WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT.pdf
PDF 47 KB Posted
- Attached to
- Fire Extinguisher, Suppression and Alarm Inspection and Testing Federal contract opportunity
- Solicitation number
- 36C26025Q0750
About this file
This document is a Water Based Fire Protection System Report for the VA Domiciliary and Transitional Housing located at 3001 C St, Anchorage, AK. The comprehensive inspection, conducted by Yukon Fire Protection Services on 08/14/2024, evaluated the facility's wet fire protection system with a Status 4 rating. The report details a thorough examination of sprinklers, piping, control valves, alarms, and system components, finding no deficiencies and confirming that all critical systems are functioning properly.
Key findings include a city water supply with 70 PSI pressure, a 4-inch GEM F2001 wet system that passed valve and flowswitch tests, and sprinkler heads installed in 1995 (standard response), 2021 (quick response), and 2019 (dry heads). The client, Sanford Federal, was represented during the inspection, and all system components were verified as accessible, secured, and in good condition. The last internal inspection, FDC hydro, and other periodic maintenance were completed in 2024, with all sprinkler systems restored to normal operation after testing.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| VA Domiciliary - Record Set - 112315 - SG FA drawings.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_12.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_6.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_11.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_8.pdf | ||
| S06 Amendment 36C26025Q0750 0001.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_7.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_5.pdf | ||
| FIRE_ALARM_ANNUAL_INSPECTION_REPORT_9.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_1.pdf | ||
| EXTINGUISHER_INSPECTION_REPORT_8.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_3.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_2.pdf | ||
| WET_CHEMICAL_SUPPRESSION_INSPECTION_REPORT_10.pdf | ||
| WATER_BASED_FIRE_PROTECTION_SYSTEM_REPORT_4.pdf | ||
| 36C26025Q0750.pdf |
Show all 16
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
WATER BASED FIRE PROTECTION SYSTEM REPORT
LOCATION NAME
VA DOMICILIARY AND TRANSITIONAL HOUSING
LOCATION ADDRESS
3001 C ST, ANCHORAGE, AK
OCCUPANCY CLASSIFICATION - NOTE: OCCUPANCY CLASS DETERMINED BY BEST
JUDGEMENT OF INSPECTOR. THIS INSPECTION'S PURPOSE IS TO DETERMINE
FUNCTIONALITY OF THE SYSTEM(S) AS INSTALLED, NOT TO DETERMINE COMPLIANCE
WITH OCCUPANCY SPECIFIC CODE REQUIREMENTS
RESIDENTIAL (R-1, R-2, R-3, R-4)
DATE
08/14/2024
SYSTEM STATUS
STATUS 4
INSPECTOR
Timothy Riddle 15013 IIB, NICET
II:141545
CLIENT NAME
SANFORD FEDERAL
CLIENT ADDRESS
525 Corporate Dr, Stafford, VA, 22554
CLIENT PHONE #
907-268-8804
CLIENT EMAIL ADDRESS
KEITH.LAFLAMME@VA.GOV
GENERAL
CHOICE
CAN OWNER CONFIRM NO CHANGES TO THE OCCUPANCY CLASSIFICATION, MACHINERY OR OPERATIONS
SINCE LAST INSPECTION? YES
CAN OWNER CONFIRM THERE HAVE BEEN NO REPAIRS OR CHANGES MADE TO THE SYSTEM SINCE LAST
INSPECTION? YES
ARE BUILDING AREAS PROTECTED BY WET SYSTEM PROPERLY HEATED, INCLUDING BLIND ATTICS AND
PERIMETER AREAS WHERE ACCESSIBLE? YES
ARE ALL VISIBLE EXTERIOR OPENINGS PROTECTED AGAINST THE ENTRANCE OF COLD AIR? YES
SPRINKLERS AND PIPING
CHOICE
DO SPRINKLERS GENERALLY APPEAR TO BE IN GOOD EXTERNAL CONDITION? YES
DO SPRINKLERS GENERALLY APPEAR TO BE FREE OF CORROSION, PAINT, LOADING AND VISIBLE
OBSTRUCTION? YES
IS THERE PROPER CLEARANCE BETWEEN STORAGE AND SPRINKLER DEFLECTOR? YES
IS A SUFFICIENT STOCK OF SPARE SPRINKLER HEADS/NOZZLES AVAILABLE ON THE PREMISES? YES
IS THERE A WRENCH ON SITE FOR CHANGING SPRINKLER HEADS/NOZZLES? YES
DOES THE EXTERIOR CONDITION OF PIPING, TUBING, DRAIN VALVES, CHECK VALVES, HANGERS, PRESSURE GAUGES, OPEN SPRINKLER AND STRAINERS APPEAR TO BE SATISFACTORY? YES
ARE ALL STRAINERS AND FILTERS IN PLACE AND FREE OF OBSTRUCTION? N/A
IS SYSTEM PRESSURIZED WITH A FIRE PUMP? (IF YES, COMPLETED FIRE PUMP TEST REPORT) N/A
TANKS, PUMPS, FIRE DEPARTMENT CONNECTIONS
CHOICE
HAS/HAVE FIRE PUMP(S) BEEN TESTED TO FULL CAPACITY WITHIN THE PAST YEAR? N/A
ARE GRAVITY, SURFACE OR PRESSURE TANKS PROTECTED FROM FREEZING? N/A
DO FIRE PUMPS, GRAVITY, SURFACE OR PRESSURE TANKS APPEAR TO BE IN GOOD EXTERNAL
CONDITION? N/A
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 1 of 3
ARE GRAVITY, SURFACE AND PRESSURE TANKS AT PROPER PRESSURE AND/OR WATER LEVELS? N/A ARE FIRE DEPARTMENT CONNECTIONS IN SATISFACTORY CONDITION, COUPLINGS FREE, CAPS OR PLUGS
IN PLACE AND CHECK VALVES TIGHT? YES
ARE FIRE DEPARTMENT CONNECTIONS VISIBLE AND ACCESSIBLE? YES
CONTROL VALVES
SERVICES QTY TYPE ACCESSIBLE? POSITION SECURED? NOTES
CITY SUPPLY 2 OS&Y YES OPEN YES-SUPERVISED BACKFLOW
WATER SUPPLY
SOURCE PRESSURE TANK CAPACITY LAST INTERNAL TANK INSPECTION (IF APPLICABLE)
CITY 70
WATERFLOW TEST RESULTS
TEST PIPE LOCATION TEST PIPE SIZE (IN) STATIC BEFORE (PSI) FLOW (PSI) STATIC AFTER (PSI)
RISER 2 70 65 65
SYSTEM INFORMATION
THE FOLLOWING SYSTEM(S) EXIST AT THIS LOCATION
WET
ANTIFREEZE
STANDPIPE
DRY
PRE-ACTION
DELUGE
WATERMIST
WET
SIZE (IN) MAKE AND MODEL VALVE, FLOWSWITCH AND DELAY TEST NOTES
4 GEM F2001 PASS
ALARMS
DID ALARM BELL OR WATER MOTOR GONG OPERATE DURING TESTING?
YES-ALARM BELL
YES-WATER MOTOR GONG
YES-HORN/STROBE
NO-FAIL
WERE SUPERVISORY SIGNALS SENT DURING TESTING?
YES
SPRINKLER HEAD TEST LOG (SAMPLE TEST OR REPLACE STANDARD = 50 YRS, QUICK RESPONSE = 20 YRS, DRY = 15 YRS FROM
INSTALL THEN 10 YRS THEREAFTER)
STANDARD
RESPONSE HEADS
PRESENT?
INSTALL
DATE/DATE LAST
TESTED
QUICK RESPONSE
HEADS PRESENT?
INSTALL
DATE/DATE LAST
TESTED
DRY HEADS
PRESENT?
INSTALL
DATE/DATE LAST
TESTED
YES 1995 YES 2021 YES 2019
ARE THERE SPRINKLER HEADS DUE FOR SAMPLE TESTING OR REPLACEMENT?
NO
PERIODIC MAINTENANCE LOG
LAST INTERNAL
INSPECTION
LAST FDC
HYDRO
LAST DRY
FULL TRIP
LAST PITCH
CHECK
LAST STANDPIPE
HYDRO
GAUGES REPLACED OR
CALIBRATED
2024 2024 2024
WERE ALL SPRINKLER SYSTEMS RESTORED TO NORMAL OPERATION AFTER TESTING?
YES
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 2 of 3
DEFICIENCIES
n/a
CLIENT REPRESENTATIVE
X
REPRESENTATIVE SIGNATURE
INSPECTOR
Timothy Riddle 15013 IIB, NICET II:141545
INSPECTOR SIGNATURE
YUKON FIRE PROTECTION SERVICES, INC. 5451 LAONA DR, ANCHORAGE AK 99518 MAIN: (907) 563-3608 FAX: (907) 562-2754 Page 3 of 3