Amendment 0001 - Livermore Inspection.pdf

PDF 7 MB Posted

Attached to
Fire Alarm and Protection System Inspection and PM
Solicitation number
36C26127Q0025
Issued by

About this file

This file contains fire/life safety system inspection, testing, and maintenance certificates for three Livermore, California buildings (LV6, LV30, and LV62) performed by scDataCom in compliance with NFPA 101 (2024), NFPA 72 (2022), and NFPA 90A (2022) standards, with inspection completion dates ranging from April 15-21, 2026. The certificates document annual and semi-annual testing of fire alarm and life safety devices including heat detectors, smoke detectors, pull stations, speaker/strobes, control panels, batteries, waterflow switches, duct detectors, and supervisory devices across multiple facility locations.

The inspections reveal significant maintenance and compliance issues across the three buildings. Building LV6 (4951 Arroyo Road) contains 40 total devices with all tests passing but existing network issues noted on all alarm panels requiring troubleshooting. Building LV30 (4195 Arroyo Road) comprises 15 devices with all tests passing; however, some batteries were removed during inspection and network issues persist. Building LV62 (4951 Arroyo Road) is the most complex facility with 539 total devices tested, including extensive sprinkler system supervision, duct detection for HVAC shutdown, and off-site fire responder notification systems. Eight batteries failed testing at LV62 and require replacement (model PS-12550U and PS-1250F1 on a time-and-materials basis), along with widespread network connectivity problems and outdated barcodes/device information requiring correction across all three facilities. The common recommendation across all sites is immediate troubleshooting of network issues to restore all alarm panels to normal system operation.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

LVD 6

4951 Arroyo Road Livermore, CA 94550

This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR

CONDITIONING/VENTILATING SYSTEMS.

This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Apr 22, 2026

Building: LV6 Company: scDataCom Contact: Doug Gambrell Contact: Derrick Tillman

Title: Manager Title: Technician scDataCom 1 Download Date: 04/24/2026

Executive Summary

Generated by: BuildingReports.com

Building Information

Building: LV6 Contact: Doug Gambrell

Address: 4951 Arroyo Rad Phone: 4403192479

Address: Fax:

City/State/ZIP Code: Livermore, CA 94550 Mobile:

Country: United States of America Email: d.gambrell@scdatacom.net

Inspection Performed By

Company: scDataCom Inspector: Derrick Tillman

Address: 2700 Gregory St Ste 180 Phone: (669) 333-6375

Address: Fax:

City/State/ZIP Code: Savannah, GA 31404 Mobile:

Country: United States of America Email: dtillman@pavion.com

System Control Unit

Manufacturer: est Inspection Date: 04/30/2025 IDC Style: B

Model Number: est-3 Install Date: 05/25/2017 SLC Style:

Software Version: Version Date: 05/25/2017 NAC Style: Y

Location: 2nd office hallway Current Protection: Breaker scDataCom 2 Download Date: 04/24/2026

Inspection Completion Date: Apr 22, 2026

Building: LV6

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Heat Detector 0 0 0 0 7 7

Pull Station 1 1 0 1 7 8

Smoke Detector 0 0 0 0 6 6

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Bell 0 0 0 0 1 1

Speaker/Strobe 0 0 0 0 12 12

Strobe 0 0 0 0 1 1

LS 02.01.34 EP 02

Protected master fire alarm control panel

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Control Panel 0 0 0 0 1 1

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Battery 0 0 0 0 2 2

Special Control 0 0 0 0 2 2

Total Device Count: 40 scDataCom 3 Download Date: 04/24/2026

Certification

Company: scDataCom Building: LV6

Inspector: Derrick Tillman Contact: Doug Gambrell

Signed: Apr 22, 2026 Signed:

scDataCom 4 Download Date: 04/24/2026

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.

General Note

EXISTING ISSUES:

Network issues on All Alarm Panels still exist .

Needs troubleshooting to be corrected and returned back to system normal.

scDataCom 5 Download Date: 04/24/2026

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.

Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))

Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity

Heat Detector 0 0 0 0 7

Device Type Location ScanID Address Q2/25 Q2/26

Heat Detector Basement generator room 8999258 1-sg-1 h3 04/30-P

Heat Detector Basement store room 8999260 1-n-a 04/30-P

Heat Detector 1st outsude filter room 8999259 1-2 9 04/30-P

Heat Detector 1st outsude filter room 45213574 1-sg-1 h1 04/30-P

Heat Detector 2nd cat walk over boiler 8999251 1-sg-1 h-4 04/30-P

Heat Detector 2nd cat walk over boiler 08999252 1-sg-1 h-4 04/30-P

Heat Detector 2nd cat walk over boiler 08999253 1-sg-1 h-4 04/30-P

Device Total: 7 scDataCom 6 Download Date: 04/24/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5))

Pull Station 1 1 0 1 8

Pull Station Basement rear entrance 8999256 1-sg-1 f4 04/30-P

Pull Station Basement side exit stair well 8999254 1-sg-1 f6 04/30-P

Pull Station 1st front entrance landing stairwell 8999186 1-sg-1 f5 04/30-P 04/22-P

Pull Station 1st side entrance door 08999254 1-sg-1 f3 04/30-P

Pull Station 1st side entrance door 01163725 1-sg-1 f3 04/30-P

Pull Station 1st side entrance door 45213558 1-sg-1 f3 04/30-P

Pull Station 1st side entrance door 08999251 1-sg-1 f3 04/30-P

Pull Station 2nd office exit hallway 8999247 1-n-a 04/30-P

Device Total: 8 scDataCom 7 Download Date: 04/24/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a))

Smoke Detector 0 0 0 0 6

Smoke Detector 1st side entrance door 45213563 1-n-a 04/30-P

Smoke Detector 2nd office rear hallway 08999247 1-sg-1 s1 04/30-P

Smoke Detector 2nd office rear hallway 08999250 1-sg-1 s1 04/30-P

Smoke Detector 2nd office rear hallway 08999256 1-sg-1 s1 04/30-P

Smoke Detector 2nd rear of Building 8999198 1-sg-1 s-3 04/30-P

Smoke Detector 2nd rear of Building 08999260 1-sg-1 s-3 04/30-P

Device Total: 6 scDataCom 8 Download Date: 04/24/2026

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1))

Bell 0 0 0 0 1

Bell 1st outside building 45213572 1 04/30-P

Device Total: 1 scDataCom 9 Download Date: 04/24/2026

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2))

Speaker/Strobe 0 0 0 0 12

Speaker/Strobe Basement back wall 1163058 1-nac-2 5 04/30-P

Speaker/Strobe Basement generator room back wall 8999257 1-nac-2 4 04/30-P

Speaker/Strobe Basement side exit stair well 8999255 1-nac-2 6 04/30-P

Speaker/Strobe 1st outsude filter room 45213573 1-nac-2 1 04/30-P

Speaker/Strobe 1st side entrance door 1163060 1-nac-2 2 04/30-P

Speaker/Strobe 2nd hallway 45213564 1-n-a 04/30-P

Speaker/Strobe 2nd hallway 1163121 1-nac-1 6 04/30-P

Speaker/Strobe 2nd hallway 1163120 1-nac-1 7 04/30-P

Speaker/Strobe 2nd locker room 1163057 1-nac1 5 04/30-P

Speaker/Strobe 2nd office 45213566 1-nac-1 1 04/30-P

Speaker/Strobe 2nd office bathroom 1163054 1-nac1 4 04/30-P

Speaker/Strobe 2nd office exit hallway 8999245 1-nac1 2 04/30-P

Device Total: 12 scDataCom 10 Download Date: 04/24/2026

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3))

Strobe 0 0 0 0 1

Strobe 2nd office rear hallway 45213565 1-sg-1 s1 04/30-P scDataCom 11 Download Date: 04/24/2026

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))

Control Panel 0 0 0 0 1

Control Panel 2nd office hallway 45213571 1 04/30-P scDataCom 12 Download Date: 04/24/2026

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9))

Battery 0 0 0 0 2

Battery 2nd office hallway 45213570 1 04/30-P

Battery 2nd office hallway 45213567 1 04/30-P

Device Total: 2 scDataCom 13 Download Date: 04/24/2026

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))

Special Control 0 0 0 0 2

Special Control 2nd office hallway 45213569 1 04/30-P

Special Control 2nd office hallway 45213568 1 04/30-P scDataCom 14 Download Date: 04/24/2026

Service Summary

The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed

Battery Tested 2

Bell Tested 1

Control Panel Tested 1

Heat Detector Tested 7

Pull Station Tested 8

Smoke Detector Tested/Cleaned 6

Speaker/Strobe Tested 12

Special Control Tested/Cleaned 2

Strobe Tested 1

Total 40

Grand Total 40 scDataCom 15 Download Date: 04/24/2026

Battery & Power Supply Testing

Building: LV6 Control Panel: 1 - est est-3

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated Ah

Rated Volts

Pre Test

Post Test

Min Ah

Tested Ah

Passed Sealed Lead Acid 2nd office hallway 18-NB 12

Sealed Lead Acid 2nd office hallway 18-NB 12 scDataCom 16 Download Date: 04/24/2026

Inventory & Warranty Report

Building: LV6 Control Panel: 1 - est est-3

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Battery Control 5.00% 2

Bell Indicating 2.50% 1

Control Panel Control 2.50% 1

Heat Detector Initiating 17.50% 7

Pull Station Initiating 20.00% 8

Smoke Detector Initiating 15.00% 6

Speaker/Strobe Indicating 30.00% 12

Special Control Control 5.00% 2

Strobe Indicating 2.50% 1

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

Power-sonic

Battery 2 PS-12180-f2 Sealed Lead Acid 02/13/2023

In Service - 5 Years to 10 Years

Edwards

Bell 1 439D-8aw-r

05/25/2017 est

Control Panel 1 est-3 Addressable 05/25/2017

Heat Detector 1 siga-278

Heat Detector 4 siga-iphs

Heat Detector 2 siga-ps

Pull Station 8 siga-278

Smoke Detector 3

Smoke Detector 3 siga-ps

Speaker/Strobe 1 757-7a-TW

Speaker/Strobe 11 G1RF-vm

Special Control 2 siga-mcc1s

Strobe 1 202-7a-t scDataCom 17 Download Date: 04/24/2026

Zone Address Report

Building: LV6 Control Panel: 1 - est est-3

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Zone/Circuit: 2 9 Heat Detector 1st outsude filter room 8999259

Zone/Circuit: n-a Heat Detector Basement store room 8999260 Smoke Detector 1st side entrance door 45213563 Speaker/Strobe 2nd hallway 45213564 Pull Station 2nd office exit hallway 8999247

Zone/Circuit: nac1 2 Speaker/Strobe 2nd office exit hallway 8999245 4 Speaker/Strobe 2nd office bathroom 1163054 5 Speaker/Strobe 2nd locker room 1163057

Zone/Circuit: nac-1 1 Speaker/Strobe 2nd office 45213566 6 Speaker/Strobe 2nd hallway 1163121 7 Speaker/Strobe 2nd hallway 1163120

Zone/Circuit: nac-2 1 Speaker/Strobe 1st outsude filter room 45213573 2 Speaker/Strobe 1st side entrance door 1163060 4 Speaker/Strobe Basement generator room back wall 8999257 5 Speaker/Strobe Basement back wall 1163058 6 Speaker/Strobe Basement side exit stair well 8999255

Zone/Circuit: sg-1 f3 Pull Station 1st side entrance door 01163725 f3 Pull Station 1st side entrance door 08999251 f3 Pull Station 1st side entrance door 08999254 f3 Pull Station 1st side entrance door 45213558 f4 Pull Station Basement rear entrance 8999256 f5 Pull Station 1st front entrance landing stairwell 8999186 f6 Pull Station Basement side exit stair well 8999254 h1 Heat Detector 1st outsude filter room 45213574 h3 Heat Detector Basement generator room 8999258 h-4 Heat Detector 2nd cat walk over boiler 08999252 h-4 Heat Detector 2nd cat walk over boiler 08999253 h-4 Heat Detector 2nd cat walk over boiler 8999251 s1 Smoke Detector 2nd office rear hallway 08999247 s1 Smoke Detector 2nd office rear hallway 08999250 s1 Smoke Detector 2nd office rear hallway 08999256 s1 Strobe 2nd office rear hallway 45213565 scDataCom 18 Download Date: 04/24/2026 s-3 Smoke Detector 2nd rear of Building 08999260 s-3 Smoke Detector 2nd rear of Building 8999198

For

LVD 30

4195 Arroyo Rd.

Livermore, CA 94550

This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR

CONDITIONING/VENTILATING SYSTEMS.

This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Apr 15, 2026

Building: LV30 Company: scDataCom

Building: LV30 Contact: Doug Gambrell

Address: 4195 Arroya Rd Phone: 4403192479

Address: Fax:

Address: 2700 Gregory St Ste 180 Phone: (669) 333-6375

Address: Fax:

Manufacturer: est Inspection Date: 04/15/2026 IDC Style:

Model Number: est3 Install Date: 05/25/2017 SLC Style:

Software Version: Version Date: 05/25/2017 NAC Style:

Location: 1st 4 storage room Current Protection:

Inspection Completion Date: Apr 15, 2026

Building: LV30

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Heat Detector 1 1 0 1 0 1

Pull Station 2 2 0 2 0 2

Smoke Detector 2 2 0 2 0 2

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Speaker/Strobe 6 6 0 6 0 6

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Control Panel 1 1 0 1 0 1

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Battery 2 2 0 2 0 2

Special Control 1 1 0 1 0 1

Total Device Count: 15

Company: scDataCom Building: LV30

Signed: Apr 15, 2026 Signed:

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.

General Note

EXISTING ISSUES:

Network issues on All Alarm Panels still exist .

Needs troubleshooting to be corrected and returned back to system normal.

The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.

Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))

Heat Detector 1 1 0 1 1

Heat Detector 1st 4 out side hallway 12202946 1-sg-1 s2 05/05-P 04/15-P

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5))

Pull Station 2 2 0 2 2

Pull Station 1st 4 storage room 12202944 1-SG-1 F1 05/05-P 04/15-P

Pull Station 1st entrance living room 1163613 1-sg-1 f2 05/05-P 04/15 Removed

Pull Station 1st entrance living room 01163613 1-sg-1 f2

04/15-P

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a))

Smoke Detector 2 2 0 2 2

Smoke Detector 1st 4 storage room 12202947 1-SG-1 S1 05/05-P 04/15-P

Smoke Detector 1st entrance living room 12202945 1-SG-1 S3 05/05-P 04/15-P

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(2))

Speaker/Strobe 6 6 0 6 6

Speaker/Strobe 1st bathroom 01163625 1-nac-1 1

Speaker/Strobe 1st bathroom 1163625 1-nac-1 1 05/05-P 04/15-P

Speaker/Strobe 1st entrance living room 01163626 1-nac-1 3

Speaker/Strobe 1st entrance living room 1163626 1-nac-1 3 05/05-P 04/15-P

Speaker/Strobe 1st entrance rear hallway 01163627 1-nac-1 2

Speaker/Strobe 1st entrance rear hallway 1163627 1-nac-1 2 05/05-P 04/15-P

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))

Control Panel 1 1 0 1 1

Control Panel 1st 4 storage room 45213562 1 05/05-F 04/15-P

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9))

Battery 2 2 0 2 2

Battery 1st 4 storage room 45213559 1-nac-1 1 05/05-P 04/15 Removed

Battery 1st 4 storage room 45213560 1-nac-1 1 05/05-P 04/15

Battery 1st 4 storage room 12202950 1-nac-1 1

Battery 1st 4 storage room 12202949 1-nac-1 1

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))

Special Control 1 1 0 1 1

Special Control 1st 4 storage room 45213561 1 05/05-P 04/15-P

Service Summary

The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed

Battery Tested 2

Control Panel Tested 1

Heat Detector Tested 1

Pull Station Tested 2

Smoke Detector Tested/Cleaned 2

Speaker/Strobe Tested 6

Special Control Tested/Cleaned 1

Total 15

Grand Total 15

Battery & Power Supply Testing

Building: LV30 Control Panel: 1 - est est3

The Battery & Power Supply Testing section details the readings and measurements of batteries and power supplies used to provide power to the fire alarm and life safety systems. Items are grouped by Passed or Failed/Other.

Battery

Type Location Rated Ah

Rated Volts

Pre Test

Post Test

Min Ah

Tested Ah

Passed Sealed Lead Acid 1st 4 storage room 18-QC 12

Sealed Lead Acid 1st 4 storage room 18-QC 12

Inventory & Warranty Report

Building: LV30 Control Panel: 1 - est est3

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Battery Control 13.33% 2

Control Panel Control 6.67% 1

Heat Detector Initiating 6.67% 1

Pull Station Initiating 13.33% 2

Smoke Detector Initiating 13.33% 2

Speaker/Strobe Indicating 40.00% 6

Special Control Control 6.67% 1

Type Qty Model # Description Install Date

In Service - 1 Year to 2 Years

Interstate

Battery 2 ps-12180 f2 Sealed Lead Acid 04/22/2025

In Service - 5 Years to 10 Years

EST

Pull Station 2 siga-278 Dual Action 05/25/2017

Smoke Detector 1 siga-ps Hardwire - Photoelectric 05/25/2017 est

Control Panel 1 est3

Heat Detector 1 siga-ps

Smoke Detector 1 siga-ps Hardwire - Photoelectric 05/25/2017

Speaker/Strobe 6 G1RF-vm

Special Control 1 siga-mcc1s

Zone Address Report

Building: LV30 Control Panel: 1 - est est3

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Zone/Circuit: SG-1 F1 Pull Station 1st 4 storage room Dual Action 12202944 S1 Smoke Detector 1st 4 storage room Hardwire -

Photoelectric 12202947

S3 Smoke Detector 1st entrance living room Hardwire - Photoelectric

12202945

Zone/Circuit: nac-1 1 Battery 1st 4 storage room Sealed Lead Acid 12202949 1 Battery 1st 4 storage room Sealed Lead Acid 12202950 1 Speaker/Strobe 1st bathroom 01163625 1 Speaker/Strobe 1st bathroom 1163625 2 Speaker/Strobe 1st entrance rear hallway 01163627 2 Speaker/Strobe 1st entrance rear hallway 1163627 3 Speaker/Strobe 1st entrance living room 01163626 3 Speaker/Strobe 1st entrance living room 1163626

Zone/Circuit: sg-1 f2 Pull Station 1st entrance living room Dual Action 01163613 s2 Heat Detector 1st 4 out side hallway 12202946

For

LVD 62

4951 Arroyo Road Livermore, CA 94550

This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR

CONDITIONING/VENTILATING SYSTEMS.

This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Apr 21, 2026

Building: LV62 Company: scDataCom

Building: LV62 Contact: Doug Gambrell

Address: 4951 Arroyo Rad Phone: 4403192479

Address: Fax:

Address: 2700 Gregory St Ste 180 Phone: (669) 333-6375

Address: Fax:

Manufacturer: Siemens Inspection Date: 04/20/2026 IDC Style:

Model Number: MXL Install Date: 05/03/2017 SLC Style:

Software Version: Version Date: 05/03/2017 NAC Style:

Location: 1st North FACP Room Current Protection:

Central Station Signal Verification

Type: Mfg: EST Model #: est-2

Test Time/Date: 4/20/26 12:23:25 PM Restore Time: Note:

Type of Signal Signal Confirmation Notes

Confirmed Time:

Confirmed Time:

Inspection Completion Date: Apr 21, 2026

Building: LV62

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices.

Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Supervisory Device 2 2 0 2 0 2

Supervisory Valve 1 1 0 1 0 1

Tamper Switch 21 21 0 21 0 21

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Waterflow Switch 19 19 0 19 0 19

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Duct Detector 17 17 0 17 0 17

Heat Detector 6 6 0 6 0 6

Pull Station 41 41 0 41 0 41

Smoke Detector 73 73 0 73 0 73

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Indicating Device 16 16 0 16 0 16

Releasing Device 29 29 0 29 0 29

Speaker 14 14 0 14 0 14

Speaker/Strobe 85 85 0 85 0 85

Strobe 56 56 0 56 0 56

EC 02.03.05 EP 05

Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Communication Line 12 12 0 12 0 12

Communicator 1 1 0 1 0 1

Monitor Device 4 4 0 4 0 4

Monitoring 2 2 0 2 0 2

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Duct Detector 17 17 0 17 0 17

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Control Panel 4 4 0 4 0 4

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Battery 16 8 8 16 0 16

Expander Panel 10 10 0 10 0 10

Fault Isolation Module 8 8 0 8 0 8

Handset 6 6 0 6 0 6

Initiating Device 26 26 0 26 0 26

Phone Jack 21 21 0 21 0 21

Power Supply 2 2 0 2 0 2

Smoke Alarm 1 1 0 1 0 1

Special Control 46 46 0 46 0 46

Total Device Count: 539

Company: scDataCom Building: LV62

Signed: Apr 21, 2026 Signed:

Discrepancy Report

Building: LV62 Control Panel: 1 - Siemens MXL

The Discrepancy Report consolidates each discrepancy listed within the various Testing sections of your Inspection.

Discrepancies are listed by Category, and grouped by device type. The description of the problem is provided and where appropriate, code references are listed for your convenience. Any item that was inspected that is subject to a recall or part of a manufacturer's replacement/upgrade program is included.

Device Type Manufacturer ModelNumber Date Qty

Items listed for Recall or Replacement/Upgrade No items found during this inspection.

ScanID Location Problem Address Reference

LS 02.01.34 EP 10 All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery 12202534 Basement Failed Test 1 NFPA72 Table

14.4.3.2 (9) 12202535 Basement Failed Test 1 NFPA72 Table

14.4.3.2 (9) 45213516 1st outside room 156 hallway Failed Test 1 NFPA72 Table

14.4.3.2 (9) 45213517 1st outside room 156 hallway Failed Test 1 NFPA72 Table

14.4.3.2 (9) 12202589 Roof Mechanical Room NAC_C Failed Test 1 NFPA72 Table

14.4.3.2 (9) 12202590 Roof Mechanical Room NAC_C Failed Test 1 NFPA72 Table

14.4.3.2 (9) 12202587 Roof Mechanical Room NAC_D Failed Test 1 NFPA72 Table

14.4.3.2 (9) 12202588 Roof Mechanical Room NAC_D Failed Test 1 NFPA72 Table

14.4.3.2 (9)

Code References NFPA72 Table

14.4.3.2 (9)

Replace any battery cell/unit if the temperature is greater than 18F above ambient. Replace the battery when any cell/unit measures a voltage less than 13.26 volts. Replace the battery when any cell/unit has an internal ohmic value outside of the acceptable range.

Proposed Solutions Report

Building: LV62 Control Panel: 1 - Siemens MXL

The Proposed Solution Report provides a solution for each discrepancy listed on the Discrepancy Report. Provide a check mark where indicated to approve repairs listed within the report. Items listed as T/M are available for repair on a Time and Materials basis.

ScanID Location Solution Model # Cost Fix

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Battery

12202534 Basement Replace Battery PS-12550 T/M

12202535 Basement Replace Battery PS-12550 U T/M

45213516 1st outside room 156 hallway Replace Battery PS-12550U T/M

45213517 1st outside room 156 hallway Replace Battery PS-12550U T/M

12202589 Roof Mechanical Room NAC_C Replace Battery PS-1250 F1 T/M

12202590 Roof Mechanical Room NAC_C Replace Battery PS-1250 F1 T/M

12202587 Roof Mechanical Room NAC_D Replace Battery PS-1250 F1 T/M

12202588 Roof Mechanical Room NAC_D Replace Battery PS-1250 F1 T/M

Internal WO/PO #: (none) T/M

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.

General Note

EXISTING ISSUES:

Network issues on All Alarm Panels still exist .

Needs troubleshooting to be corrected and returned back to system normal.

Various batteries are expired and need to be replaced.

Barcodes for various devices need to be replaced and device information address location description needs to be corrected /updated

The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices.

Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))

Supervisory Device 2 2 0 2 2

Supervisory Device 6th Stairwell West Wing Isolator Module in FATC_6N

45213642 1 05/27-P 04/21-P

Supervisory Device 6th Stairwell 67 East Wing Isolator Module inside FATC 6S

12202670 1 05/27-P 04/21-P

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices.

Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a))

Supervisory Valve 1 1 0 1 1

Supervisory Valve 7th Elevator Machine Room 10360805 1 05/27-P 04/21-P

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices.

Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a))

Tamper Switch 21 21 0 21 21

Tamper Switch Outside 45205477 1 05/14-P 04/17-P

Tamper Switch Basement Center Sprinkler OSNY Tamper 08999115 1 05/14-P 04/20-P

Tamper Switch Basement East Wing Fire Sprinkler Closet 13362727 1 05/14-P 04/17-P

Tamper Switch Basement Center Fire Sprinkler Closet Room 2B

8999114 1 05/14-P 04/21 Removed

Tamper Switch Basement Center Fire Sprinkler Closet Room 2B

8999144 1 05/14-P 04/21 Removed

Tamper Switch Basement Center Fire Sprinkler Closet Room 2B

8999145 1 05/13-F 04/21 Removed

Tamper Switch Basement East Wing by Double Doors Exit

12202531 1 05/14-P 04/21 Removed

Tamper Switch 1st West Wing Fire Sprinkler Closet 45213542 1 05/14-P 04/17-P

Tamper Switch 1st East Wing Fire Sprinkler Closet 45213525 1 05/13-P 04/17-P

Tamper Switch 1st Center Fire Sprinkler Closet 08999147 1

04/17-P

Tamper Switch 1st Center Fire Sprinkler Closet 8999147 1 05/13-P 04/21 Removed

Tamper Switch 1st West Stairwell A 40968488 1-001-003 05/14-P 04/21 Removed

Tamper Switch 2nd Main Hallway Southeast Wing Sprinkler Closet

08999205 1

Tamper Switch 2nd Main Hallway Northwest Wing Inside Sprinkler Clo

08999218 1

Tamper Switch 2nd Stub Wing Fire Sprinkler Closet Outside RM 233

08999216 1-SG 7 W2

Tamper Switch 2nd Main Hallway Northwest Wing Inside Sprinkler Clo

8999218 1 05/14-P 04/21 Removed

Tamper Switch 2nd Main Hallway Southeast Wing Sprinkler Closet

8999205 1 05/13-P 04/21 Removed

Tamper Switch 2nd Stub Wing Fire Sprinkler Closet Outside RM 233

8999216 1-SG 7 W2 05/13-P 04/21

Tamper Switch 3rd East Wing Fire Sprinkler Closet 08999125 1

Tamper Switch 3rd West Wing Fire Sprinkler Closet 08999181 1

Tamper Switch 3rd Center Fire Sprinkler Closet 08Q6176 1

Tamper Switch 3rd 8999181 1 05/14-P 04/21 Removed

Tamper Switch 3rd Center Fire Sprinkler Closet 8999176 1 05/13-P 04/21 Removed

Tamper Switch 3rd East Wing Fire Sprinkler Closet 8999125 1 05/13-P 04/21 Removed

Tamper Switch 3rd West Wing Fire Sprinkler Closet 3 1 05/14-P 04/21

Tamper Switch 4th Northwest Wing Fire Sprinkler Closet 08999174 1-SG-6 W2

Tamper Switch 4th Short Wing Fire Sprinkler Closet 13362726 1-SG-6 W2 05/13-P 04/17-P

Tamper Switch 4th East Wing Fire Sprinkler Closet 08999131 1-SG-6 W2

Tamper Switch 4th East Wing Fire Sprinkler Closet 8999131 1-SG-6 W2 05/13-P 04/21 Removed

Tamper Switch 4th Northwest Wing Fire Sprinkler Closet 8999174 1-SG-6 W2 05/14-P 04/21

Tamper Switch 5th Southeast Wing Inside Fire Sprinkler 08999124 1

Closet

Tamper Switch 5th Short Wing Fire Sprinkler Closet 08999163 1

Tamper Switch 5th Northwest Wing Fire Sprinkler Closet 08999168 1

Tamper Switch 5th Northwest Wing Fire Sprinkler Closet 8999168 1 05/14-P 04/21 Removed

Tamper Switch 5th Short Wing Fire Sprinkler Closet 8999163 1 05/13-P 04/21 Removed

Tamper Switch 5th Southeast Wing Inside Fire Sprinkler Closet

8999124 1 05/13-P 04/21 Removed

Tamper Switch 6th West 45213512 1 05/14-P 04/17-P

Tamper Switch 6th East 08999133 1

Tamper Switch 6th Center 45213504 1 05/13-P 04/17-P

Tamper Switch 6th East 8999133 1 05/13-P 04/21 Removed

Tamper Switch 7th Penthouse 12202503 1 05/27-P 04/21

Device Total: 21

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11))

Waterflow Switch 19 19 0 19 19

Waterflow Switch Basement East Wing Fire Sprinkler Closet 08999138 1

Waterflow Switch Basement Center Fire Sprinkler Closet Room 2B

8999143 1 05/14-P 04/21 Removed

Waterflow Switch Basement East Wing Fire Sprinkler Closet 8999138 1 05/14-P 04/21

Waterflow Switch 1st East Wing Fire Sprinkler Closet 08999151 1

Waterflow Switch 1st East Wing Fire Sprinkler Closet 08999120 1

Waterflow Switch 1st Center Fire Sprinkler Closet 08999146 1

Waterflow Switch 1st Center Fire Sprinkler Closet 8999146 1 05/13-P 04/21 Removed

Waterflow Switch 1st East Wing Fire Sprinkler Closet 8999120 1 05/13-P 04/21 Removed

Waterflow Switch 1st East Wing Fire Sprinkler Closet 8999151 1 05/14-P 04/21 Removed

Waterflow Switch 2nd Main Hallway Southeast Wing Sprinkler Closet

08999206 1

Waterflow Switch 2nd Main Hallway Northwest Wing Inside Sprinkler Clo

08999217 1-SG7 W1

Waterflow Switch 2nd Stub Wing Fire Sprinkler Closet Outside RM 233

08999214 1-SG 7 W2

Waterflow Switch 2nd Main Hallway Northwest Wing Inside Sprinkler Clo

8999217 1-SG7 W1 05/14-P 04/21

Removed

Waterflow Switch 2nd Main Hallway Southeast Wing Sprinkler Closet

8999206 1 05/13-P 04/21 Removed

Waterflow Switch 2nd Stub Wing Fire Sprinkler Closet Outside RM 233

8999214 1-SG 7 W2 05/13-P 04/21

Waterflow Switch 3rd East Wing Fire Sprinkler Closet 08999126 1

Waterflow Switch 3rd West Wing Fire Sprinkler Closet 08999180 1

Waterflow Switch 3rd Center Fire Sprinkler Closet 08999175 1

Waterflow Switch 3rd Center Fire Sprinkler Closet 8999175 1 05/13-P 04/21 Removed

Waterflow Switch 3rd East Wing Fire Sprinkler Closet 8999126 1 05/13-P 04/21 Removed

Waterflow Switch 3rd West Wing Fire Sprinkler Closet 8999180 1 05/14-P 04/21

Waterflow Switch 4th Northwest Wing Fire Sprinkler Closet 08999173 1-SG-6 W2

Waterflow Switch 4th Short Wing Fire Sprinkler Closet 08999170 1-SG-6 W3

Waterflow Switch 4th East Wing Fire Sprinkler Closet 08999132 1

Waterflow Switch 4th East Wing Fire Sprinkler Closet 8999132 1 05/13-P 04/21 Removed

Waterflow Switch 4th Northwest Wing Fire Sprinkler Closet 8999173 1-SG-6 W2 05/14-P 04/21 Removed

Waterflow Switch 4th Short Wing Fire Sprinkler Closet 8999170 1-SG-6 W3 05/13-P 04/21 Removed

Waterflow Switch 5th Southeast Wing Inside Fire Sprinkler Closet

13362725 1 05/13-P 04/17-P

Waterflow Switch 5th Short Wing Sprinkler Closet 08999164 1

Waterflow Switch 5th Northwest Hallway Fire Sprinkler Closet

45205947 1 05/14-P 04/17-P

Waterflow Switch 5th Short Wing Sprinkler Closet 8999164 1 05/13-P 04/21

Waterflow Switch 6th West 45213513 1-376 05/27-P 04/17-P

Waterflow Switch 6th East 08999134 1-370

Waterflow Switch 6th Center 08999161 1

Waterflow Switch 6th Center 8999161 1 05/13-P 04/21 Removed

Waterflow Switch 6th East 8999134 1-370 05/13-P 04/21 Removed

Waterflow Switch 7th Penthouse 45213474 1-126 05/27-P 04/21

Device Total: 19

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))

Duct Detector 17 17 0 17 17

Duct Detector 1st canteen lobby 12202631 1-DTS-15, 05/26-P 04/17-P

Duct Detector 2nd Service Elevator Lobby 08999202 1-DTS 12

The above device replaced ScanID 8999202:

Duct Detector 2nd Service Elevator Lobby 8999202 1-DTS 12 05/26-P 04/17-R

Duct Detector 2nd Hallway To BLDG 64 08999215 1-DS 18

The above device replaced ScanID 8999215:

Duct Detector 2nd Hallway To BLDG 64 8999215 1-DS 18 05/26-P 04/17-R

Duct Detector 3rd Inside Room 303 45206032 1-DS 19 05/27-P 04/17-P

Duct Detector 3rd Short Wing Roof Access 45205951 1-DS 14 05/27-P 04/20 Removed

Duct Detector 4th Room 403 Staff Lounge 12202630 1-DTS-16 05/27-P 04/17-P

Duct Detector 4th Room 403 2631 1-DTS-16 05/27-P 04/20 Removed

Duct Detector 4th Room 403 12202583 1-DTS-16 05/27-P 04/20 Removed

Duct Detector 4th Room 403 12202585 1-DTS-16 05/27-P 04/20 Removed

Duct Detector Roof East Wing Stairwell Exit to Roof On

AC1

45213511 1-DS7 05/26-P 04/21-P

Duct Detector Roof Outside Weather Proof on Duct at far edge

45213503 1-DS 13 05/26-P 04/21-P

Duct Detector Roof Outside Weather Proof on Ductwork of EF-3

45213502 1 05/26-P 04/21-P

Duct Detector Roof Mechanical Room On EF-14 12202592 1-DS 17 05/27-P 04/21-P

Duct Detector Roof East Wing Stairwell Exit to Roof On

AH2

12202580 1-DS6 05/27-P 04/21-P

Duct Detector Roof East Wing Stairwell Exit to Roof On

AH2

12202579 1-DS5 05/27-P 04/21-P

Duct Detector Roof East Wing Stairwell Exit to Roof On

AC1

12202575 1-DS8 05/26-P 04/21-P

Duct Detector Roof Radio Room Exit to Roof On AH1 12202572 1-DS1 05/26-P 04/21-P

Duct Detector Roof West Wing Stairwell Exit to Roof On

AC3

12202570 1-DS3 05/27-P 04/21-P

Duct Detector Roof West Wing Stairwell Exit to Roof On

AC3

12202568 1-DS4 05/27-P 04/21-P

Duct Detector Roof DS-9 12202566 1-SG5 S8 05/27-P 04/21-P

Duct Detector Roof Radio Room Exit to Roof On AH1 12202563 1-DS2 05/27-P 04/21-P

Device Total: 17

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.

Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))

Heat Detector 6 6 0 6 6

Heat Detector Roof IT Room by Pulley3 By Stair 12202599 1-SG5 H5 05/26-P 04/21-P

Heat Detector Roof IT Room by Pulley3 Above Pulley3 12202598 1-SG5 H6 05/26-P 04/21-P

Heat Detector Roof Elevator Control Room Between Controller1 & Controller2

12202597 1-SG5 H4 05/09-P 04/21-P

Heat Detector Roof Elevator Control Room Above Pulley1

12202596 1-SG5 H2 05/09-P 04/21-P

Heat Detector Roof Elevator Control Room Between Pulley1 & Pulley2

12202595 1-SG5 H1 05/09-P 04/21-P

Heat Detector Roof Elevator Control Room Between Pulley1 & Pulley2

12202594 1-SG5 H3 05/09-P 04/21-P

scDataCom 16 Download Date: 04/24/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5))

Pull Station 41 41 0 41 41

Pull Station Basement Near 19 01162511 1-SG_1F_1

The above device replaced ScanID 1162511:

Pull Station Basement Near 19 1162511 1-SG_1F_1 05/13-P 04/17-R

Pull Station Basement Near Side Exit 01162509 1-SG_1 F7

The above device replaced ScanID 1162509:

Pull Station Basement Near Side Exit 1162509 1-SG_1 F7 05/13-P 04/17-R

Pull Station Basement Near 6 01162502 1-SG_1 F6

The above device replaced ScanID 1162502:

Pull Station Basement Near 6 1162502 1-SG_1 F6 05/13-P 04/17-R

Pull Station Basement Near Main Elevator Lobby 01162740 1-SG_1 F2

The above device replaced ScanID 1162740:

Pull Station Basement Near Main Elevator Lobby 1162740 1-SG_1 F2 05/13-P 04/17-R

Pull Station Basement Outside Room Next To High Voltage Room

12202504 3 05/26-P 04/20 Removed

Pull Station Basement Outside High Voltage Room 10358115 3 05/26-P 04/20 Removed

Pull Station 1st pharmacy hallway rear exit 12602507 1-SG-2 F4 05/13-P 04/17-P

Pull Station 1st outside stair well 01162527 1-SG-6 F1

The above device replaced ScanID 1162527:

Pull Station 1st outside stair well 1162527 1-SG-6 F1 05/13-P 04/17-R

Pull Station 1st room 105 outside hallway 10358111 1-SG-2 F1 05/13-P 04/17-P

Pull Station 1st voluntary sevices/service elevator 68126808 1-SG-6 F3

The above device replaced ScanID 1162514:

Pull Station 1st voluntary sevices 1162514 1-SG-6 F3 05/26-P 04/17-R

Pull Station 1st 119 62-3 outside hallway 21001291 1-SG-2 F3

The above device replaced ScanID 1162621:

Pull Station 1st 119 62-3 outside hallway 1162621 1-SG-2 F3 05/13-P 04/17-R

Pull Station 1st main entrance 45213521 1-sg-2 f5 05/13-P 04/17-P

Pull Station 1st by elevator lobby 08999116 1-SG_2 F2

The above device replaced ScanID 8999116:

Pull Station 1st by elevator lobby 8999116 1-001-002 05/13-P 04/17-R

Pull Station 1st emergency entrance hallway 45213518 1-sg-6 f2 05/13-P 04/17-P

Pull Station 1st South Floor Lobby B 40968490 1-001-002 05/26-P 04/20 Removed

Pull Station 1st corridor hallway leading to bldg 64 1162543 1-sg-1 f1 05/26-P 04/20 Removed

Pull Station 1st corridor hallway leading to bldg 64 front of Exit door

1162541 1-sg-1 f2 05/26-P 04/20 Removed

Pull Station 1st corridor hallway leading to bldg 64 1162538 1-sg-1 f3 05/26-P 04/20 Removed

Pull Station 2nd Main Hallway Southeast Wing Outside RM 208

21001290 1-SG 3 F1

The above device replaced ScanID 1162635:

Pull Station 2nd Main Hallway Southeast Wing Outside RM 208

1162635 1-SG 3 F1 05/13-P 04/17-R

Pull Station 2nd Service Elevator Lobby 21001289 1-SG 7 F4

The above device replaced ScanID 1162569:

Pull Station 2nd Service Elevator Lobby 1162569 1-SG 7 F4 05/13-P 04/17-R

Pull Station 2nd Main Hallway Northwest Wing Outside Room 244

21001288 1-SG 7 F1

The above device replaced ScanID 1162652:

scDataCom 17 Download Date: 04/24/2026

Pull Station 2nd Main Hallway Northwest Wing Outside Room 244

1162652 1-SG 7 F1 05/13-P 04/17-R

Pull Station 2nd Stub Wing Hallway Entrance To Stairs Outside RM 233

45205941 1-SG 7 F3 05/13-P 04/17-P

Pull Station 2nd Main Elevator Lobby 21001287 1-SG 7 F2

The above device replaced ScanID 1162630:

Pull Station 2nd Main Elevator Lobby 1162630 1-SG 7 F2 05/13-P 04/17-R

Pull Station 2nd Hallway To Bldg 64 Double Doors 1162578 1-SG 2 F1 05/26-P 04/20

Pull Station 3rd Near 309 01162730 1-SG_4_F1

The above device replaced ScanID 1162730:

Pull Station 3rd Near 309 1162730 1-SG_4_F1 05/13-P 04/17-R

Pull Station 3rd Near 343 21001286 1-SG_8 F1

The above device replaced ScanID 1162720:

Pull Station 3rd Near 343 1162720 1-SG_8 F1 05/13-P 04/17-R

Pull Station 3rd Service elevator lobby 21001285 1-SG_4 F4

The above device replaced ScanID 1162711:

Pull Station 3rd Service elevator lobby 1162711 1-SG_4 F4 05/13-P 04/17-R

Pull Station 3rd Near 330 45213203 1-SG_8 F1 05/13-P 04/17-P

Pull Station 3rd Near Main Elevator Lobby 01162699 1-SG_4 _F2

The above device replaced ScanID 1162699:

Pull Station 3rd Near Main Elevator Lobby 1162699 1-SG_4 _F2 05/13-P 04/17-R

Pull Station 4th Northwest Wing Stairwell Entrance 21001284 1-SG 6 F4

The above device replaced ScanID 1162743:

Pull Station 4th Northwest Wing Stairwell Entrance 1162743 1-SG 6 F4 05/27-P 04/17-R

Pull Station 4th Service Elevator Lobby 21001283 1-SG 6 F7

The above device replaced ScanID 1162680:

Pull Station 4th Service Elevator Lobby 1162680 1-SG 6 F7 05/27-P 04/17-R

Pull Station 4th Short Wing Central Stairwell Entrance 21001282 1-SG 6 F6

The above device replaced ScanID 1162770:

Pull Station 4th Short Wing Central Stairwell Entrance 1162770 1-SG 6 F6 05/27-P 04/17-R

Pull Station 4th Main Elevator Lobby 21001281 1-SG 6 F5

The above device replaced ScanID 1162767:

Pull Station 4th Main Elevator Lobby 1162767 1-SG 6 F5 05/27-P 04/17-R

Pull Station 4th Near East Stairwell Exit 21001280 1-SG_2 F6

The above device replaced ScanID 1162763:

Pull Station 4th Near East Stairwell Exit 1162763 1-SG_2 F6 05/27-P 04/17-R

Pull Station 5th Southeast Wing Outside Room 516 68126807 1-SG 3 F2

The above device replaced ScanID 1162830:

Pull Station 5th Southeast Wing Outside Room 516 1162830 1-SG 3 F2 05/13-P 04/17-R

Pull Station 5th Short Wing Central Stairwell Entrance 01162820 1-SG 3 F4

The above device replaced ScanID 1162820:

Pull Station 5th Short Wing Central Stairwell Entrance 1162820 1-SG 3 F4 05/13-P 04/17-R

Pull Station 5th Main Elevator Lobby 01162826 1-SG 3 F3

The above device replaced ScanID 1162826:

Pull Station 5th Main Elevator Lobby 1162826 1-SG 3 F3 05/13-P 04/17-R

Pull Station 5th Service Elevator Lobby 68126806 1-SG 7 F7

The above device replaced ScanID 1162858:

Pull Station 5th Service Elevator Lobby 1162858 1-SG 7 F7 05/09-P 04/17-R

Pull Station 5th Northwest Stairwell Entrance 01162841 1-SG 7 F6

The above device replaced ScanID 1162841:

Pull Station 5th Northwest Stairwell Entrance 1162841 1-SG 7 F6 05/09-P 04/17-R

Pull Station 6th West Wing Corridor Outside Room

1162868 1-8 F2 05/13-P 04/17-P

Pull Station 6th West Wing Elevator Lobby Occupational Therapy Waiting Area

1162786 1-8 F3 05/13-P 04/17-P

Pull Station 6th West Wing Corridor Outside Room 21001279 1-8 F2 scDataCom 18 Download Date: 04/24/2026

Pull Station 6th Service Elevator Lobby 21001278 1-SG 8 F3

Pull Station 6th East Wing Corridor Outside 606 01162780 1-4 F5

The above device replaced ScanID 1162780:

Pull Station 6th East Wing Corridor Outside 606 1162780 1-4 F5 05/13-P 04/17-R

Pull Station 6th Elevator Lobby 01162774 1-8 F4

The above device replaced ScanID 1162774:

Pull Station 6th Elevator Lobby 1162774 1-8 F4 05/09-P 04/17-R

Pull Station 6th Corridor Outside Stairwell 612 01162735 1-8 F5

The above device replaced ScanID 1162735:

Pull Station 6th Corridor Outside Stairwell 612 1162735 1-8 F5 05/09-P 04/17-R

Pull Station Roof IT Room Main Entrance 1162666 1-SG5 F2 05/09-P 04/21-P

Pull Station Roof Top of Stairs Between Roof and Penthouse Entrances

1162656 1-SG5 F1 05/09-P 04/21-P

Device Total: 41 scDataCom 19 Download Date: 04/24/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a))

Smoke Detector 73 73 0 73 73

Smoke Detector Basement Near Control Panel 21004981 1 05/26-P 04/17-P

Smoke Detector Basement In Front of Elevator 12202601 1 05/09-P 04/17-P

Smoke Detector Basement Near 15 08999140 1-NAC_A1_04

The above device replaced ScanID 8999140:

Smoke Detector Basement Near 15 8999140 1-NAC_A1_04 05/13-P 04/17-R

Smoke Detector Basement In Front of Elevator 10358109 1 05/09-P 04/17-P

Smoke Detector 1st corridor hallway leading to bldg 64 12202620 1-sg-1 s1 05/26-P 04/17-P

Smoke Detector 1st corridor hallway leading to bldg 64 front of Exit door

12202619 1-n/a 05/26-P 04/17-P

Smoke Detector 1st corridor hallway leading to bldg 64 12202618 1-sg-1 s3 05/26-P 04/17-P

Smoke Detector 1st room 137 outside hallway 08999150 1-SG-6 S1

The above device replaced ScanID 8999150:

Smoke Detector 1st room 137 outside hallway 8999150 1-SG-6 S1 05/13-P 04/17-R

Smoke Detector 1st room 178 outside hallway 08999149 1

The above device replaced ScanID 8999149:

Smoke Detector 1st room 178 outside hallway 8999149 1 05/13-P 04/17-R

Smoke Detector 1st room 102 outside hallway 08999119…

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .