This document provides details for a federal construction solicitation. The solicitation will be issued by Network Contracting Office 21 on behalf of the Veterans Affairs Sierra Nevada Health Care System to award a firm fixed-price contract for interior upgrades to the Inpatient Mental Health Ward. Upgrades include installation of an anti-ligature alarm system, door renovations, a temporary security entrance, replacement of an existing sally port entrance, installation of a CCTV monitoring system, and expansion and integration of the fire protection system throughout the ward. The performance period is 122 days from notice to proceed. This project is set aside 100% for Service Disabled Veteran Owned Small Businesses. The NAICS code is 236220 and size standard is $39.5 million. The solicitation is scheduled for release on or around March 30, 2020 with bids due 30 days later. The contract will be awarded in accordance with the solicitation procedures.
36C26120B0012 0002 654-17-730 Addendum_01.pdf
View the file
Other files
Show 40 more
Latest 50 of 56 listed here. See the rest on GovTribe.
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ADDENDUM 01
E design@spur-design.com W spur-design.com
PROJECT NAME: 654-17-713, Inpatient Mental Health Corrections
SPUR PROJ. NO.: 1795.01
ISSUE DATE: February 3, 2020
CHANGES TO SPECIFICATIONS:
1. Section 08 71 00 – DOOR HARDWARE
a. Revised Section 08 71 00 Provided with this Addendum – includes revised hardware sets.
2. Section 28 23 00 – VIDEO SURVEILLANCE
a. Revised Section 28 23 00 Provided with this Addendum
CHANGES TO DRAWINGS:
1. Sheet 12-ES-202, ELECTRICAL DOOR ANTI-LIGATURE FLOOR PLAN / SECURITY CAMERA PLAN:
a. General Notes, Note 2 - remove and replace with the following: ‘PROVIDE ANTI-LIGATURE SECURITY
CAMERAS IN THE QUANTITY SHOWN ON THE VIDEO SURVEILLANCE PLAN. COORDINATE WITH VA FOR EXACT
CAMERA LOCATIONS/VIEW COVERAGE. NEW CAMERAS TO BE ROUTED TO NEW RECORDING EUQIPMENT
LOCATED IN IT CLOST B6142. COORDINATE EXACT LOCATION OF IT CLOSET WITH VA COR. REFER TO SHEET
12-ES-301 FOR ADDITIONAL INFORMATION.’
b. Electrical New Plan Notes, Note 6 – remove and replace with the following: ‘VIDEO MONITORING
STATION/CAPABILITY SHALL BE PROVIDED AT NURSE STATION AND CONNECTED TO LOCAL VEDEO
VIEWING/RECORDING EQUIPMENT LOCATED IN THE ASSOCIATED IT ROOM. COORDINATE EXACT
MONITORING LOCATION WITH VA.’
2. Sheet 12-ES-301, ELECTRICAL SCHEDULES AND DETAILS:
a. New Detail 4, Existing Data Rack IT Closet B6142.
b. Video Surveillance Camera Schedule, Note 4 – remove and replace with the following: ‘SSTV-CAMERA TO BE
CONNECTED TO NEW RECORDING EQUIPMENT IN IT CLOSET B6142. REFER TO DETAIL 4, SHEET 12-ES-301
FOR ADDITIONAL INFORMATION.’
END OF ADDENDUM NO. 1
Attachments:
Specification Sections in PDF format:
08 71 00R1 Door Hardware
28 23 00R1 Video Surveillance
Drawing Sheets in PDF format:
001_12-ES-202
002_12-ex-301
Project No. 654-17-713
VASNHCS – Reno, NV
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-1
SECTION 08 71 00
DOOR HARDWARE
PART 1 - GENERAL
1.1 DESCRIPTION
A. Door hardware and related items necessary for complete installation and operation of doors.
1.2 RELATED WORK
A. Caulking: Section 07 92 00 JOINT SEALANTS.
B. Application of Hardware: Section 08 14 00, WOOD DOORS, Section 08 11
13, HOLLOW METAL DOORS AND FRAMES.
C. Finishes: Section 09 06 00, SCHEDULE FOR FINISHES.
D. Painting: Section 09 91 00, PAINTING.
E. Card Readers: Section 28 13 11, PHYSICAL ACCESS CONTROL SYSTEMS.
F. Electrical: Division 26, ELECTRICAL.
G. Fire Detection: Section 28 31 00, FIRE DETECTION AND ALARM.
1.3 GENERAL
A. All hardware shall comply with UFAS, (Uniform Federal Accessible
Standards) unless specified otherwise.
B. Provide rated door hardware assemblies where required by most current version of the International Building Code (IBC).
C. Hardware for Labeled Fire Doors and Exit Doors: Conform to requirements of NFPA 80 for labeled fire doors and to NFPA 101 for exit doors, as well as to other requirements specified. Provide hardware listed by UL, except where heavier materials, large size, or better grades are specified herein under paragraph HARDWARE SETS. In lieu of UL labeling and listing, test reports from a nationally recognized testing agency may be submitted showing that hardware has been tested in accordance with UL test methods and that it conforms to NFPA requirements.
D. Hardware for application on metal and wood doors and frames shall be made to standard templates. Furnish templates to the fabricator of these items in sufficient time so as not to delay the construction.
E. The following items shall be of the same manufacturer, except as otherwise specified:
1. Mortise locksets.
2. Hinges for hollow metal and wood doors.
3. Surface applied overhead door closers.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-2
1.4 WARRANTY
A. Automatic door operators shall be subject to the terms of FAR Clause
52.246-21, except that the Warranty period shall be two years in lieu of one year for all items except as noted below:
1. Locks, latchsets, and panic hardware: 5 years.
2. Door closers and continuous hinges: 10 years.
1.5 MAINTENANCE MANUALS
A. In accordance with Section 01 00 00, GENERAL REQUIREMENTS Article titled "INSTRUCTIONS", furnish maintenance manuals and instructions on all door hardware. Provide installation instructions with the submittal documentation.
1.6 SUBMITTALS
A. Submittals shall be in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA AND SAMPLES. Submit 6 copies of the schedule per Section
01 33 23. Submit 2 final copies of the final approved schedules to VAMC
Locksmith as record copies (VISN Locksmith if the VAMC does not have a locksmith).
B. Hardware Schedule: Prepare and submit hardware schedule in the following form:
Hardware
Item
Quantity Size Reference
Publication
Type No.
Finish Mfr.
Name and
Catalog
No.
Key
Control
Symbols
UL Mark
(if fire rated and listed)
ANSI/BHMA
Finish
Designation
C. Ligature Resistant Door Alarm Riser Diagram: Prepare and submit 6 copies of shop drawings of electric riser diagram complete with all required equipment components. Submission shall be in accordance with requirements per Section 01 33 23 for review and approval by project
CO. Along with shop drawing submittal provide installation data. At completion of project provide CO with operation and maintenance manuals.
D. Samples and Manufacturers' Literature:
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-3
1. Samples: All hardware items (proposed for the project) that have not been previously approved by Builders Hardware Manufacturers
Association shall be submitted for approval. Tag and mark all items with manufacturer's name, catalog number and project number.
2. Samples are not required for hardware listed in the specifications by manufacturer's catalog number, if the contractor proposes to use the manufacturer's product specified.
E. Certificate of Compliance and Test Reports: Submit certificates that hardware conforms to the requirements specified herein. Certificates shall be accompanied by copies of reports as referenced. The testing shall have been conducted either in the manufacturer's plant and certified by an independent testing laboratory or conducted in an independent laboratory, within four years of submittal of reports for approval.
1.7 DELIVERY AND MARKING
A. Deliver items of hardware to job site in their original containers, complete with necessary appurtenances including screws, keys, and instructions. Tag one of each different item of hardware and deliver to
Resident Engineer for reference purposes. Tag shall identify items by
Project Specification number and manufacturer's catalog number. These items shall remain on file in Resident Engineer's office until all other similar items have been installed in project, at which time the
Resident Engineer will deliver items on file to Contractor for installation in predetermined locations on the project.
1.8 PREINSTALLATION MEETING
A. Convene a preinstallation meeting not less than 30 days before start of installation of door hardware. Require attendance of parties directly affecting work of this section, including Contractor and Installer, Architect, Contracting Officer’s Representative and VA Locksmith, Hardware Consultant, and Hardware Manufacturer’s Representative.
Review the following:
1. Inspection of door hardware.
2. Job and surface readiness.
3. Coordination with other work.
4. Protection of hardware surfaces.
5. Substrate surface protection.
6. Installation.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-4
7. Adjusting.
8. Repair.
9. Field quality control.
10. Cleaning.
1.9 INSTRUCTIONS
A. Hardware Set Symbols on Drawings: Except for protective plates, door stops, mutes, thresholds and the like specified herein, hardware requirements for each door are indicated on drawings by symbols.
Symbols for hardware sets consist of letters (e.g., "HW") followed by a number. Each number designates a set of hardware items applicable to a door type.
B. Keying: All cylinders shall be keyed into existing Key System. Provide removable core cylinders that are removable only with a special key or tool without disassembly of knob or lockset.
1.10 APPLICABLE PUBLICATIONS
A. The publications listed below form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only. In text, hardware items are referred to by series, types, etc., listed in such specifications and standards, except as otherwise specified.
B. American Society for Testing and Materials (ASTM):
F883-04.................Padlocks
E2180-07................Standard Test Method for Determining the
Activity of Incorporated Antimicrobial Agent(s)
In Polymeric or Hydrophobic Materials
C. American National Standards Institute/Builders Hardware Manufacturers
Association (ANSI/BHMA):
A156.1-06...............Butts and Hinges
A156.2-03...............Bored and Pre-assembled Locks and Latches
A156.3-08...............Exit Devices, Coordinators, and Auto Flush
Bolts
A156.4-08...............Door Controls (Closers)
A156.5-14...............Cylinders and Input Devices for Locks.
A156.6-05...............Architectural Door Trim
A156.8-05...............Door Controls-Overhead Stops and Holders
A156.11-14..............Cabinet Locks
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-5
A156.12-05 .............Interconnected Locks and Latches
A156.13-05..............Mortise Locks and Latches Series 1000
A156.14-07 .............Sliding and Folding Door Hardware
A156.15-06..............Release Devices-Closer Holder, Electromagnetic and Electromechanical
A156.16-08..............Auxiliary Hardware
A156.17-04 .............Self-Closing Hinges and Pivots
A156.18-06..............Materials and Finishes
A156.20-06 .............Strap and Tee Hinges, and Hasps
A156.21-09..............Thresholds
A156.22-05..............Door Gasketing and Edge Seal Systems
A156.23-04..............Electromagnetic Locks
A156.24-03..............Delayed Egress Locking Systems
A156.25-07 .............Electrified Locking Devices
A156.26-06..............Continuous Hinges
A156.28-07 .............Master Keying Systems
A156.29-07 .............Exit Locks and Alarms
A156.30-03 .............High Security Cylinders
A156.31-07 .............Electric Strikes and Frame Mounted Actuators
A156.36-10..............Auxiliary Locks
A250.8-03...............Standard Steel Doors and Frames
D. National Fire Protection Association (NFPA):
80-10...................Fire Doors and Other Opening Protectives
101-09..................Life Safety Code
E. Underwriters Laboratories, Inc. (UL):
Building Materials Directory (2008)
PART 2 - PRODUCTS
2.1 CONTINUOUS HINGES
A. ANSI/BHMA A156.26, Grade 1-600.
1. Listed under Category N in BHMA's "Certified Product Directory."
B. General: Minimum 0.120-inch- (3.0-mm-) thick, hinge leaves with minimum overall width of 4 inches (102 mm); fabricated to full height of door and frame and to template screw locations; with components finished after milling and drilling are complete
C. Continuous, Barrel-Type Hinges: Hinge with knuckles formed around a
Teflon-coated 6.35mm (0.25-inch) minimum diameter pin that extends entire length of hinge.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-6
1. Base Metal for Interior Hinges: Stainless steel.
2. Base Metal for Hinges for Fire-Rated Assemblies: Stainless steel.
3. Provide with non-removable pin (hospital tip option) at lockable outswing doors.
4. Where required to clear adjacent casing, trim, and wall conditions and allow full door swing, provide wide throw hinges of minimum width required.
5. Provide with manufacturer’s cut-outs for separate mortised power transfers and/or mortised automatic door bottoms where they occur.
6. Where thru-wire power transfers are integral to the hinge, provide hinge with easily removable portion to allow easy access to wiring connections.
7. Where models are specified that provide an integral wrap-around edge guard for the hinge edge of the door, provide manufacturer’s adjustable threaded stud and machine screw mechanism to allow the door to be adjusted within the wrap-around edge guard.
2.2 DOOR CLOSING DEVICES
A. Closing devices shall be products of one manufacturer for each type specified.
2.3 OVERHEAD CLOSERS
A. Conform to ANSI A156.4, Grade 1.
B. Closers shall conform to the following:
1. The closer shall have minimum 50 percent adjustable closing force over minimum value for that closer and have adjustable hydraulic back check effective between 60 degrees and 85 degrees of door opening.
2. Where specified, closer shall have hold-open feature.
3. Size Requirements: Provide multi-size closers, sizes 1 through 6, except where multi-size closer is not available for the required application.
4. Material of closer body shall be forged or cast.
5. Arm and brackets for closers shall be steel, malleable iron or high strength ductile cast iron.
6. Where closers are exposed to the exterior or are mounted in rooms that experience high humidity, provide closer body and arm assembly of stainless steel material.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-7
7. Closers shall have full size metal cover; plastic covers will not be accepted.
8. Closers shall have adjustable hydraulic back-check, separate valves for closing and latching speed, adjustable back-check positioning valve, and adjustable delayed action valve.
9. Provide closers with any accessories required for the mounting application, including (but not limited to) drop plates, special soffit plates, spacers for heavy-duty parallel arm fifth screws, bull-nose or other regular arm brackets, longer or shorter arm assemblies, and special factory templating. Provide special arms, drop plates, and templating as needed to allow mounting at doors with overhead stops and/or holders.
10. Closer arms or backcheck valve shall not be used to stop the door from overswing, except in applications where a separate wall, floor, or overhead stop cannot be used.
11. Provide parallel arm closers with heavy duty rigid arm.
12. Where closers are to be installed on the push side of the door, provide parallel arm type except where conditions require use of top jamb arm.
13. Provide all surface closers with the same body attachment screw pattern for ease of replacement and maintenance.
14. All closers shall have a 1 ½” (38mm) minimum piston diameter.
2.4 DOOR STOPS
A. Conform to ANSI A156.16.
B. Provide door stops wherever an opened door or any item of hardware thereon would strike a wall, column, equipment or other parts of building construction. For concrete, masonry or quarry tile construction, use lead expansion shields for mounting door stops.
C. Where cylindrical locks with turn pieces or pushbuttons occur, equip wall bumpers Type L02251 (rubber pads having concave face) to receive turn piece or button.
D. Provide floor stops (Type L02141 or L02161 in office areas; Type L02121 x 3 screws into floor elsewhere. Wall bumpers, where used, must be installed to impact the trim or the door within the leading half of its width. Floor stops, where used, must be installed within 4-inches of the wall face and impact the door within the leading half of its width.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-8
E. Where drywall partitions occur, use floor stops, Type L02141 or L02161 in office areas, Type L02121 elsewhere.
F. Provide stop Type L02011, as applicable for exterior doors. At outswing doors where stop can be installed in concrete, provide stop mated to concrete anchor set in 76mm (3-inch) core-drilled hole and filled with quick-setting cement.
G. Omit stops where floor mounted door holders are required and where automatic operated doors occur.
H. Provide appropriate roller bumper for each set of doors (except where closet doors occur) where two doors would interfere with each other in swinging.
I. Provide appropriate door mounted stop on doors in individual toilets where floor or wall mounted stops cannot be used.
J. Provide door stops on doors where combination closer magnetic holders are specified, except where wall stops cannot be used or where floor stops cannot be installed within 4-inches of the wall.
K. Where the specified wall or floor stop cannot be used, provide concealed overhead stops (surface-mounted where concealed cannot be used).
2.5 OVERHEAD DOOR STOPS AND HOLDERS
A. Conform to ANSI Standard A156.8. Overhead holders shall be of sizes recommended by holder manufacturer for each width of door. Set overhead holders for 110 degree opening, unless limited by building construction or equipment. Provide Grade 1 overhead concealed slide type: stop-only at rated doors and security doors, hold-open type with exposed hold-open on/off control at all other doors requiring overhead door stops.
2.6 LOCKS AND LATCHES
A. Conform to ANSI A156.2. Locks and latches for doors 45 mm (1-3/4 inch) thick or over shall have beveled fronts. Lock cylinders shall have pins as required by VA Facilities. Cylinders for all locksets shall be removable core type. Cylinder shall be removable by special key or tool. Construct all cores so that they will be interchangeable into the core housings of all mortise locks, rim locks, cylindrical locks, and any other type lock included in the Master Key System. Disassembly of lever or lockset shall not be required to remove core from lockset. All locksets or latches on double doors with fire label shall have latch bolt with 19 mm (3/4 inch) throw, unless shorter throw allowed by the
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-9 door manufacturer’s fire label. Provide temporary keying device or construction core to allow opening and closing during construction and prior to the installation of final cores.
B. In addition to above requirements, locks and latches shall comply with following requirements:
1. Mortise Lock and Latch Sets: Conform to ANSI/BHMA A156.13. Mortise locksets shall be series 1000, minimum Grade 2.
2. Auxiliary locks shall be as specified under hardware sets and conform to ANSI A156.36.
3. Locks on designated doors in Psychiatric (Mental Health) areas shall be paddle type with arrow projection covers and be UL Listed.
Provide these locks with paddle in the down position on both sides of the door. Locks shall be fabricated of wrought stainless steel.
2.7 ELECTROMAGNETIC LOCKS
A. ANSI/BHMA A156.23; electrically powered, of strength and configuration indicated; with electromagnet attached to frame and armature plate attached to door. Listed under Category E in BHMA's "Certified Product
Directory."
1. Type: Full exterior or full interior, as required by application indicated.
2. Strength Ranking: 1000 lbf (4448 N).
3. Inductive Kickback Peak Voltage: Not more than 0 V.
4. Residual Magnetism: Not more than 0 lbf (0 N)to separate door from magnet.
B. Delayed-Egress Locks: BHMA A156.24. Listed under Category G in BHMA's
"Certified Product Directory".
1. Means of Egress Doors: Lock releases within 15 seconds after applying a force not more than 15 lbf (67 N) for not more than 3 seconds, as required by NFPA 101.
2. Security Grade: Activated from secure side of door by initiating device.
3. Movement Grade: Activated by door movement as initiating device.
4. The lock housing shall not project more than 4-inches (101mm) from the underside of the frame head stop.
2.8 ELECTRIC STRIKES
A. ANSI/ BHMA A156.31 Grade 1.
B. General: Use fail-secure electric strikes at fire-rated doors.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-10
2.9 KEYS
A. Stamp all keys with change number and key set symbol. Furnish keys in quantities as follows:
Locks/Keys Quantity
Cylinder locks 2 keys each
Cylinder lock change key blanks
100 each different key way
Master-keyed sets 6 keys each
Grand Master sets 6 keys each
Great Grand Master set 5 keys
Control key 2 keys
B. Psychiatric keys shall be cut so that first two bittings closest to the key shoulder are shallow to provide greater strength at point of greatest torque.
2.10 ARMOR PLATES, KICK PLATES, MOP PLATES AND DOOR EDGING
A. Conform to ANSI Standard A156.6.
B. Provide protective plates as specified below:
1. Kick plates, mop plates and armor plates of metal, Type J100 series.
2. Provide kick plates and mop plates where specified. Kick plates shall be 254 mm (10 inches) or 305 mm (12 inches) high. Mop plates shall be 152 mm (6 inches) high. Both kick and mop plates shall be minimum 1.27 mm (0.050 inches) thick. Provide kick and mop plates beveled on all 4 edges (B4E). On push side of doors where jamb stop extends to floor, make kick plates 38 mm (1-1/2 inches) less than width of door, except pairs of metal doors which shall have plates
25 mm (1 inch) less than width of each door. Extend all other kick and mop plates to within 6 mm (1/4 inch) of each edge of doors. Kick and mop plates shall butt astragals. For jamb stop requirements, see specification sections pertaining to door frames.
3. Kick plates and/or mop plates are not required on following door sides:
a. Armor plate side of doors;
b. Exterior side of exterior doors;
c. Closet side of closet doors;
d. Both sides of aluminum entrance doors.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-11
4. Armor plates for doors are listed under Article "Hardware Sets".
Armor plates shall be thickness as noted in the hardware set, 875 mm
(35 inches) high and 38 mm (1-1/2 inches) less than width of doors, except on pairs of metal doors. Provide armor plates beveled on all
4 edges (B4E). Plates on pairs of metal doors shall be 25 mm (1 inch) less than width of each door. Where top of intermediate rail of door is less than 875 mm (35 inches) from door bottom, extend armor plates to within 13 mm (1/2 inch) of top of intermediate rail.
On doors equipped with panic devices, extend armor plates to within
13 mm (1/2 inch) of panic bolt push bar.
5. Provide stainless steel edge guards where so specified at wood doors. Provide mortised type instead of surface type except where door construction and/or ratings will not allow. Provide edge guards of bevel and thickness to match wood door. Provide edge guards with factory cut-outs for door hardware that must be installed through or extend through the edge guard. Provide full-height edge guards except where door rating does not allow; in such cases, provide edge guards to height of bottom of typical lockset armor front. Forward edge guards to wood door manufacturer for factory installation on doors.
2.11 LIGATURE RESISTANT DOOR ALARM:
A. Provide ligature resistant, monitoring and notification system capable of detecting a ligature-initiated event at a patient bedroom door. An alarm system will trigger audio and visual notification devices at the bedroom door and nurse’s station to alert staff of a ligature emergency. The system shall be addressable, self-monitoring, and able to diagnose alarm and system problems. The system shall be capable of documenting ligature-initiated events
B. Components of Alarm System:
1. Ligature-initiating Alarm:
a. Photoelectric sensor alarm assembly: Photoelectric sensors shall be positioned on the door and frame within anti-ligature casings constructed of Acetal (Polyoxmethylene-POM) an impact resistant plastic commonly called Delrin. Provide the following installation configuration for the sensors:
1) One set of sensors at the top of the door and one set of sensors at the bottom at the undercut of the door.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-12
b. The alarm assembly circuit shall be concealed and redundant providing a tamper resistant, failsafe operation.
c. The alarm assemblies are to be installed with tamper resistant fasteners only.
2. Hinge and Power Transfer
a. Power transfer section of hinge shall be housed at the top end of the continuous hinge to eliminate the potential of exposed wires or flex conduit.
b. The power transfer section of the hinge shall be field removable to eliminate the need to remove the door when addressing electrical service issues.
3. Local Visual Alarm (Strobe)
a. Install in corridor above monitored room doors throughout facility.
b. Alarm unit shall be anti-ligature with a sloped top, made of resilient material and fastened with tamper resistant hardware.
c. Door alarm units shall flash when any monitored door alarm is triggered at a ligature point initiated event.
d. The door alarm strobe shall be turned off when a user’s code is entered at the keypad at the room door.
4. Local Keyswitch:
a. Wall mounted, shall be flush mounted or designed to be anti-ligature.
b. Coordinate specific location with COR and Unit Manager
c. Designed for momentary actuation with spring return.
5. Keypad:
a. Provide an LCD display notification for activation of all monitored patient bedroom doors.
b. Flush mounted or designed to be anti-ligature
6. Remote Monitoring Panel and Audible Alarm:
a. The remote monitoring panel shall allow monitoring of each patient bedroom door from the nurse’s station with a visual indicator of the location of the ligature-initiated event.
b. The remote audible alarm will be a distinct tone not to be confused with other alarms located in the vicinity.
7. Control Panel:
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-13
a. Panel and all elements of the alarm system shall be equipped with a dedicated battery backup system and emergency power feed for maintaining power to the control panel in the event of a power failure due to a power outage.
b. Provide software for printing documented alarm events.
2.12 DOOR PULLS WITH PLATES
A. Conform to ANSI A156.6. Pull Type J401, 152 mm CTC (6 inches CTC) length by 19 mm (3/4 inches) diameter minimum with plate Type J302, 90 mm by 381 mm (3-1/2 inches by 15 inches), unless otherwise specified.
Provide pull with projection of 57.2 mm (2 1/4 inches) minimum and a clearance of 38.1 mm (1 1/2 inches) minimum. Cut plates of door pull plate for cylinders, or turn pieces where required.
2.13 PUSH PLATES
A. Conform to ANSI A156.6. Metal, Type J302, 203 mm (8 inches) wide by
406.4 mm (16 inches) high. Provide metal Type J302 plates 102 mm (4 inches) wide by 406.4 mm (16 inches) high where push plates are specified for doors with stiles less than 203 mm (8 inches) wide. Cut plates for cylinders, and turn pieces where required.
2.14 MISCELLANEOUS HARDWARE
A. Mutes: Conform to ANSI A156.16. Provide door mutes or door silencers
Type L03011 or L03021, depending on frame material, of white or light gray color, on each steel or wood door frame, except at fire-rated frames. Furnish 3 mutes for single doors.
2.15 FINISHES
A. Exposed surfaces of hardware shall have ANSI A156.18, finishes as specified below. Finishes on all hinges, pivots, closers, thresholds, etc., shall be as specified below under "Miscellaneous Finishes." For field painting (final coat) of ferrous hardware, see Section 09 91 00, PAINTING.
B. 626 or 630: All surfaces on exterior and interior of buildings, except where other finishes are specified.
C. Miscellaneous Finishes:
1. Hinges --exterior doors: 626 or 630.
2. Hinges --interior doors: 652 or 630.
3. Pivots: Match door trim.
4. Door Closers: Factory applied paint finish. Dull or Satin Aluminum color.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-14
5. Thresholds: Mill finish aluminum.
6. Other primed steel hardware: 600.
D. Hardware Finishes for Existing Buildings: U.S. Standard finishes shall match finishes of hardware in (similar) existing spaces.
F. Anti-microbial Coating: All hand-operated hardware (levers, pulls, push bars, push plates, paddles, and panic bars) shall be provided with an anti-microbial/anti-fungal coating that has passed ASTM E2180 tests.
Coating to consist of ionic silver (Ag+). Silver ions surround bacterial cells, inhibiting growth of bacteria, mold, and mildew by blockading food and respiration supplies.
2.16 BASE METALS
A. Apply specified U.S. Standard finishes on different base metals as following:
Finish Base Metal
652 Steel
630 Stainless steel
PART 3 - EXECUTION
3.1 HARDWARE HEIGHTS
A. For existing buildings locate hardware on doors at heights to match existing hardware. The Contractor shall visit the site, verify location of existing hardware and submit locations to VA Resident Engineer for approval.
B. Hardware Heights from Finished Floor:
1. Locksets and latch sets centerline of strike 1024 mm (40-5/16 inches).
2. Deadlocks centerline of strike 1219 mm (48 inches).
3. Centerline of door pulls to be 1016 mm (40 inches).
4. Push plates and push-pull shall be 1270 mm (50 inches) to top of plate.
5. Push-pull latch to be 1024 mm (40-5/16 inches) to centerline of strike.
6. Locate other hardware at standard commercial heights. Locate push and pull plates to prevent conflict with other hardware.
3.2 INSTALLATION
A. Closer devices, including those with hold-open features, shall be equipped and mounted to provide maximum door opening permitted by
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-15 building construction or equipment. Closers shall be mounted on side of door inside rooms, inside stairs, and away from corridors.
B. Hinge leaves shall be sufficiently wide to allow doors to swing clear of door frame trim and surrounding conditions.
C. Fastenings: Suitable size and type and shall harmonize with hardware as to material and finish. Provide machine screws and lead expansion shields to secure hardware to concrete, ceramic or quarry floor tile, or solid masonry. Fiber or rawl plugs and adhesives are not permitted.
All fastenings exposed to weather shall be of nonferrous metal.
D. After locks have been installed; show in presence of Resident Engineer that keys operate their respective locks in accordance with keying requirements. (All keys, Master Key level and above shall be sent
Registered Mail to the Medical Center Director along with the bitting list. Also a copy of the invoice shall be sent to the Resident Engineer for his records.) Installation of locks which do not meet specified keying requirements shall be considered sufficient justification for rejection and replacement of all locks installed on project.
3.3 FINAL INSPECTION
A. Installer to provide letter to VA Resident/Project Engineer that upon completion, installer has visited the Project and has accomplished the following:
1. Re-adjust hardware.
2. Evaluate maintenance procedures and recommend changes or additions, and instruct VA personnel.
3. Identify items that have deteriorated or failed.
4. Submit written report identifying problems.
3.4 DEMONSTRATION
A. Demonstrate efficacy of mechanical hardware and electrical, and electronic hardware systems, including adjustment and maintenance procedures, to satisfaction of Resident/Project Engineer and VA
Locksmith.
3.5 HARDWARE SETS
A. Following sets of hardware correspond to hardware symbols shown on drawings. Only those hardware sets that are shown on drawings will be required. Disregard hardware sets listed in specifications but not shown on drawings.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-16
B. Hardware Consultant working on a project will be responsible for providing additional information regarding these hardware sets. The numbers shown in the following sets come from BHMA standards.
C. All hardware finishes to be US32D Satin Stainless Steel & US27 Satin
Aluminum.
INTERIOR SINGLE DOORS
A. Manufacturer’s Abbreviations:
1. MR - Markar
2. SA - SARGENT
3. RF - Rixson
4. RO - Rockwood
5. PE - Pemko
6. SU - Securitron
7. MK - McKinney
Set: 1.0
Doors: B6CD01
1 Continuous Hinge FM3500 AMS CTP 630 MR
1 Fail Secure Lock 8273 BHW MK US32D SA
1 Concealed Closer 91N 90N Torx 689 RF
1 Kick Plate K1050 10" Torx Screws US32D RO
1 Door Stop 471 TORX (L02131) US26D RO
1 Gasketing S44BL PE
1 Electric Power Transfer EL-CEPT SU
1 Frame Harness QC-C1500P (as required) MK
1 Door Harness QC-C__P (as required) MK
1 ElectroLynx Harness QC-C__P (for door sensor) MK
1 Position Switch DPS-M-BK SU
1 Power Supply EPS-05 (as needed) SU
2 Card Reader provided by access control.
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-17
Set: 2.0
Doors: B6CD02
1 Continuous Hinge FM3500 AMS CTP 630 MR
1 Fail Secure Lock 8273 BHW MK US32D SA
1 Concealed Closer 91N 90N Torx 689 RF
1 Kick Plate K1050 10" Torx Screws US32D RO
1 Door Stop 471 TORX (L02131) US26D RO
3 Silencer 608 (L03011) RO
1 Electric Power Transfer EL-CEPT SU
1 Frame Harness QC-C1500P (as required) MK
1 Door Harness QC-C__P (as required) MK
1 ElectroLynx Harness QC-C__P (for door sensor) MK
1 Position Switch DPS-M-BK SU
1 Power Supply EPS-05 (as needed) SU
2 Card Reader provided by access control.
Set: 3.0
Doors: B6D124
1 Continuous Hinge FM3500 630 MR
1 Storeroom Lock 8204 BHW MK (ANSI F07) US32D SA
1 Concealed Closer 91N 90N Torx 689 RF
1 Kick Plate K1050 10" Torx Screws US32D RO
1 Door Stop 471 TORX (L02131) US26D RO
3 Silencer 608 (L03011) RO
1 Finger Guards Royde & Tucker SR71 (by others)
Correct Inpatient Mental Health Deficiencies
Addendum 01
11-01-19
DOOR HARDWARE
08 71 00-18
Set: 4.0
Doors: 127, 131, 135, 137, 147, 149, 150
1 Continuous Hinge FM3500 AMS 630 MR
1 Dormitory Lock 8225 BHW MK (ANSI F13) US32D SA
1 Kick Plate K1050 10" Torx Screws US32D RO
1 Wall Stop 412 TORX (L12111) US26D RO
3 Silencer 608 (L03011) RO
1 ElectroLynx Harness QC-C__P (for door sensor) MK
Set: 5.0
Doors: 143, 146, 192, 194, 200, 204, 206, 208
1 Continuous Hinge FM3500 AMS 630 MR
1 Storeroom Lock 8227 BHW MK (ANSI F21 modified) US32D SA
1 Kick Plate K1050 10" Torx Screws US32D RO
1 Wall Stop 412 TORX (L12111) US26D RO
3 Silencer 608 (L03011) RO
1 ElectroLynx Harness QC-C__P (for door sensor) MK
- - - E N D - - -
Correct Inpatient Mental Health Deficiencies
Bid Documents
09-11
28 23 00 - 1
VIDEO SURVEILLANCE
SECTION 28 23 00
PART 1 – GENERAL
1.1 DESCRIPTION
A. Provide and install a complete Video Surveillance System, which is identified as the Video Assessment and Surveillance System hereinafter referred to as the VASS System as specified in this section.
B. This Section includes video surveillance system consisting of cameras, data transmission wiring, and a control station with its associated equipment.
C. Video surveillance system Video assessment & surveillance system shall be integrated with monitoring and control system specified in Division
28 Section PHYSICAL ACCESS CONTROL that specifies systems integration.
1.2 RELATED WORK
A. Section 01 00 00 - GENERAL REQUIREMENTS. For General Requirements.
B. Section 07 84 00 - FIRESTOPPING. Requirements for firestopping application and use.
C. Section 10 14 00 - SIGNAGE. Requirements for labeling and signs.
D. Section 26 05 11 - REQUIREMENTS FOR ELECTRICAL INSTALLATIONS.
Requirements for connection of high voltage.
E. Section 26 05 21 - LOW VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
(600 VOLTS AND BELOW). Requirements for power cables.
F. Section 28 05 00 – COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for general requirements that are common to more than one section in Division 28.
G. Section 28 05 13 - CONDUCTORS AND CABLES FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for conductors and cables.
H. Section 28 05 26 - GROUNDING AND BONDING FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for grounding of equipment.
I. Section 28 05 28.33 - CONDUITS AND BACKBOXES FOR ELECTRONIC SAFETY AND
SECURITY. Requirements for infrastructure.
J. Section 28 13 00 - PHYSICAL ACCESS CONTROL SYSTEM. Requirements for physical access control system integration.
Addendum 01
Correct Inpatient Mental Health Deficiencies
28 23 00 - 2
1.3 DEFINITIONS
A. AGC: Automatic gain control.
B. B/W: Black and white.
C. CCD: Charge-coupled device.
D. CIF: Common Intermediate Format CIF images are 352 pixels wide and
88/240 (PAL/NTSC) pixels tall (352 x 288/240).
E. 4CIF: resolution is 704 pixels wide and 576/480 (PAL/NTSC) pixels tall
(704 x 576/480).
F. H.264 (also known as MPEG4 Part 10): a encoding format that compresses video much more effectively than older (MPEG4) standards.
G. ips: Images per second.
H. MPEG: Moving picture experts group.
I. MPEG4: a video encoding and compression standard that uses inter-frame encoding to significantly reduce the size of the video stream being transmitted.
J. NTSC: National Television System Committee.
K. UPS: Uninterruptible power supply.
L. PTZ: refers to a movable camera that has the ability to pan left and right, tilt up and down, and zoom or magnify a scene.
1.4 QUALITY ASSURANCE
A. The Contractor shall be responsible for providing, installing, and the operation of the VASS System as shown. The Contractor shall also provide certification as required.
B. The security system shall be installed and tested to ensure all components are fully compatible as a system and can be integrated with all associated security subsystems, whether the security system is stand-alone or a part of a complete Information Technology (IT) computer network.
C. The Contractor or security sub-contractor shall be a licensed security
Contractor as required within the state or jurisdiction of where the installation work is being conducted.
D. Manufacturers Qualifications: The manufacturer shall regularly and presently produce, as one of the manufacturer's principal products, the equipment and material specified for this project, and shall have manufactured the item for at least three years.
Correct Inpatient Mental Health Deficiencies
28 23 00 - 3
E. Product Qualification:
1. Manufacturer's product shall have been in satisfactory operation, on three installations of similar size and type as this project, for approximately three years.
2. The Government reserves the right to require the Contractor to submit a list of installations where the products have been in operation before approval.
F. Contractor Qualification:
1. The Contractor or security sub-contractor shall be a licensed security Contractor with a minimum of five (5) years experience installing and servicing systems of similar scope and complexity.
The Contractor shall be an authorized regional representative of the
Video Assessment and Surveillance System’s (VASS) manufacturer. The
Contractor shall provide four (4) current references from clients with systems of similar scope and complexity which became operational in the past three (3) years. At least three (3) of the references shall be utilizing the same system components, in a similar configuration as the proposed system. The references must include a current point of contact, company or agency name, address, telephone number, complete system description, date of completion, and approximate cost of the project. The owner reserves the option to visit the reference sites, with the site owner’s permission and representative, to verify the quality of installation and the references’ level of satisfaction with the system. The Contractor shall provide copies of system manufacturer certification for all technicians. The Contractor shall only utilize factory-trained technicians to install, program, and service the VASS. The
Contractor shall only utilize factory-trained technicians to install, terminate and service cameras, control, and recording equipment. The technicians shall have a minimum of five (5) continuous years of technical experience in electronic security systems. The Contractor shall have a local service facility. The facility shall be located within 60 miles of the project site. The local facility shall include sufficient spare parts inventory to support the service requirements associated with this contract. The
Correct Inpatient Mental Health Deficiencies
28 23 00 - 4 facility shall also include appropriate diagnostic equipment to perform diagnostic procedures. The COTR reserves the option of surveying the company’s facility to verify the service inventory and presence of a local service organization.
2. The Contractor shall provide proof project superintendent with BICSI
Certified Commercial Installer Level 1, Level 2, or Technician to provide oversight of the project.
3. Cable installer must have on staff a Registered Communication
Distribution Designer (RCDD) certified by Building Industry
Consulting Service International. The staff member shall provide consistent oversight of the project cabling throughout design, layout, installation, termination and testing.
G. Service Qualifications: There shall be a permanent service organization maintained or trained by the manufacturer which will render satisfactory service to this installation within four hours of receipt of notification that service is needed. Submit name and address of service organizations.
1.5 SUBMITTALS
A. Submit below items in conjunction with Master Specification Sections 01
33 23, Shop Drawings, Product Data, and Samples, and Section 02 41 00, Demolition Drawings.
B. Provide certificates of compliance with Section 1.4, Quality Assurance.
C. Provide a pre-installation and as-built design package in both electronic format and on paper, minimum size 1220 x 1220 millimeters
(48 x 48 inches); drawing submittals shall be per the established project schedule.
D. Pre-installation design and as-built packages shall include, but not be limited to:
1. Index Sheet that shall:
a. Define each page of the design package to include facility name, building name, floor, and sheet number.
b. Provide a list of all security abbreviations and symbols.
c. Reference all general notes that are utilized within the design package.
Correct Inpatient Mental Health Deficiencies
28 23 00 - 5
d. Specification and scope of work pages for all security systems that are applicable to the design package that will:
1) Outline all general and job specific work required within the design package.
2) Provide a device identification table outlining device
Identification (ID) and use for all security systems equipment utilized in the design package.
2. Floor plans, site plans, and enlarged plans shall:
a. Include a title block as defined above.
b. Define the drawings scale in both standard and metric measurements.
c. Provide device identification and location.
d. Address all signal and power conduit runs and sizes that are associated with the design of the electronic security system and other security elements (e.g., barriers, etc.).
e. Identify all pull box and conduit locations, sizes, and fill capacities.
f. Address all general and drawing specific notes for a particular drawing sheet.
3. A riser drawing for each applicable security subsystem shall:
a. Indicate the sequence of operation.
b. Relationship of integrated components on one diagram.
c. Include the number, size, identification, and maximum lengths of interconnecting wires.
d. Wire/cable types shall be defined by a wire and cable schedule.
The schedule shall utilize a lettering system that will correspond to the wire/cable it represents (example: A = 18 AWG/1
Pair Twisted, Unshielded). This schedule shall also provide the manufacturer’s name and part number for the wire/cable being installed.
4. A system drawing for each applicable security system shall:
a. Identify how all equipment within the system, from main panel to device, shall be laid out and connected.
b. Provide full detail of all system components wiring from point-to-point.
Correct Inpatient Mental Health Deficiencies
28 23 00 - 6
c. Identify wire types utilized for connection, interconnection with associate security subsystems.
d. Show device locations that correspond to the floor plans.
e. All general and drawing specific notes shall be included with the system drawings.
5. A schedule for all of the applicable security subsystems shall be included. All schedules shall provide the following information:
a. Device ID.
b. Device Location (e.g. site, building, floor, room number, location, and description).
c. Mounting type (e.g. flush, wall, surface, etc.).
d. Power supply or circuit breaker and power panel number.
e. In addition, for the VASS Systems, provide the camera ID, camera type (e.g. fixed or pan/tilt/zoom (P/T/Z), lens type (e.g. for fixed cameras only) and housing model number.
6. Detail and elevation drawings for all devices that define how they were installed and mounted.
E. Provide manufacturer security system product cut-sheets. Submit for approval at least 30 days prior to commencement of formal testing, a
Security System Operational Test Plan. Include procedures for operational testing of each component and security subsystem, to include performance of an integrated system test.
F. Submit manufacturer’s certification of Underwriters Laboratories, Inc.
(UL) listing as specified. Provide all maintenance and operating manuals per the VA General Requirements, Section 01 00 00, GENERAL
REQUIREMENTS.
1.6 APPLICABLE PUBLICATIONS
A. The publications listed below (including amendments, addenda, revisions, supplement, and errata) form a part of this specification to the extent referenced. The publications are referenced in the text by the basic designation only.
B. American National Standards Institute (ANSI)/Electronic Industries
Alliance (EIA):
330-09..................Electrical Performance Standards for CCTV
Cameras
Correct Inpatient Mental Health Deficiencies
28 23 00 - 7
375A-76.................Electrical Performance Standards for CCTV
Monitors
C. Institute of Electrical and Electronics Engineers (IEEE):
C62.41-02...............IEEE Recommended Practice on Surge Voltages in
Low-Voltage AC Power Circuits
802.3af-08..............Power over Ethernet Standard
D. Federal Communications Commision (FCC):
(47 CFR 15) Part 15 Limitations on the Use of Wireless
Equipment/Systems
E. National Electrical Contractors Association (NECA):
303-2005................Installing Closed Circuit Television (CCTV)
Systems
F. National Fire Protection Association (NFPA):
70-17...................Article 780-National Electrical Code
G. Federal Information Processing Standard (FIPS):
140-2-02................Security Requirements for Cryptographic Modules
H. Underwriters Laboratories, Inc. (UL):
983-06..................Standard for Surveillance Camera Units
3044-01.................Standard for Surveillance Closed Circuit
Television Equipment
1.7 COORDINATION
A. Coordinate arrangement, mounting, and support of video surveillance equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping and conduit installed at required slope.
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.
B. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
Correct Inpatient Mental Health Deficiencies
28 23 00 - 8
C. Coordinate location of access panels and doors for video surveillance items that are behind finished surfaces or otherwise concealed.
1.8 WARRANTY OF CONSTRUCTION
A. Warrant VASS System work subject to the Article “Warranty of
Construction” of FAR clause 52.246-21.
B. Demonstration and training shall be performed prior to system acceptance.
PART 2 – PRODUCTS
2.1 GENERAL
A. Surge Protection: Protect components from voltage surges originating external to equipment housing and entering through power, communication, signal, control, or sensing leads. Include surge protection for external wiring of each conductor entry connection to components.
B. Power Connections: Comply with requirements in Section 28 05 00 COMMON
WORK REQUIREMENTS FOR ELECTRONIC SAFETY AND SECURITY, Part 2, as recommended by manufacturer for type of line being protected.
C. Tamper Protection: Tamper switches on enclosures, control units, pull boxes, junction boxes, cabinets, and other system components shall initiate a tamper-alarm signal when unit is opened or partially disassembled. Control-station, control-unit alarm display shall identify tamper alarms and indicate locations.
2.2 CAMERAS
A. All Cameras will be EIA 330 and UL 1.Minimum Protection for Power
Connections 120 V and more: Auxiliary panel suppressors shall comply with requirements in Section 28 05 00 COMMON WORK REQUIREMENTS FOR
ELECTRONIC SAFETY AND SECURITY, Part 2.
B. Minimum Protection for Communication, Signal, Control, and Low-Voltage
983 compliant as well as:
1. Will be charge coupled device (CCD cameras and shall conform to
National Television System Committee (NTSC) formatting.
2. Fixed cameras shall be color and the primary choice for monitoring following the activities described below. Pan/Tilt/Zoom (P/T/Z)
Correct Inpatient Mental Health Deficiencies
28 23 00 - 9 cameras shall be color and are to be utilized to complement the fixed cameras.
3. Shall be powered over Ethernet. Network switches supporting PoE cameras shall have a back-up power source to ensure cameras are still operational in the event of loss of primary power to the VASS
System.
4. Shall be rated for continuous operation under the environmental conditions listed in Part 1, Project Conditions.
5. Will be home run to a monitoring and recording device via a controlling device such as a matrix switcher or network server and monitored on a 24-hour basis at a designated Security Management
System location.
6. Each function and activity shall be addressed within the system by a unique user defined name, with minimum of twenty (20) characters.
The use of codes or mnemonics identifying the VASS action shall not be accepted.
7. Shall come with built-in video motion detection that shall automatically monitor and process information from each camera. The camera motion detection shall detect motion within the camera's field of view and provide automatic visual, remote alarms as a result of detected motion.
8. Shall be programmed to digitally flip from color to black and white at dusk and vice versa at low light conditions.
9. Will be fitted with AI/DC lenses to ensure the image quality under different light conditions.
10. Dummy or fake cameras will not be utilized at any time.
11. Appropriate signage shall be designed, provided, and posted that notifies people…