These documents are plumbing design and demolition plans for Building 17 at the Department of Veterans Affairs (VA) facility located at 4800 Memorial Drive in Waco, Texas. The project involves comprehensive plumbing system renovations, including demolition of existing water heaters, piping, and fixtures across the basement and first level, followed by installation of new domestic water, sanitary sewer, and vent systems. Key components include two domestic hot water recirculation pumps (17-PP-1 and 17-PP-2), a steam domestic water heater (17-SDWH-1), a sump pump (17-SP-1), and an air compressor (17-COMP-1). The plumbing fixture schedule details replacement of various fixtures like water closets, urinals, sinks, electric water coolers, and emergency eye wash stations. The design emphasizes maintaining existing system functionality while upgrading infrastructure, with specific notes on providing backflow preventers, water hammer arrestors, and adhering to VA specifications for installation and penetration sealing.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GENERAL PLUMBING SYMBOLS

DIRECTION OF PIPE PITCH (DOWN)

DIRECTION OF FLOW

GUIDE

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45° OR 90°

BOTTOM CONNECTION, 45° OR 90°

SIDE CONNECTION

CAPPED OUTLET

RISE OR DROP IN PIPE

UNION

PIPE UP

PIPE DOWN

POINT OF CONNECTION BETWEEN NEW

AND EXISTING WORK

LIMIT OF DEMOLITION

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES

FLOAT & THERMOSTATIC TRAP SET

INCLUDING PIPING ACCESSORIES

STRAINER

THERMOMETER

PRESSURE GAGE

FLOW ELEMENT

WALL CLEAN OUT

CLEAN OUT

HOSE BIBB, FAUCET HEAD, SHOWER HEAD

WATER HAMMER ARRESTOR (PLAN VIEW)

FE

CO

MA

MV

LA

LV

OA

IA

D

SS

SD

SD

TWR

DWS

DWR

TWS

SS

SCW

FCW

NO

O

N

NG

NG

FOD

FOS

FOR

FOV

PLUMBING PIPING SYMBOLS

DOMESTIC COLD WATER, COLD WATER

DOMESTIC HOT WATER, HOT WATER

DOMESTIC HOT WATER RETURN

MEDICAL AIR

MEDICAL VACUUM

LABORATORY AIR

LABORATORY VACUUM

ORAL EVACUATION

INDUSTRIAL AIR

DRAIN

VENT (SANITARY)

SOIL, WASTE, OR SANITARY SEWER

SANITARY SEWER, BELOW GRADE

STORM WATER

STORM WATER, BELOW GRADE

SOFTEN COLD WATER

FILTERED COLD WATER

DRINKING WATER SUPPLY

DRINKING WATER RETURN

TEMPERED WATER RETURN

TEMPERED WATER SUPPLY

NITROUS OXIDE

OXYGEN

NITROGEN

NATURAL GAS

NATURAL GAS, BELOW GRADE

FUEL OIL DISCHARGE

FUEL OIL SUPPLY

FUEL OIL VENT

FUEL OIL RETURN

REAGENT WATER

REAGENT WATER RETURN

CORROSION RESISTANT SANITARY SEWER

CORROSION RESISTANT VENT (SANITARY)

GREASE WASTE

NEW PIPING

EXISTING PIPING

PIPE TO BE DEMOLISHED

FIXTURE OR EQUIPMENT TO BE DEMOLISHED

AV

PLUMBING VALVE SYMBOLS

GENERIC VALVE (REF SPEC FOR TYPE)

GENERIC VALVE WITH 3/4" HOSE ADAPTER

CHECK VALVE

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

CONTROL VALVE

THREE-WAY CONTROL VALVE

PRESSURE REGULATING VALVE

AUTOMATIC FLOW CONTROL VALVE

PRESSURE RELIEF VALVE

MANUAL AIR VENT

TEST PLUG (PRESSURE/TEMPERATURE)

AUTOMATIC AIR VENT

THERMOSTATIC MIXING VALVE

RWR

RW

V CRP

SS CRP

GW

P-###

H4

H7

A

DETAIL NUMBER

DRAWING NUMBER WHERE SHOWN

SECTION LETTER

TYPICAL FIXTURE NUMBER

DRAWING NUMBER WHERE DRAWN

DRAWING SYMBOLS

NEW FIXTURE/EQUIPMENT (SHAPE VARIES, REF: SYMBOLS,

TAGS, & NOTES. SCHEDULED ITEMS ARE NEW UNO)

(E) EXISTING COMPONENT

(X) DEMOLISHED COMPONENT

26-SF 3

TYPICAL EQUIPMENT NUMBER

## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF PQ

SHEET SERIES FOR CONNECTION SCHEDULE

PLUMBING GENERAL NOTES

A. PIPING IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED IN A FURRED

CHASE OR ABOVE THE CEILING. REF SPECIFICATION 22 05 11.

B. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH

SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS

FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.

COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF

SPECIFICATION 08 31 13.

C. PROVIDE ACOUSTICAL SEALANT PER SPECIFICATION 07 92 00 AT PIPE

PENETRATIONS THROUGH SOUND RATED PARTITIONS.

D. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS

FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME

AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING

UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF

SPECIFICATION 01 33 23 AND 22 05 11.

GENERAL NOTES

A. PROVIDE TEMPORARY CONSTRUCTION PARTITIONS AND INFECTION

CONTROL BARRIERS AS APPLICABLE AROUND THE PROJECT AREA

CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY

THE VHA. REFER TO SPECIFICATION 01 35 26.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

8:

A M

P-001

PLUMBING ABBREVIATIONS,

SYMBOLS, & LEGENDS

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

A

A/E ARCHITECT/ENGINEER

AD AREA DRAIN/ACCESS DOOR

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AG AIR GAP

AS AUTOMATIC SPRINKLER

ASD ADJUSTABLE SPEED DRIVES

ASD AUTOMATIC SPRINKLER DRAIN

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION,

AND AIR CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANCIAL ENGINEERS

ASPE AMERICAN SOCIETY OF PLUMBING ENGINEERS

AV ACID VENT

AW ACID WASTE

B

BAS BUILDING AUTOMATION SYSTEM

BFP REDUCED PRESSURE BACKFLOW PREVENTER

BHP BREAK HORSEPOWER

BOD BASIS OF DESIGN

BSP BLACK STEEL PIPE

BT BATHTUB

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

C

CA COMPRESSED AIR

CFM CUBIC FEET PER MINUTE

CGA COMPRESSED GAS ASSOCATION

CI CAST IRON

CO CLEANOUT

COMP COMPRESSOR

CRP CORROSION RESISTANT PIPE

CS CLINICAL SINK

CV CONTROL VALVE

D

DCW DOMESTIC COLD WATER

DEMO DEMOLISH

DFU DRAINAGE FIXTURE UNITS

DHW DOMESTIC HOT WATER

DHWR DOMESTIC HOT WATER RETURN

DI DEIONIZED WATER

DIV DIVISION

DN DOWN

DOE DEPARTMENT OF ENERGY

DS DOWNSPOUT

DW DISHWASHER

DWG DRAWING

DWH DOMESTIC WATER HEATER

DWR DRINKING WATER RETURN

DWS DRINKING WATER SUPPLY

DWV DRAIN WASTE VENT

E

EL ELEVATION

EMCS ENERGY MANAGEMENT CONTROL SYSTEM

EPA ENVIRONMENTAL PROTECTION AGENCY

EPACT ENERGY POLICY ACT

ESC ESCUTCHEON

ESH EMERGENCY SHOWER

ET EXPANSION TANK

EWC ELECTRIC WATER COOLER

EWH ELECTRIC WATER HEATER

EWS EYE WASH STATION

EWS/SH EYE WASH/DRENCH SHOWER

EX EXISTING

F

F FARENHEIT

FCO FLOOR CLEANOUT

FCW FILTERED COLD WATER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT (HOSE) CONNECTION

FM FLOW METER

FOP FUEL OIL PUMP

FOR FUEL OIL RETURN

FOS FUEL OIL SUPPLY

FOV FUEL OIL VENT

FS FLOOR SINK

FS FLOW SWITCH

FU FIXTURE UNITS

G

GAL GALLON

GCO GRADE CLEANOUT

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GRS GAS REGULATOR STATION

GT GREASE TRAP

GVTR GAS VENT THROUGH ROOF

GWB GYPSUM WALL BOARD

PLUMBING ABBREVIATIONS

GWH GAS FIRED WATER HEATER

H

HB HOSE BIB

HD HUB DRAIN

HP HORSEPOWER

HR HR

HS HAND SINK

HST HOT WATER STORAGE TANK (DOMESTIC)

HWB HOT WATER BOILER

HWCP HOT WATER CIRCULATING PUMP

HWP HOT WATER PUMP

HX HEAT EXCHANGER

HYD HYDRANT

I

ICW INDUSTRIAL COLD WATER

ID INSIDE DIAMETER

IE INVERT ELEVATION

IHW INDUSTRIAL HOT WATER

INV INVERT

IPC INTERNATIONAL PLUMBING CODE

IRW IRRIGATION WATER

IW INDIRECT WASTE

IWH INSTANTANEOUS WATER HEATER

IWR INDUSTRIAL WATER RETURN

IWS INDUSTRIAL WATER SUPPLY

K

KW KILOWATT

KWH KILOWATT-HOUR

L

LA LABORATORY AIR

LAV LAVATORY

LB POUND

LCW LABORATORY COLD WATER

LHW LABORATORY HOT WATER

LNG LIQUID NATURAL GAS

LOX LIQUID OXYGEN

LV LABORATORY VACUUM

LW LOW WATER

M

M METER

MA MEDICAL AIR

MAV MANUAL AIR VENT

MBH 1000 BTUH

MED MEDICAL

MER MECHANICAL EQUIPMENT ROOM

MFR MANUFACTURER

MH MANHOLE

MOU MEMORANDUM OF UNDERSTANDING

MSB MOP SERVICE BASIN

MV MEDICAL VACUUM

N

N2 NITROGEN

N2O NITROUS OXIDE

NC NORMALLY CLOSED

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NORMALLY OPEN

NOM NOMINAL

NPS NOMINAL PIPE SIZE

NPW NON POTABLE WATER

NTS NOT TO SCALE

O

O2 OXYGEN

OC ON CENTER

OD OUTSIDE DIAMETER

OFD OVERFLOW DRAIN

OH OVER HEAD

OR OPERATING ROOM

OVFL OVERFLOW

P

P&ID PROCESS & INSTRUMENTATION DIAGRAM

PB PUSH BUTTON

PD PRESSURE DROP OR DIFFERENCE

PDI PLUMBING AND DRAINAGE INSTITUTE

PG PRESSURE GAUGE

PH PHASE

PLBG PLUMBING

PLUM PLUMBING

PP PLUMBING PUMP

PPM PARTS PER MILLION

PRS PRESSURE REDUCING STATION

PRV PRESSURE REDUCING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH ABSOLUTE

PSIG POUNDS PER SQUARE INCH GAGE

PTRV PRESSURE TEMPERATURE RELIEF VALVE

PW POTABLE WATER

R

RD ROOF DRAIN

RDL ROOF DRAIN LEADER

REF REFERENCE OR REFER TO

RH ROOF HYDRANT

RL ROOF LEADER

RO REVERSE OSMOSIS WATER

RP RECIRCULATION PUMP

RPZA REDUCED PRESSURE BACKFLOW PREVENTION

ASSEMBLY

RW REAGENT WATER

RWL RAIN WATER LEADER

RWR REAGENT WATER RETURN

S

SAN SANITARY SEWER

SCFM STANDARD CUBIC FEET PER MINUTE

SCW SOFTENED COLD WATER

SDMH STORM DRAIN MANHOLE

SIM SIMILAR

SMACNA SHEET METAL AND AIR CONDITIONING

CONTRACTORS NATIONAL ASSOCATION

SMH SANITARY MANHOLE

SP SUMP PUMP

SPR SPRINKLER LINE

SQFT/SF SQUARE FEET

SS SANITARY SEWER

SST STAINLESS STEEL

ST STORAGE TANK

SW STORM WATER

T

TCV TEMPERATURE CONTROL VALVE

TD TEMPERATURE DIFFERENCE

TD TRENCH DRAIN

TDH TOTAL DYNAMIC HEAD

TEMP TEMPERATURE

TMV THERMOSTATIC MIXING VALVE

TP TRAP PRIMER

TSTAT THERMOSTAT

TWR TEMPERED WATER RETURN

TWS TEMPERED WATER SUPPLY

TYP TYPICAL

U

UF UNDER FLOOR

UNO UNLESS NOTED OTHERWISE

UR URINAL

V

V VENT

VAC VACUUM OR VOLTAGE (AC)

VB VACUUM BREAKER

VCO VACUUM CLEANER OUTLET

VP VACUUM PUMP

VS VENT STACK

VSD VARIABLE SPEED DRIVE

VTR VENT THROUGH ROOF

W

W WASTE

WC WATER CLOSET

WCO WALL CLEANOUT

WG WATER GAGE

WH WALL HYDRANT

WH WATER HEATER

WHA WATER HAMMER ARRESTER

WL WATER LINE

WM WATER METER

WPD WATER PRESSURE DROP

WS WASTE STACK

WSFU WATER SUPPLY FIXTURE UNITS

X

XP EXPLOSION PROOF

Y

YCO YARD CLEANOUT

YH YARD HYDRANT

Number: Revision: Date:

0 100% CONSTRUCTION DOCUMENTS 12/08/2023

STEAM SUPPLY

PRV WHERE REQUIRED

(REF SCHEDULE)

VACUUM

BREAKER

(TYP)

ST-DS ASSEMBLY

(TYP)

DCW

LPR OUT (TYP)

DHWR

DHWR PUMP

NOTE 5

DHW

ET

ROUTE BYPASS

TO DRAIN

DIGITAL WATER

TEMPERATURE CONTROL

VALVE

TEMPORARY

CONNECTION

1.

2.

3.

4.

GENERAL NOTES:

THIN LINEWEIGHT PIPING AND COMPONENTS ARE FACTORY PRE-PIPED WITH WATER HEATER.

FIELD-PROVIDE THICK LINEWEIGHT PIPING AND COMPONENTS. CONNECT TO WATER HEATER

PACKAGE FACTORY CONNECTIONS.

COORDINATE WITH WATER HEATER MFR AND FIELD-PROVIDE COMPONENTS NOT FACTORY-

PROVIDED BY OTHER THAN BASIS OF DESIGN.

PROVIDE 120V POWER FOR DIGITAL WATER TEMPERATURE CONTROL VALVE AND STEAM

CONTROL VALVES. COORDINATE WITH MFR FOR REQUIREMENTS.

STEAM DOMESTIC

WATER HEATER (TYP)

STEAM CONTROL

VALVE (TYP)

5. REDUNDANT PUMP NOT SHOWN FOR CLARITY.

TO

REDUNDANT

DWHR PUMP

AV

AV

A. FOR ALL SCHEDULED EQUIPMENT, PROVIDE BASIS OF DESIGN OR APPROVED

EQUAL. REFER TO SPECIFICATIONS 01 33 23 AND 22 05 11 FOR FURTHER

REQUIREMENTS.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTIONS 22 40 00 AND 22 13 00.

2. FIXTURES SHALL BE ACCESSIBLE

UNO. REFER TO GENERAL AND

ARCH PLANS FOR REQUIREMENTS.

3. PROVIDE LEGIONELLA WATER

FILTER.

4. PROVIDE FD-D, SQUARE FACE

MATCHING FAUCET COLOR.

REMARKS:

1. REFER ALSO TO SPECIFICATIONS:

A. 22 11 23 FOR DCW & DHW

PUMPS.

B. 22 13 29 FOR SW PUMPS.

C. 22 14 29 FOR SUMP PUMPS.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 22 35 00

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 22 15 00.

2. PROVIDE COMPRESSED AIR

CONDENSATE OIL/WATER

SEPARATOR CAPABLE OF

REDUCING CONDENSATE OIL

CONTENT TO AT MOST 40 PARTS

PER MILLION.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PQ601

EQUIPMENT & FIXTURE

SCHEDULES

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

PLUMBING FIXTURE SCHEDULE

MARK DESCRIPTION

DCW

CONNECTION

(NPS)

DHW

CONNECTION

(NPS)

SS

CONNECTION

(NPS)

VENT

CONNECTION

(NPS) REMARKS

FD-D3 FLOOR DRAIN, 6" FOR MEMBRANE FLOOR - - 3 1 1/2 <varies>

FD-E FLOOR DRAIN, 9" FOR VINYL FLOOR - - 3 1 1/2 1, 2

FD-M3 FLOOR DRAIN, 7" WITH HUB FUNNEL - - 3 1 1/2 1

P-103 WC, WALL MOUNT, FLUSH VALVE 1 - 4 2 1, 2

P-201 UR, WALL MOUNT, NON-ACCESSIBLE 3/4 - 2 1 1/2 1, 2

P-417 1 COMPARTMENT SINK, WALL HUNG 1/2 1/2 3 1 1/2 1, 2

P-501 1 COMPARTMENT SINK, WALL HUNG 1/2 1/2 3 1 1/2 1, 2

P-502 MOP SERVICE SINK, FLOOR MOUNT 1/2 1/2 3 1 1/2 1, 2

P-516 SINK, 1 COMPARTMENT, CRS 1/2 1/2 1-1/2 1 1/2 1, 2

P-524 SINK, 2 COMPARTMENT, COUNTER MOUNT 1/2 1/2 1-1/2 1 1/2 1, 2

P-609 EWC, DUAL HEIGHT, RECESSED REFRIGERATION 1/2 - 1 1/2 1 1/2 1, 2

P-701 SHOWER BATH FIXTURE, DETACHABLE HOSE SPRAY 1/2 1/2 2 1 1/2 1, 2, 3, 4

P-708 EMERGENCY EYE AND FACE WASH, WALL MOUNT 3/4 3/4 - - 1, 2

P-801 WALL HYDRANT, NON-FREEZE, DETACHABLE T-HANDLE 1/2 - - - 1,2

P-812 WATER SUPPLY OUTLET BOX 1/2 - - - 1, 2

PLUMBING PUMP (PP) SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED SYSTEM PUMP TYPE FLUID GPM

HEAD

(FT WG)

FLUID

TEMP

(°F)

MIN %

EFF

ELECTRICAL/MOTOR DATA

BOD MFR AND

MODEL

REMARKSHP VAC PH

MAX

RPM CONTROL

17-PP-1 BASEMENT BLDG 17 DHW RECIRCULATION INLINE WATER 10.5 6.8 140 45 1 1/2 208 3 1800 VSD

BELL & GOSSETT

PD40

17-PP-2 BASEMENT BLDG 17 DHW RECIRCULATION INLINE WATER 10.5 6.8 140 45 1 1/2 208 3 1800 VSD

BELL & GOSSETT

PD40

17-SP-1 BASEMENT BLDG 17 SUMP INLINE WATER 61 25 140 45 3/4 208 3 1800 AUTOMATIC BOESCH BC 1

STEAM DOMESTIC WATER HEATER (SDWH) SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

FLOW (GPM)

TEMPERATU

RE RISE (F)

STEAM PRESSURE (PSIG)

STEAM

LB/HR

STEAM

TRAP MARK

ELECTRICAL DATA

BASIS OF

DESIGN

REMARKS

ENTERING

CONTROL

VALVE

ENTERING

HX VAC PH MCA MOCP

17-SDWH-1 BASEMENT BLDG 17 44 80 15 10 1846 ST-3 120 1 1 15

ARMSTRONG

535PP-PR

AIR COMPRESSOR (COMP) SCHEDULE

MARK LOCATION SYSTEM SCFM

OUTLET

PRESSURE

(PSIG)

SETPOINT

DEADBAND

(PSIG)

RECEIVER SIZE

(GAL)

ELECTRICAL/MOTOR DATA

BOD MFR

AND MODEL

REMARKSHP VAC PH

17-COMP-1 BASEMENT

ENGINEERING

SHOPS

51 90 175 120 15 208 3

INGERSOLL

RAND

7100E15 1, 2

NTS

DUAL STEAM TO HOT WATER HEAT EXCHANGER

F8

A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

8"ø SS

4" ø

S S

4"ø SS 1"ø DHW

1"ø SS

2" ø

D C

W 1" ø D

H W

(E) 2"ø DCW

4" ø

S S

4" ø

S S

2"ø SS

2"ø SS

4"ø SS

4"ø SS

2"ø SS

4"ø SS

2" ø

V E

N T

4" ø

S S

3"ø SS

1/

2" ø

S S

3"ø SS

2"ø DHW

1" ø

D H

W

1" ø

D H

W

1" ø

D H

W

WH-1

WH-3

WH-2

WH-4

/F1 PD111/F1 PD111

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

8:

A M

PD110

DEMOLITION PLANS - BASEMENT

NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION PLANS - BASEMENT NORTH

F1

1. DEMOLISH EXISTING WATER HEATERS AND ASSOCIATED PLUMBING PIPING

TYP.

2. REFER TO CIVIL SHEETS FOR DCW CONTINUATION.

3. EXISTING PLUMBING PIPING EXTENDS THROUGHOUT CRAWLSPACE.

CONTRACTOR SHALL REMOVE PIPING FROM THIS POINT TO FIXTURES ON

THE FLOOR ABOVE.

4. PLUMBING PIPING LOCATED IN CRAWLSPACE.

A

B

C

D

21 3 4 5 6 7 8 9 10 11 12

A'

1' 2' 3' 4'

A''

1"ø DHW

2"ø DCW

2" ø

D C

W

(E) 6"ø SD

3/4"ø DHW

2"ø DCW

3/ 4" ø D

H W

3/ 4" ø D

H W

3/ 4" ø D

C W

2" ø

S S

4"ø SS4"ø SS

/F1 PD110 /F1 PD110

2 2

A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

8:

A M

PD111

DEMOLITION PLANS - BASEMENT

SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION PLANS - BASEMENT - SOUTH

F1

1. DEMOLISH PLUMBING FIXTURE AND ALL ASSOCIATED PLUMBING BACK TO

MAIN.

2. EXISTING PLUMBING PIPING EXTENDS THROUGHOUT CRAWLSPACE.

CONTRACTOR SHALL REMOVE PIPING FROM THIS POINT TO FIXTURES ON

THE FLOOR ABOVE.

3. CAP 4" SANITARY SEWER TO EXISTING RESTROOMS AT TEE.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

/F1 PD113 /F1 PD113

4"ø VENT 4"ø SS 4"ø SS

4"ø VENT

1"ø DHW

1"ø SS

1"ø SS1

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

8:

A M

PD112

DEMOLITION PLANS - LEVEL 1

NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

1. DEMOLISH PLUMBING FIXTURES AND ASSOCIATED PLUMBING BACK TO

ACTIVE MAIN.

3/16" = 1'-0"

DEMOLITION PLANS - LEVEL 1 - NORTH

F1

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF PENETRATIONS NOT

REPLACED IN KIND. MATCH AESTHETICS AND LIFE SAFETY RATINGS OF THE

SURROUNDING CONSTRUCTION. ENGAGE LICENSED AND SITE-APPROVED

ROOFING CONTRACTOR TO PATCH AND SEAL WHERE ITEMS ARE REMOVED

THROUGH THE EXISTING ROOF. MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES AT LIMITS OF DEMOLITION. CAP ENDS WHERE

NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL REMAIN IN

SERVICE FOLLOWING DEMOLITION.

H. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

I. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

A

B

C

D

21 3 4 5 6 7 8 9 10 11 12

A'

1' 2' 3' 4'

A''

/F1 PD112 /F1 PD112

2" ø

V E

N T

2"ø SS

3/4"ø DHW

2"ø DCW

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PD113

DEMOLITION PLANS - LEVEL 1

SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION PLANS - LEVEL 1 - SOUTH

F1

1. DEMOLISH PLUMBING FIXTURE AND ALL ASSOCIATED PLUMBING BACK TO

MAIN.

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

17-SP-1

1/

2" ø

D H

W

3" ø

D C

W

2"ø DCW

2"ø DCW

2" ø

D C

W

1"ø DHWR

1" ø

D C

W

1"ø DCW

/F1 PP111 /F1 PP111

1/2"ø DCW

A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PP110

DOMESTIC WATER PLANS -

BASEMENT NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

1. CONNECT TO EXISTING DCW PLUMBING FROM MAIN. PLUMBING SHOWN

EXTERIOR TO THE BUILDING IS FOR REFERENCE.

2. EXTERIOR HOSE BIBB WATER SERVICE.

3. PLUMBING PIPING LOCATED IN CRAWLSPACE.

4. PROVIDE SUMP PUMP. REFER TO SPECIFICATION 22 14 29 AND MQ SERIES

SHEETS.

5. PROVIDE BACKFLOW PREVENTERS IN PLUMBING PIPING WHERE REQUIRED

IN SPECIFICATION 22 05 23.

3/16" = 1'-0"

DOMESTIC PLANS - BASEMENT - NORTH

F1

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

A

B

C

D

21 3 4 5 6 7 8 9 10 11 12

A'

1' 2' 3' 4'

A''

17-SDWH-1

17-PP-1

17-PP-2

2" ø

D C

W

3/4"ø DHWR 1 1/4"ø DHW 1 1/2"ø DCW

BASEMENT

MECHANICAL

3/4"ø DHWR

1 1/4"ø DHW

1 1/2"ø DCW

1 1/4"ø DCW 1 1/4"ø DHW

2"ø DCW1 1/2"ø DHW

1 1/4"ø DCW

/F1 PP110 /F1 PP110

1"ø DCW

1"ø DCW

1"ø DHWR

1/2"ø DCW

1/2"ø DCW

1/2"ø DCW

1" ø

D H

W R

1 1/4"ø CA

17-COMP-1

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PP111

DOMESTIC WATER PLANS -

BASEMENT SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DOMESTIC PLANS - BASEMENT - SOUTH

F1

1. EXTERIOR HOSE BIBB WATER SERVICE.

2. ALSO REFER TO DETAIL ON PQ SERIES SHEETS.

3. PROVIDE DCW MAKE UP WITH BACKFLOW PREVENTER TO MECHANICAL

SYSTEMS. REFER TO MECHANICAL.

4. PROVIDE AUTOMATIC FLOW CONTROL DEVICE.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

OPEN OFFICE

OFFICE

OFFICE

WAITING

WEST ENTRY

CONFERENCE ROOM

OFFICE

OFFICE

OFFICE

INTERIOR DESIGN

OFFICE

OFFICE124

WAITING

LOCKSMITH

LOCKSMITH

OFFICE

OFFICE

OFFICE

RECEPTION

VISITOR TOILET

OFFICE

CONFERENCE ROOM

RECEPTION

C04

CORRIDOR

C01

CORRIDOR

C01

CORRIDOR

C03A

CORRIDOR

PLAN ROOM

BREAK / TRAINING

ROOM

IT ROOM

STORAGE

HAC

OFFICE

STAFF TOILET

ELECTRICAL

STORAGE

BREAK ROOM

WOMENS TOILET

MENS TOILET

C06

CORRIDOR

136B

MENS SHOWER

C02

CORRIDOR

P-103

P-103

P-501 P-103

P-103

P-501

P-502

P-502

P-524

136A

MENS LOCKERS

P-417

P-417

P-701 P-103

INTERIOR DESIGN

LIBRARY

HAC

2"ø DHW

112A

ENGINEERING

TECHNICIAN OFFICE

KITCHEN

132A

ENTRYWAY

132B

ENTRYWAY

135B

WOMENS SHOWER

C05B

CORRIDOR

ELECTRICAL ROOM

P-103

P-417

P-417

3/ 4" ø D

C W

P-609

P-201 P-201 P-201

P-609

1 1/4"ø DHW

C03C

CORRIDOR

C03B

CORRIDOR

P-524

P-201

135A

WOMENS LOCKERS

1" ø

D H

W R

2 1/2"ø DCW

3/4"ø DHW 1 1/2"ø DCW

1 1/2"ø DCW

1 1/2"ø DHW 2"ø DCW

1"ø DHWR 1 1/2"ø DHW

2"ø DCW

1 1/2"ø DCW

1"ø DCW

1"ø DCW

3/4"ø DHW

1 1/4"ø DCW

1/

4" ø

D C

W

P-801

P-801

P-801

/F1 PP113 /F1 PP113

P-812

P-812

FD-M3

FD-M3

P-812

P-801

P-801

TYP

FD-D3

FD-D3

FD-D3

1"ø DCW

1 1/4"ø DHW

P-701

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PP112

DOMESTIC WATER PLANS - LEVEL

1 NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DOMESTIC PLANS - LEVEL 1 - NORTH

F1

1. DHWR RISER DOWN TO BASEMENT.

2. 2 1/2" DCW AND 2" DHW RISER MAINS UP FROM BASEMENT.

3. PROVIDE BALL VALVE AND 3/8" NIPPLE, OR MANUFACTURER REQUIRED

SIZE, AND EXTEND TO ICE MACHINE, REFRIGERATOR, AND COFFEE

MAKERS.

4. PROVIDE NEW WATER HAMMER ARRESTOR FOR DCW. REFER TO PK

SERIES SHEET FOR DETAIL. SEE ARCHITECTURAL PLAN FOR ACCESS

PANEL AND FINISH.

5. PROVIDE THERMOSTATIC MIXING VALVE TO PLUMBING FIXTURES UTILIZING

DHW. REFER TO SPECIFICATION 22 05 23.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

A

B

C

D

21 3 4 5 6 7 8 9 10 11 12

A'

1' 2' 3' 4'

A''

PLAN ROOM

HVAC / PLUMBING

SHOP

RECEIVING

CARPENTRY SHOP

WELDING SHOP

148B

WELDING

FIRE RISER

148A

WELDING STORAGE

142A

OFFICE

144A

OFFICE

C05A

CORRIDOR

C05A

CORRIDOR

ELECTRICAL SHOP

142B

HVAC/PLUMBING

STORAGE

144B

CARPENTRY

STORAGE

P-708 P-516

P-516 P-516

P-708 P-801

P-801

P-801

/F1 PP112 /F1 PP112

P-801

FD-E

FD-E

1 1/4"ø CA

1/ 2" ø C

A

1 1/4"ø CA

1/ 2" ø C

A

1/ 2" ø C

A

1 1/4"ø CA

1 1/4"ø CA

1/ 2" ø C

A

1/ 2" ø C

A

1/ 2" ø C

A 1/

2" ø

C A

1/ 2" ø C

A

1 1/4"ø CA

1/2"ø CA

1/2"ø CA

1/2"ø CA

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PP113

DOMESTIC WATER PLANS - LEVEL

1 SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DOMESTIC PLANS - LEVEL 1 - SOUTH

F1

P-501

P-417

P-103

P-103

P-103

P-417

P-502

P-524

P-502

P-103

P-201

P-103

P-103

P-201

P-201 P-201

P-417

P-609 P-524

P-609

2" ø

D H

W 3" ø D

C W

2 1/2"ø DHW

3"ø DCW

2"ø DCW

2"ø DHW

2"ø DCW

1 1/2"ø DHW

1 1/2"ø DHW

1 1/2"ø DCW

3/4"ø DHW

1 1/4"ø DCW 1"ø DCW

1 1/4"ø DHW

2"ø DCW

P-417

1 1/2"ø DHW

2"ø DCW

1"ø DHWR

2"ø DHW

2 1/2"ø DCW

FD-E

P-516

P-708

P-516

FD-E

P-708

P-516

P-801

1" ø

D C

W

1"ø DCW

1"ø DCW

P-801

1/ 2" ø D

C W

1"ø DCW

P-801

1/ 2" ø D

C W

1 1/2"ø DCW3/4"ø DHWR 1 1/4"ø DHW

1 1/2"ø DCW

1 1/2"ø DCW

1"ø DHWR

1 1/2"ø DHW2"ø DCW

3/4"ø DHW

1"ø DCW

FD-D3

FD-M3

1"ø DCW

1 1/4"ø DCW

1 1/2"ø DCW

2"ø DCW

1"ø DCW 1 1/2"ø DCW

3/4"ø DHWR

1 1/4"ø DHW

P-801

P-701

P-801

P-701

FD-D3

P-812

FD-M3

P-812

P-812

P-801

FD-D3

P-801

(E) 2"ø DCW

17-SDWH-1

P-801

P-701

P-801

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PP601

DOMESTIC WATER RISER DIAGRAM CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

A. ISOMETRIC VIEWS ARE INTENDED TO DEPICT GENERAL 3-DIMENSIONAL

ARRANGMENT OF MAJOR MECHANICAL COMPONENTS FOR VISUAL

REFERENCE ONLY. NOT ALL ITEMS (EG PLUMBING, PIPING, ELECTRICAL,

STRUCTURAL, ETC) IN THE AREA MAY BE SHOWN. REFER TO PLAN VIEWS

FOR SIZES AND OTHER SCOPE DETAILS.

NTS

DOMESTIC WATER RISER DIAGRAM

F1

CONFERENCE ROOM

OFFICE

OFFICE

OFFICE

OFFICE

INTERIOR DESIGN

OFFICE

ELECTRICAL

STORAGE

BREAK ROOM

C06

CORRIDOR

WOMENS TOILET

MENS TOILET

PLAN ROOM

INTERIOR DESIGN

LIBRARY

VISITOR TOILET

RECEPTION

LOCKSMITH

OFFICE

OFFICE

OFFICE

OFFICE

C04

CORRIDOR

CONFERENCE ROOM

OPEN OFFICE

OFFICE

OFFICE

WAITING

WEST ENTRY

STAFF TOILET

C03A

CORRIDOR

BREAK / TRAINING

ROOM

STORAGE

IT ROOM

ELECTRICAL ROOM

C01

CORRIDOR

C01

CORRIDOR

136B

MENS SHOWER

WAITING

RECEPTION

OFFICE

HAC

P-501

P-502

P-524

P-103

P-103

136A

MENS LOCKERS

P-502

P-103

P-501

P-103

P-417

P-103

P-701

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

P-103 P-201 P-201

P-201

P-417

KITCHEN

132B

ENTRYWAY

135B

WOMENS SHOWER

112A

ENGINEERING

TECHNICIAN OFFICE

C02

CORRIDOR

C03B

CORRIDOR

C03C

CORRIDOR

C05B

CORRIDOR131

HAC

132A

ENTRYWAY

2"ø SS

4" ø

S S

4"ø SS

3" ø

S S

P-201

P-417 P-417 wco

P-609

2"ø VENT

2"ø VENT

1 1/2"ø VENT

3"ø VENT

1 1/2"ø VENT

2" ø

V E

N T

2"ø VENT 2"ø VENT

1/

2" ø

V E

N T

1/

2" ø

V E

N T

1/

2" ø

V E

N T

2" ø

V E

N T

P-609

2"ø VENT

P-524

3" ø

S S

1 1/2"ø SS 4"ø SS

4" ø

S S

4"ø SS

4"ø SS

3" ø

S S

FD-D3

3"ø SS

3" ø

S S

FD-D3

FD-D3

FD-D3

3" ø

S S

3" ø

S S

FD-M3

/F1 PW112 /F1 PW112

FD-M3

P-812

P-812

P-812

/F1 PW112

P-801

P-801

P-801 wco wco wco wco wco

P-801 wco wco wco wco wco

2" ø

S D

4"ø SD

6"ø SS

6"ø SD

FD-D3

FD-D3

P-701

2"ø VENT VTR

1 1/2"ø VENT VTR

3"ø VENT VTR

4" ø

S D

6" ø

S D

4"ø SD

4"ø SD

A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL

NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PW111

DRAIN-WASTE-VENT PLANS -

LEVEL 1 NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DRAIN-WASTE-VENT - LEVEL 1 - NORTH

F1

1. PROVIDE PRIME-EZE OR APPROVED EQUAL TRAP PRIMER AT LAVATORY

P-TRAPS. ROUTE 3/4" INDIRECT DRAIN PIPING TO ASSOCIATED FLOOR

DRAIN.

2. PROVIDE STORM DRAIN PLUMBING TO SUMP PUMP IN BASEMENT. REFER

TO PP SERIES SHEETS FOR SUMP PUMP LOCATION.

3. STORM AND SANITARY PLUMBING EXTERIOR TO THE BUILDING SHOWN

FOR REFERENCE. REFER TO CIVIL SHEETS FOR SS AND SD CONTINUATION.

4. PROVIDE VENT PIPING TO ROOF.

5. STORM DRAIN PIPING DOWN FROM ROOF. PROVIDE SD IN PIPE BASEMENT

FROM THIS LOCATION TO EXISTING LOCATION TIE. VIF, ASSUME

CONNECTION IS NEAR 6" SERVICE TO BUILDING.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

A

B

C

D

21 3 4 5 6 7 9 10 11 12

A'

1' 2' 3' 4'

A''

148B

WELDING

RECEIVING

HVAC / PLUMBING

SHOP

CARPENTRY SHOP

WELDING SHOP

148A

WELDING STORAGE

142B

HVAC/PLUMBING

STORAGE

144B

CARPENTRY

STORAGE

3"ø SS

3" ø S

S

P-516

P-708

3" ø

S S

P-516 P-708

3" ø

S S

1 1/2"ø VENT

FD-E

3" ø

S S

P-516

FD-E

P-801

3"ø SS

1 1/2"ø VENT

3" ø

S S

1 1/2"ø VENT

3"ø SS

1 1/2"ø VENT

/F1 PW111 /F1 PW111/F1 PW111

P-801

P-801

6"ø SD

144A

OFFICE

142A

OFFICE

FIRE RISER

PLAN ROOMC05A

CORRIDOR

ELECTRICAL SHOP

WCO

WCO

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PW112

DRAIN-WASTE-VENT PLANS -

LEVEL 1 SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DRAIN-WASTE-VENT - LEVEL 1 - SOUTH

F1

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:

a. DOMESTIC WATER

b. MED GAS

c. STORM DRAINAGE

d. VENTS

F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:

a. SANITARY SEWER

b. STORM DRAINAGE

G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND

PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.

H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

1 1/2"ø VENT VTR

2"ø VENT VTR

3"ø VENT VTR

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PW113

DRAIN-WASTE-VENT PLANS - ROOF

NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DRAIN-WASTE-VENT - ROOF NORTH

F1

1. EXISTING ROOF STORM DRAINS.

2. SANITARY VENT PIPING UP THROUGH ROOF.

P-502

P-524

P-103

P-103

P-502

P-103

P-103

P-609

P-103

P-103

P-201

P-201

P-201

P-524

P-609

P-201

P-417

P-417

P-417

P-417

4"ø SS

1 1/2"ø SS

4"ø SS

6"ø SS

4"ø SS

4"ø SS

2"ø SS

4"ø SS

3"ø SS

3"ø SS

3"ø VENT 1 1/2"ø VENT

3"ø SS

1 1/2"ø VENT

(E) 6"ø SS

(E) 6"ø SD

1 1/2"ø VENT

2"ø VENT

2" ø

V E

N T

V T

R

2"ø VENT

3" ø

V E

N T

V T

R

3"ø SS1 1/

2" ø

V E

N T

1/

2" ø

V E

N T

1/

2" ø

V E

N T

FD-E

P-708

P-516

FD-E

P-516

P-708

3"ø SS

FD-M3

3"ø SS

1/

2" ø

V E

N T

P-516

3"ø SS

3"ø SS

3"ø SS

3" ø

S S

3"ø SS

2"ø VENT

4"ø SS

1/

2" ø

V E

N T

2" ø

V E

N T

1/

2" ø

V E

N T

1/

2" ø

S S

3" ø

S S

1/

2" ø

V E

N T

3" ø

S S

FD-D3

FD-D3

1/

2" ø

S S

1/

2" ø

S S

1/

2" ø

V E

N T1

1/ 2" ø V

E N

T

FD-M3

FD-D3

FD-D3

3" ø

S S

3" ø

S S

2"ø VENT

1/

2" ø

V E

N T

3"ø SS

2" ø

V E

N T

2"ø VENT

2" ø

V E

N T

2" ø

V E

N T

3"ø SS

3"ø SS

1/

2" ø

V E

N T

2" ø

S S

1/

2" ø

S S

1/

2" ø

S S

2"ø VENT

1/

2" ø

V E

N T

1/

2" ø

S S

P-812

P-812

6"ø SD

6"ø SD

FD-D3

FD-D3

6"ø SD

4"ø SD

4"ø SD

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PW601

DRAIN-WASTE-VENT RISER

DIAGRAM

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

A. ISOMETRIC VIEWS ARE INTENDED TO DEPICT GENERAL 3-DIMENSIONAL

ARRANGMENT OF MAJOR MECHANICAL COMPONENTS FOR VISUAL

REFERENCE ONLY. NOT ALL ITEMS (EG PLUMBING, PIPING, ELECTRICAL,

STRUCTURAL, ETC) IN THE AREA MAY BE SHOWN. REFER TO PLAN VIEWS

FOR SIZES AND OTHER SCOPE DETAILS.

DRAIN-WASTE-VENT RISER DIAGRAM

F1

FAUCET SEE

SPECIFICATIONS

LAMINAR FLOW

CONTROL DEVICE

OFFSET

WASTE

TRAP

PARALLEL

TO WALL

LOOSE KEY STOP

ESCUTCHEON

FINISHED FLOOR

NOTE: PROVIDE COVER FOR EXPOSED PIPING

F O

R F

IX

T

U R

E H

E

IG

H T

S S

E E

R C

H

IT

E C

T U

R A

L D

R A

W

IN

G S

AA

WALL ANCHOR

STEEL WALL

PLATE

STUDS

SECTION A

FOR FIXTURE

HEIGHT SEE

ARCH DRAWINGS

STEEL HANGER

BY LAV MFGR

NOTE:

1. AT LAVS WITH FOOT PEDAL CONTROLS

PROVIDE AN ADDITIONAL 16 GAGE

GALVANIZED STEEL PLATE 12" x 16" SECURED

TO A MIN 2 STUDS PER FOOT PEDAL.

2. PROVIDE 20 GAGE STUDS WHEN HEIGHT

EXCEEDS 12'-0"

1/4" Ø MOLLY BOLT HOLLOW WALL

ANCHOR (1 EACH SIDE OF LAV)

PLAN

V A

R

IE

S

MIN 16 GAGE GALVANIZED

STEEL PLATE 12" x 48"

SECURED TO A MIN 4

STUDS PER LAVATORY

1/4"1/8"

TYP

MIN 5 1/4" Ø GALV

MACHINE BOLTS

WELDED TO PLATE

MIN (3) 1/4" MACHINE

BOLTS W/DOUBLE

LOCK NUTS ON

BACK SIDE

COMPRESSION

CHAMBER

A

J.R. SMITH

FIG. NO.

FIXTURE UNIT

RATING

A

SIZE

5005 1 - 11 3/4"

NOTES:

1. SELECT & INSTALL WATER HAMMER ARRESTORS PER PDH-WH 201, REFER TO 22 11 00.

2. INSTALL WATER HAMMER ARRESTORS AT END OF EACH BRANCH LINE BETWEEN LAST 2

FIXTURES SERVED.

3. INSTALL ADDITIONAL WATER HAMMER ARRESTOR IN BRANCH LINES EXCEEDING 20' IN

LENGTH.

4. INSTALL WATER HAMMER ARRESTORS IN UPRIGHT POSITION WITH GATE VALVE.

5. INSTALL MIN. 6"x 8" ACCESS PANEL. SEE ARCHITECTURAL SPECIFICAITON FOR FINISH.

B

SIZE

4"

1"

1"

1"

1"

1"

5"

6"

7"

8"

9"

12 - 32

33 - 60

61 - 113

114 - 154

155 - 330

SHELL

BELLOWS

B

3"ø

90°

PIPE NIPPLE

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

9:

A M

PK501

TYPICAL DETAILS CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

NTS

TYPICAL WHEELCHAIR LAVATORY DETAIL

F9

NTS

LAVATORY MOUNTING DETAIL

D9

NTS

TYPICAL WATER HAMMER ARRESTOR DETAIL

F7