FIRE_ALARM_ANNUAL_INSPECTION_REPORT_11.pdf
PDF 58 KB Posted
- Attached to
- Fire Extinguisher, Suppression and Alarm Inspection and Testing Federal contract opportunity
- Solicitation number
- 36C26025Q0750
About this file
This document is a Fire Alarm System Inspection Report for the VA Domiciliary and Transitional Housing located at 944 E 12th Ave in Anchorage, Alaska, conducted on 08/14/2024 by Yukon Fire Protection Services. The inspection covered a residential occupancy system with an ESL 1503 fire alarm panel using AES Radio communication, monitored by Guardian Security. The system testing involved notifications to the monitoring organization, building management, building occupants, and the Authority Having Jurisdiction (AHJ).
The inspection report details the system's components, including 1 bell, 1 horn, 9 horn/strobe notification appliances, and initiating devices such as 1 pull station, 9 smoke detectors, 1 heat detector, and 1 flow/pressure switch. The primary power supply is a 120V dedicated circuit in the boiler room, with a standby battery installed in 01/24. All system monitoring functions were confirmed as received, including alarm signals, trouble signals, and supervisory signals. The system was restored to normal operation at 1:00 PM, with no deficiencies noted in the report.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| VA Domiciliary - Record Set - 112315 - SG FA drawings.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_12.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_6.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_8.pdf | ||
| S06 Amendment 36C26025Q0750 0001.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_7.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_5.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_9.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_1.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_8.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_3.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_2.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_10.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_4.pdf | ||
| 36C26025Q0750.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM SYSTEM INSPECTION REPORT
LOCATION NAME
VA DOMICILIARY AND TRANSITIONAL HOUSING
LOCATION ADDRESS
944 E 12th Ave, ANCHORAGE, AK
OCCUPANCY CLASSIFICATION - NOTE: OCCUPANCY CLASS DETERMINED BY BEST
JUDGEMENT OF INSPECTOR. THIS INSPECTION'S PURPOSE IS TO DETERMINE
FUNCTIONALITY OF THE SYSTEM(S) AS INSTALLED, NOT TO DETERMINE COMPLIANCE
WITH OCCUPANCY SPECIFIC CODE REQUIREMENTS
RESIDENTIAL (R-1, R-2, R-3, R-4)
DATE
08/14/2024
SYSTEM STATUS
STATUS 4
INSPECTOR
Bert Davis 22-0001 IB
CLIENT NAME
SANFORD FEDERAL
CLIENT REPRESENTATIVE NAME
Keith
CLIENT PHONE #
907-268-8804
CLIENT EMAIL ADDRESS
keith.laflamme@va.gov
SYSTEM DETAILS
PRIMARY PANEL INFORMATION
MANUFACTURER MODEL FIRMWARE REV. COMMUNICATION PATH COMMUNICATOR MAKE/MODEL
ESL 1503 RADIO AES Radio
MONITORING INFORMATION
CENTRAL STATION CALL OUT NUMBER(S) ACCOUNT # PASSWORD
Guardian Security 610-707
CIRCUITS IN USE
AUXILIARY INITIATING NOTIFICATION SIGNALING LINE
IN USE 2 3 1
TOTAL 2 3 2
SYSTEM TESTING
NOTIFICATIONS MADE PRIOR TO TESTING AND WHEN COMPLETE
CONTACT NOTIFIED
MONITORING ORGANIZATION Guardian Security PRIOR
COMPLETE
BUILDING MANAGEMENT Keith PRIOR
COMPLETE
BUILDING OCCUPANTS Verbal PRIOR
COMPLETE
AHJ AFD PRIOR
COMPLETE
OTHER, IF REQUIRED
CONTROL PANEL FUNCTION
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 1 of 3
TYPE DESCRIPTION LAMPS FUSES BUTTONS SUPERVISION NOTES
MAIN FACP Boiler Room PASS PASS PASS PASS
PRIMARY POWER SUPPLY
BREAKER LOCATION A/C VOLTAGE DEDICATED CIRCUIT?
Boiler Room 120 YES
STANDBY POWER SUPPLY
BATTERY
(AH)
CHARGING
(V)
STANDBY
(V)
LOAD
(V) OR REMAINING AH
(L)
REMAINING AH
(R)
INSTALL DATE
(MMYY)
7 27 27 OR 01/24
NOTIFICATION APPLIANCES
TYPE TOTAL TESTED FAILED NOTES
BELL 1 1
HORN 1 1
HORN/STROBE 9 9
INITIATING DEVICES
TYPE TOTAL TESTED FAILED NOTES
PULL STATION 1 1
SMOKE DETECTOR 9 9
HEAT DETECTOR 1 1
FLOW/PRESSURE SWITCH 1 1
YEAR LAST SMOKE DETECTOR SENSITIVITY TEST PERFORMED (IF APPLICABLE)
UNKNOWN
SUPERVISING STATION MONITORING
RECEIVED COMMENTS
ALARM SIGNAL YES
ALARM RESTORATION YES
TROUBLE SIGNAL YES
TROUBLE RESTORATION YES
SUPERVISORY SIGNAL YES
SUPERVISORY RESTORATION YES
TIME SYSTEM RESTORED TO NORMAL OPERATION
1:00PM
DEFICIENCIES
COMMENTS
CLIENT SIGNATURE INSPECTOR SIGNATURE
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 2 of 3
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 3 of 3