This is a Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate for building MV801 located at 1776 Old Middlefield Way, Mountain View, CA 94043. The annual inspection was completed on June 5, 2026, by scDataCom (Inspector: Derrick Tillman) and was performed in accordance with NFPA 101 (2024 Life Safety Code), NFPA 72 (2022 Fire Alarm Systems), and NFPA 90A (2022 Air Conditioning/Ventilating Systems), as well as The Joint Commission/VHA Standards. The building contact is Doug Gambrell, Manager.

The inspection covered 77 total devices across multiple categories, with 68 devices tested and passed, including tamper switches (4), waterflow switches (2), duct detectors (7), heat detectors (0 tested of 1 total), pull stations (6), smoke detectors (3 tested of 6 total), horn/strobes (20), strobes (20), communicators (1), control panels (1), annunciators (1), and batteries (3). Nine devices remain untested, including 5 elevators, 1 heat detector, and 3 smoke detectors. The control system is a Notifier NFS-640 unit installed May 19, 2017, located in the 1st Floor Main Electrical Room 128. All tested devices passed their respective tests with zero failures. A general note indicates that elevator smoke and heat detectors require scheduling and testing with the Elevator Company. The inspection was downloaded on June 11, 2026.

View the file

Other files

Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Fire/Life Safety System Inspection, Testing and/or Maintenance Certificate

For

MV801

1776 Old Middlefield Way Mountain View, CA 94043

This inspection was performed in accordance with NFPA 101, EDITION 2024, LIFE SAFETY CODE, NFPA 72, EDITION 2022, FIRE ALARM SYSTEMS and NFPA 90A, EDITION 2022, AIR

CONDITIONING/VENTILATING SYSTEMS.

This inspection and testing service has been performed in compliance with The Joint Commission/VHA Standards. The inspection/testing frequencies adhered to for this service have been performed in accordance with the latest Joint Commission/VHA Clarification Memorandum on EC & LS Standards.

Annual Inspection Inspection Completion Date Jun 5, 2026

Building: MV801 Company: scDataCom Contact: Doug Gambrell Contact: Derrick Tillman

Title: Manager Title: Technician scDataCom 1 Download Date: 06/11/2026

Executive Summary

Generated by: BuildingReports.com

Building Information

Building: MV801 Contact: Doug Gambrell

Address: 1776 Old Middlefield Way Phone: 4403192479

Address: Fax:

City/State/ZIP Code: Mountain View, CA 94043 Mobile:

Country: United States of America Email:

Inspection Performed By

Company: scDataCom Inspector: Derrick Tillman

Address: 2700 Gregory St Ste 180 Phone: (669) 333-6375

Address: Fax:

City/State/ZIP Code: Savannah, GA 31404 Mobile:

Country: United States of America Email: dtillman@pavion.com

System Control Unit

Manufacturer: Notifier Inspection Date: 06/05/2026 IDC Style:

Model Number: NFS-640 Install Date: 05/19/2017 SLC Style:

Software Version: Version Date: 05/19/2017 NAC Style:

Location: 1st Floor Main Electrical Room 128 Current Protection:

Central Station Signal Verification

Type: Mfg: Power-Sonic Model #: TG-7

Test Time/Date: 6/5/26 5:59:58 PM Restore Time: Note:

scDataCom 2 Download Date: 06/11/2026

Inspection Completion Date: Jun 5, 2026

Building: MV801

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices.

Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Tamper Switch 4 4 0 4 0 4

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Waterflow Switch 2 2 0 2 0 2

EC 02.03.05 EP 03

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Duct Detector 7 7 0 7 0 7

Heat Detector 0 0 0 0 1 1

Pull Station 6 6 0 6 0 6

Smoke Detector 3 3 0 3 3 6

EC 02.03.05 EP 04

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Horn/Strobe 20 20 0 20 0 20

Strobe 20 20 0 20 0 20

EC 02.03.05 EP 05

Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Communicator 1 1 0 1 0 1

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Duct Detector 7 7 0 7 0 7

LS 02.01.34 EP 02

Protected master fire alarm control panel

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD

Control Panel 1 1 0 1 0 1

LS 02.01.34 EP 10

All other Life Safety Code fire alarm requirements related to NFPA 101-2024 18/19.3.4

Devices

Tested This Quarter Pass Fail

Tested YTD (2026)

Untested YTD (2026) Total Quantity

Annunciator 1 1 0 1 0 1

Battery 3 3 0 3 0 3

LS 02.01.50 EP 07

Annual - Elevators are fully equipped and protected

Devices Tested This Pass Fail Tested YTD Untested YTD Total Quantity scDataCom 3 Download Date: 06/11/2026

Quarter (2026) (2026)

Elevator 0 0 0 0 5 5

Total Device Count: 77 scDataCom 4 Download Date: 06/11/2026

Certification

Company: scDataCom Building: MV801

Inspector: Derrick Tillman Contact: Doug Gambrell

Signed: Jun 5, 2026 Signed:

scDataCom 5 Download Date: 06/11/2026

Notes & Recommendations

The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection.

General Note

Elevator smokes and heat detectors need to be scheduled and tested with Elevator Company scDataCom 6 Download Date: 06/11/2026

Inspection & Testing

The Inspection & Testing section lists all of the items inspected in your building, which are then categorized by the applicable code reference. The most recent inspection is listed in the far right column and is based on the Finish Date of that inspection. The latest inspection uploaded in each previous quarter appears in the four columns to the left.

Passed=P, Failed=F, Replaced=R

EC 02.03.05 EP 01

Annual test of supervisory signal devices: pressure supervisory; pressure tank, pressure supervisory for a dry pipe (both high and low conditions), steam pressure: water level supervisory signal initiating device;

water temperature supervisory; room temperature supervisory and other supervisory initiating devices.

Semi-annual test of valve supervisory switches (tamper switches). NFPA 72 (2022) Table 14.4.3.2 (17)(10)(b-g)

Operate valve and verify signal receipt shall be verified to be within the first two revolutions of the hand wheel or within one-fifth of the travel distance, or per the manufacturer's published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(10)(a))

Devices Tested Q2/26 Pass Q2/26 Fail Q2/26 Tested YTD (2026) Total Quantity

Tamper Switch 4 4 0 4 4

Device Type Location ScanID Address Q2/25 Q2/26

Tamper Switch Exterior At The Street OS&Y 45208306 1-L01 M07 05/20-P 05/29-P

Tamper Switch Exterior At The Street OS&Y 45208305 1-L01 M07 05/20-P 05/29-P

Tamper Switch West Stair 1st Floor Riser 45208293 1-L01 M09 05/20-P 05/29-P

Tamper Switch West Stair 2nd Floor Riser 45208295 1-L01 M13 05/20-P 05/29-P

Device Total: 4 scDataCom 7 Download Date: 06/11/2026

EC 02.03.05 EP 02

Semi-annual testing of water flow devices and valve tamper switches. NFPA 72 (2022) Table 14.4.3.2 (17)(10)(a) & (17)(11)

Water shall be flowed through an inspector's test connection indicating the flow of water equal to that from a single sprinkler of the smallest orifice size installed in the system for wet-pipe systems, or an alarm test bypass connection for dry-pipe, pre-action, or deluge systems in accordance with NFPA 25-20. (NFPA 72-22 Table 14.4.3.2 (17)(11))

Waterflow Switch 2 2 0 2 2

Waterflow Switch West Stair 2nd Floor Riser 45208296 1-L01 M14 05/20-P 05/29-P

Waterflow Switch West Stair 1st Floor Riser 45208294 1-L01 M08 05/20-P 05/29-P

Device Total: 2 scDataCom 8 Download Date: 06/11/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))

Duct Detector 7 7 0 7 7

Duct Detector 1st Floor Break Room 125 45208267 1-L01 D06 05/20-P 05/29-P

Duct Detector 1st Floor Break Rm 125 45208266 1-L01 D05 05/20-P 05/29-P

Duct Detector 2nd Floor Hallway Outside Copy Room Above Tile 220

45208290 1-L01 D09 05/20-P 05/29-P

Duct Detector 2nd Floor Copy/Printer Room 220 45208291 1-L01 D08 05/20-P 05/29-P

Duct Detector 2nd At Stair 2 Above Ceiling Tile Next storage rm 229

40968497 1-2 3 05/20-P 06/05-P

Duct Detector Roof ON AHU-1 45211715 1-AHU1 Return 05/20-P 05/29-P

Duct Detector Roof ON AHU-1 45211711 1-AHU1 Supply 05/20-P 05/29-P

Device Total: 7 scDataCom 9 Download Date: 06/11/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Restorable: Perform heat test with a listed and labeled heat source or in accordance with the manufacturer's published instructions.

Non-Restorable: Do not perform heat test. Test functionality mechanically and electrically. (NFPA 72-22 Table 14.4.3.2 (17)(4)(a))

Heat Detector 0 0 0 0 1

Heat Detector 1st Floor Elev Mach Rm 135 45208299 1-L001 D002 05/20-P

Device Total: 1 scDataCom 10 Download Date: 06/11/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Operate manual fire alarm boxes per the manufacturer's published instructions. Test both key-operated presignal and general alarm manual fire alarm boxes. (NFPA 72-22 Table 14.4.3.2 (17)(5))

Pull Station 6 6 0 6 6

Pull Station 1st Floor West Exit 45208254 1-L001 M006 05/20-P 05/29-P

Pull Station 1st Floor Main Lobby 45208246 1-L01 M05 05/20-P 05/29-P

Pull Station 1st Floor East Exit 45208260 1-L001 M004 05/20-P 05/29-P

Pull Station 2nd Floor Center Stair 45208270 1-L01 M16 05/20-P 05/29-P

Pull Station 2nd Floor West Stair 45208273 1-L001 M012 05/20-P 05/29-P

Pull Station 2nd Floor East Stair 45208280 1-L001 M017 05/20-P 05/29-P

Device Total: 6 scDataCom 11 Download Date: 06/11/2026

Annual testing of duct detectors, heat detectors, manual fire alarm boxes, and smoke detectors. NFPA 72 (2022) Table 14.4.3.2 (17)

Test smoke detectors in place to ensure smoke entry into the sensing chamber and an alarm response. (NFPA 72-22 Table 14.4.3.2 (17)(7)(a))

Smoke Detector 3 3 0 3 6

Smoke Detector 1st Floor Main Electrical Room 128 45208241 1-L001 D004 05/20-P 06/05-P

Smoke Detector 1st Floor Elev Lobby 45208248 1-L001 D003 05/20-P

Smoke Detector 1st Floor Elev Mach Rm 135 45208298 1-L001 D001 05/20-P

Smoke Detector 2nd Floor IDF/IT Room 237 45211718 1-L01 D14 05/20-P 05/29-P

Smoke Detector 2nd Floor Elec Room 45208297 1-L001 D014 05/20-P 05/29-P

Smoke Detector 2nd Floor Elevator Lobby 45208269 1-L001 D011 05/20-P

Device Total: 6 scDataCom 12 Download Date: 06/11/2026

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify the operation of the notification appliances. (NFPA 72-22 Table 14.4.3.2 (22)(1))

Horn/Strobe 20 20 0 20 20

Horn/Strobe 1st Floor Nurse Recruitment Room 140 45208261 1-P2 4 05/20-P 05/29-P

Horn/Strobe 1st Floor CPM Room 122 45208257 1-P1 1 05/20-P 05/29-P

Horn/Strobe 1st Floor Conference Room 110 45208255 1-P1 9 05/20-P 05/29-P

Horn/Strobe 1st Floor West Corridor Near Lobby 45208252 1-P1 5 05/20-P 05/29-P

Horn/Strobe 1st Floor Elevator Lobby 45208249 1-P2 3 05/20-P 05/29-P

Horn/Strobe 1st Floor Main Lobby 45208247 1-P1 8 05/20-P 05/29-P

Horn/Strobe 1st Floor Personnel Security Room 150 45208264 1-P2 7 05/20-P 05/29-P

Horn/Strobe 1st Floor Personnel Security Room 150 45208263 1-P1 7 05/20-P 05/29-P

Horn/Strobe 1st Floor East Corridor Near Lobby 45208258 1-P1 6 05/20-P 05/29-P

Horn/Strobe 1st Floor Staff Break Room 125 45208256 1-P1 4 05/20-P 05/29-P

Horn/Strobe 2nd Floor Near Room 264 45208277 1-P4 11 05/20-P 05/29-P

Horn/Strobe 2nd Floor Near Room 252 45208279 1-P4 5 05/20-P 05/29-P

Horn/Strobe 2nd Floor Near Room 251 45208281 1-P4 4 05/20-P 05/29-P

Horn/Strobe 2nd Floor Near Room 225 45208286 1-P3 3 05/20-P 05/29-P

Horn/Strobe 2nd Floor Near Room 223 45208289 1-P3 5 05/20-P 05/29-P

Horn/Strobe 2nd Floor Work Room 220 45208292 1-P3 7 05/20-P 05/29-P

Horn/Strobe 2nd Floor Near Room 208 45208276 1-P3 11 05/20-P 05/29-P

Horn/Strobe 2nd Floor West Corridor Near Work Room

45208272 1-P3 8 05/20-P 05/29-P

Horn/Strobe 2nd Floor Elevator Lobby 45208268 1-P4 1 05/20-P 05/29-P

Horn/Strobe 1st Near Room 120 HR 45205286 1-P3 3 05/20-P 05/29-P

Device Total: 20 scDataCom 13 Download Date: 06/11/2026

Annual test of visual and audible fire alarms, including speakers and door releasing devices. NFPA 72 (2022) Table 14.4.3.2 (22)

For periodic testing, verify that each appliance flashes. (NFPA 72-22 Table 14.4.3.2 (22)(3))

Strobe 20 20 0 20 20

Strobe 1st Floor Personnel Security Room Photo Area 150

45208265 1-P2 8 05/20-P 05/29-P

Strobe 1st Floor Nurse Recruitment Meeting Room 140-D

45208262 1-P2 5 05/20-P 05/29-P

Strobe 1st Floor East Corridor Near Exit 45208259 1-P2 6 05/20-P 05/29-P

Strobe 1st Floor West Corridor Near Exit 45208253 1-P1 2 05/20-P 05/29-P

Strobe 1st Floor Women's Room 45208251 1-P2 2 05/20-P 05/29-P

Strobe 1st Floor Men's Room 45208250 1-P2 1 05/20-P 05/29-P

Strobe 2nd Floor Inside Workroom 251 225 45211719 1-P4 8 05/20-P 05/29-P

Strobe 2nd Floor Inside File Room 263 225 45211717 1-P4 10 05/20-P 05/29-P

Strobe 2nd Floor Inside Room 208 45211716 1-P3 12 05/20-P 05/29-P

Strobe 2nd Floor Men's Room 45208288 1-P3 2 05/20-P 05/29-P

Strobe 2nd Floor Women's Room 45208287 1-P3 1 05/20-P 05/29-P

Strobe 2nd Floor Kitchenette 236 45208285 1-P4 9 05/20-P 05/29-P

Strobe 2nd Floor Kitchenette 236 45208284 1-P4 3 05/20-P 05/29-P

Strobe 2nd Floor Near IDF/IT Room 237 45208283 1-P4 2 05/20-P 05/29-P

Strobe 2nd Floor Near Room 263 45208282 1-P4 7 05/20-P 05/29-P

Strobe 2nd Floor Near Room 260 45208278 1-P4 12 EOL 05/20-P 05/29-P

Strobe 2nd Floor Conference Room 1 207 45208275 1-P3 10 05/20-P 05/29-P

Strobe 2nd Floor East Corridor Near Electrical Room 221

45208274 1-P3 6 05/20-P 05/29-P

Strobe 2nd Floor Room 205 45208271 1-P3 9 05/20-P 05/29-P

Strobe 2nd Inside Bathroom Mens 40968496 1-V3-24A 05/20-P 05/29-P

Device Total: 20 scDataCom 14 Download Date: 06/11/2026

EC 02.03.05 EP 05

Annual test of fire alarm equipment for notifying off-site fire responders. NFPA 72 (2022) Table 14.4.3.2 (4)

Test all system functions and features in accordance with the equipment manufacturer's published instructions for correct operation in conformance with the applicable sections of Chapter 26. Except for DACT, actuate initiating device and verify receipt of the correct initiating device signal at the supervising station within 90 seconds. Upon completion of the test, restore the system to its functional operating condition. (NFPA 72-22 Table 14.4.3.2 (4))

Communicator 1 1 0 1 1

Communicator 1st Floor Main Electrical Room 128 45211713 1 05/20-P 06/05-P scDataCom 15 Download Date: 06/11/2026

EC 02.03.05 EP 19

Annual test of automatic smoke-detection shutdown devices for air-handling equipment. NFPA 90A (2024) 6.4.1

Test duct smoke detectors that use sampling tubes to ensure that they will properly sample the airstream in the duct using a method acceptable to the manufacturer or in accordance with their published instructions. (NFPA 72-22 Table 14.4.3.2 (17)(7)(e))

Duct Detector 7 7 0 7 7

Duct Detector 1st Floor Break Room 125 45208267 1-L01 D06 05/20-P 05/29-P

Duct Detector 1st Floor Break Rm 125 45208266 1-L01 D05 05/20-P 05/29-P

Duct Detector 2nd Floor Hallway Outside Copy Room Above Tile 220

45208290 1-L01 D09 05/20-P 05/29-P

Duct Detector 2nd Floor Copy/Printer Room 220 45208291 1-L01 D08 05/20-P 05/29-P

Duct Detector 2nd At Stair 2 Above Ceiling Tile Next storage rm 229

40968497 1-2 3 05/20-P 06/05-P

Duct Detector Roof ON AHU-1 45211715 1-AHU1 Return 05/20-P 05/29-P

Duct Detector Roof ON AHU-1 45211711 1-AHU1 Supply 05/20-P 05/29-P

Device Total: 7 scDataCom 16 Download Date: 06/11/2026

LS 02.01.34 EP 02

Protected master fire alarm control panel

Verify correct receipt of alarm, supervisory and trouble signals (inputs), operation of evacuation signals and auxiliary functions (outputs), circuit supervision including detection of open circuits and ground faults, and power supply supervision for detection of loss of ac power and disconnection of secondary batteries. (NFPA 72-22 Table 14.4.3.2 (2)(1))

Control Panel 1 1 0 1 1

Control Panel 1st Floor Main Electrical Room 128 45208244 1 05/20-P 06/05-P scDataCom 17 Download Date: 06/11/2026

Verify the correct operation and identification of annunciators. If provided, verify the correct operation of annunciator under a fault condition. (NFPA 72-22 Table 14.4.3.2 (11))

Annunciator 1 1 0 1 1

Annunciator 1st Floor Main Lobby 45208245 1 05/20-P 06/05-P scDataCom 18 Download Date: 06/11/2026

With the batteries fully charged and connected to the charger, measure the voltage across the batteries with a voltmeter. Then, with the battery charger disconnected, load test the batteries following the manufacturer's recommendations. (NFPA 72-22 Table 14.4.3.2 (9))

Battery 3 3 0 3 3

Battery 1st Floor Main Electrical Room 128 45208242 1 05/20-P 06/05-P

Battery 1st Floor Main Electrical Room 128 45208243 1 05/20-P 06/05-P

Battery 1st Floor Main Electrical Communicater Room 128 Above Facp

45211712 1 05/20-P 06/05-P

Device Total: 3 scDataCom 19 Download Date: 06/11/2026

LS 02.01.50 EP 07

Annual - Elevators are fully equipped and protected

Test interface equipment connections by operating or simulating the equipment being supervised. Verify signals required to be transmitted are received at the control unit. (NFPA 72-22 Table 14.4.3.2 (20))

Elevator 0 0 0 0 5

Elevator 1st Floor Elev Mach Rm 135 45208300 1-L001 M002 05/20-P

Elevator 1st Floor Elev Mach Rm 135 45208301 1-L001 M003 05/20-P

Elevator 1st Floor Elev Mach Rm 135 45208302 1-L001 M001 05/20-P

Elevator 1st Floor Elev Mach Rm 135 45208303 1-L001 M010 05/20-P

Elevator 1st Floor Elev Mach Rm 135 45208304 1-L001 M011 05/20-P

Device Total: 5 scDataCom 20 Download Date: 06/11/2026

Service Summary

The Service Summary section provides an overview of the services performed in this report.

Device Type Service Quantity

Passed

Annunciator Tested 1

Battery Tested 3

Communicator Tested 1

Control Panel Tested 1

Duct Detector Tested 7

Horn/Strobe Tested 20

Pull Station Tested 6

Smoke Detector Tested/Cleaned 3

Strobe Tested 20

Tamper Switch Tested 4

Waterflow Switch Tested 2

Total 68

Untested

Elevator

Heat Detector

Smoke Detector

Total 9

Grand Total 77 scDataCom 21 Download Date: 06/11/2026

Auxiliary Functions Testing

Building: MV801 Control Panel: 1 - Notifier NFS-640

The Auxiliary Functions Testing section lists each of the ancillary items, systems, and emergency equipment that are controlled by the system control unit. Items are grouped by Passed or Failed/Other. The items are listed by device type, and a check box is provided to indicate if the test conducted was simulated.

Type Location Comment ScanID Simulated

Untested

Elevator

1st Floor Elev Mach Rm 135

45208300

45208301

45208302

45208303

45208304 scDataCom 22 Download Date: 06/11/2026

Time, Temperature & Level Testing

The Time, Temperature, & Level Testing section details the measurements taken from various devices that are designed to respond in a certain amount of time, respond at a certain temperature, or respond within the acceptable range of volume or level. Items are grouped by Passed or Failed/Other.

Type Location Comment Sec Deg Lvl ScanID

Passed Waterflow Switch

West Stair 1st Floor Riser Passed 75 n/a n/a 45208294 West Stair 2nd Floor Riser Passed 70 n/a n/a 45208296 scDataCom 23 Download Date: 06/11/2026

Inventory & Warranty Report

Building: MV801 Control Panel: 1 - Notifier NFS-640

The Inventory & Warranty Report lists each of the devices and items that are included in your Inspection Report. A complete inventory count by device type and category is provided. Items installed within the last 90 days, within the last year, and devices installed for two years or more are grouped together for easy reference.

Device or Type Category % of Inventory Quantity

Annunciator Control 1.30% 1

Battery Control 3.90% 3

Communicator Control 1.30% 1

Control Panel Control 1.30% 1

Duct Detector Initiating 9.09% 7

Elevator Auxiliary 6.49% 5

Heat Detector Initiating 1.30% 1

Horn/Strobe Indicating 25.97% 20

Pull Station Initiating 7.79% 6

Smoke Detector Initiating 7.79% 6

Strobe Indicating 25.97% 20

Tamper Switch Supervisory 5.19% 4

Waterflow Switch Initiating 2.60% 2

Type Qty Model # Description Install Date

In Service - 3 Years to 5 Years

Power-Sonic

Battery 1 PS 1270 F1

10/24/2022

Power Sonic

Battery 1 PS 12180 NB

10/22/2022

Battery 1 PS 12180 NB

10/22/2022

In Service - 5 Years to 10 Years

Notifier

Annunciator 1 ACM-24AT

05/19/2017

Control Panel 1 NFS-640

Duct Detector 2 FSP-851

Duct Detector 4 FSP-851 Photoelectric 05/19/2017

Elevator 5 FRM-1

Heat Detector 1 FST-851

Horn/Strobe 20 P2W

Pull Station 4 NBG-12LX

Pull Station 2 NBG-12LX Keyed 05/19/2017

Smoke Detector 5 FSP-851

Smoke Detector 1 FSP-851 Hardwire - Photoelectric 05/19/2017

Strobe 19 SW

Tamper Switch 2 OSY2/FRM-1

System Sensor/Notifi

Waterflow Switch 2 WFD30-2/FMM-10 scDataCom 24 Download Date: 06/11/2026

Tyco

Tamper Switch 2 BFV-N

In Service - 10 Years to 15 Years

Communicator 1 TG-7

10/24/2014

In Service - 15 Years to 25 Years

Siemens

Duct Detector 1 HFP-11

05/03/2011

Wheelock

Strobe 1 RSS-241575W-FR

05/03/2011 scDataCom 25 Download Date: 06/11/2026

Zone Address Report

The Zone Address Report lists all of the devices and items that have an individual address, or are grouped together under a common zone. The device type, location, and description are included for your reference.

Address Device Type Location Type ScanID

Zone/Circuit: 2 3 Duct Detector 2nd At Stair 2 Above Ceiling Tile Next storage rm 229 40968497

Zone/Circuit: L001 D001 Smoke Detector 1st Floor Elev Mach Rm 135 45208298 D002 Heat Detector 1st Floor Elev Mach Rm 135 45208299 D003 Smoke Detector 1st Floor Elev Lobby 45208248 D004 Smoke Detector 1st Floor Main Electrical Room 128 45208241

Zone/Circuit: L01 D05 Duct Detector 1st Floor Break Rm 125 Photoelectric 45208266 D06 Duct Detector 1st Floor Break Room 125 Photoelectric 45208267 D08 Duct Detector 2nd Floor Copy/Printer Room 220 Photoelectric 45208291 D09 Duct Detector 2nd Floor Hallway Outside Copy Room

Above Tile 220 Photoelectric 45208290

Zone/Circuit: L001 D011 Smoke Detector 2nd Floor Elevator Lobby 45208269 D014 Smoke Detector 2nd Floor Elec Room 45208297

Zone/Circuit: L01 D14 Smoke Detector 2nd Floor IDF/IT Room 237 Hardwire -

Photoelectric 45211718

Zone/Circuit: L001 M001 Elevator 1st Floor Elev Mach Rm 135 45208302 M002 Elevator 1st Floor Elev Mach Rm 135 45208300 M003 Elevator 1st Floor Elev Mach Rm 135 45208301 M004 Pull Station 1st Floor East Exit 45208260

Zone/Circuit: L01 M05 Pull Station 1st Floor Main Lobby Keyed 45208246

Zone/Circuit: L001 M006 Pull Station 1st Floor West Exit 45208254

Zone/Circuit: L01 M07 Tamper Switch Exterior At The Street OS&Y 45208305 M07 Tamper Switch Exterior At The Street OS&Y 45208306 M08 Waterflow Switch West Stair 1st Floor Riser 45208294 M09 Tamper Switch West Stair 1st Floor Riser 45208293

Zone/Circuit: L001 M010 Elevator 1st Floor Elev Mach Rm 135 45208303 scDataCom 26 Download Date: 06/11/2026

M011 Elevator 1st Floor Elev Mach Rm 135 45208304 M012 Pull Station 2nd Floor West Stair 45208273

Zone/Circuit: L01 M13 Tamper Switch West Stair 2nd Floor Riser 45208295 M14 Waterflow Switch West Stair 2nd Floor Riser 45208296 M16 Pull Station 2nd Floor Center Stair Keyed 45208270

Zone/Circuit: L001 M017 Pull Station 2nd Floor East Stair 45208280

Zone/Circuit: P1 1 Horn/Strobe 1st Floor CPM Room 122 45208257 2 Strobe 1st Floor West Corridor Near Exit 45208253 4 Horn/Strobe 1st Floor Staff Break Room 125 45208256 5 Horn/Strobe 1st Floor West Corridor Near Lobby 45208252 6 Horn/Strobe 1st Floor East Corridor Near Lobby 45208258 7 Horn/Strobe 1st Floor Personnel Security Room 150 45208263 8 Horn/Strobe 1st Floor Main Lobby 45208247 9 Horn/Strobe 1st Floor Conference Room 110 45208255

Zone/Circuit: P2 1 Strobe 1st Floor Men's Room 45208250 2 Strobe 1st Floor Women's Room 45208251 3 Horn/Strobe 1st Floor Elevator Lobby 45208249 4 Horn/Strobe 1st Floor Nurse Recruitment Room 140 45208261 5 Strobe 1st Floor Nurse Recruitment Meeting

Room 140-D 45208262

6 Strobe 1st Floor East Corridor Near Exit 45208259 7 Horn/Strobe 1st Floor Personnel Security Room 150 45208264 8 Strobe 1st Floor Personnel Security Room Photo

Area 150 45208265

Zone/Circuit: P3 1 Strobe 2nd Floor Women's Room 45208287 2 Strobe 2nd Floor Men's Room 45208288 3 Horn/Strobe 2nd Floor Near Room 225 45208286 3 Horn/Strobe 1st Near Room 120 HR 45205286 5 Horn/Strobe 2nd Floor Near Room 223 45208289 6 Strobe 2nd Floor East Corridor Near Electrical

Room 221 45208274

7 Horn/Strobe 2nd Floor Work Room 220 45208292 8 Horn/Strobe 2nd Floor West Corridor Near Work

Room 220 45208272

9 Strobe 2nd Floor Room 205 45208271 10 Strobe 2nd Floor Conference Room 1 207 45208275 11 Horn/Strobe 2nd Floor Near Room 208 45208276 12 Strobe 2nd Floor Inside Room 208 45211716

Zone/Circuit: P4 1 Horn/Strobe 2nd Floor Elevator Lobby 45208268 2 Strobe 2nd Floor Near IDF/IT Room 237 45208283 3 Strobe 2nd Floor Kitchenette 236 45208284 4 Horn/Strobe 2nd Floor Near Room 251 45208281 5 Horn/Strobe 2nd Floor Near Room 252 45208279 7 Strobe 2nd Floor Near Room 263 45208282 scDataCom 27 Download Date: 06/11/2026

8 Strobe 2nd Floor Inside Workroom 251 225 45211719 9 Strobe 2nd Floor Kitchenette 236 45208285

10 Strobe 2nd Floor Inside File Room 263 225 45211717 11 Horn/Strobe 2nd Floor Near Room 264 45208277

12 EOL Strobe 2nd Floor Near Room 260 45208278

Zone/Circuit: V3-24A Strobe 2nd Inside Bathroom Mens 40968496

AHU1 Return Duct Detector Roof ON AHU-1 45211715 AHU1 Supply Duct Detector Roof ON AHU-1 45211711

MV Bldg 801 Annual Device Testing ( May 2026 )

File details come from the government source that posted it. Updated .