WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_3.pdf
PDF 47 KB Posted
- Attached to
- Fire Extinguisher, Suppression and Alarm Inspection and Testing Federal contract opportunity
- Solicitation number
- 36C26025Q0750
About this file
This document is a Water Based Fire Protection System Report for the VA Domiciliary and Transitional Housing located at 932 E 12th in Anchorage, Alaska, conducted by Yukon Fire Protection Services on 08/14/2024. The comprehensive inspection report details the status and condition of the facility's wet fire protection system, including sprinklers, piping, alarms, and control valves, with all key system components assessed as functioning properly. The inspection confirmed no changes to the occupancy classification or system since the last review, with a system status of 4 and a 1-1/2 inch shotgun riser that passed valve, flowswitch, and delay testing.
The report includes specific technical details such as water supply source (city water with 72 PSI pressure), waterflow test results showing static pressure before and after testing, and verification of alarm systems including alarm bell, water motor gong, and supervisory signals. Sprinkler heads were installed in 2017, with no heads currently due for sample testing or replacement. The client is Sanford Federal, located in Stafford, VA, and the inspection was performed by Timothy Riddle, a certified NICET Level II inspector, with all systems confirmed as restored to normal operation after testing.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| VA Domiciliary - Record Set - 112315 - SG FA drawings.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_12.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_6.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_11.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_8.pdf | ||
| S06 Amendment 36C26025Q0750 0001.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_7.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_5.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_9.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_1.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_8.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_2.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_10.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_4.pdf | ||
| 36C26025Q0750.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WATER BASED FIRE PROTECTION SYSTEM REPORT
LOCATION NAME
VA DOMICILIARY AND TRANSITIONAL HOUSING
LOCATION ADDRESS
932 E 12TH, ANCHORAGE AK
OCCUPANCY CLASSIFICATION - NOTE: OCCUPANCY CLASS DETERMINED BY BEST
JUDGEMENT OF INSPECTOR. THIS INSPECTION'S PURPOSE IS TO DETERMINE
FUNCTIONALITY OF THE SYSTEM(S) AS INSTALLED, NOT TO DETERMINE COMPLIANCE
WITH OCCUPANCY SPECIFIC CODE REQUIREMENTS
RESIDENTIAL (R-1, R-2, R-3, R-4)
DATE
08/14/2024
SYSTEM STATUS
STATUS 4
INSPECTOR
Timothy Riddle 15013 IIB, NICET
II:141545
CLIENT NAME
SANFORD FEDERAL
CLIENT ADDRESS
525 Corporate Dr, Stafford, VA, 22554
CLIENT PHONE #
907-268-8804
CLIENT EMAIL ADDRESS
KEITH.LAFLAMME@VA.GOV
GENERAL
CHOICE
CAN OWNER CONFIRM NO CHANGES TO THE OCCUPANCY CLASSIFICATION, MACHINERY OR OPERATIONS
SINCE LAST INSPECTION? YES
CAN OWNER CONFIRM THERE HAVE BEEN NO REPAIRS OR CHANGES MADE TO THE SYSTEM SINCE LAST
INSPECTION? YES
ARE BUILDING AREAS PROTECTED BY WET SYSTEM PROPERLY HEATED, INCLUDING BLIND ATTICS AND
PERIMETER AREAS WHERE ACCESSIBLE? YES
ARE ALL VISIBLE EXTERIOR OPENINGS PROTECTED AGAINST THE ENTRANCE OF COLD AIR? YES
SPRINKLERS AND PIPING
CHOICE
DO SPRINKLERS GENERALLY APPEAR TO BE IN GOOD EXTERNAL CONDITION? YES
DO SPRINKLERS GENERALLY APPEAR TO BE FREE OF CORROSION, PAINT, LOADING AND VISIBLE
OBSTRUCTION? YES
IS THERE PROPER CLEARANCE BETWEEN STORAGE AND SPRINKLER DEFLECTOR? YES
IS A SUFFICIENT STOCK OF SPARE SPRINKLER HEADS/NOZZLES AVAILABLE ON THE PREMISES? YES
IS THERE A WRENCH ON SITE FOR CHANGING SPRINKLER HEADS/NOZZLES? YES
DOES THE EXTERIOR CONDITION OF PIPING, TUBING, DRAIN VALVES, CHECK VALVES, HANGERS, PRESSURE GAUGES, OPEN SPRINKLER AND STRAINERS APPEAR TO BE SATISFACTORY? YES
ARE ALL STRAINERS AND FILTERS IN PLACE AND FREE OF OBSTRUCTION? YES
IS SYSTEM PRESSURIZED WITH A FIRE PUMP? (IF YES, COMPLETED FIRE PUMP TEST REPORT) N/A
TANKS, PUMPS, FIRE DEPARTMENT CONNECTIONS
CHOICE
HAS/HAVE FIRE PUMP(S) BEEN TESTED TO FULL CAPACITY WITHIN THE PAST YEAR? N/A
ARE GRAVITY, SURFACE OR PRESSURE TANKS PROTECTED FROM FREEZING? N/A
DO FIRE PUMPS, GRAVITY, SURFACE OR PRESSURE TANKS APPEAR TO BE IN GOOD EXTERNAL
CONDITION? N/A
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 1 of 3
ARE GRAVITY, SURFACE AND PRESSURE TANKS AT PROPER PRESSURE AND/OR WATER LEVELS? N/A ARE FIRE DEPARTMENT CONNECTIONS IN SATISFACTORY CONDITION, COUPLINGS FREE, CAPS OR PLUGS
IN PLACE AND CHECK VALVES TIGHT? N/A
ARE FIRE DEPARTMENT CONNECTIONS VISIBLE AND ACCESSIBLE? N/A
CONTROL VALVES
SERVICES QTY TYPE ACCESSIBLE? POSITION SECURED? NOTES
CITY SUPPLY 1 BALL YES OPEN YES-LOCKED
WATER SUPPLY
SOURCE PRESSURE TANK CAPACITY LAST INTERNAL TANK INSPECTION (IF APPLICABLE)
CITY 72
WATERFLOW TEST RESULTS
TEST PIPE LOCATION TEST PIPE SIZE (IN) STATIC BEFORE (PSI) FLOW (PSI) STATIC AFTER (PSI)
RISER 1-1/4 72 10 62
SYSTEM INFORMATION
THE FOLLOWING SYSTEM(S) EXIST AT THIS LOCATION
WET
ANTIFREEZE
STANDPIPE
DRY
PRE-ACTION
DELUGE
WATERMIST
WET
SIZE (IN) MAKE AND MODEL VALVE, FLOWSWITCH AND DELAY TEST NOTES
1-1/2 SHOTGUN RISER PASS
ALARMS
DID ALARM BELL OR WATER MOTOR GONG OPERATE DURING TESTING?
YES-ALARM BELL
YES-WATER MOTOR GONG
YES-HORN/STROBE
NO-FAIL
WERE SUPERVISORY SIGNALS SENT DURING TESTING?
YES
SPRINKLER HEAD TEST LOG (SAMPLE TEST OR REPLACE STANDARD = 50 YRS, QUICK RESPONSE = 20 YRS, DRY = 15 YRS FROM
INSTALL THEN 10 YRS THEREAFTER)
STANDARD
RESPONSE HEADS
PRESENT?
INSTALL
DATE/DATE LAST
TESTED
QUICK RESPONSE
HEADS PRESENT?
INSTALL
DATE/DATE LAST
TESTED
DRY HEADS
PRESENT?
INSTALL
DATE/DATE LAST
TESTED
NO YES 2017 NO
ARE THERE SPRINKLER HEADS DUE FOR SAMPLE TESTING OR REPLACEMENT?
NO
PERIODIC MAINTENANCE LOG
LAST INTERNAL
INSPECTION
LAST FDC
HYDRO
LAST DRY
FULL TRIP
LAST PITCH
CHECK
LAST STANDPIPE
HYDRO
GAUGES REPLACED OR
CALIBRATED
PLASTIC 2021
WERE ALL SPRINKLER SYSTEMS RESTORED TO NORMAL OPERATION AFTER TESTING?
YES
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 2 of 3
CLIENT REPRESENTATIVE
X
REPRESENTATIVE SIGNATURE
INSPECTOR
Timothy Riddle 15013 IIB, NICET II:141545
INSPECTOR SIGNATURE
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 3 of 3
File details come from the government source that posted it. Updated .