36C25919R0011-0001004.pdf

PDF 1 MB Posted

Attached to
554-19-121 LV01 Power and HVAC in RMR Auditorium (VA-18-00150843)
Solicitation number
36C25919R0011
Issued by

About this file

36C25919R0011 0001 2 - 01.MP.100-D_JSI104-C.pdf

View the file

Other files

File Type Posted
36C25919R0011-0003001.docx DOCX document
36C25919R0011-0003002.pdf PDF
36C25919R0011-0003000.docx DOCX document
36C25919R0011-0003003.docx DOCX document
36C25919R0011-0002000.docx DOCX document
36C25919R0011-0002001.docx DOCX document
36C25919R0011-0002002.pdf PDF
36C25919R0011-0001002.docx DOCX document
36C25919R0011-0001008.pdf PDF
36C25919R0011-0001009.docx DOCX document
36C25919R0011-0001007.pdf PDF
36C25919R0011-0001003.pdf PDF
36C25919R0011-0001006.pdf PDF
36C25919R0011-0001005.pdf PDF
36C25919R0011-009.pdf PDF
36C25919R0011-007.pdf PDF
36C25919R0011-005.pdf PDF
36C25919R0011-001.docx DOCX document
36C25919R0011-004.pdf PDF
36C25919R0011-006.pdf PDF
36C25919R0011-003.pdf PDF
36C25919R0011-010.docx DOCX document
36C25919R0011-002.pdf PDF
36C25919R0011-008.pdf PDF
36C25919R0011-000.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

01.MH.302

01-SV-A36-01

SANITATION/RECYCLING

01-SV-A36-02

NON-FOOD STOR

01-SV-A36-03

DRY FOOD STOR

01-SV-A37-04

FOOD PREP

01-SV-A37-02

POT WASH

01-SV-A37-01

FOOD COURT

RECEIVING

01-SV-A38-01

WASTE PULPER01-SV-A7-04

HAC

3 CHILLED WATER, 2 HIGH

PRESSURE STEAM,

2 PUMPED CONDENSATE

MAINS WITH TAKE-OFFS

HVAC PIPING NOTES:

SEE STEAM AND CHILLED WATER

RISER DIAGRAMS FOR PIPE SIZES

AND CAPACITIES

01.MH.303

01.MH.303

01.MH.304

12" CHR

12" CHS

12" CHS

1 - FCU26

1 - FCU27

1 - AHU4

1 - FCU28

1 - FCU29

1-PRV2

1 - FCU31

1-HWP2

1-HWP1

1-HWP3

1-HWP4

1-ET2

1-ET1

1 - AHU5

1 - AHU6

1 - AHU10

1 - AHU8

1 - AHU7

" P

C

" C

H S

" H

P S

M

M

M

M

M

" P

C

" C

H S

" C

H R

12" HPS

12" HPS

6" PC

6" PC

6" PC

6" PC

1-CP3

ROUTE 6" HWS/R

DOWN TUNNEL TO

4" FOR RESEARCH

AND 5" FOR CBS

10" STEAM VENT UP

1-HWCP8

1-HWCP6

1-HWCP7

1-HWCP10

1-HWCP5

ROUTE CHS/R TO

REFRIGERATION UNITS

" C

H R

" C

H S

/4 " C

H R

/4 " C

H S

2" CHR

2" CHS

1 1/4" CHR

1 1/4" CHS

01.MH.302

E

A

B

C

D

Z

SA

SB

SC

SD

S38

S37

S36

S35

S34.6

S34

S33

S32

S31

S30

S29.3

6" PC

6" PC

12" HPS

12" HPS

1 - TU4-8

1 - TU7-5

1 - TU10-4

2" HWS/R UP

T

T

T

T T

T

T

T

T

T

T

1-HWCP4

1" CHR

1" CHS

1 1/2" CHR

1 1/2" CHS

3" CHS

1 1/4" GCS

1 1/4" GCR

3/4" HWS

2" LPS

01.MH.304

4" LPS

2" LPS

2 1/2" CHR

2 1/2" CHS

2" GCS

2" GCR

2" CHR

2" CHS

1 1/2" LPS

2" CHR

2" CHS

1 1/2" LPS

1 1/2" CHS

1 1/2" CHR

1 1/2" LPS

1 - FCU30

1" CHS

1" CHR

2" CHR

2" CHS2" CHS

2" CHR

1 - FCU37

C H

S

C H

R

4" HPS

4" LPS

4" HPS TO DOMESTIC

WATER HEAT EXCHANGERS

" L

P S

" L

P S

4" LPS6" LPS

" H

W R

" H

W S

3" LPS

3" LPS

6" HWS

6" HWR

1-SWHX3

1-SWHX4

12" CHR

12" CHS

12" CHS

10" VALVE AND CAP FOR

FUTURE CHILLED WATER

PIPE CONNECTIONS.

" C

H R

2" STEAM VENT

FROM 1-CP3 UP

FLOW LIMITING

DEVICE 30.8 GPM

01-SV-A37-02

POT WASH

01-SV-A37-01

FOOD COURT

RECEIVING

01-SV-A38-01

WASTE PULPER

12" CHR12" CHS

1 - FCU33

1 - FCU32

1 - FCU34

1 - FCU35

12" HPS12" HPS

6" PC

6" PC

" C

H R

M

5"HWS/R

4"LPS

2"LPC

ROUTE 6" HWS/R

DOWN TUNNEL TO

4" FOR RESEARCH

AND 5" FOR CBS

4" HWS/R TO

RESEARCH

12" CHS

" C

H S

E

A

B

C

D 01

Z

S38

T

T

T

T

6" HWS HIGH

6" HWR LOW6" HWS

6" HWR

2" LPR

4" LPS

2" CHR

2" CHS

1-CP4

11 12 08 09 13

03040506

Drawing Number

Building Number

Project NumberProject Title

Location

Date Checked Drawn

Drawing Title

Approved: Project Director

Key Plan

CONSULTANTS:

DateRevisions

1 2 3 4 5 6 7 8 9 10 11 12

D

C

B

A

554-501REPLACEMENT MEDICAL CENTER

FACILITY, EASTERN COLORADO

HEALTH CARE SYSTEM

AURORA, COLORADO

N

C O

N

R E

S

D A

T

I B

S

I B

N

E N

C

C L C

C B

N

C B

C

C B

S

P S

N

P V

N

P V

S

13 14

1 2 3 4 5 6 7 8 9 10 11 12 13 14

E o n e e ig h th i n c h o n e f o o t

OFFICE OF

CONSTRUCTION

AND FACILITIES

MANAGEMENT

ARCHITECT/ENGINEERS:

H+L Architecture 1755 Blake Street, Suite 400 Denver, CO 80202

Skidmore, Owings & Merrill LLP 224 South Michigan Avenue Suite 1000 Chicago, IL 60604

Cator, Ruma & Associates 896 Tabor Street Lakewood, CO 80401

S. A. Miro, Inc.

4582 South Ulster Street Pkwy.

Suite 300 Denver, CO 80237

Professional Seal

/4

/2

:4 :1

A

M D

R e v it L o c a l F ile s \2

\M

H -C

O N

M

J o h n s o n .r v t

01.MP.100-D

SERVICE LEVEL HVAC PIPING PLAN -

AREA E/F

CONCOURSE

08/31/2012

0' 4' 8' 16' 32'0' 4' 8' 16' 32'

NORTH

FE

DBA C

0' 4' 8' 16' 32'0' 4' 8' 16' 32'

FLAG NOTES:

CHILLED WATER BRANCH PIPING. ARRANGE VALVES TO ALLOW SWING

PIPE TO SERVE THE CHS OR CHR PIPING.

SLIP TYPE EXPANSION JOINTS (TYPICAL) WITH INJECTABLE PACKING

FOR HPS AND PC PIPING.

PIPE ANCHORS (TYPICAL) FOR HPS AND PC PIPING.

PIPE GUIDES (TYPICAL) FOR HPS AND PC PIPING. MINIMUM NUMBER OF

PIPE GUIDES INDICATED. INCREASE THE NUMBER OF PIPE GUIDES IF

RECOMMENDED BY THE EXPANSION JOINT MANUFACTURER.

STEAM DRIP LEG AND TRAP ASSEMBLY. SEE DETAIL. ROUTE 3/4" HPC

TO NEAREST CONDENSATE PUMP.

(NOT ALL FLAG NOTES USED ON THIS SHEET)

1/8" = 1'-0"1

SERVICE LEVEL HVAC PIPING

PLAN - AREA E

1/8" = 1'-0"2

SERVICE LEVEL HVAC PIPING

PLAN - AREA F

CDI No. 12 08/31/2012

JSI No. 104 09/04/2014

Jacqueline.Cipriani Cloud

Jacqueline.Cipriani Arrow

Jacqueline.Cipriani Text Box Per KT RFI #2228 / VA RFI #1993, no expansion joints are required for the chilled water piping down the length of the Concourse.

Jacqueline.Cipriani Arrow

Jacqueline.Cipriani Rectangle

Jacqueline.Cipriani Callout See RFI KT #3549/ VA #3114 placement of pipe bracing.

Jacqueline.Cipriani Rectangle

Jacqueline.Cipriani Callout See RFI KT #3549/ VA #3114 placement of pipe bracing.

Jacqueline.Cipriani Polygon

Jacqueline.Cipriani Callout See RFI KT #3736/ VA #3356 for relocation of the two 6" HWS/HWR lines

Jacqueline.Cipriani Cloud

Jacqueline.Cipriani Callout See KT RFI #4326 - Original KT RFI #3738 / VA #3356a and KT RFI #4707 / VA #4221 for Ceiling Height Clarification at Room 01-SV-A37-01

Jacqueline.Cipriani Cloud

Jacqueline.Cipriani Callout T

Jacqueline.Cipriani Callout See KT RFI 5487 / VA #4858 Thermostat Location Approved Rm: MECH 01-SV-SB37-V15 System: 1-FCU-37

Jacqueline.Cipriani Callout See RFI #1329 for routing of vent lines for 1-CP1,2, and 3.

Jacqueline.Cipriani Text Box See KT RFI #1333 for Chilled Water Main Sizing

Andrew.Seamans Callout

RFI 6303

Modifications to the mechanical piping.

Andrew.Seamans Cloud

Andrew.Seamans Image

Andrew.Seamans Image

Andrew.Seamans Cloud

Francisco.Vazquez Cloud

Francisco.Vazquez Callout See KT RFI 1328/VA RFI 1208

VA.PLAN

Callout

KT RFI #4010/VA #3666:

See RFI for information on how to field fit 1-CP3 and flash tank.

sarah.hartsfield Callout KT RFI #4204 / VA RFI #3845 - CON steam meter is shown on 01.MP.100-C, between grids 16 and 17 and between grids B and C, and another on 01.MP.100-D at grids 34 and C.

Tony.Escobar-PTR Text Box Review response to RFI 7870 for clarifications to the the steam system; See response and sketches MH.X282; MH.X283; & MH.X284

Peter.Bernard Cloud

Peter.Bernard Callout Per RFI #8044 (CON-DIV23-Htg Equip Rm Panel Locations), and attached sketch, it is acceptable to move (4) Equipment Control Panels and (1) Snow Melt Panel outside of the Room 01-SV-B35-M1.

Jorge.Almeida Cloud

Jorge.Almeida Text Box See RFI 8731 for added condensate cooler and piping required for AHU-4.

Jorge.Almeida Cloud

Jorge.Almeida Arrow

Jorge.Almeida Cloud

Jorge.Almeida Text Box See RFI 8731 for added condensate cooler and piping required for AHU-5.

Jorge.Almeida Cloud

Jorge.Almeida Arrow

Jorge.Almeida Cloud

Jorge.Almeida Text Box See RFI 8731 for added condensate cooler and piping required for AHU-6, AHU-7, and AHU-10.

Jorge.Almeida Cloud

Jorge.Almeida Arrow

Amelia.Cecchini Cloud

Amelia.Cecchini Callout Reference RFI #9064 for clarification on additional control valve placement for fin tube radiators in the South Concourse.

Amelia.Cecchini Cloud

Amelia.Cecchini Callout Reference RFI #9064 for clarification on additional control valve placement for fin tube radiators in the South Concourse.