18-416 Bid CombDWG 20210223_Part3.pdf
PDF 6 MB Posted
- Attached to
- Z2DZ--Upgrade Chiller Plant (VA-21-00024244)
- Solicitation number
- 36C25921R0061
About this file
This is a presolicitation notice for an upgrade chiller plant project at the Jack C. Montgomery VA Medical Center in Muskogee, Oklahoma. The project magnitude is estimated between $5-10 million and is set aside 100% for service-disabled veteran-owned small businesses. A request for quote will be posted on April 15, 2021. The NAICS code is 238220 and small business size standard is $39.5 million. The point of contact is Robyn Young who can be reached at 307-433-3728 or robyn.young2@va.gov. Apparent successful offerors must be verified and listed in the Vendor Information Pages database as a service-disabled veteran-owned small business to be considered for award. The contractor will provide construction services to complete the upgrade chiller plant project.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25921R0061 0003.docx | DOCX document | |
| G-101.pdf | ||
| Pre Bid RFIs - 18-416.pdf | ||
| 013526 Safety Reqs.pdf | ||
| 18-416 Bid CombSpecs 20210223-RFI.pdf | ||
| 36C25921R0061 0002.docx | DOCX document | |
| 36C25921R0061 0001.docx | DOCX document | |
| S04 -Site Visit Meeting Doc.pdf | ||
| IMG_0257.jpg | JPG image | |
| Site Visit Station Map.pdf | ||
| 18-416 Bid CombDWG 20210223_Part2.pdf | ||
| 36C25921R0061_1.docx | DOCX document | |
| S02 Past Performance Questionnaire.docx | DOCX document | |
| 18-416 Bid CombDWG 20210223_Part1.pdf | ||
| Site Visit Hatbox Parking.pdf | ||
| 18-416 Bid CombSpecs 20210223.pdf |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
52-CH-3
EX 52-CH-2
EX 52-CH-1
52-P-12
EX 52-P-2
EX 52-P-5
52-P-6
10"
CHS10"
CHR
12"
CHR
16" CHS
16" CHS
16" CHS
C H S
C H S
C H S
C H R
C H R
C H R
C H R
C H S
C H S
12" CHR
12" CHR
16" CHR
16" CHS
16" CHS
16" CHS
16" CHR
16" CHS16" CHR
16" CHS16" CHR
C H R
12" CHS
12" CHS
12" CHS 12" CHR
12"
CHS
52-P-4
52-P-1
C H R
C H R
C H R
C H S
C H S
52-CH-3
52-P-12
52-P-6
16" CHS
16" CHS
16" CHS
16" CHR
16" CHS
16" CHS
12" CHR
16" CHR
16" CHS
16" CHS
16" CHR
12" CHR
16" CHR
16" CHR
16" CHS
C H S
C H R
C H R
C H R
C H R
C H S
C H S
C H S
12" CHS
12" CHS
12" CHS
12" CHR
12"
CHS
12"
CHR
10"
CHS10"
CHR
52-P-4
52-P-1
C H S
C H R
EX 52-CH-2
52-CH-1
EX 52-P-5
EX 52-P-2
52-CH-3
12"
CHR
10"
CHS
10"
CHR
16" CHS
16" CHS
16" CHR
16" CHS
16" CHS16" CHS
16" CHR
12" CHR 16" CHS
16" CHR
12" CHR
16" CHR
16" CHS
16" CHR
16" CHS
C H R
C H S
C H R
C H R12
C H S
C H S
C H S
12" CHS
12" CHS
12" CHS
12" CHR
52-P-12
52-P-6
C H S
12"
CHS
52-P-4
52-P-1
C H R
C H S
C H R
C H R
C H S
C H R
EX 52-P-2
EX 52-P-5
52-CH-1
EX 52-CH-2
52-CH-3
52-CH-2
52-CH-1
52-FPHX-1
52-P-12
52-P-2
52-P-3
52-P-1
52-P-4
52-P-5
52-P-6
12" CHS
12" CHS
12" CHS
12" CHR
16" CHS
16" CHS
16" CHS
C H S
C H S
C H S
C H R
C H R
C H R
C H R
C H R
C H R
C H S
16" CHR
16" CHS
16" CHS16" CHR
16" CHS
16" CHR
12" CHR
12" CHR
16" CHR
16" CHS
16" CHS
16" CHR
12"
CHR
10"
CHS10"
CHR
12"
CHS
12" CHR
12" CHR
12" CHS
12" CHS 10" CHR
C H R
C H R
C H R
C H R
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
W ALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:5
:4
P
M
M-905
CHILLED W ATER PIPING ISOMETRIC VIEW S -
PHASE 3 AND PHASE 4
46 48AKS, WRS
UPGRADE CHILLER PLANT
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
RBK
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale:
CHILLED WATER PIPING DEMOLITION - PHASE 3
Scale:
CHILLED WATER PIPING NEW WORK - PHASE 3
Scale:
CHILLED WATER PIPING DEMOLITION - PHASE 4
Scale:
CHILLED WATER PIPING NEW WORK - PHASE 4
DocuSign Envelope ID: B32A6B38-868E-4D60-B593-FDD61A5FDCEC
2/23/2021
EX 52-P-8
EX 52-P-7
EX 52-CH-1
EX 52-CH-2
EX 52-FPHX-1
EX 52-CH-3
EX 52CT-1A
EX 52CT-1B
EX 52CT-2A
EX 52CT-2B
EX 52CT-3
20" CWR
20" CWR
20" CWR
20" CWR
C W R
20" CWS
C W R
C W R
20" CWS
20" C
WS
C W S
C W S
C W S
C W S
C W R
C W S
CW
R
C W R
C W S
C W R
C W S
C W R
12" CWR
C W S
EX 52P-13
8" CWR
8" CWR
8" CWR
8" CWR
8" CWR
8" CWR
8" CWR
8" CWR
8" CWR
8" CWR
10" CWR
10" CWR
10" CWR
10" CWR
10" CWR
14" CWR
52-CT-1
52-CT-2
EX 52CT-3
8" CWR
8" CWR
10" CW R
8" CWR
10" CW R
8" CWR
8" CWR
10" CW R
8" CWR
8" CWR
10" CW R
52-WT-4
52-WT-3
52-WT-2
52-WT-1
8" CWR
10" CWR
8" CWR
20" CWR
20" CWS
C W S
C W S
12" CWR
14" CWR
C W S
C W S20" C
WS
20" CWR
20" CWS
C W S
C W R
20" CWR
C W S
C W R
20" CWS
20" CWS
20" CWR
CW
R
C W S
EX 52P-13
20" CWR
14" CW R
14" CWS
52-P-7
52-P-8
C
W
S 10" CWS
10" CWS
EX 52-CH-1
EX 52-CH-2
EX 52-CH-3
10" CWS
20" CWR
52-CT-1
8" CWR
10" CWR
8" CWR
8" CWR
10" CWR
8" CWR
52-CT-2
8" CWR
10" CWR
8" CWR
8" CWR
10" CWR
52-WT-4
52-WT-3
52-WT-2
52-WT-1
EX 52CT-3
8" CWR
10" CWR
8" CWR
20" CWR
20" CWS
20" CWR
20" CWR
20" CWS
20" CWR
20" CWR
20" CWS
20" C
WS
14" CWR
C W S
C W S
C W S
C W S
C W R
C W S
C W S
C W S
C W R
C W R10
C W S
52-P-8
52-P-7
C W S
EX 52-CH-1
EX 52-CH-2
EX 52-CH-3
EX 52P-13
C W S
14" CWR
14" CWS
12" CWR
20" CWR
52-CT-1
8" CWR
10" CWR
8" CWR
8" CWR
10" CWR
8" CWR
52-CT-2
8" CWR
10" CWR
8" CWR
8" CWR
10" CWR
8" CWR
52-CT-3
20" CWR
20" CWR
20" CWR
20" CWR
20" CWS
20" CWS
20" CWS
20" C
WS
C W S
14" CWR
C W S
C W S
C W S
12" CWR
C W S
C W R
C W S
C W R
52-P-7
52-P-8
52-P-13
C W S
C W S
C W S
EX 52-CH-1
EX 52-CH-2
52-CH-3
14" CWR
14" CWS
20" CWR
14" EQL
14" EQL
14" EQL
52-WT-5
52-WT-6
C
W S
C
W S
10" CWS
C
W R
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
W ALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:5
:4
P
M
M-906
CONDENSER W ATER PIPING ISOMETRIC
VIEW S - PHASE 1 AND PHASE 2
47 48AKS, WRS
UPGRADE CHILLER PLANT
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
RBK
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale:
CONDENSER WATER PIPING DEMOLITION - PHASE 1
Scale:
CONDENSER WATER PIPING NEW WORK - PHASE 1
Scale:
CONDENSER WATER PIPING DEMOLITION - PHASE 2
Scale:
CONDENSER WATER PIPING NEW WORK - PHASE 2
52-CT-1
8" CWR
10" CWR
52-WT-1
8" CWR
10" CWR
52-WT-2
8" CWR
8" CWR
52-CT-2
8" CWR
10" CWR
52-WT-3
8" CWR
8" CWR
10" CWR
8" CWR
52-WT-452-CT-3
52-P-7
52-P-8
52-P-13
EX 52-CH-1
EX 52-CH-2
52-CH-3
C W S
C W S
C W S
12" CWR
14" CWR
20" CWR
20" CWR
20" CWR
20" CWR
20" CWS
20" CWS
20" C
WS
C W S
C W S
C W S
C W S12
C W R
C W S
C W R
14" CWR
14" CWS
20" CWR
14" EQL
14" EQL
14" EQL
C W R
10" C
WS
C W R
14" EQL
14" EQL
8" CWR
8" CWR
8" CWR
8" CWR
10" CWR
10" CWR
52-CT-1
8" CWR
10" CWR
8" CWR
52-WT-1
8" CWR
10" CWR
52-WT-2
8" CWR
52-CT-2
8" CWR
10" CWR
52-WT-3
8" CWR
52-CT-2
8" CWR
10" CWR
52-WT-4
8" CWR
52-CT-3
52-P-7
52-P-8
52-P-13
52-CH-3
10" CWS
20" CWR
20" CWS
20" CWR
20" CWS
20" CWR
20" CWS
20" CWR
20" C
WS
C W S
C W S
C W S
C W S
C W S
C W S
C W S
14" CWR
12" CWR
C W
S14" CWR
14" CWS
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
10" CWR
8" CWR
8" CWR
C W S
10" C
WS
C W R
8" CWR
10" CWR
8" CWR
EX 52-CH-2
52-CH-1
52-CT-1
8" CWR
10" CWR
8" CWR
52-WT-1
8" CWR
10" CWR
52-WT-2
52-CT-2
8" CWR
10" CWR
52-WT-3
8" CWR
8" CWR
10" CWR
52-WT-4
52-CT-3
52-P-7
52-P-8
52-P-13
52-CH-3
20" CWS
20" CWR
20" CWR
20" CWS
20" CWR
20" CWS
20" CWR
20" C
WS
C W S
14" CWR
C W S
C W S
C W S
12" CWR
C W S
C W R
C W S
C W S
C W S
10" CWS
14" CWR
14" CWS
20" CWR
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
10" C
WS
C W R
8" CWR
8" CWR
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
8" CWR
10" CWR
8" CWR
10" CWR
8" CWR
EX 52-CH-2
52-CH-1
52-CT-1
8" CWR
10" CWR
52-WT-1
8" CWR
8" CWR
10" CWR
52-WT-2
8" CWR
52-CT-2
8" CWR
10" CWR8" CWR
10" CWR
8" CWR
52-WT-4
C W S
12" CWR
C W S
C W S
C W S
20" C
WS
14" CWR
20" CWR
20" CWS
20" CWR
C W R
10" CWS
C W S
CW
R
20" CWS
20" CWR
20" CWR
20" CWS
10" CWS
10" CWS
14" CWR
14" CWS
52-CH-3
52-CH-2
52-CH-1
52-FPHX-1
52-P-13
52-P-8
52-P-7
C W S
C W S
C W S
C W S
C W R
C W R
10" CWR
52-CT-3
20" CWR
C W R
C W S
C W S
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL
14" EQL 14" EQL
8" CWR
8" CWR
8" CWR
10" CWR
8" CWR
10" CWR
8" CWR
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
W ALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:5
:5
P
M
M-907
CONDENSER W ATER PIPING ISOMETRIC
VIEW S - PHASE 3 AND PHASE 4
48 48AKS, WRS
UPGRADE CHILLER PLANT
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
RBK
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
Scale:
CONDENSER WATER PIPING DEMOLITION - PHASE 3
Scale:
CONDENSER WATER PIPING NEW WORK - PHASE 3
Scale:
CONDENSER WATER PIPING DEMOLITION - PHASE 4
Scale:
CONDENSER WATER PIPING NEW WORK - PHASE 4
L L
SR SURFACE RACEWAY
SS STAINLESS STEEL
SSW SELECTOR SWITCH
STD STANDARD
SURF SURFACE MOUNTED
SW SWITCH
SWBD SWITCHBOARD
SYM SYMMETRICAL
SYS SYSTEM
TC TIMECLOCK
TEL TELEPHONE
TEL/DATA TELEPHONE/DATA
TERM TERMINAL
TP TWISTED PAIR
TPS TWISTED PAIR SHIELDED
TR TAMPER RESISTANT
T-STAT THERMOSTAT
TTB TELEPHONE TERMINAL BOARD
TTC TELEPHONE TERMINAL
CABINET
TV TELEVISION
TYP TYPICAL
UC UNDER COUNTER
UE UNDERGROUND ELECTRICAL
UG UNDERGROUND
UH UNIT HEATER
UL UNDERWRITER'S LABORATORY
UT UNDERGROUND TELEPHONE
UTP UNSHIELDED TWISTED PAIR
UTIL UTILITY
UV UNIT VENTILATOR OR
ULTRAVIOLET
V VOLT
VA VOLT-AMPERES
VERT VERTICAL
VFD VARIABLE FREQUENCY DRIVE
VOL VOLUME
W WATT
W/ WITH
WH WATER HEATER
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
XFR TRANSFER
ANGLE
@ AT
DELTA
' FEET
" INCHES
# NUMBER
Φ PHASE
C CENTER LINE
P PLATE
MTR MOTOR, MOTORIZED
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURER'S ASSOCIATION
NFDS NON-FUSED SAFETY DISCONNECT
SWITCH
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OH OVERHEAD
OL OVERLOAD
PA PUBLIC ADDRESS
PB PULL BOX OR PUSHBUTTON
PBPU PREFABRICATED BEDSIDE PATIENT
UNIT
PCB POLYCHLORINATED BYPHENYL
PC PHOTOELECTRIC CELL
PED PEDESTAL
PEND PENDANT
PF POWER FACTOR
PH PHASE
PIV POST INDICATING VALVE
PNL PANEL
POE POWER-OVER-ETHERNET
PR PAIR
PRI PRIMARY
PROJ PROJECTION
PRV POWER ROOF VENTILATOR
PT POTENTIAL TRANSFORMER
PVC POLYVINYL CHLORIDE (CONDUIT)
PWR POWER
QTY QUANTITY
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
REQD REQUIRED
RGS RIGID GALVANIZED STEEL
RM ROOM
RMS ROOT MEAN SQUARE
RTU ROOF TOP UNIT
SC SURFACE CONDUIT
SEC SECONDARY
SF SQUARE FEET/FOOT
SHT SHEET
SI INTERNATIONAL SYSTEM OF UNITS
SIM SIMILAR
S/N SOLID NEUTRAL
SPEC SPECIFICATION
SPKR SPEAKER
SP SPARE
1P 1 POLE (2P, 3P, 4P, ETC.)
1PH 1 PHASE
2/C TWO-CONDUCTOR (3/C, 4/C, ETC.)
W2 TWO-WIRE (3W, 4W, ETC.)
3PH 3 PHASE
A AMPERE
AAP ALARM ANNUNCIATOR PANEL
AC ABOVE COUNTER
AIR CONDITIONER
ALTERNATING CURRENT
ACC ACCESSIBLE
ACLG ABOVE CEILING
ADO AUTOMATIC DOOR OPENER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AFC AVAILABLE FAULT CURRENT (KILOAMPS)
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AFI ARC FAULT CIRCUIT INTERRUPTER
AHJ AUTHORITY HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMPERE INTERRUPTING CAPACITY
AL ALUMINUM
ALT ALTERNATE
AMP AMPERE
APPROX APPROXIMATELY
ARCH ARCHITECT, ARCHITECTURAL
AT AMP TRIP
ATS AUTOMATIC TRANSFER SWITCH
AUTO AUTOMATIC
AUX AUXILIARY
AV AUDIO VISUAL
AWG AMERICAN WIRE GAUGE
BAS BUILDING AUTOMATION SYSTEM
BATT BATTERY
BC BARE COPPER
BD BOARD
BFF BELOW FINISHED FLOOR
BLDG BUILDING
BMS BUILDING MANAGEMENT SYSTEM
BYP BYPASS
C CONDUIT
CAB CABINET
CALC CALCULATED
CAP CAPACITY
CAT CATALOG, CATEGORY
CATV COMMUNITY ANTENNA TELEVISION
CB CIRCUIT BREAKER
CCR CONTROL CONTACTOR
CCTV CLOSED CIRCUIT TELEVISION
cd CANDELA
CD CONSTRUCTION DOCUMENTS
CF CONTRACTOR-FURNISHED
CKT CIRCUIT
CLG CEILING
CO CONTRACTING OFFICER
COAX COAXIAL CABLE
COMM COMMUNICATION
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUATION OR CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CPT CONTROL POWER TRANSFORMER
CRI COLOR RENDERING INDEX
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CTR CENTER
CU COPPER
CU FT CUBIC FEET
dB DECIBEL
DB DIRECT BURIAL
DC DIRECT CURRENT
DEG C DEGREES CELSIUS
DEG F DEGREES FAHRENHEIT
DEMO DEMOLISH/DEMOLITION
DEPT DEPARTMENT
DIA DIAMETER
DISC DISCONNECT
DIST DISTRIBUTION
DN DOWN
DS SAFETY DISCONNECT SWITCH
DT DOUBLE THROW
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EG EQUIPMENT GROUND
ELEC ELECTRIC, ELECTRICAL
ELEV ELEVATOR
EM EMERGENCY
EMI ELECTROMAGNETIC INTERFERENCE
EMS ENERGY MANAGEMENT SYSTEM
EMT ELECTRICAL METALLIC TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ESMT EASEMENT
ETR EXISTING TO REMAIN
EWC ELECTRIC WATER COOLER
EWH ELECTRIC WALL HEATER
ELECTRIC WATER HEATER
EX EXISTING
EXP EXPLOSION PROOF
FA FIRE ALARM
FAAP FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROL PANEL
FC FOOTCANDLE
FCU FAN COIL UNIT
FIXT FIXTURE
FLR FLOOR
FLUOR FLUORESCENT
FU FUSE
FUDS FUSED SAFETY DISCONNECT SWITCH
FVR FULL VOLTAGE REVERSING
FVNR FULL VOLTAGE NON-REVERSING
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERATOR
GFI GROUND FAULT CIRCUIT INTERRUPTER
GND GROUND
GRS GALVANIZED RIGID STEEL (CONDUIT)
GYP BDGYPSUM BOARD
HID HIGH-INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSEPOWER
HT HEIGHT
HTR HEATER
HV HIGH VOLTAGE
HVAC HEATING, VENTILATING AND AIR
CONDITIONING
IES ILLUMINATION ENGINEERING SOCIETY
IG ISOLATED GROUND
IMC INTERMEDIATE METAL CONDUIT
IR INFRARED
I/W INTERLOCK WITH
IWH INSTANTANEOUS WATER HEATER
J-BOX JUNCTION BOX
KV KILOVOLT
KVA KILOVOLT-AMPERE
KVAR KILOVOLT-AMPERE REACTIVE
KW KILOWATT
KWH KILOWATT HOUR
LED LIGHT-EMITTING DIODE
LF LINEAR FEET/FOOT
LM LUMEN
LRA LOCKED ROTOR AMPS
LT LIGHT
LTG LIGHTING
LTNG LIGHTNING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
METAL-CLAD (CONDUIT)
MCA MINIMUM CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MDP MAIN DISTRIBUTION PANEL
MECH MECHANICAL
MFR MANUFACTURER
MFS MAIN FUSED DISCONNECT SWITCH
MH MANHOLE
MIC MICROPHONE
MIN MINIMUM
MISC MISCELLANEOUS
MLO MAIN LUGS ONLY
MOA MULTIOUTLET ASSEMBLY
MSBD MAIN SWITCHBOARD
MT MOUNT
A1 b
E1 c d
T1
'LPN'
THE LIGHTING FIXTURE TYPE IS INDICATED BY AN UPPER CASE LETTER OR AN UPPER CASE LETTER
AND NUMBER.
THE SWITCH DESIGNATION (IF NEEDED) IS INDICATED BY A LOWER CASE LETTER.
EXAMPLE: LIGHTING FIXTURE TYPE 'A1' IS CONTROLLED BY SWITCH 'b' (IF SWITCH
IS LABLED EM, THE FIXTURE IS CIRCUITED TO AN EMERGENCY CIRCUIT).
EXIT SIGNS: STEM INDICATES WALL MOUNTING. NO STEM INDICATES CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S). ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED
FACE(S).
DEVICES: THE SWITCH DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
THE CONTROL DEVICE DESIGNATION IS INDICATED BY A LOWER CASE LETTER.
TRANSFORMERS: THE TRANSFORMER TYPE IS INDICATED BY A NUMBER FOLLOWING THE UPPER
CASE LETTER 'T'. SEE THE TRANSFORMER SCHEDULE OR THE SINGLE LINE DIAGRAM FOR THE
TRANSFORMER DESCRIPTION AND REQUIREMENTS.
PANELBOARDS: PANELBOARD DOORS MAY BE SHOWN TO INDICATE OPENING SIDE OF RECESSED
PANELBOARDS. SEE PANELBOARD IDENTIFICATION FOR DESIGNATION CODES.
SHEET KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE NUMBER INDICATED
IN THE HEXAGON.
HOME RUN TO BRANCH CIRCUIT PANEL: THE PANEL DESIGNATION AND CIRCUIT DESIGNATION ARE
SHOWN ADJACENT TO THE HOME RUN ARROW.
CIRCUIT BREAKER SIZES (AMPS/NUMBER OF POLES) ARE SHOWN IN THE PANEL SCHEDULE WITH
THE CORRESPONDING PANEL AND CIRCUIT DESIGNATION.
SYMBOL NOTATIONS: UPPER CASE LETTERS ADJACENT TO SYMBOLS INDICATE A UNIT TYPE. SEE
APPROPRIATE SCHEDULE OR SPECIFICATIONS.
'LPN'-1,3,5
EXAMPLE 1: WALL MOUNTED EXIT SIGN TYPE 'E1' WITH SINGLE FACE AND DIRECTIONAL
ARROW.
EXAMPLE 2: CEILING MOUNTED EXIT SIGN TYPE 'E2' WITH DOUBLE FACE AND DIRECTIONAL
ARROWS.
E2
EXAMPLE: SPLIT DUPLEX RECEPTACLE; ONE RECEPTACLE OUTLET IS
CONTROLLED BY SWITCH 'c'.
EXAMPLE: SINGLE POLE SWITCH 'd' TO CONTROL LIGHTING FIXTURES INDICATED BY 'd'.
EXAMPLE: TRANSFORMER TYPE 'T1'.
EXAMPLE: HOME RUN TO PANELBOARD 'LPN'; CIRCUITS 1, 3, 5.
# DEMOLITION KEY NOTE: SEE THE SHEET KEY NOTES ON THAT SHEET FOR THE NOTE NUMBER
INDICATED IN THE SQUARE.
2' X 2' RECESSED DIRECT/INDIRECT TROFFER
2' X 4' RECESSED DIRECT/INDIRECT TROFFER
SYMBOL
HEIGHT
AFF * DESCRIPTION
--- 2' X 4' RECESSED FLAT PRISMATIC LENS TROFFER
WALL SCONCE
6'-0"
CENTER
6" DIAMETER RECESSED DOWNLIGHT---
EXIT SIGN - WALL MOUNTED
EXIT SIGN - CEILING MOUNTED---
7'-5"
BOTTOM
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
OS: OCCUPANCY SENSOR, DUAL TECHNOLOGY
VS: VACANCY SENSOR, DUAL TECHNOLOGY
LV: LOW VOLTAGE
LVD: LOW VOLTAGE DIMMER
D: LINE VOLTAGE DIMMER
T: DIGITAL TIMER
K: KEYED
3: 3 WAY
48"
CENTER
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL DEVICE
OCCUPANCY SENSOR, DUAL
TECHNOLOGY - WALL/CORNER MOUNTED
2' LINEAR - WALL MOUNTED
7'-0"
CENTER
EMERGENCY LIGHT BATTERY
OPERATED - WALL MOUNTED
7'-6"
CENTER
RC
* - ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE
LISTED HERE.
LIGHT LEVEL SENSOR, SINGLE ZONE
DIMMING CLOSED LOOP - CEILING MOUNTED
--- LOW VOLTAGE LIGHTING CONTROL
DEVICE WITH 0-10V DIMMING
RCD
4' LINEAR - WALL MOUNTED
7'-0"
CENTER
OS
OS
LS
A. PHASE 1
1. INSTALLATION OF NEW PANELS "HM1", "HM2", "HM3", "HM4", & “LCT2”, INCLUDING ASSOCIATED FEEDERS.
a. REPLACE EXISTING 800A, 3P CIRCUIT BREAKER IN SUBSTATION #1 TO FEED PANEL “HM1”.
b. SPLICE-IN NEW PANEL “HM2” FEEDERS TO EXISTING MCC-1 FEEDERS INSIDE SUBSTATION #1
DISTRIBUTION SWITCHBOARD.
c. INSTALL PANEL “HM4”, INCLUDING ASSOCIATED FEEDERS TO SPARE 800A, 3P CIRCUIT BREAKER IN
SUBSTATION #4.
d. INSTALL NEW PANEL “LCT2” VIA NEW TRANSFORMER, INCLUDING ASSOCIATED FEEDERS AND
CONNECT TO SPARE CIRCUIT BREAKER IN SUBSTATION #4.
2. PROVIDE TEMPORARY FEEDERS FOR TEMPORARY COOLING TOWERS AND CONNECT TO NEW PANEL
“HM1” OR PANEL “HM2”.
3. DISCONNECT/REMOVE EXISTING COOLING TOWERS CT-1 AND CT-2, INCLUDING ASSOCIATED FEEDERS.
4. PROVIDE NEW BRANCH CIRCUIT FEEDERS TO THE FOLLOWING HVAC EQUIPMENT AND CONNECT TO
PANELS
INDICATED BELOW:
a. PANEL “HM1” : 52-P-1, 52-P4, 52-P-7, EXIST. 52-P-13 (TEMPORARY CONNECTION), NEW 52-P-13 CT-1, CT-1 BASIN HEATERS, 52-AHU-1, AND 52-AHU-2.
b. PANEL “HM2” : 52-EF-1, 52-EF-2, AND 52-EF-3
c. PANEL “HM4” : 52-P-3, 52-P-8, 52-P-14, CT-2, AND CT-2 BASIN HEATERS
5. DISCONNECT AND REMOVE MCC-1, INCLUDING ASSOCIATED FEEDERS AND ALL CONNECTED BRANCH
CIRCUIT WIRING.
6. TERMINATE PANEL “HM2” FEEDERS TO 800A, 3P CIRCUIT BREAKER VACATED BY MCC-1.
7. INSTALL VFD’S FOR COOLING TOWERS AT FORMER MCC-1 LOCATION.
8. PREPARE A TEMPORARY FEEDER CHILLER #1 TO THE CUBICLE SERVING CHILLER #3. TERMINATE BOTH
ENDS OF THE FEEDER PRIOR TO DISCONNECTING ANY POWER. DISCONNECT CHILLER #3 AND
TERMINATE THE TEMPORARY FEEDERS.
9. DURING A WEEKEND OUTAGE AT NIGHT DISCONNECT CHILLER #1 AND RECONNECT IT TO THE TEMPORARY FEEDER. OUTAGE TO BE LIMTED TO 1 HOUR OR LESS AND MUST OCCUR WHEN CHILLER
PLANT DEMAND LESS THAN 800 TONS.
10. REMOVE SUBST. #2 TRANSFORMER & DISTRIBUTION SECTIONS, 15KV SELECTOR SWITCH SHALL REMAIN.
INSTALL NEW SUBSTATION #2 TRANSFORMER & DISTRIBUTION SECTIONS. COMMISSION SECONDARY
DISTIBUTION OF SUBSTATION #2
11. INSTALL NEW FEEDER BUSWAYS FOR NEW CHILLERS #1, #3, & CROSS CONNECTION TO TEMPORARY
CHILLER DISCONNECT TO NEW SUBST. #2.
12. PROVIDE TEMPORARY FEEDERS FOR CRITICAL EQUIPMENT BEFORE ELECTRICAL SHUTDOWN.
a. TEMPORARY CONNECT 52-P-5 TO MCC-EQB.
b. TEMPORARY CONNECT EM LIGHTING CIRCUIT TO MCC-EQB.
c. TEMPORARY CONNECT LIGHTING AND POWER OF PLANT CONTROL ROOM (ENGINEERING
OFFICE-106) TO MCC-EQB.
d. TEMPORARY CONNECTION OF AHU-1 TO MCC-EQB.
13. PROVIDE TEMPORARY LIGHTING FOR EQUIPMENT THAT IS IN OPERATION DURING THE ELECTRICAL
SHUTDOWN FOR EMERGENCY MAINTENANCE.
14. INITIATE/PROVIDE ELECTRICAL SHUTDOWN TO THE CHILLER PLANT FOR THE REPLCEMENT OF THE 15 KV SWITCH ASSOCIATED WITH UNIT SUBSTATION #2 (EC TO VERIFY WITH MC THAT TEMPORARY CHILLER IS
WORKING AS INTENDED AND OPERATIONAL THROUGH THE SHUTDOWN BEFORE POWER OUTAGE).
OUTAGE TO BE LIMTED TO 12 HOURS AND OCCUR ON A FRIDAY NIGHT STARTING AT 9PM. THIS OUTAGE
WILL REMOVE POWER TO THE ENTIRE CHILLER PLANT.
a. REPLACE EXISTING SUBSTATION #2 15KV SELECTOR SWITCH WITH THE NEW SUBST. #2 15KV
SELECTOR SWITCH AND CONNECT TRANSFORMER/DISTRIBUTION SECTIONS TO 15KV SELECTOR
SWITCH. PERFORM FINAL COMMISSIOING OF SUBSTATION.
B. PHASE 2
1. CONNECT NEW CHILLER #3 TO SUBST. #2 BY THE NEW FEEDER BUSWAY.
2. PROVIDE NEW BRANCH CIRCUIT FEEDERS TO THE FOLLOWING HVAC EQUIPMENT AND CONNECT TO
PANEL
“HM2”: 52-P-6, 52-P-12, 52-P-13, CT-3, AND CT-3 BASIN HEATERS
C. PHASE 3
1. DISCONNECT EXISTING CHILLER #1 FROM SUBSTATION #3.
2. CONNECT NEW CHILLER #1 TO SUBSTATION #2 BY THE NEW FEEDER BUSWAY.
D. PHASE 4
1. INITIATE/PROVIDE ELECTRICAL SHUTDOWN OF THE CHILLER PLANT TO DISCONNECT POWER TO SUBSTATION #3. DISCONNECT FEEDERS TO SUBSTATION #3 AT SUBSTATION #4. RESTORE POWER TO THE CHILLER PLANT. OUTAGE TO BE LIMTED TO 1 HR. OUTAGE TO OCCUR AT NIGHT DURING A WEEKEND.
2. REPLACE EXISTING SUBST. #3 WITH NEW.
3. INITIATE/PROVIDE ELECTRICAL SHUTDOWN OF THE CHILLER PLANT TO RECONNECT POWER TO
SUBSTATION #3. RECONNECT FEEDERS TO SUBSTATION #3 AT SUBSTATION #4. RESTORE POWER TO THE CHILLER PLANT. OUTAGE TO BE LIMTED TO 1 HR. OUTAGE TO OCCUR AT NIGHT DURING A WEEKEND.
4. INSTALL CHILLER #2 FEEDERS AND CONNECT NEW CHILLER #2 TO NEW SUBSTATION #3
5. CONNECT NEW PANEL “HM3”, INCLUDING ASSOCIATED FEEDERS AND CONNECT TO SUBSTATION #3.
6. PROVIDE NEW BRANCH CIRCUIT FEEDERS TO THE FOLLOWING HVAC EQUIPMENT AND CONNECT TO
PANEL
"HM3": 52-P-2, 52-P-5, 52-EF-4, 52-EF-5, 52-EF-6, 52-EF-7, AND 52-SF-1
7. DISCONNECT AND REMOVE MCC-3, INCLUDING ASSOCIATED FEEDERS AND ALL CONNECTED BRANCH
CIRCUIT WIRING.
GENERAL ELECTRICAL NOTES
1. ALL ELECTRICAL DEVICES, FIXTURES, EQUIPMENT AND FEEDERS SHALL BE INSTALLED IN
ACCORDANCE WITH THE PROJECT SPECIFICATIONS, THE MANUFACTURER'S RECOMMENDED
PROCEDURES, ALL APPLICABLE LOCAL AND STATE CODES, AMERICANS WITH DISABILITIES ACT AND
WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE AND VA STANDARDS.
2. PROVIDE ADDITIONAL SUPPORT FOR DEVICES, FIXTURES, EQUIPMENT AND FEEDERS WHERE THE
BUILDING CONSTRUCTION IS NOT SUITABLE FOR DIRECT MOUNTING.
3. FIRESTOP, DRAFTSTOP, SMOKESTOP AND/OR PROTECT THE ANNULAR SPACE AROUND ALL
PENETRATIONS THROUGH WALLS, PARTITIONS, FLOORS, CEILING, AND ROOFS IN ACCORDANCE
WITH THE REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE, UL LISTING REQUIREMENT AND
THE APPLICABLE BUILDING CODES.
4. PROTECT EXISTING UNDERGROUND AND BUILDING INTERIOR UTILITIES DURING CONSTRUCTION.
5. BRANCH CIRCUIT CONDUCTORS SHALL BE 12 AWG COPPER MINIMUM.
6. COORDINATE ANY AND ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION SO AS TO
AVOID CONFLICT DURING CONSTRUCTION.
7. ALL PANELS SHALL HAVE TYPED, COMPLETED DIRECTORIES INDICATING EQUIPMENT SERVED AND ROOM NUMBER (AS INDICATED ON FINAL BUILDING ROOM SIGNAGE) OF EQUIPMENT LOCATION, OR
SPARE, OR SPACE.
8. MANUFACTURER'S NAME AND MODEL NUMBER ARE GIVEN FOR DESCRIPTIVE PURPOSES, TO
INDICATE A QUALITY STANDARD, AND ARE NOT INTENDED TO LIMIT PRODUCTS TO A PARTICULAR
MANUFACTURER. PRODUCTS DEEMED EQUAL AND APPROVED BY THE DESIGNER WILL BE
ACCEPTED. ALL PRODUCTS MUST COMPLY WITH "BUY AMERICAN ACT".
9. ALL FEEDERS AND CIRCUITRY SHALL BE TORQUED PER THE PANEL, BREAKER, AND/OR PARTICULAR
EQUIPMENT MANUFACTURER'S SPECIFICATIONS.
10. CIRCUITRY TO SWITCHES, RECEPTACLES, AND ALL OTHER DEVICES SHALL BE TERMINATED ON THE
DEVICE'S SCREW TERMINALS.
11. MOUNTING HEIGHTS INDICATED ARE TO CENTER OF DEVICE, OUTLET, FIXTURE, OR EQUIPMENT
UNLESS NOTED OTHERWISE.
12. ALL WIRE TERMINATIONS SHALL BE RATED FOR 75 DEGREES C.
13. ALL CONDUCTORS SHALL HAVE THHN/THWN INSULATION, UNLESS OTHERWISE NOTED.
14. ALL CONDUIT SHALL BE RGS OR EMT UNLESS OTHERWISE NOTED. FMC CONDUIT SHALL BE USED ON VIBRATING EQUIPMENT (MAXIMUM LENGTH OF 6 FEET). PVC SHALL BE USED FOR UNDERGROUND
CONDUIT OR WHERE CONCRETE-ENCASED. WHERE VIBRATING EQUIPMENT IS LOCATED OUTSIDE,
LFMC CONDUIT SHALL BE USED (MAXIMUM SIX FEET) FOR FINAL CONNECTIONS.
15. ALL ELECTRICAL MATERIALS, DEVICES, APPLIANCES AND EQUIPMENT SHALL BE LABEL LISTED BY AN
APPROVED THIRD PARTY TESTING AGENCY.
16. FOR ALL LED FIXTURES, THE FIXTURE MUST BE CAPABLE OF SELF-RESETTING TO THE
SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC
PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE
MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT
BROWNOUT PROTECTION, WILL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY.
PROVIDE STATEMENT WITH THE FIXTURE SUBMITTALS.
17. IN CASE OF CONFLICTS OR DISCREPANCIES WITHIN OR AMONG THE CONTRACT DRAWINGS, THE
BETTER QUALITY, MORE STRINGENT REQUIREMENTS OR GREATER QUANTITY OF WORK , AS
DETERMINED BY THE GOVERNMENT, SHALL BE PROVIDED.
18. COMPRESSION COUPLINGS SHALL BE USED. NO SET SCREW FITTINGS ARE ALLOWED.
19. THE TERMS "MOTOR CONTROLLER" AND "MOTOR STARTER" ARE BOTH USED IN THESE PLANS. BOTH TERMS SHALL BE CONSIDERED TO MEAN THE SAME THING, WHICH IS THE MOTOR CONTROLLER AS
DESCRIBED IN THE NATIONAL ELECTRICAL CODE.
20. FOR NEW MECHANICAL AND ELECTRICAL EQUIPMENT TO BE PROVIDED AND INSTALLED UNDER THIS
PROJECT, SEE SHEET E-607 FOR CONDUCTOR AND RACEWAY TYPES AND SIZES, FOR MOTOR
CONTROLLER REQUIREMENTS, AND FOR OTHER INSTALLATION REQUIREMENTS. EC SHALL PROVIDE
POWER WIRING. MC SHALL PROVIDE CONTROL WIRING. LIGHTING FIXTURE SCHEDULE
A. MANUFACTURER AND CATALOG NUMBERS SHOWN ARE FOR BASIS OF DESIGN, DESCRIPTIVE AND QUALITY STANDARDS ONLY, NOT TO BE USED FOR ORDERING WITHOUT VERIFICATION AND APPROVAL. CONTRACTOR TO PROVIDE PRODUCT OR EQUAL FOR APPROVAL BY OWNER, ARCHITECT AND ENGINEER. ENGINEER SHALL NOT BE RESPONSIBLE
FOR MISMATCHED OR INACCURATE PART NUMBERS.
B. VERIFY ALL LIGHT FIXTURE MOUNTING TYPES AND COLORS WITH ARCHITECT.
C. FOR ALL LED FIXTURES, THE FIXTURE SHALL BE CAPABLE OF SELF-RESETTING TO THE SWITCHED/CONTROLLED STATE DURING ANY FLUCTUATION IN POWER SUPPLY WHERE AUTOMATIC PROTECTIVE MEASURES DISABLE THE LED LAMPS. PROVIDE A LETTER OR STATEMENT FROM THE MANUFACTURER, OR OTHER ACCEPTABLE PROOF, THAT ALL LED FIXTURES, WITH OR WITHOUT BROWNOUT PROTECTION, SHALL RETURN TO THE SWITCHED/CONTROLLED STATE AUTOMATICALLY. PROVIDE STATEMENT WITH THE FIXTURE
SUBMITTALS.
D. LIGHTING CONTROLS, INCLUDING CONTROL SCHEMATICS, DEVICES, SWITCHES, SENSORS AND GRAPHIC DISPLAYS/CONTROLLERS. THIS INFORMATION MUST BE SUBMITTED WITH
THE LIGHT FIXTURE SHOP DRAWINGS, FOR A COMPLETE REVIEW.
E. PROVIDE SPECIAL DRILLING AND BACKING AS REQUIRED FOR MOUNTING A 24” LIGHTNING PROTECTION SYSTEM AIR TERMINAL TO PROJECT UP FROM THE TOP OF EACH LIGHT POLE. POLE SHALL HAVE ENTRY HOLE AT THE TOP FOR ENTRY OF LIGHTNING PROTECTION SYSTEM DOWN-CONDUCTOR, AND SHALL HAVE ACCESSIBLE GROUND CONNECTION BUSHINGS INSIDE THE POLE AT THE TOP AND AT THE BOTTOM FOR BONDING CONNECTION OF DOWN-CONDUCTOR TO THE TOP AND THE BOTTOM OF EACH POLE.
GENERAL NOTES:
SYMBOL
HEIGHT
AFF * DESCRIPTION
120V DUPLEX RECEPTACLE18"
18"
18"
18"
18"
18"
R S
H
T
L
VS
E
VFD
J
AS NOTED
72" TOP
72" TOP
72" TOP
AS NOTED
48"
120V DUPLEX RECEPTACLE EMERGENCY OUTLET AND
COVER PLATE SHALL BE RED IN COLOR
120V QUADRUPLEX RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY OUTLET
AND COVER PLATE SHALL BE RED IN COLOR
208V DUPLEX RECEPTACLE
120V DUPLEX RECEPTACLE FLOOR BOX
120V QUADRUPLEX RECEPTACLE FLOOR BOX
120V DUPLEX RECEPTACLE EMERGENCY FLOOR BOX
OUTLET AND COVER PLATE SHALL BE RED IN COLOR
SPECIAL RECEPTACLE
120V QUADRUPLEX RECEPTACLE EMERGENCY FLOOR
BOX OUTLET AND COVER PLATE SHALL BE RED IN
COLOR
RECEPTACLE MODIFIERS:
AC: 3" ABOVE COUNTERTOP/BACKSPLASH
GFI: GROUND FAULT CURRENT INTERRUPTER
WP: WEATHERPROOF ENCLOSURE
DED: DEDICATED CIRCUIT
AUDIBLE/VISUAL REFRIGERANT LOSS ALARM
BASIN WATER HEATER
BASIN WATER HEATER THERMOSTAT
LOW WATER LEVEL SHUDOWN SENSOR
VIBRATION SHUTDOWN SWITCH
MOTOR
EQUIPMENT CONNECTION
PANELBOARD
DISCONNECT SWITCH NON-FUSED
DISCONNECT SWITCH FUSED
JUNCTION BOX
LIGHTNING PROTECTION AIR TERMINAL
LIGHTNING PROTECTION EXOTHERMIC WELD -
GROUND
COMBINATION MOTOR STARTER WITH INTERGRAL
DISCONNECT AND OVER-CURRENT PROTECTION
VARIABLE FREQUENCY DRIVE (VFD) MOTOR
CONTROLLER WITH INTERGRAL DISCONNECTING DEVICE
SINGLE POLE WALL SWITCH
SWITCH MODIFIERS:
M: MOTOR RATED
ALL HEIGHTS ARE TO CENTER OF DEVICE UNO.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:2
P
M
E-001
ELECTRICAL GENERAL NOTES, SYMBOL
LEGENDS, AND ABBREVIATIONS
1 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
ELECTRICAL ABBREVIATIONS LIST
ELECTRICAL SYMBOL NOTES
LIGHTING SYMBOL LEGEND
ELECTRICAL WORK SEQUENCING PLAN
TYPE DESCRIPTION MOUNTING LAMP DRIVER VOLTAGE WATTS MANUFACTURER MODEL NUMBER
- 1' X 4' DIRECT/INDIRECT TROFFER; CHAIN
SUSPEND
EXISTING EXISTING 277 V 30 W EXISTING -
A1 4' LINEAR LED STRIPLIGHT WITH LENS CHAIN
SUSPEND
LED; 5000 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
277 V 50 W EATON 4SNLED-LD5-44SL-LW-UNV-L840-CD
A2 4' LINEAR LED STRIPLIGHT WITH LENS CHAIN
SUSPEND
LED; 5000 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
277 V 50 W EATON 4SNLED-LD5-56SL-LW-UNV-L840-CD1
B1 4' LINEAR LED STRIPLIGHT WITH LENS CHAIN
SUSPEND
LED; 5000 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
277 V 50 W EATON 8TSNLED-LD5-88SL-LW-UNV-L840-CD1
B2 4' LINEAR LED STRIPLIGHT WITH LENS CHAIN
SUSPEND
LED; 5000 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
277 V 50 W EATON 8TSNLED-LD5-110HL-LW-UNV-L840-CD1
C 2' X 2' DIRECT/INDIRECT TROFFER; RECESSED
GRID
LED; 3400 LUMENS;
80 CRI; 3500K
0-10V DIMMABLE TO
5% DRIVER
277 V 30 W EATON 22CZ-LD5-34-S-UNLV-L835-CD1-U
D SINGLE HEAD RECTANGULAR FULL CUTOFF SHOEBOX,
DARK BRONZE FINISH, TYPE IV DISTRIBUTION, HOUSE
SIDE SHEILD, UL LISTED FOR WET LOCATION,
MOUNTED ON 25'-0" ROUND TAPERED STEEL POLE.
POLE LED; 4836 LUMENS;
80 CRI; 4000K
ELECTRONIC LED
DRIVER
277 V 65 W KIM
VALMONT POLE
1SA-SAR4-E35-60L-4K-208-DB-SF-LS-NFO-TL
DS210-590A250-D1-PC-FP-DB-NC-AB (CUSTOM
CUT STANDARD 25-FOOT POLE TO
ALLOW FOR 22-FOOT FIXTURE MOUNTING
HEIGHT.)
ETR CONTEMPORARY LED SINGLE FACED EXIT SIGN WITH
BLACK POWDER PAINT ALUMINUM HOUSING,
BRUSHED ALUMINUM FACE, RED LETTERS, AND
CHEVRON ARROWS AS SHOWN ON PLANS.
UNIVERSAL LED --- 120 V 5 W EXISTING
ELECTRICAL SYMBOL LEGEND
DocuSign Envelope ID: EC584823-3079-447F-BB84-1D8AD0835F75
7A
7A
7A
7A 7A
7A
7A
7B
7B
7BA
7BF
7BA
7B
7A
7BF
5A
5A
5B
AB
AB
5B
5B
5B
5A5A
5A 5A
5A
5A
5B
5B
5B
5B
5B
MVG
MV FEEDER #5
ABANDONED / CUT IN
MANHOLE 2A
EXISTING DUCT,
UNKNOWN IF USABLE
4A
4A
4A
4A
4B
4BE
4BC
4B
4B
4BA
4BA
4BF
4A
4A
4B
4A
4BC
4BF
H O N O R
H E
IG
H T S
D R
IV
E
B U F F A L O
D R
IV
E
P A R K
D R
IV
E
18 11
1A
1B
1E
1C
G
G
G
E
GGENERATORS -
FEEDER #4
TRANSFORMERS -
MANHOLES -
FEEDER #5
FEEDER #7
59T
G
G G
FEEDER #9
FEEDER #8
#7
#1
#2
#2A
#9
#8
#4
#10
#2A
OG&E
E
K
M
LJ P
N
O
USS 3
USS 4
USS 2 USS 1
ATS-SA
USS "I"
USS 5
USS 6
USS 7
XFMR A
XFMR FGENERATORS 46 A & B
SEC. CABINET MV4
XFMR E
XFMR D
XFMR B
GENERATORS 56 1 & 2
GENERATOR 18
GENERATORS SG-4
ATS SG-4
GENERATOR 52
12,470v / 1.25 MVA
XFMR C
#3
PRIMARY SWITCHGEAR BUILDING
EXISTING MEDIUM VOLTAGE
DISTRIBUTION SYSTEM MAIN
SWITCHGEAR BUILDING #54
PROJECT LOCATION,
CHILLER PLANT
BUILDING #52
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
/2
/2
:0
:2
P
M
ES101
ELECTRICAL SITE PLAN
2 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
NORTH
0 5025 100
Scale: 1" = 50'-0"
ELECTRICAL SITE PLAN
A. THIS DRAWING DIAGRAMS THE EXISTING VA
MEDICAL CENTER CAMPUS MEDIUM VOLTAGE
ELECTRICAL POWER DISTRIBUTION SYSTEM
FOR REFERENCE ONLY AND IT IDENTIFIES THE
PROJECT LOCATION, CHILLER PLANT BUILDING
52. NO NEW WORK IS SHOWN ON THIS SHEET.
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7
S U B
S U B
F R O N T
T
T
S U B
F R O N T
T
4 F R O N T
S U B
V F
D V
F D
V F
D
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
TO CT-#3,
CELL #5
TO COOLING
TOWER SEPARATOR
TO PUMP 52P-13 ON
MEZZANINE
03 03
(EX) MV MOTOR CONTROLLER
FOR CHILLER #2
01 01 01
TO BASIN HEATERS,
CT-#3, CELL #5
'MCC-2' - 7A
'MCC-2' - 8E
'MCC-2' - 9A
'MCC-1' - 1S
'MCC-1' - 3E
'MCC-1' - 5U
'MCC-2' - 3M
(ETR) PANEL 'HCT'
(ETR) PANEL 'DP1C'
(ETR) TRANSFORMER 'TA'
(ETR) PANEL 'LCT'
(ETR) PANEL 'EQLCP'
(ETR) TRANSFORMER
(ETR) TRANSFORMER
(ETR) PANEL 'ECHCP'
(ETR) ATS-ECB
(ETR) SUB #1
(EX) SUB #2
(ETR) SUB #4
(ETR) ATS-EQB
(ETR) MCC EQB
(ETR) ATS-SA
(EX) MCC -2 (EX) MCC -1
(EX) SUB #3
(EX) MV MOTOR CONTROLLER
FOR CHILLER #1
(EX) MV MOTOR CONTROLLER
FOR CHILLER #2
'MCC-2' - 3A
CHILLER #3
CONTROL PANEL
UP TO EF-5 ON
MEZZANINE SEE
SHEET ED103
'MCC-2' - 1A
CHILLER #2
CONTROL PANEL
CHILLER #1
CONTROL PANEL
'MCC-2' - 2G
'MCC-1' - 7J
'MCC-2' - 7M
'MCC-2' - 7M03 03
(EX) PUMP CONTROLLER
(ETR)
VFD 52-P-11
(EX)
VFD 52-P-2
(EX)
VFD 52-P-3
(EX)
VFD 52-P-9
'MCC-1' - 2A
'ECHCP' - 7,9,11
V F D
(ETR)
'EQLCP'-28
(EX)
VFD 52-P-10
(EX)
VFD 52-P-1
XFMR
(ABOVE)
XFMR
(FLOOR
MOUNT)
(ETR) PUMP CONTROLLER
52-CTSSF-1
52-EF-1
(ABOVE)
EX 52-P-6EX 52-P-5EX 52-P-4EX 52-P-1
EX 52-P-8
EX 52-P-2EX 52-P-3
EX 52-P-12
EX 52-EF-2EX 52-EF-7
EX 52-P-9
EX 52-P-10
EX 52-P-11
EX 52-CH-3 EX 52-CH-2 EX 52-CH-1
EX 52-P-7 (ETR)
(ETR)
(ETR)
EX 52-P-14
(ETR) PANEL
'PDP-52HT'
EX 52-LA-9
EX 52-LA-12A1
EX 52-LA-12A2
EX 52-LA-12B1
EX 52-LA-12B2
EX 52-LA-1
EX 52-LA-6
EX 52-LA-5
EX 52-LA-2
04 04
ENGINEERING OFFICE
TOILET
CHILLER PLANT
WATER SAMPLING
STORAGE
TRANSFORMER VAULT
TRANSFORMER VAULT
CHILLER PLANT
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:4
P
M
ED101
FIRST FLOOR ELECTRICAL DEMOLITION
PLAN
3 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
FIRST FLOOR ELECTRICAL DEMOLITION PLAN
01 DISCONNECT POWER FEEDER FROM
INDICATED 4,160V CHILLER TO BE REPLACED
BY MC. REMOVE INDICATED 5KV FEEDER
CONDUCTORS AND RACEWAYS BACK TO
SOURCE.
02 DISCONNECT POWER FEEDER FROM
INDICATED 4,160V CHILLER MOTOR
CONTROLLER TO BE REPLACED BY MC.
REMOVE INDICATED 5KV FEEDER
CONDUCTORS AND RACEWAYS BACK TO
SOURCE.
03 DISCONNECT POWER FEEDER FROM
INDICATED 460V MOTOR TO BE REPLACED BY
MC. REMOVE INDICATED FEEDER
CONDUCTORS AND RACEWAYS BACK TO
SOURCE.
04 DISCONNECT POWER FEEDER FROM
INDICATED 460V MOTOR CONTROLLER BACK
TO MOTOR AND POWER SOURCE.
05 DISCONNECT AND REMOVE INDICATED
400-AMP SAFETY SWITCH. REINSTALL THE
SWITCH AT NEW LOCATION. EXTEND
EXISTING WIRING TO RELOCATED
DISCONNECT SWITCH’S NEW LOCATION,
INCLUDING SUPPORTS AND SPLICE BOX IF
REQUIRED.
06 MOTORIZED VALVE ETR. WIRING
CONNECTION TO EXISTING 120V MOTORIZED
VALVE FROM CHILLER CONTROL PANEL.
REWORK WIRING AS REQUIRED TO ACTUATE
EXISTING VALVES FROM NEW CHILLER
CONTROL SYSTEM.
07 REMOVE AND REPLACE INDICATED
12.5KV-4.16KV UNIT SUBSTATION. REFER TO
SEQUENCING PLAN ON E-001 FOR DETAILS.
08 CONTRACTOR SHALL REMOVE INDICATED
EXISTING MOTOR CONTROL CENTER (MCC),
INCLUDING ASSOCIATED FEEDERS AND ALL
BRANCH CIRCUIT WIRING CONNECTED TO
MCC. REFER TO ELECTRICAL SEQUENCING
PLAN ON E-001.
09 INDICATED EXISTING EXHAUST FAN SHALL BE
REPLACED BY MC. REPLACE INDICATED
DISCONNECT SWITCH WITH NEW
COMBINATION MOTOR CONTROLLER. SEE
MECHANICAL EQUIPMENT SCHEDULE FOR
STARTER CHARACTERISTICS. REWORK
EXISTING BRANCH CIRCUIT WIRING AS
REQUIRED AND CONNECT TO DESIGNATED
NEW PANEL.
11 EXISTING FILTER UNIT, '52-CWSSF-11' AND ITS
ASSOCIATED CONTROLLER SHALL BE
REPLACED BY MC. EC SHALL DISCONNECT,
AND REWORK EXISTING ELECTRICAL
SERVICES AS REQUIRED.
12 REFER TO ELECTRICAL SEQUENCING PLAN
FOR REPLACEMENT OF PUMP, NEW MOTOR
WILL BE PROVIDED WITH INTEGRAL VFD.
13 EXISTING REFRIGERANT LOSS MONITOR
PANEL TO BE REPLACED BY MC IS
CONNECTED TO EXISTING RECEPTACLE
OUTLET BELOW WITH CORD AND PLUG.
14 DURING THE REPLACEMENT OF CHILLER #2,
PROVIDE BRANCH CIRCUIT WIRING FOR NEW
52-P-5 AND CONNECT TO PANEL “HM3”.
15 INDICATED TRANSFORMERS TO BE
DEMOLISHED ARE ISOLATION
TRANSFORMERS CONNECTED IN SERIES
WITH ADJACENT VFD CONTROLLERS TO BE
DEMOLISHED.
16 INDICATED DISCONNECTS ARE FED FROM
BELOW.
B. INDICATED CIRCUIT INFORMATION IS BASED ON
RECORD DRAWINGS AND CASUAL FIELD
OBSERVATIONS. CONTRACTOR SHALL VERIFY
INFORMATION PROVIDED AND OBTAIN ANY
INFORMATION NOT PROVIDED THROUGH FIELD
INVESTIGATION.
A. ELECTRICAL EQUIPMENT SHOWN ON THIS SHEET
IS EXISTING TO REMAIN (ETR) UNLESS
OTHERWISE NOTED (UON).
## KEY NOTES:
3 3 3
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
SEE MEZZANNE LIGHTING
DEMOLITION PLAN 1/ED104
FOR THIS AREA
CHILLER PLANT
ENGINEERING OFFICE
STORAGE
WATER SAMPLING
TOILET
107TRANSFORMER VAULT
TRANSFORMER VAULT
CHILLER PLANT
CORRIDOR
CHILLER PLANT
EM
EM
EM
EM
EM
EM
EM
EM
EM
ETR
ETR
ETR
ETR
ETRETR
ETR ETR
ETRETR
ETR
ETR
ETR
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:4
P
M
ED102
FIRST FLOOR LIGHTING DEMOLITION PLAN
4 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
FIRST FLOOR LIGHTING DEMOLITION PLAN
01 REMOVE AND REPLACE INDICATED EXISTING
LIGHT SWITCHES AND COVERPLATES WITH
NEW ONES TO MATCH EXISTING.
B. REPLACEMENT OF EXISTING LIGHTING FIXTURES
SHALL BE AN ALTERNATE.
A. REMOVE AND REPLACE EXISTING FLUORESCENT
LIGHT FIXTURES SHOWN WITH DASHED LINES ON
THIS DRAWING. REMOVE AND REPLACE
INDICATED EXIT SIGNS. RETAIN EXISTING
CIRCUITING FOR REUSE. SEE SHEET EL101 FOR
NEW LIGHTING PLAN.
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
(EX) 'MCC-1' - 4R
'MCC-2' - 2A
DOWN TO
DISCONNECT
SWITCH ON
FIRST FLOOR
LEVEL SEE
SHEET ED101
'MCC-1' - 5E 'MCC-2' - 3A
'MCC-1' - 5I
EX 52P-13
EX 52-EF-6
EX 52-EF-5
EX 52-EF-3
EX 52-SF-1
52-AHU-1
52-AHU-2
05 05
'MCC-1' - 6D
EX 52-LA-3
EX 52-LA-4
EX 52-LA-7
EX 52-LA-8
EX 52-LA-10 EX 52-LA-11
TELECOMMUNICATION
ROOM
OFFICE
OFFICE
TOILET
OFFICE
OFFICE
MEZZANINE
MEZZANINE
CORRIDOR
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:5
P
M
ED103
MEZZANINE ELECTRICAL DEMOLITION PLAN
5 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
01 DISCONNECT POWER FEEDER FROM
INDICATED 460V MOTOR TO BE REPLACED BY
MC. REMOVE INDICATED FEEDER
CONDUCTORS AND RACEWAYS BACK TO
SOURCE.
02 INDICATED EXISTING EXHAUST FAN SHALL BE
REPLACED BY MC. REPLACE INDICATED
DISCONNECT SWITCH WITH NEW
COMBINATION MOTOR CONTROLLER. SEE
MECHANICAL EQUIPMENT SCHEDULE FOR
STARTER CHARACTERISTICS. REWORK
EXISTING BRANCH CIRCUIT WIRING AS
REQUIRED AND CONNECT TO DESIGNATED
NEW PANEL.
05 MOTORIZED VALVE ETR. WIRING
CONNECTION TO EXISTING 120V MOTORIZED
VALVE FROM CHILLER CONTROL PANEL.
REWORK WIRING AS REQUIRED TO ACTUATE
EXISTING VALVES FROM NEW CHILLER
CONTROL SYSTEM.
06 INDICATED AHU SHALL REMAIN. REPLACE
EXISTING DISCONNECT SWITCH WITH NEW
MOTOR CONTROLLER. SEE SHEET E-701 FOR
CONTROLLER TYPE. COORDINATE WITH MC.
REWORK EXISTING BRANCH CIRCUIT WIRING
AND CONNECT TO DESIGNATED NEW PANEL.
07 DISCONNECT AND REMOVE EXISTING
DISCONNECT SWITCH, INCLUDING
ASSOCIATED BRANCH CIRCUIT WIRING BACK
TO SOURCE.
Scale: 1/4" = 1'-0"
MEZZANINE ELECTRICAL DEMOLITION PLAN
NORTH
0 2 4 8
B. INDICATED CIRCUIT INFORMATION IS BASED ON
RECORD DRAWINGS AND CASUAL FIELD
OBSERVATIONS. CONTRACTOR SHALL VERIFY
INFORMATION PROVIDED AND OBTAIN ANY
INFORMATION NOT PROVIDED THROUGH FIELD
INVESTIGATION.
A. ELECTRICAL EQUIPMENT SHOWN ON THIS SHEET
IS EXISTING TO REMAIN (ETR) UNLESS
OTHERWISE NOTED (UON).
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
01 01
01 01 01
OPEN TO FLOOR BELOW
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
'HCT' - 6
'HCT' - 8
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:5
P
M
ED104
MEZZANINE LIGHTING DEMOLITION PLAN
6 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
01 REMOVE AND REPLACE INDICATED EXISTING
LIGHT SWITCHES AND COVERPLATES WITH
NEW ONES TO MATCH EXISTING.
B. REPLACEMENT OF EXISTING LIGHTING FIXTURES
SHALL BE AN ALTERNATE.
A. REMOVE AND REPLACE EXISTING FLUORESCENT
LIGHT FIXTURES SHOWN WITH DASHED LINES ON
THIS DRAWING. REMOVE AND REPLACE
INDICATED EXIT SIGNS. RETAIN EXISTING
CIRCUITING FOR REUSE. SEE SHEET EL102 FOR
NEW LIGHTING PLAN.
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
MEZZANINE LIGHTING DEMOLITION PLAN
GFI
WP
GFI
WP
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
H T H
VS
H T H
VS
H T H
VS
H T H
VS
H T H
VS
BASIN WATER HEATER
(TYPICAL)
BASIN WATER THERMOSTAT
(TYPICAL)
LOW WATER LEVEL BASIN HEATER
SHUTDOWN SENSOR
(TYPICAL)
VIBRATION SHUTDOWN SWITCH
WITH MANUAL RESET
(TYPICAL)
VERIFY EXACT
LOCATION IN FIELD
(TYPICAL)
'MCC-2'
COOLING TOWER FAN MOTOR
(TYPICAL)
DISCONNECT SWITCH FOR
CT-3, CELL-5 FAN MOTOR
'MCC-2'
'MCC-2' 'MCC-2'
'MCC-1'
'MCC-1'
'MCC-EQB'
L L L L L
LIGHTNING PROTECTION
AIR TERMINAL
(TYPICAL)
HCT-11
HCT-11
HCT-11
BASIN HEATER
CONTROL PANEL
(TYPICAL)
DISCONNECT SWITCH FOR
CT-3, CELL 5 BASIN HEATERS
CONTROLLER
FOR DOLPHIN 5
CONTROLLER
FOR DOLPHIN 4
CONTROLLER
FOR DOLPHIN 3
CONTROLLER
FOR DOLPHIN 1
CONTROLLER
FOR DOLPHIN 2
T
AMBIENT
TEMPERATURE
SENSOR
'LCT LT'
-39,41
'LCT'-65
WATER LEVEL CONTROLLER
'LCT LT'
-39,41
DISCONNECT
SWITCH FOR
CT-2, CELL-4
FAN MOTOR
DISCONNECT
SWITCH FOR
CT-2, CELL-3
FAN MOTOR
DISCONNECT
SWITCH FOR
CT-2, CELL-4
BASIN HEATERS
DISCONNECT
SWITCH FOR
CT-2, CELL-3
BASIN HEATERS
DISCONNECT
SWITCH FOR
CT-1, CELL-1
BASIN HEATERS
'LCT LT'
-39,41
'LCT LT'
-39,41
DISCONNECT SWITCH FOR
CT-1, CELL-2 BASIN HEATERS
B H
C P
B H
C P
B H
C P
B H
C P
B H
C P
EXISTING PITCH-PAN WITH (4) 1"C & (1) 1-1/2"C
THROUGH ROOF FROM BELOW.
EXISTING PITCH-
PAN WITH (3) 3/4"C
& (2) 2"C THROUGH
ROOF FROM
BELOW.
EXISTING PITCH-PAN
WITH (3) 1"C, (1) 3/4"C &
(2) 2"C THROUGH ROOF
FROM BELOW.
01 01
'LCT'-65
EXISTING UNDERGROUND
GROUND RING ELECTRODE
TO REMAIN, TYPICAL.
DISCONNECT
SWITCH FOR
CT-1, CELL-1
FAN MOTOR
DISCONNECT
SWITCH FOR
CT-1, CELL-2
FAN MOTOR
EX 52CT-1A
EX 52CT-3
EX 52CT-2B
EX 52CT-2A EX 52CT-1B
FLOOR MOUNTED
JUNCTION BOX
(TYPICAL)
ETR
ETR
ETR
ETR
ETR
ETR ETR
EX 52CT-3 EX 52CT-2B EX 52CT-2A EX 52CT-1B EX 52CT-1A
EX 52-EF-4
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:5
P
M
ED105
ROOF ELECTRICAL & LIGHTING
DEMOLITION PLAN
7 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
ROOF ELECTRICAL & LIGHTING DEMOLITION PLAN
01 EXISTING PITCH -PAN WITH INDICATED
CONDUITS THROUGH ROOF FROM BELOW.
PRESERVE AND PROTECT PITCH-PAN AND
CONDUITS CONTAINED WITHIN FOR REUSE
TO FEED NEW COOLING TOWER CIRCUITS.
02 DISCONNECT EXISTING FEEDER TO EXISTING
EXHAUST FAN 52-EF-4. MAINTAIN EXISTING
FEEDER TO FEED NEW REPLACEMENT FAN.
PROVIDE NEW UNFUSED DISCONNECT
SWITCH FOR NEW FAN.
03 REMOVE THREE (3) EXISTING LIGHT FIXTURE
SUPPORT STANDARDS AND ASSOCIATED
FIVE (5) EXISTING HID LIGHT FIXTURES.
REUSE EXISTING LIGHTING BRANCH CIRCUIT
TO FEED NEW LIGHTING ATTACHED TO NEW
COOLING TOWERS.
04 EXISTING PITCH PAN ROOF PENETRATION
WITH EXISTING CONDUITS. REFER TO
DETAILS 1/E-501, 2/E-501, AND 3/E-501.
05 DISCONNECT AND REMOVE ALL COOLING
TOWER EQUIPMENT, ACCESSORIES, AND
ASSOCIATED POWER/CONTROL WIRING BACK
TO SOURCE.
B. INDICATED CIRCUIT INFORMATION IS BASED ON
RECORD DRAWINGS AND CASUAL FIELD
OBSERVATIONS. CONTRACTOR SHALL VERIFY
INFORMATION PROVIDED AND OBTAIN ANY
INFORMATION NOT PROVIDED THROUGH FIELD
INVESTIGATION.
A. ELECTRICAL EQUIPMENT SHOWN ON THIS SHEET
IS EXISTING TO REMAIN (ETR) UNLESS
OTHERWISE NOTED (UON).
3 3 3
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
B1
B1
B1
B1
B1 B1
B1 B1
B1
B1
B1
B1 B1
B1
B1 B1 B1 B1
B1B1
B1
A1
B1
B1 B1
B1 B1 B1
B1 B1
B1 B1
B1
B1 A1
B1 B1
B1
B1
B1 B1
B1
A1
A2 A2 A2
A2
A2
ETR
ETR
ETR
ETR
ETRETR
ETR ETR
ETRETR
ETR
ETR
ETR
EM
EM
EM
EM
EM
SEE MEZZANNE LIGHTING
DEMOLITION PLAN 1/ED104
FOR THIS AREA
CHILLER PLANT
CHILLER PLANT
CHILLER PLANT
TRANSFORMER VAULT
TRANSFORMER VAULT
TOILET
ENGINEERING OFFICE
WATER SAMPLING
STORAGE
CORRIDOR
CORRIDOR
C
EM
EM
EM
EM
EM
EM EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:0
P
M
EL101
FIRST FLOOR LIGHTING PLAN
8 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
FIRST FLOOR LIGHTING PLAN
01 PROVIDE NEW LIGHT SWITCHES AND COVER
PLATES TO MATCH EXISTING IN EXISTING
OUTLET BOXES WHERE INDICATED.
02 PROVIDE TEMPORARY FEEDER TO CONNECT
ASSOCIATED LIGHTING CIRCUIT TO EXISTING
MCC ‘EQB’-3T FOR 12 HOUR ELECTRICAL
SHUTDOWN. FOR MORE INFORMATION SEE
SHEET E-601.
C. PROVIDE TEMPORARY FEEDER TO CONNECT EM
LIGHTING CIRCUIT TO MCC ‘EQB’-2M FOR 12 HOUR
ELECTRICAL SHUTDOWN. FOR MORE
INFORMATION SEE SHEET E-601.
B. REPLACEMENT OF EXISTING LIGHTING FIXTURES
SHALL BE AN ALTERNATE.
A. INDICATED LIGHT FIXTURES AND EXIT SIGNS
SHALL BE NEW. INSTALL THE NEW FIXTURES IN
APPROXIMATELY THE SAME LOCATIONS AS THE
REMOVED FIXTURES. CONNECT NEW FIXTURES
TO THE EXISTING WIRING AT EXISTING LIGHTING
OUTLET BOXES. SUSPEND FIXTURES FROM
STRUCTURE. MAINTAIN EXISTING LIGHTING
CONTROLS. REWORK EXISTING RACEWAYS AND
CONDUCTORS AS REQUIRED.
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
OPEN TO FLOOR BELOW
'HCT' - 6
'HCT' - 8
01 01 01
A1
B1
B1
B1
A1
B1
B1
B1
A1
B1
B1
B1
A1
B1
B1
B1
A1
B1
B1
B1
A1
B1
B1
B1
A1
B1
B1
B1
A1
B1
B1
B1
B1
B2B2B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
B2
A1 A1 A1
B2B2
B2
B2 B2
B2
A1
B2
B2
B2
A1
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM EM
EM EM
EM
Engineers Architects
## KEY NOTES:
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
SHEET NOTES:
WALL RATING LEGEND
1 HR - FIRE SEPARATION
2 HR - FIRE SEPARATION
SMOKE RESISTIVE HAZARDOUS AREA
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
S S S S
/2
/2
:0
:0
P
M
EL102
MEZZANINE LIGHTING PLAN
9 19EFJ
UPGRADE CHILLER PLANT
MUSKOGEE VAMC
1011 HONOR HEIGHTS DR,
MUSKOGEE, OK 74401
FEBRUARY 22, 2021
100% BID DOCUMENTS
623-16-10118-416
JAV
N
SCOPE OUTLINE
KEY PLAN
SCALE: NO SCALE
NORTH
0 2 4 8
Scale: 1/4" = 1'-0"
MEZZANINE LIGHTING PLAN
01 PROVIDE NEW LIGHT SWITCHES AND COVER
PLATES TO MATCH EXISTING IN EXISTING
OUTLET BOXES WHERE INDICATED.
C. PROVIDE TEMPORARY FEEDER TO CONNECT EM
LIGHTING CIRCUIT TO MCC ‘EQB’-2M FOR 12 HOUR
ELECTRICAL SHUTDOWN. FOR MORE
INFORMATION SEE SHEET E-601.
B. REPLACEMENT OF EXISTING LIGHTING FIXTURES
SHALL BE AN ALTERNATE.
A. INDICATED LIGHT FIXTURES AND EXIT SIGNS
SHALL BE NEW. INSTALL THE NEW FIXTURES IN
APPROXIMATELY THE SAME LOCATIONS AS THE
REMOVED FIXTURES. CONNECT NEW FIXTURES
TO THE EXISTING WIRING AT EXISTING LIGHTING
OUTLET BOXES. SUSPEND FIXTURES FROM
STRUCTURE. MAINTAIN EXISTING LIGHTING
CONTROLS. REWORK EXISTING RACEWAYS AND
CONDUCTORS AS REQUIRED.
S U B
S U B
F R O N T
T
T
S U B
F R O N T
T
4 F R O N T
S U B
V F
D V
F D
V F
D
VFD VFDVFD
VFD
VFD
VF
D
VFD
VFDVFD
V
FD
VFDVFDVFDVFDVFD VFD
H G.5 G F.5 F E.5 E
6.A
6B
7A
8A
(ETR) SUB #1
SUB #2
(ETR) SUB #4
(ETR) ATS-EQB
(ETR) MCC EQB
(ETR) ATS-SA
SUB #3
'HM2' - 25,27,29
'HM3'
- 13,15,17
(ETR)
VFD 52-P-9
(ETR)
VFD 52-P-10
(ETR)
VFD 52-P-11
040404
'HM2'
- 1,3,5
'HM3'
- 8,10,12
'HM1'
- 14,16,18
'HM2'
- 7,9,11
'HM3'
- 2,4,6
'HM1'
- 13,15,17
'HM1'
- 20,22,24
'HM2'
- 13,15,17
'HM4'
- 7,9,11
'HM1'
- 19,21,23
'HM3'
- 1,3,5
06 0606
'LCT2'
- 1 (PART)
'LCT2'
- 1 (PART)
'LCT2'
- 1 (PART)
'LCT2'
- 1 (PART)
'LCT2'
- 1 (PART)
'LCT2'
- 1 (PART)
'LCT2'
- 1 (PART)
(ETR) PUMP CONTROLLER
'ECHCP' -
7,9,11 09
(ETR) PANEL 'HCT'
(ETR) PANEL 'DP1C'
(ETR) TRANSFORMER 'TA'
(ETR) PANEL 'LCT'
(ETR) PANEL 'EQLCP'
(ETR) TRANSFORMER
(ETR) TRANSFORMER
(ETR) PANEL 'ECHCP'
(ETR) ATS-ECB
(NEW)
'LCT2' - 3
(ETR)
'EQLCP' - 28
'HM2'
- 19,21,23
600A, DISCONNECT
SWITCH
SEE SHEET E-603
52-P-352-P-252-P-12
52-CH-3
52-CH-2 52-CH-1
52-P-1 52-P-4 52-P-6
EX 52-P-9
EX 52-P-10
EX 52-P-11
52-P-8
52-P-7
52-P-13
52-P-5
52-EF-7
52-EF-2
52-LA-6
52-LA-5
52-LA-9
52-LA-12A2 52-LA-12B2
52-LA-12A1 52-LA-12B1
52-LA-1
52-LA-2
'HM3'
- 1,3,5
TO EXHAUST FAN
EF-5 LOCATED ON
MEZZANINE FLOOR.
52-FPHX-1
CONTROL
PANEL
'52-CWCDS-1'
PANEL 'HM2'
PANEL 'HM1'
PANEL 'HM3'
PANEL 'HM4'
EX-52-RLM-1
TRANSFORMER 'TCT2'
(ABOVE PANEL'LCT2')
PANEL 'LCT2'
T
52-CTSSF-1
VFD CT-1, C1
VFD CT-1, C2
VFD CT-2, C3VFD CT-2, C4
VFD CT-3, C5
VFD CT-3, C6
'HM2' -
8,10,12
'HM4' -
20,22,24
'HM1' -
1,3,5
'HM1' -
7,9,11
'HM2' -
2,4,6
'HM4' -
14,16,18
52-CTSSF-1
16 16
16 16 16
TRANSFORMER VAULT
TRANSFORMER VAULT
CHILLER PLANT
TOILET
ENGINEERING OFFICE
WATER SAMPLING
STORAG…