This document is a Request for Information (RFI) for the VA Northern California Health Care System's McClellan Building 98 Power Upgrade project. The RFI, numbered 002 and associated with solicitation 36C26125R0071, focuses on technical details for removable bollards, specifying requirements such as a two-piece construction with a flush mount embedment sleeve, schedule 40 steel material, 6-inch diameter, 48-inch height, and powder-coated yellow finish. The bollards are to be secured with an external padlock and are based on a "post guard or approved equal" design.
The accompanying mechanical details sheet (M-301) provides additional technical specifications for the project, including concrete pad details for generator and electrical equipment. The document emphasizes specific construction requirements such as using normal weight concrete with a minimum 28-day compressive strength of 5,000 PSI, air-entrained concrete surfaces, control joint specifications, and anchor bolt installation compliant with 2022 ASCE 7 and 2023 VA seismic design requirements. The project is located at 5342 Dudley Blvd, McClellan Park, CA 95652, and involves providing backup power for Building 98 of the VA medical center.
View the file
Other files
Show all 20
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
07/16/2025
0001RFI 002 36C26125R0071 Power Upgrade
See Detail 1, "Removable Bollards" in the revised sheet M-301 that includes additional notes detailing regarding details of the bollard and the bollard sleeves.
Notes:
1. Basis of design is post guard or approved equal.
2. Bollard is two-piece construction and a flush mount embedment sleeve.
3. Bollards shall be schedule 40 steel with a smooth dome top.
4. Bollards shall be powder-coated yellow, 6-inch diameter and height 48 inches.
5. Bollards shall be secured in place with an external padlock.
7/21/2025
NTS
REMOVABLE BOLLARDS
ELECTRICAL EQUIPMENT PAD
SECTION VIEW
CONDUIT AREA.
VERIFY ACTUAL
OPENING SIZE
REQUIRED BY
MANUFACTURER.
CONDUIT AREA.
VERIFY ACTUAL
OPENING SIZE
REQUIRED BY
MANUFACTURER.
CONTROL JOINT (SEE NOTE 6
AND CONCRETE CONTROL
JOINT DETAIL)
NTS
GENERATOR EQUIPMENT CONCRETE PAD DETAILS
NOTES:
1. CONTRACTOR TO VERIFY WITH MECHANICAL AND ELECTRICAL FOR PAD DIMENSIONS, CONDUIT AREA OPENING DIMENSIONS PRIOR TO CONSTRUCTION. EXACT PAD LOCATION IS TO BE DETERMINED IN FIELD.
2. THE ANCHOR BOLTS SHALL BE INSTALLED PER THE FUEL OIL TANK MANUFACTURER SPECIFICATIONS AND IN COMPLIANCE WITH 2022 ASCE 7 AND 2023 VA SEISMIC DESIGN REQUIREMENTS H-18-8 MANUAL.
3. CONTRACTOR TO COORDINATE WITH THE MANUFACTURER FOR THE ANCHOR BOLT SIZE, LOCATION AND QUANTITY.
4. THE CAST-IN-PLACE CONCRETE SHALL BE NORMAL WEIGHT CONCRETE WITH THE MIN. 28 DAYS COMPRESSIVE
STRENGTH 5,000 PSI. CONCRETE SHALL BE TESTED BY AN APPROVED AGENCY PAID BY CONTRACTOR.
5. THE CONCRETE SHALL BE AIR ENTRAINED AND THE SURFACE SHALL BE TREATED OR SEALED PROPERLY.
6. THE MAXIMUM SPACE FOR THE CONTROL JOINT IS 25 FT.
7. POST-INSTALLED ANCHORS SHALL BE HILTO BOLTS - TZ OR APPROVED EQUAL.
8. PROVIDE 3/4" CHAMFER ON ALL VERTICAL AND HORIZONTAL CORNERS EXPOSED TO VIEW.
MECHANICAL EQUIPMENT PAD
PLAN VIEW
ATS
CHAMFFER (SEE NOTE 8)
2" MIN. REBAR COVER
3" MIN. REBAR COVER
COMPACT CRUSH STONE
8" CMU WALL W/ #6 REBAR@ EA. CORE. GROUT SOLID.
BOND BM @ EVERY 4 COURSES. SEE ELEC FOR LOCATION.
ELECTRICAL EQUIPMENT
BY OTHERS
#5 REBAR@ 12" OC EA.
WAY/EA. FACE, STD
HOOK AT EA. END
ANCHOR BOLT (TYP.
SEE NOTE 3)
FINISHED GRADE
12"
4"
SEE ELEC DRAWINGS (96" MAX.)
8"
12"
8"
NTS
ELECTRICAL EQUIPMENT CONCRETE PAD DETAILS
CHAMFFER (SEE NOTE 8)
2" MIN. REBAR COVER
3" MIN. REBAR COVER
COMPACT CRUSH STONE
MECHANICAL
EQUIPMENT BY OTHERS
#5 REBAR@ 12" OC EA.
WAY/EA. FACE, STD
HOOK AT EA. END
ANCHOR BOLT (TYP.
SEE NOTE 3)
FINISHED GRADE
16"
6"
14"
12"
16" 8"
56'-0"
14'-0"
MECHANICAL EQUIPMENT PAD
SECTION VIEW
SWITCHGEAR
15'
7'-6"
SAW CUT 4" DEEP NO LATER THAN 12
HR AFTER POUR. FILL WITH SEALANT.
CONCRETE PAD CONTROL JOINT
DETAIL
ELECTRICAL EQUIPMENT PAD
PLAN VIEW
NOTES:
1. CONTRACTOR TO VERIFY WITH CIVIL AND ELECTRICAL FOR THE PAD LOCATION AND DIMENSIONS PRIOR TO CONSTRUCTION.
2. THE ANCHOR BOLTS SHALL BE INSTALLED PER THE EQUIPMENT MANUFACTURER SPECIFICATIONS AND IN COMPLIANCE WITH 2022
ASCE 7 AND 2023 VA SEISMIC DESIGN REQUIREMENTS H-18-8 MANUAL
3. CONTRACTOR TO COORDINATE WITH THE MANUFACTURER FOR THE ANCHOR BOLT SIZE, LOCATION AND QUANTITY.
4. THE CAST-IN-PLACE CONCRETE SHALL BE NORMAL WEIGHT CONCRETE WITH THE MIN. 28 DAYS COMPRESSIVE STRENGTH 5,000
PSI. CONCRETE SHALL BE TESTED BY AN APPROVED AGENCY PAID BY CONTRACTOR.
5. THE CONCRETE SHALL BE AIR ENTRAINED AND THE SURFACE SHALL BE TREATED OR SEALED PROPERLY.
6. THE MAXIMUM SPACE FOR THE CONTROL JOINT IS 25-FT.
7. POST-INSTALLED ANCHORS SHALL BE HILTI KWIK BOLTS -TZ OR APPROVED EQUAL.
8. PROVIDE 3/4" CHAMFER ON ALL VERTICAL AND HORIZONTAL CORNERS EXPOSED TO VIEW.
9. CMU SHALL CONFORM TO ASTM C-90 WITH MIN. F'M=2000 PSI
10. MAINTAIN A MINIMUM 6" BETWEEN ELECTRICAL EQUIPMENT AND ALL OBSTRUCTIONS (E.G. WALLS, FENCES)
EXISTING GAS AND
CHEMICAL STORAGE
CONTAINER
PROVIDE CHAIN
LINK FENCE TO
SECURE
EQUIPMENT
8" CMU WALL
21"
24"
Ø11.25"
48"
12"
Ø6.63"
ELEVATION VIEW
END VIEW - FOUNDATION
TOP VIEW OF CLOSED LID
TOP VIEW POST ONLY
LID
CUSTOMER
PROVIDED LOCK
EMBEDMENT SLEEVE
& HINGING LID
#4 REBAR STIRRUPS
& HORIZONTAL
REINFORCEMENT
NOTES:
1. BASIS OF DESIGN IS POST GUARD OR APPROVED EQUAL.
2. BOLLARD IS TWO-PIECE CONSTRUCTION AND A FLUSH MOUNT EMBEDMENT SLEEVE.
3. BOLLARDS SHALL BE SCHEDULE 40 STEEL WITH A SMOOTH DOME TOP.
4. BOLLARDS SHALL BE POWDER-COATED YELLOW, 6-INCH DIAMETERS AND HEIGHT 48 INCHES
5. BOLLARDS SHALL BE SECURED IN PLACE WITH AN EXTERNAL PADLOCK.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
Fi le P at h
6/
/2
:3 9:
P
M
CONSTRUCTION
DOCUMENTS
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMP
321 4 5 6 7 8 9 10
07/14/2023Revisions: Date:
C-508-19-102
McCLELLAN VAMC, 5342 DUDLEY BLVD McCLELLAN PARK, CA 95652
NORTH ARROW
248 Copeland Street Quincy, MA 02169
(617) 481.6390
PROVIDE BACK UP POWER FOR McLELLAN VAMC BUILDING 98Office of
Construction and Facilities Management
CONSULTANT
PS QN
S:\active projects\22019 Sacramento 5-yr CM support\3 - WIP\Templates from VA\ChillerReplacement_100%-AlaresLogorev10-23-19v1-1355560.jpg
30 Turnpike Road, Suite #1 Southborough, MA 02169
(508) 485.1830
Engineering New England
M-301
MECHANICAL - DETAILS