FIRE_ALARM_ANNUAL_INSPECTION_REPORT_9.pdf
PDF 63 KB Posted
- Attached to
- Fire Extinguisher, Suppression and Alarm Inspection and Testing Federal contract opportunity
- Solicitation number
- 36C26025Q0750
About this file
This document is a Fire Alarm System Inspection Report for the VA Domiciliary and Transitional Housing located at 3001 C ST in Anchorage, AK, conducted by Yukon Fire Protection Services on 08/14/2024. The inspection covered a comprehensive review of the fire alarm system, including primary panel information (FireLite MS9200UDLS), monitoring details (Guardian Security), and a thorough assessment of system components. The report details testing of 1 bell, 56 horn/strobe, and 28 strobe notification appliances, along with 5 pull stations, 55 smoke detectors, 3 heat detectors, and various other initiating devices.
The inspection revealed one key deficiency: a CO sensor in the boiler is not working and needs replacement. The system was restored to normal operation at 12:00 PM, with all supervising station monitoring signals (alarm, trouble, and supervisory) successfully received and restored. The fire alarm system is classified as Status 2 for a residential occupancy (R-1, R-2, R-3, R-4), and the primary power supply is a dedicated 120V circuit located in Room 1A113, Panel E #25. The client representative is Keith from Sanford Federal, with contact information provided for follow-up.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| EXTINGUISHER_INSPECTION_REPORT_8.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_3.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_2.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_10.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_4.pdf | ||
| VA Domiciliary - Record Set - 112315 - SG FA drawings.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_12.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_6.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_11.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_8.pdf | ||
| S06 Amendment 36C26025Q0750 0001.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_7.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_5.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_1.pdf | ||
| 36C26025Q0750.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM SYSTEM INSPECTION REPORT
LOCATION NAME
VA DOMICILIARY AND TRANSITIONAL HOUSING
LOCATION ADDRESS
3001 C ST, ANCHORAGE, AK
OCCUPANCY CLASSIFICATION - NOTE: OCCUPANCY CLASS DETERMINED BY BEST
JUDGEMENT OF INSPECTOR. THIS INSPECTION'S PURPOSE IS TO DETERMINE
FUNCTIONALITY OF THE SYSTEM(S) AS INSTALLED, NOT TO DETERMINE COMPLIANCE
WITH OCCUPANCY SPECIFIC CODE REQUIREMENTS
RESIDENTIAL (R-1, R-2, R-3, R-4)
DATE
08/14/2024
SYSTEM STATUS
STATUS 2
INSPECTOR
Bert Davis 22-0001 IB
CLIENT NAME
SANFORD FEDERAL
CLIENT REPRESENTATIVE NAME
Keith
CLIENT PHONE #
907-268-8804
CLIENT EMAIL ADDRESS
keith.laflamme@va.gov
SYSTEM DETAILS
PRIMARY PANEL INFORMATION
MANUFACTURER MODEL FIRMWARE REV. COMMUNICATION PATH COMMUNICATOR MAKE/MODEL
FireLite MS9200UDLS DACT On Board
MONITORING INFORMATION
CENTRAL STATION CALL OUT NUMBER(S) ACCOUNT # PASSWORD
Guardian Security 790-057
CIRCUITS IN USE
AUXILIARY INITIATING NOTIFICATION SIGNALING LINE
IN USE 18 9 1
TOTAL 18 9 2
SYSTEM TESTING
NOTIFICATIONS MADE PRIOR TO TESTING AND WHEN COMPLETE
CONTACT NOTIFIED
MONITORING ORGANIZATION Guardian Security PRIOR
COMPLETE
BUILDING MANAGEMENT Keith PRIOR
COMPLETE
BUILDING OCCUPANTS Verbal PRIOR
COMPLETE
AHJ AFD PRIOR
COMPLETE
OTHER, IF REQUIRED
CONTROL PANEL FUNCTION
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 1 of 3
TYPE DESCRIPTION LAMPS FUSES BUTTONS SUPERVISION NOTES
MAIN FACP Front Desk PASS PASS PASS PASS ANNUNCIATOR Police Office PASS PASS PASS
PRIMARY POWER SUPPLY
BREAKER LOCATION A/C VOLTAGE DEDICATED CIRCUIT?
Room 1A113, Panel E #25 120 YES
STANDBY POWER SUPPLY
BATTERY
(AH)
CHARGING
(V)
STANDBY
(V)
LOAD
(V) OR REMAINING AH
(L)
REMAINING AH
(R)
INSTALL DATE
(MMYY)
26 27 27 OR 01/24
AUXILIARY & BOOSTER POWER SUPPLIES
LOCATION/DESCRIPTION A/C
BREAKER
BATTERY
(AH)
CHARGING
(V)
STANDBY
(V)
LOAD
(V) OR REMAINING
AH (L)
REMAINING
AH (R)
INSTALL
DATE
(MMYY)
Police Office Room 1A113, Panel E #25
7 27 27 01/24
Room 134 Room 1A113, Panel E #25
7 27 27 01/24
Room 134 Room 1A113, Panel E #25
7 27 27 01/24
Room 134 Room 1A113, Panel E #25
7 27 27 01/24
NOTIFICATION APPLIANCES
TYPE TOTAL TESTED FAILED NOTES
BELL 1 1
HORN/STROBE 56 56
STROBE 28 28
INITIATING DEVICES
TYPE TOTAL TESTED FAILED NOTES
PULL STATION 5 5
SMOKE DETECTOR 55 55
HEAT DETECTOR 3 3
SUPPRESSION SWITCH 1 1 Kitchen Hood
DUCT DETECTOR 4 4
FLOW/PRESSURE SWITCH 1 1
SUPERVISORY SWITCH 2 2 Sprinkler Tampers OTHER 4 4 Remote Test Switch OTHER 15 15 CO Sensors
SPECIALTY INITIATING DEVICES
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 2 of 3
TYPE TOTAL TESTED FAILED MAKE/MODEL NOTES
BEAM DETECTOR 2 2
YEAR LAST SMOKE DETECTOR SENSITIVITY TEST PERFORMED (IF APPLICABLE)
Self Test
AUXILIARY EQUIPMENT
TYPE TOTAL TESTED FAILED NOTES
AHU SHUTDOWN 2 2
DOOR HOLDERS 4 4
SUPERVISING STATION MONITORING
RECEIVED COMMENTS
ALARM SIGNAL YES
ALARM RESTORATION YES
TROUBLE SIGNAL YES
TROUBLE RESTORATION YES
SUPERVISORY SIGNAL YES
SUPERVISORY RESTORATION YES
TIME SYSTEM RESTORED TO NORMAL OPERATION
12:00PM
DEFICIENCIES
CO sensor in boiler not working and needs to be replaced.
COMMENTS
CLIENT SIGNATURE INSPECTOR SIGNATURE
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 3 of 3