36C25919R0011-0001006.pdf
PDF 1 MB Posted
- Solicitation number
- 36C25919R0011
About this file
36C25919R0011 0001 4 - 01_PL_100-D_JSI041.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25919R0011-0003001.docx | DOCX document | |
| 36C25919R0011-0003002.pdf | ||
| 36C25919R0011-0003000.docx | DOCX document | |
| 36C25919R0011-0003003.docx | DOCX document | |
| 36C25919R0011-0002000.docx | DOCX document | |
| 36C25919R0011-0002001.docx | DOCX document | |
| 36C25919R0011-0002002.pdf | ||
| 36C25919R0011-0001002.docx | DOCX document | |
| 36C25919R0011-0001008.pdf | ||
| 36C25919R0011-0001009.docx | DOCX document | |
| 36C25919R0011-0001007.pdf | ||
| 36C25919R0011-0001004.pdf | ||
| 36C25919R0011-0001003.pdf | ||
| 36C25919R0011-0001005.pdf | ||
| 36C25919R0011-009.pdf | ||
| 36C25919R0011-007.pdf | ||
| 36C25919R0011-005.pdf | ||
| 36C25919R0011-001.docx | DOCX document | |
| 36C25919R0011-004.pdf | ||
| 36C25919R0011-006.pdf | ||
| 36C25919R0011-003.pdf | ||
| 36C25919R0011-010.docx | DOCX document | |
| 36C25919R0011-002.pdf | ||
| 36C25919R0011-008.pdf | ||
| 36C25919R0011-000.docx | DOCX document |
Show all 25
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UP
UP
01-SV-C29-V10
ELEV MACH RM
01-SV-C29-E7
ELEC
01-SV-C31-M3
MECH
01-SV-C34-E8
ELEC
01-SV-C35-M4
MECH
01-SV-C37-E9
ELEC
01-SV-SE15
ELEV
01-SV-SB37-V15
ELEV MACH RM
01-SV-ST5
STAIR
01-SV-C33-T3
DATA / TELECOMM
01-SV-PGE10
ELEV
01-SV-B35-M1
HEATING EQUIP
RM
01-SV-A36-01
SANITATION/RECYCLING
01-SV-A36-02
NON-FOOD STOR
01-SV-A36-03
DRY FOOD STOR
01-SV-A37-04
FOOD PREP
01-SV-A37-02
POT WASH
01-SV-A37-01
FOOD COURT
RECEIVING
01-SV-A38-01
WASTE PULPER
01-SV-A7-04
HAC
FINISHED FLOOR
ELEVATION 80.0'
(5368.0' USGS)
4"FD-B
4"FD-B W/
HALF GRATE
4"FD-B
4"FD-B W/
HALF GRATE
4"FD-B W/
HALF GRATE
4"FD-B
4"FD-B
4"FD-B W/
HALF GRATE
4"FD-B W/
HALF GRATE
4"FD-B
4"FD-B W/
HALF GRATE
4"FD-B W/
HALF GRATE
4"V UP
FROM
BELOW
FLOOR.
4"FD-B W/
HALF GRATE
4"FD-B W/
HALF GRATE
4"FD-B W/
HALF GRATE
4"FD-B
3"V UP FROM
BELOW FLOOR.
4"V UP FROM
BELOW FLOOR.
4"FD-B W/
HALF GRATE
4"FD-B W/
HALF GRATE
M A T C H L
IN
E A R E A D
M A T C H L
IN
E A R E A E
M A T C H L
IN
E A R E A E
M A T C H L
IN
E A R E A F
6"W 6"W
6"W DN BELOW
FLOOR W/ WCO
INV.: 92.0'
(5380.0' USGS)
6"W DN BELOW
FLOOR W/ WCO
4"GD DN BELOW
FLOOR W/ WCO
6"W
3"W UP
TO SS
1-1/2"W
UP TO DF
2"W UP
TO FD
3"W
2"W UP
TO FD
2"W UP
TO FD
4"W UP
TO WCs
2"W UP
TO LAVs 2"W UP
TO LAVs 4"W
2"W UP
4"W UP
3"W UP
TO MSB
2"W UP
TO EWC
4"W
2"W UP
2"W UP TO FD
2"W
4"W
2"W UP
TO LAVs
4"W UP
TO WCs
2"W UP TO LAVs
4"FCO
4"FD-S W/
HALF GRATE
4"FD-S W/
HALF GRATE
4"FD-S W/
HALF GRATE
4"FD-S W/
HALF GRATE
4"FD-S W/
HALF GRATE
3"FD-C
3"FD-C
3"GV
2"GV
3"FD-C
2"GV
3"GV
3"GV
3"GV
3"GV
4"FCO
4"FD-S
4"GV
2"GV
3"GV
3"V
2"V
4"GD
4"GD
2" WCO
4"FCO
4"GD
4"GD
4"GD
4"GD
3"GD
4"GD
2"V UP
4"GD
4"GD
3"GD 2"W
2"GV
4"V UP TO
LEVEL ABOVE
4"V
3"V UP
4"V UP
4"FD-B
4"FD-B4"FD-B
4"FCO
4"FCO
PROVIDE
SHEETMETAL PAN W/
1" IW BELOW PIPING
IN FOOD STORAGE
AREA. ROUTE IW TO
FD W/ 1" AIR GAP.
4"FCO
2"IW DN IN
WALL TO MSB
W/ 2" AIR GAP.
2" PUMPED IW
UP FROM
BELOW.
2"IW
2"IW 4"FD-S W/
HALF GRATE
4"FD-S W/
HALF GRATE
4"FCO
TP-1 TRAP PRIMER
LOCATION. EXTEND
1/2" TRAP PRIMER
LINE TO EACH FD.
P-502
3"V
3"V
2"PUMPED
IW
4"FD-B W/
HALF GRATE
3/4"IW DN
TO FD W/2"
AIR GAP
1"IW DN TO
FD W/2" AIR
GAP
1-1/4"IW DN
TO FD W/2"
AIR GAP
1"IW
6"FCO
4"FD-B W/
HALF GRATE
6"SW
1 - AHU5
1 - AHU4
1 - AHU7
1 - AHU10
1 - AHU6
1 - AHU8
1-HWP1
1-HWP4
1-ET2
1-HWP2
1-HWCP6
1-HWCP7
1-HWCP10
1-SAD6A 1-HWCP8
1-SWHX1
1-SWHX2
1 - FCU31
1-PRV2 1-SAD5
1-HWCP5
1-SAD4A
D
D
C
C
B
B
A
A
E
E
A
B
B
R1
SB
SB
SC
S29.3
S30
S31
SD
SD
S32
S33
S34
S35
S36
S37
S38
S38
11.5
01-SV-C37-E9
ELEC
01-SV-C39-01
CART DEPOT
01-SV-C11-O
DATA / TELECOMM
01-SV-C11-N
CONDENSATE
LIFT / STORM &
SAN
01-SV-C39-02
LOAD RM
01-SV-C40-01
CORRIDOR
01-SV-A38-01
WASTE PULPER
FINISHED FLOOR
ELEVATION 80.0'
(5368.0' USGS)
4"FCO
3"V(SP SUMP)
3"V(SP SUMP) UP TO
CLG SPACE.
1 1/2"PUMPED SW
6"SW
6"SW UP TO
RD ABOVE.
4"GCO
INV.: 95.50' (5383.50'
USGS).
2345 SQ FT (217.9 SQ
METERS) RE: CIVIL
DWGS.
INV.: 95.25'
(5383.25' USGS)
8' - 5"
1 1/2" PUMPED SW
UP FROM SUMP
PUMP SYSTEM.
M A T C H L
IN
E A R E A E
M A T C H L
IN
E A R E A F
3"V
3"V
01-SP-2
4"FD-B
4"FD-B W/
HALF GRATE
D
C
B
A
A
E
S38
A
B
B.5
B.7
C
11 12 08 09 13
03040506
Drawing Number
Building Number
Project NumberProject Title
Location
Date Checked Drawn
Drawing Title
Approved: Project Director
Key Plan
CONSULTANTS:
DateRevisions
1 2 3 4 5 6 7 8 9 10 11 12
D
C
B
A
554-501REPLACEMENT MEDICAL CENTER
FACILITY, EASTERN COLORADO
HEALTH CARE SYSTEM
AURORA, COLORADO
N
C O N
R E S
D A T
I B S
I B N
E N C
C L C
C B N
C B C
C B S
P S N
P V N
P V S
13 14
1 2 3 4 5 6 7 8 9 10 11 12 13 14
E o n e e ig h th i n c h o n e f o o t
OFFICE OF
CONSTRUCTION
AND FACILITIES
MANAGEMENT
ARCHITECT/ENGINEERS:
H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202
Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604
Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401
S. A. Miro, Inc.
4582 South Ulster Street Pkwy.
Suite 300 Denver, CO 80237
Professional Seal
/1 /2 :4 :5 P M
D R e v it L o c a l P ro je c ts \2 \P L -I F O -S h e e ts b g e tt e l.
rv t
01.PL.100-D
SERVICE LEVEL WASTE, DRAIN AND
VENT PIPING PLAN - AREA E/F
CONCOURSE
08/31/2012
0' 4' 8' 16' 32'0' 4' 8' 16' 32'
NORTH
FE
DBA C
1/8" = 1'-0"1
SERVICE LEVEL WASTE, DRAIN
AND VENT PIPING PLAN - AREA E
1/8" = 1'-0"2
SERVICE LEVEL WASTE, DRAIN
AND VENT PIPING PLAN - AREA F
0' 4' 8' 16' 32'0' 4' 8' 16' 32'
CDI No.12 08/31/2012
JSI No. 041 11/16/2012
See RFI 1842
Emeka.Nwabunwanne Cloud
Emeka.Nwabunwanne Callout KT RFI #4720 / VA #4174 - Wall was revised to receive Type A6 Wall
Tony.Escobar-PTR Callout RFI #6544: This pipe can be shifted west as needed to facilitate not running into the CBS foundation.
RFI 6544a/6878: Pipe can be shifted North (NOT West)
Bill.Sullivan-PTR Text Box
Bill.Sullivan-PTR Polygon
Sarah.Hartsfield Callout
KT RFI #2361/VA RFI #2061
VA requests shop drawings for engineered pulping system, which will revise MEP to Items 95, 96, & 98.
Sarah.Hartsfield Arrow
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Ellipse
Christopher.Betts Rectangle
Christopher.Betts Rectangle
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Ellipse
Christopher.Betts Rectangle
Christopher.Betts Rectangle
Christopher.Betts Rectangle
Christopher.Betts Rectangle
Christopher.Betts Typewritten Text KT RFI 3184(va 2823):
FCU condensate as shown
Christopher.Betts Typewritten Text
3/4" IW
Christopher.Betts Typewritten Text
1" IW
Christopher.Betts Arrow
Christopher.Betts Arrow
Christopher.Betts Typewritten Text
(1) 1" IW &
(1) 3/4" IW DN to FD w/2" AIR GAP
Christopher.Betts Arrow
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Line
Christopher.Betts Ellipse
Christopher.Betts Rectangle
Christopher.Betts Rectangle
Christopher.Betts Typewritten Text
1" IW
Christopher.Betts Arrow
Christopher.Betts Typewritten Text
1" IW DN TO FD
W/2" AIR GAP
Christopher.Betts Arrow
Christopher.Betts Typewritten Text KT RFI 3184(va 2823) FCU condensate as shown
Christopher.Betts Arrow
Christopher.Betts Snapshot
Christopher.Betts Typewritten Text in this area
Christopher.Betts Cloud
Adam.Horecki-PTR Text Box
Adam.Horecki-PTR Callout KT RFI 3903 (VA 3596): Reference this RFI for revision of storm pipe elevations. KT RFI 3797 (VA 3425) is a duplicate to this RFI.
Adam.Horecki-PTR Callout KT RFI #3797/VA #3425: Acceptable to raise INV. elevation to 92'-10" and core drill.
Xavier.Larsen Callout See RFI KT # 1842 / VA # 1706a regarding the plumbing beam conflict.
Xavier.Larsen Callout See RFI KT # 1843 / VA # 1705 regarding clear path/conflicts for this line.
Peter.Bernard Text Box
Peter.Bernard Callout KT RFI #1669/VA #1455: Re-route storm to avoid [pneumatic] intake well.
VA.PLAN
Cloud
VA.PLAN
Callout RFI #7882: This storm drain line is not constructible. The VA selects the option of draining the area by sloping to the swale. James Chang (COTR) will provide grading directions to KT Superintendent in the field to achieve positive drainage to a proper location.
Any cost associated with this RFI has to be approved through authorization process.
Xavier.Larsen Callout See RFI # 7981 regarding CON Kitchen Disposer Waste Pipe routing.
Xavier.Larsen Callout Reference RFI #8584 regarding Garbage Disposal #41 plumbing/venting re-route
Charlie.Stiens Callout See RFI #8848 regarding relocation of trough drain.
xavier.larsen Callout RFI # 9476 CON-Div22-SL Kitchen Food Prep Area (walk-in freezer/cooler) Condensate Drain Tripping Hazard - add table here xavier.larsen Callout RFI # 9520 - Relocate Air Compressor
Jorge.Almeida Cloud
Jorge.Almeida Callout Per RFI 10250, reroute pipe to the North side of the elevator door to avoid any conflict, then back to the South side of the elevator door and reconnect to the existing core drill. Field coordinate exact routing to avoid all conflicts.