WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_1.pdf
PDF 44 KB Posted
- Attached to
- Fire Extinguisher, Suppression and Alarm Inspection and Testing Federal contract opportunity
- Solicitation number
- 36C26025Q0750
About this file
The document is a Wet Chemical Suppression Inspection Report for the VA Domiciliary and Transitional Housing located at 3001 C St, Anchorage, AK. The inspection was conducted by Yukon Fire Protection Services on 08/14/2024 and covers a kitchen fire suppression system manufactured by Ansul (Model R-102, installed in 2005). The report details a comprehensive inspection of the fire suppression system, including system components, visual inspection, and system testing.
Key details include a CO2 101-30 Automan II cartridge from 2017, a 3-gallon cylinder with hydrostatic testing due in 2029, and an electrical shunt control type. The inspection verified multiple safety aspects, such as UL300 compliance, proper nozzle placement, manual pull station functionality, and automatic system responses. Three fusible links were replaced during the inspection, and the system was restored to service at 09:10:15. The client representative was Keith LaFlamme from Sanford Federal, and the inspector was Chris King with certification number 2000486 FE 24-0029 IV.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| VA Domiciliary - Record Set - 112315 - SG FA drawings.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_12.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_6.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_11.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT.pdf | ||
| S06 Amendment 36C26025Q0750 0001.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_7.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_5.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_9.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_8.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_3.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_2.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_10.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_4.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_8.pdf | ||
| 36C26025Q0750.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WET CHEMICAL SUPPRESSION INSPECTION REPORT
LOCATION NAME
VA DOMICILIARY AND TRANSITIONAL HOUSING
LOCATION ADDRESS
3001 C ST, ANCHORAGE, AK
DATE
08/14/2024
SYSTEM STATUS
INSPECTOR
Chris King 2000486 FE 24-0029 IV
CLIENT NAME
SANFORD FEDERAL
CLIENT ADDRESS
525 Corporate Dr, Stafford, VA, 22554
CLIENT PHONE NUMBER
Keith LaFlamme @ 907-268-8804
CLIENT EMAIL ADDRESS
Keith LaFlamme @ 907-268-8804
SYSTEM INFORMATION
SYSTEM LOCATION MANUFACTURER MODEL CONTROL HEAD YEAR MANUF.
Kitchen Ansul R-102 Mechanical 2005
DISCHARGE/ACTUATION CARTRIDGE INFORMATION
CARTRIDGE TYPE CARTRIDGE DATE CARTRIDGE WEIGHT
C02 101-30 Automan II 2017 60oz
CYLINDER INFORMATION
CAPACITY (GAL) PRESSURE (PSI) HYDRO DUE NO DAMAGE/CORROSION? PROPERLY MOUNTED/SECURE?
3 N/A 2029 YES YES
ENERGY CONTROLS
CONTROL TYPE GAS VALVE SIZE LOCATION NOTES
ELECTRICAL SHUNT Reset is next to ansul box
VISUAL INSPECTION
SELECTION
FAN WARNING SIGN ON HOOD? YES
SIGNAGE IN PLACE FOR MANUAL PULL STATION? YES
IS SYSTEM UL300 COMPLIANT? YES
DO FILTERS COMPLY WITH CLEANLINESS REQUIREMENTS OF NFPA 96 YES
DO VISIBLE DUCT AND PLENUM AREAS COMPLY WITH CLEANLINESS REQUIREMENTS OF NFPA 96? YES
PIPING AND CONDUIT PROPERLY SECURED AND UNOBSTRUCTED? YES
CHECK CONDITION AND TRAVEL OF CABLE AND CONDITION OF LINK BRACKETS, NUTS, CRIMPS AND
S-HOOKS? YES
DUCT/PLENUM PROPERLY COVERED WITH CORRECT NOZZLES? YES
APPLIANCES PROPERLY COVERED WITH CORRECT NOZZLES? YES
PROPER SEPARATION BETWEEN FRYERS AND FLAME? N/A
CHECKED NOZZLES FOR FOULING, CORRECT COVERS AND CLEANED AS REQUIRED? YES
ARE NOZZLES AIMED PROPERLY? YES
SYSTEM TESTING
Column Label
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 1 of 3
CUTTING TERMINAL FUSIBLE LINK ACTIVATES SYSTEM? YES
MANUAL PULL STATION ACTIVATES SYSTEM? YES
MICROSWITCH IN CONTROL HEAD ACTIVATES BUILDING FIRE ALARM OR OCCUPANT NOTIFICATION? YES
POWER SHUNTED TO ALL ELECTRIC APPLIANCES IN THE HOOD ENVELOPE? YES
POWER SHUNTED TO LIGHTING UNDER THE HOOD? YES
POWER SHUNTED TO MAKEUP AIR? YES
EXHAUST FAN TURNS ON AUTOMATICALLY? YES
GAS APPLIANCE PILOTS EXTINGUISHED? YES
VERIFY ACTUATION AND/OR DISCHARGE CATRIDGE PUNCTURE PIN EXTENDED? YES
RESTORING SYSTEM TO SERVICE
SELECTION
GAS VALVE RESET? YES
SHUNTS RESET? YES
ALL APPLIANCE PILOTS RE-LIT? YES
VERIFY FUSIBLE LINKS CENTERED IN LINK HOLDERS? YES
FILTERS RE-INSTALLED? YES
CHECK FOR PROPER TENSION ON LINK LINE? YES
CHECK FOR PROPER SLACK ON PULL STATION LINE? YES
CARTRIDGE(S) INSTALLED AND LOCKOUT PIN (IF APPLICABLE) REMOVED? YES
COVER IN PLACE? YES
TAGS & SEALS INSTALLED? YES
SYSTEM RESTORED TO SERVICE AT THIS TIME:
09:10:15
FUSIBLE LINKS REPLACED
QUANTITY TYPE TEMP RATING (F) YEAR
3 ML 360 2024
K-CLASS EXTINGUISHER
LOCATED IN KITCHEN? CORRECTLY MOUNTED? SIGNAGE IN PLACE? PROPERLY SERVICED? NOTES
YES YES YES YES
DEFICIENCIES
COMMENTS/ADDITIONAL PARTS USED
CLIENT REPRESENTATIVE
Keith LaFlamme @ 907-268-8804
REPRESENTATIVE'S SIGNATURE
INSPECTOR
Chris King 2000486 FE 24-0029 IV
INSPECTOR'S SIGNATURE
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 2 of 3
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 3 of 3