42 n/a n/a 12535372
2nd North Stair 3 Passed 44 n/a n/a 12535377
2nd South Fire Exit Stairwell Passed 45 n/a n/a 12535405
3rd Stairs 1 Passed 45 n/a n/a 12535419
3rd Stairs Exit Police Passed 45 n/a n/a 12535526
3rd Stair 3 Stairs Exit Passed 45 n/a n/a 45210219
4th Area B Stair Riser Passed 75 n/a n/a 12535555
4th Stair 1 Passed 65 n/a n/a 12535551
4th North Stair 3 Passed 37 n/a n/a 12535543
Roof Area A Stair Riser Penthouse Passed 70 n/a n/a 12535537 scDataCom 32 Download Date: 02/04/2026
Battery & Power Supply Testing
NFS-3030D
The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.
Battery
Type Location
Rated
Ah
Rated
Volts
Pre
Test
Post
Test
Min
Ah
Tested
Ah
Passed Sealed Lead Acid 1st Floor Electrical Room DAA
Battery Left
55-NB 12
Sealed Lead Acid 1st Floor Electrical Room DAA
Battery Right
55-NB 12
Sealed Lead Acid 1st Floor Electrical Room FACP
Battery Left
55-NB 12
Sealed Lead Acid 1st Floor Electrical Room FACP
Battery Right
55-NB 12
Sealed Lead Acid 1st Floor Electrical Room Power
Supply Battery Left
7 12
Sealed Lead Acid 1st Floor Electrical Room Power
Supply Battery Right
7 12
Sealed Lead Acid 3rd B-311 left battery 7 12
Sealed Lead Acid 3rd B-311 right battery 7 12
Sealed Lead Acid 4th Electrical Room B-425
Right battery
7 12
Sealed Lead Acid 4th B-425 house keeping closet left battery
7 12 scDataCom 33 Download Date: 02/04/2026
Inventory & Warranty Report
Building: PA5 Control Panel: 1 - Notifier NFS-3030D
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Device or Type Category % of Inventory Quantity
Annunciator Control 0.61% 2
Battery Control 3.07% 10
Control Panel Control 0.31% 1
Duct Detector Initiating 7.06% 23
Elevator Auxiliary 1.23% 4
Fan Shutdown Auxiliary 0.31% 1
Fire Pump Auto Monitor 0.31% 1
Heat Detector Initiating 7.36% 24
Monitor Device Monitor 1.84% 6
Power Supply Control 0.92% 3
Programmable Relay Auxiliary 0.31% 1
Pull Station Initiating 8.59% 28
Releasing Device Auxiliary 2.45% 8
Smoke Detector Initiating 10.12% 33
Speaker Indicating 4.91% 16
Speaker/Strobe Indicating 34.97% 114
Strobe Indicating 3.68% 12
Tamper Switch Supervisory 6.75% 22
Voice Evacuation Control 0.92% 3
Waterflow Switch Initiating 4.29% 14
Type Qty Model # Description Install Date
New (under 90 days)
Continental
Battery 2 PS-127 Sealed Lead Acid 01/30/2026
Battery 2 PS-127 Sealed Lead Acid 11/15/2025
Interstate
Battery 2 PS1270 Sealed Lead Acid 11/15/2025
Battery 4 SLA1165 Sealed Lead Acid 11/15/2025
In Service - 5 Years to 10 Years
Notifier
Monitor Device 1
09/13/2017
Power-Sonic
Power Supply 2 PS-127
Magnetic Door Holder
Releasing Device 2
05/11/2017
Elevator 2 FCM-1
Programmable Relay 1 Frm-1 scDataCom 34 Download Date: 02/04/2026
Pull Station 6 LBG-12LX
Pull Station 3 NGB-12LX
Smoke Detector 4 FSP-851
Tamper Switch 3
Tamper Switch 1 Victaulic
Waterflow Switch 4 VSR-SF
Potter Electric
Waterflow Switch 3 VCD
SIMPLEX
Speaker/Strobe 1 SIMPLEX
SimplexGrinnell
Strobe 1
System Sensor
Smoke Detector 11 FSP-851
Speaker 10 SPCR
Speaker/Strobe 65 SPSCR
Strobe 4 SCR
Victaulic
Tamper Switch 3 V-40-1520
Honeywell
Pull Station 1 NBG-12LX
05/10/2017
Annunciator 1 DVC-EM
Annunciator 1 LCD2-80
Control Panel 1 NFS-3030D
Duct Detector 21 DNR FSP-851
Duct Detector 2 FSP-851
Elevator 2 FSP-851
Fan Shutdown 1 FRM-1
Heat Detector 12 FST-851R Hardwire - Rate-of-Rise 05/10/2017
Heat Detector 12 FST-951R Hardwire - Rate-of-Rise 05/10/2017
Monitor Device 3 FRM-1
Power Supply 1 FCPS-24S8
Pull Station 13 NBG -12LX
Pull Station 4 NBG-12LX
Releasing Device 6 FM990
Smoke Detector 18 FSP-851
Speaker/Strobe 16 SPSCR
Tamper Switch 3
Voice Evacuation 3 DAA-5070
Waterflow Switch 3 VSR-SF
Potter Electric
Fire Pump Auto 1 GPU-208/40/3/60
Tamper Switch 6
Tamper Switch 1 OSYSU-2
Tamper Switch 1 PCVS-1
Waterflow Switch 4 VSR-SF
Simplex scDataCom 35 Download Date: 02/04/2026
Pull Station 1
Speaker/Strobe 2 4903
System Sensor
Speaker 6 SPCR
Speaker/Strobe 27 SPSCR
Speaker/Strobe 3 SPSR
Strobe 7 SCR
Victaulic
Tamper Switch 4 SERIES 708W
Building: PA5 Control Panel: 2
The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.
Type Qty Model # Description Install Date
In Service - 5 Years to 10 Years
Monitor Device 1 FCM-1
Monitor Device 1 PS-127 scDataCom 36 Download Date: 02/04/2026
Zone Address Report
NFS-3030D
The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.
Address Device Type Location Type ScanID
Zone/Circuit: 2
5 Pull Station 3rd Stairs Exit 45210245
57 Programmable Relay Roof AHU 1 45210250
D006 Smoke Detector 3rd Lobby Elevator P5 & P6 45210231
D008 Smoke Detector 3rd LOBBY Elevator S7 45210230
D11 Smoke Detector 3rd ELEV. S8 LOBBY STAIR 2 45210221
M12 Pull Station 3rd Stairs Exit 45210236 m02 Monitor Device 3rd B-311 44230232
Zone/Circuit: L001
D001 Smoke Detector 1st Floor FACP Room B 114 45207734
D01 Smoke Detector 2nd B-311 44230235
D002 Smoke Detector 1st Floor Corridor At B 106 45207755
D003 Smoke Detector 1st Floor Corridor At B 105 45207756
D004 Smoke Detector 1st Floor Elevator S7 LOBBY 45207762
D005 Smoke Detector 1st Floor Elevator P-5 & P-6 45207761
D006 Smoke Detector 1st Floor Corridor At A 183 45207765
D007 Smoke Detector 1st Floor Corridor At C 181 45207766
Zone/Circuit: L1
D8 Duct Detector 1st Room A-117A 45212767
D9 Duct Detector 1st Outside By Room A-117A Elevator
Lobby
45212766
Zone/Circuit: L001
D010 Smoke Detector 1st Floor STAIRWELL 2 Elevator Area C
NORTH
45207770
Zone/Circuit: L1
D11 Duct Detector 1st Men's Restroom Area A 45212765
D11 Duct Detector 1st Men's Restroom Area A 84048757
D12 Duct Detector 2nd In Room B-232 12535367
D13 Duct Detector 2nd In Room B-226 12535368
D16 Smoke Detector 2nd Central Hallway Elevator Lobby
ELEV. S7 LOBBY
45210631
D17 Duct Detector 2nd Back Counter In Room A252 12535397
D18 Smoke Detector 2nd Central Hallway Elevator Lobby P5 &
P6 ELEV..
45210630
D20 Smoke Detector 2nd North Entrance To Waiting Room C 45210636
D21 Smoke Detector 2nd…