G-101.pdf
PDF 2 MB Posted
- Attached to
- Z2DZ--Upgrade Chiller Plant (VA-21-00024244)
- Solicitation number
- 36C25921R0061
About this file
This document includes a federal contract opportunity notice and related project file. The contract opportunity is for construction services to upgrade the chiller plant at the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma. The project magnitude is estimated between $5 million to $10 million. The solicitation is a 100% set-aside for service-disabled veteran-owned small businesses. Offerors must be verified as SDVOSBs by the VA's Center for Verification and Evaluation by the time of proposal submission. The construction services required include upgrading the chiller plant located in Building 52 on the medical center campus. A limited amount of work is also required in the interstitial space of Building 53.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25921R0061 0003.docx | DOCX document | |
| Pre Bid RFIs - 18-416.pdf | ||
| 013526 Safety Reqs.pdf | ||
| 18-416 Bid CombSpecs 20210223-RFI.pdf | ||
| 36C25921R0061 0002.docx | DOCX document | |
| 36C25921R0061 0001.docx | DOCX document | |
| S04 -Site Visit Meeting Doc.pdf | ||
| IMG_0257.jpg | JPG image | |
| Site Visit Station Map.pdf | ||
| 18-416 Bid CombDWG 20210223_Part2.pdf | ||
| 36C25921R0061_1.docx | DOCX document | |
| 18-416 Bid CombDWG 20210223_Part3.pdf | ||
| S02 Past Performance Questionnaire.docx | DOCX document | |
| 18-416 Bid CombDWG 20210223_Part1.pdf | ||
| Site Visit Hatbox Parking.pdf | ||
| 18-416 Bid CombSpecs 20210223.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UPGRADE CHILLER
PLANT BUILDING 52
623-16-101 UPGRADE CHILLER
PLANT BUILDING 52 623-16-101
UPGRADE CHILLER
PLANT BUILDING 52 623-16-101
UPGRADE CHILLER
PLANT BLDG 52
623-16-101
UPGRADE CHILLER PLANT BLDG 52
UPGRADE CHILLER PLANT BLDG 52
623-16-101
NA
D
BUILDING 53
BUILDING 52
THIS AREA OF BUILDING 53 IS WITHIN AN
INTERSTIAL SPACE. ACCESS TO
INTERSTITIAL SPACE IS VIA LADDER
LOCATED IN MORGUE VESTIBULE
BB111-53. FINAL ACCESS POINT SHALL
BE DETERMINED BY GC AND THE COR.
BUILDING 53BUILDING 52
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:4
:1
P
M
G-101
PRE CONSTRUCTION RISK ASSESSMENT
(PCRA)
4 6GTS/LG
UPGRADE CHILLER PLANT
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
TM
A. TRAFFIC CONTROL: DESIGNATED ENTRY AND EXIT PROCEDURES
SHALL BE DEFINED. EGRESS PATHS SHALL BE FREE OF DEBRIS; ONLY
AUTHORIZED PERSONNEL SHALL BE ALLOWED TO ENTER THE
CONSTRUCTION ZONE. SIGNAGE SHALL DIRECT PEDESTRIAN
TRAFFIC AWAY FROM THE CONSTRUCTION AREA AND MATERIALS.
B. EXTERIOR WINDOWS: EXISTING WINDOWS SHALL BE PROTECTED TO
PREVENT DAMAGE BY ADJACENT CONSTRUCTION WORK.
VENTILATION AND ENVIRONMENTAL CONTROLS
C. AIR SYSTEM FLOW: THE COR VERIFY AND ACKNOWLEDGE
CONTRACTOR WHETHER THE CONSTRUCTION AREA USES
FRESH/OUTSIDE OR RE-CIRCULATED AIR; FILTERS SHALL BE ADDED
OR RETURN VENTS COVERED AS NEEDED WITH FILTER MATERIAL OR
PLASTIC. AIR MUST FLOW FROM CLEAN TO DIRTY PLACES.
D. NEGATIVE AIR PRESSURE: THE AIR WITHIN THE CONSTRUCTION AREA
SHALL BE NEGATIVE WITH RESPECT TO SURROUNDING AREAS AND
WITH NO DISRUPTION OF AIR SYSTEMS OF ADJACENT AREAS.
CONTAMINATION OF PATIENT ROOMS, SUPPLIES, EQUIPMENT AND
RELATED AREAS
E. WORKSITE CLOTHING FOR WORK WITHIN HOSPITAL: CONTRACTOR
PERSONNEL CLOTHING SHALL BE FREE OF LOOSE SOIL AND DEBRIS
BEFORE LEAVING THE CONSTRUCTION AREA. IF PROTECTIVE
APPAREL IS NOT WORN (E.G., COVERALLS, FOOTGEAR AND
HEADGEAR) A HEPA-FILTERED VACUUM SHALL BE USED TO REMOVE
DUST FROM CLOTHING BEFORE LEAVING THE BARRICADE.
F. POST CONSTRUCTION: DO NOT REMOVE BARRIERS AND KEEP ALL
HVAC ISOLATION UNTIL CONTRACTOR HAS CLEANED CONSTRUCTION
SITE, VA EMS STAFF HAS DONE A TERMINAL CLEANING, AND VA
INFECTIOUS DISEASE CONTROL HAS INSPECTED AND APPROVED THE
CLEANING.
GENERAL
G. PROVIDE TWO STICKY MATS AT EACH CONSTRUCTION ACCESS POINT
IN ALL PHASES.
H. VA REQUIRES THAT ALL APPLICABLE PERMITS BE COMPLETED AND
APPROVED PRIOR TO BEGINNING ANY WORK ON STATION.
INTERSTITIAL ICRA NOTES
I. PROVIDE ICRA PLASTIC BARRIER, FROM BENEATH THE WORK TO BE
DONE TO THE UNDERSIDE OF THE STRUCTURAL FLOOR OR
STRUCTURAL MEMBERS ABOVE, AROUND THE AREA OF THE PIPING
WORK TO BE DONE. THE PLASTIC BARRIER SHALL WRAP AROUND ALL
HVAC & ELECTRICAL DUCTS, EQUIPMENT, STEEL STRUCTURE, PIPING,
ETC. TO PROVIDE A COMPLETE DUST FREE BARRIER TO THE
SURROUNDING INTERSTITIAL FLOOR AREA.
J. DURING ANY HOT WORK ACTIVITIES, THE CONTRACTOR SHALL USE
FIRE BLANKETS TO COVER UP ANY COMBUSTIBLE MATERIALS LIKE
INSULATION, DUCT WORK, ETC. TO INSURE THAT OPEN FLAMES DO
NOT SPREAD TO SURROUNDING SURFACES.
K. THE GC SHALL PROVIDE A FIRE WATCH (DEDICATED OBSERVER)
DURING ALL INTERSTITIAL AREA WELDING OPERATIONS.
SHEET NOTES:
1 ADDENDUM 1 10/04/2021
Scale: 1/8" = 1'-0"
CONNECTION FOR NEW FIRE PROTECTION PIPING WITHIN BUILDING 53
THIS PROJECT INVOLVES WORK IN MECHANICAL
CHILLER PLANT ROOM AND ROOF OF
MECHANICAL CHILLER PLANT (BUILDING 52).
LIMITED WORK IS REQUIRED IN INTERSTITIAL
SPACE OF BUILDING 53. SEE DETAIL 1/G-101. NOT
ALL ICRA MEASURES ARE APPLICABLE.