PN 674A4-22-245_100ptc_VOL 2_23-12-07_FA.pdf
PDF 3 MB Posted
- Attached to
- 36C25726R0032_2 674A4-22-254 - CON CTX Consolidate Engineering Bldg. 17 Federal contract opportunity
- Solicitation number
- 36C25726R0032
About this file
These documents are 100% Construction Documents for the Consolidate Engineering Building 17 project at the Doris Miller Department of Veterans' Medical Center in Waco, Texas, with VA Project Number 674A4-22-254. The documents focus specifically on fire alarm and fire suppression system plans for a building renovation, covering basement, level 1, and attic spaces.
The fire protection scope involves modifying the existing fire alarm system to accommodate new ceiling and wall layouts, with the contractor required to verify the existing Fire Alarm Control Panel (FACP) has sufficient capacity for new points. The fire suppression system will involve demolishing existing mains and branches on the first floor and installing a new NFPA-compliant system. The project follows multiple codes including VA Fire Protection Design Manual, NFPA 13, NFPA 72, NFPA 101, and the 2021 International Building Code. Notably, the attic is identified as combustible, requiring fire sprinkler protection that must be coordinated across disciplines to ensure an NFPA-compliant system.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25726R0032 0005.docx | DOCX document | |
| 36C25726R0032 0004_Consolidated Engineering Building 17.docx | DOCX document | |
| 36C25726R0032 0003.docx | DOCX document | |
| PN 674A4-22-245_100ptc_VOL 2_23-12-07_EL (1).pdf | ||
| 36C25726R0032 0002.docx | DOCX document | |
| PN 674A4-22-245_100ptc_VOL 2_23-12-07_MH.pdf | ||
| 36C25726R0032 0001.docx | DOCX document | |
| Site visit sign in sheet 25_12_30.pdf | ||
| PN 674A4-22-245_100ptc_VOL 2_23-12-07_PL.pdf | ||
| Attachment 4 Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| Attachment 3 09-16368 Waco Bldg. 17 Report.pdf | ||
| Attachment 2 Specs PN674A4-22-254_100ptc_SPECS_12-08.pdf | ||
| 36C25726R0032_2.docx | DOCX document | |
| Attachment 1 Drawings PN 674A4-22-245_100ptc_VOL 1_23-12-07.pdf |
Show all 14
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
N or th
AREA OF WORK
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_A
R C
H _R
_g de nt
9T P
JY
.r vt
/7 /2
2:
:2
P M
GI002
COVER - VOLUME 2 CONSOLIDATE ENGINEERING
BUILDING 17
4800 MEMORIAL DRIVE, WACO TX 76711
674A4-22-254
GDD CPR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
DORIS MILLER DEPARTMENT OF VETERANS' MEDICAL CENTER, CTVHCS
4800 MEMORIAL DRIVE, WACO TX 76711
VAMC PROJECT #: 674A4-22-254
CONSOLIDATE ENGINEERING BUILDING 17
SHEET INDEXRENDERED IMAGEAREA OF WORK
REFER TO VOLUME 1 FOR ADDITIONAL DISCIPLINES:
• GENERAL
• HAZARDOUS MATERIALS
• SURVEY
• CIVIL
• LANDSCAPE
• STRUCTURAL SLAB REPAIR
• STRUCTURAL
• ARCHITECTURAL
SHEET NUMBER SHEET NAME
GENERAL
GI002 COVER - VOLUME 2
FIRE PROTECTION
F-001 FIRE ALARM LEGENDS, NOTES, AND SYMBOLS
F-002 FIRE SUPPRESSION LEGENDS, NOTES, AND SYMBOLS
FA110 FIRE ALARM PLANS - BASEMENT - NORTH
FA111 FIRE ALARM PLANS - BASEMENT - SOUTH
FA112 FIRE ALARM PLANS - LEVEL 1 - NORTH
FA113 FIRE ALARM PLANS - LEVEL 1 - SOUTH
FX120 FIRE SUPPRESSION PLANS - BASEMENT - NORTH
FX121 FIRE SUPPRESSION PLANS - BASEMENT - SOUTH
FX122 FIRE SUPPRESSION PLANS - LEVEL 1 - NORTH
FX123 FIRE SUPPRESSION PLANS - LEVEL 1 - SOUTH
FX124 FIRE SUPPRESSION PLANS - ATTIC - NORTH
FX125 FIRE SUPPRESSION PLANS - ATTIC - SOUTH
PLUMBING
P-001 PLUMBING ABBREVIATIONS, SYMBOLS, & LEGENDS
PQ601 EQUIPMENT & FIXTURE SCHEDULES
PD110 DEMOLITION PLANS - BASEMENT NORTH
PD111 DEMOLITION PLANS - BASEMENT SOUTH
PD112 DEMOLITION PLANS - LEVEL 1 NORTH
PD113 DEMOLITION PLANS - LEVEL 1 SOUTH
PP110 DOMESTIC WATER PLANS - BASEMENT NORTH
PP111 DOMESTIC WATER PLANS - BASEMENT SOUTH
PP112 DOMESTIC WATER PLANS - LEVEL 1 NORTH
PP113 DOMESTIC WATER PLANS - LEVEL 1 SOUTH
PP601 DOMESTIC WATER RISER DIAGRAM
PW111 DRAIN-WASTE-VENT PLANS - LEVEL 1 NORTH
PW112 DRAIN-WASTE-VENT PLANS - LEVEL 1 SOUTH
PW113 DRAIN-WASTE-VENT PLANS - ROOF NORTH
PW601 DRAIN-WASTE-VENT RISER DIAGRAM
PK501 TYPICAL DETAILS
MECHANICAL
M-001 MECHANICAL ABBREVIATIONS & NOTES
M-002 MECHANICAL SYMBOLS
MQ601 EQUIPMENT SCHEDULES
MQ602 EQUIPMENT SCHEDULES
MD110 DEMOLITION PLANS - BASEMENT NORTH
MD111 DEMOLITION PLANS - BASEMENT SOUTH
MD112 DEMOLITION PLANS - LEVEL 1 NORTH
MD113 DEMOLITION PLANS - LEVEL 1 SOUTH
MD114 DEMOLITION PLANS - ROOF NORTH
MH110 HVAC PLANS - BASEMENT
MH111 HVAC PLANS - LEVEL 1 NORTH
MH112 HVAC PLANS - LEVEL 1 SOUTH
MH113 HVAC PLANS - ROOF NORTH
MH601 HVAC FLOW DIAGRAM - SUPPLY AIR
MH602 HVAC FLOW DIAGRAM - RETURN AIR
MH603 HVAC FLOW DIAGRAM - EXHAUST AIR
MP110 PIPING PLANS - BASEMENT NORTH
MP111 PIPING PLANS - BASEMENT SOUTH
MP112 PIPING PLANS - LEVEL 1 NORTH
MP113 PIPING PLANS - LEVEL 1 SOUTH
MP114 PIPING PLANS - ROOF NORTH
MP601 PIPING RISER DIAGRAM
MI110 CONTROLS & INSTRUMENTATION PLANS - BASEMENT
MI111 CONTROLS & INSTRUMENTATION PLANS - LEVEL 1 NORTH
MI112 CONTROLS & INSTRUMENTATION PLANS - LEVEL 1 SOUTH
MI113 CONTROLS & INSTRUMENTATION PLANS - ROOF NORTH
MI601 CONTROL DIAGRAMS
MI602 CONTROL DIAGRAM
MI603 CONTROL DIAGRAM
MK501 TYPICAL DETAILS
MK502 TYPICAL DETAILS
MK503 TYPICAL DETAILS
SHEET NUMBER SHEET NAME
MK504 TYPICAL DETAILS
MK505 TYPICAL DETAILS
ELECTRICAL
E-001 ELECTRICAL ABBREVIATIONS AND GENERAL NOTES
E-002 ELECTRICAL SYMBOLS
ED110 DEMOLITION PLAN - BASEMENT
ED111 DEMOLITION PLAN - LEVEL 1
ED113 DEMOLITION PLAN - ROOF
ED121 DEMOLITION RCP - LEVEL 1
EL111 LIGHTING & LIGHTING CONTROLS RCP - ROOF AND BASEMENT
EL112 LIGHTING RCP PLAN - LEVEL 1 NORTH
EL113 LIGHTING RCP PLAN - LEVEL 1 SOUTH
EL122 LIGHTING CONTROLS RCP PLAN - LEVEL 1 NORTH
EL123 LIGHTING CONTROLS RCP PLAN - LEVEL 1 SOUTH
EL601 LIGHTING SCHEDULES
EL602 LIGHTING CONTROL WIRING DIAGRAMS
EP110 POWER PLAN - BASEMENT
EP111 POWER PLAN - NORTH - LEVEL 1
EP112 POWER PLAN - SOUTH - LEVEL 1
EP113 POWER PLAN - ROOF
EP601 POWER ONE-LINE DIAGRAM
EP602 PANEL SCHEDULES
EP603 PANEL SCHEDULES
ET111 TELECOM PLAN - NORTH - LEVEL 1
ET112 TELECOM PLAN - SOUTH - LEVEL 1
ET211 SECURITY PLAN - NORTH - LEVEL 1
ET212 SECURITY PLAN - SOUTH - LEVEL 1
ET411 TELECOMMUNICATIONS ENLARGED PLANS
EK501 TYPICAL DETAILS
EK502 TYPICAL DETAILS
EK503 TYPICAL DETAILS
Number: Revision: Date:
0 100% CONSTRUCTION DOCUMENTS 12/08/2023
FACP
F
NAC#
VS
WF
FACP
F NAC#VS WF
NAC#F VS WF
DEVICE TYPESYMBOL
FIRE ALARM SYMBOL LEGEND
FIRE ALARM CONTROL PANEL
SPEAKER STROBE
PULL STATION
NOTIFICATION APPLIANCE CIRCUIT
TAMPER SWITCH
FLOW SWITCH
BUILDING ZONE
BUILDING ZONE
A. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
B. FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER PROJECT SPECIFICATION
AND THE MANUFACTURER'S INSTRUCTIONS.
C. INITIATING DEVICES SHALL BE FIELD LOCATED BASED UPON THE LOCATION
OF DIFFUSERS, LIGHTS, AND OTHER POTENTIAL OBSTRUCTIONS.
D. ALL WIRING INSTALLATION SHALL CONFORM TO THE PROJECT
SPECIFICATIONS.
E. IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO RETURN WIRES
TO THE PANEL FREE OF OPENS, GROUNDS, SHORTS AND/OR OTHER
CONDITION THAT MAY PREVENT THE PROPER OPERATION OF THE FIRE
ALARM SYSTEM.
F. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON FIRE PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
G. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
H. THE BIDDING CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH THE
COMPLEXITIES OF THIS BUILDING. THESE DRAWINGS ARE DIAGRAMMATIC
ONLY. THE AWARDED CONTRACTOR SHALL BE RESPONSIBLE FOR
PRODUCTION OF DESIGN AND SUBMITTAL DOCUMENTS AND OBTAINING
REQUIRED INFORMATION FOR APPROVALS
I. RISER DIAGRAMS ARE CONCEPTUAL IN NATURE AND ARE NOT INTENDED TO
SHOW A COMPLETE SYSTEM. THE CONTRACTOR SHALL EXPAND ON THE
CONCEPTUAL RISER DIAGRAM FOR A COMPLETE SYSTEM.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
F-001
FIRE ALARM LEGENDS, NOTES,
AND SYMBOLS
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
FIRE ALARM PROJECT SCOPE NARRATIVE
THE FIRE ALARM SCOPE OF THIS PROJECT IS TO MODIFY THE EXISTING FIRE ALARM
SYSTEM TO ACCOMMODATE THE NEW CEILING AND WALL LAYOUTS IN THE AREAS
OUTLINED IN THIS BID PACKAGE.
IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE EXISTING FACP HAS
ENOUGH AVAILABLE CAPACITY TO SUPPORT ANY NEW POINTS REQUIRED.
APPLICABLE CODES & STANDARDS
VA FIRE PROTECTION DESIGN MANUAL (8TH EDITION - 06.01.21)
NFPA 13 - 2019 (OR MOST RECENT)
NFPA 72 - 2019 (OR MOST RECENT)
NFPA 101 - 2021 (OR MOST RECENT)
INTERNATIONAL BUILDING CODE - 2021
1/16" = 1'-0"
ALARM ZONE PLANS - LEVEL 1
11/16" = 1'-0"
ALARM ZONE PLANS - BASEMENT
FIRE ALARM ZONES ARE TO MATCH THE
SMOKE ZONES PER THE VA FIRE
PROTECTION DESIGN MANUAL
FIRE ALARM ZONES ARE TO MATCH THE
SMOKE ZONES PER THE VA FIRE
PROTECTION DESIGN MANUAL
FIRE ALARM RISER
Number: Revision: Date:
FIRE ALARM MATRIX NOTE: HVAC INTAGRATIONS ARE NOT SHOWN ON MATRIX AND ANY REQUIRED DUCT DETECTORS OR HVAC SYSTEM SHUTOFFS SHALL BE COORDINATED WITH MECHANICAL AND THE MATRIX SHALL BE UPDATED ACCORDINGLY.
UPRIGHT FIRE SPRINKLER
DEVICE TYPESYMBOL
PENDANT FIRE SPRINKLER
DRY SIDEWALL FIRE SPRINKLER
FIRE SPRINKLER SYMBOL LEGEND
A. THE FIRE PROTECTION SCOPE OF THIS PROJECT SHALL BE A DELEGATED
DESIGN AND THE DOCUMENTS PROVIDED IN THIS BID PACKAGE ARE
INTENDED TO BE USED FOR SCHEMATIC PUPORSES ONLY. IT IS THE
RESPONSIBILITY OF THE CONTRACTOR TO PROVIDE A CODE COMPLIANT
DESIGN AND VERIFY COMPATIBILITY WITH EXISTING CONDITIONS. ANY
VARIANCE FROM THE GUIDANCE PROVIDED BY THE BID DOCUMENTS SHALL
BE ADDRESSED IN THE FORM OF A FORMAL RFI.
B. THE REQUIREMENTS OUTLINED IN THE PROJECT SPECIFICATIONS
SUPERCEDE ANY INFORMATION FOUND ON THE PROJECT DRAWINGS.
C. REFERENCE ARCHITECTURAL SHEETS FOR RCP.
ELEVATION VIEW
ARRANGEMENT SHOWN IS SCHEMATIC. MODIFY TO SUIT CONDITIONS AND MEET APPLICABLE
CODE REQUIREMENTS. COORDINATE INSTALLATION OF ALARM DEVICES WITH OTHER TRADES.
WATER PRESSURE GAUGE
FLOOR
WATERFLOW SWITCH
TO NEW WET SPRINKLER
SYSTEM. SPLIT INTO 2
ZONES TO FEED THE
DIFFERENT LEVELS.
CHECK
VALVE
MAIN DRAIN
ROUTED
THROUGH
FLOOR.
MAIN DRAIN AND TEST
ASSEMBLY
A B
O V
E F
IN
IS
H E
D F
L O
O R
M A
X
GATE
VALVE
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
F-002
FIRE SUPPRESSION LEGENDS,
NOTES, AND SYMBOLS
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
FIRE SPRINKLER PROJECT SCOPE NARRATIVE
THE FACILITY HAS AN EXISTING DECOMMISSIONED FIRE SPRINKLER SYSTEM. AS PART OF
THE SCOPE OF THIS PROJECT, MAINS, BRANCHES, AND SPRINKLER HEADS ON THE FIRST
FLOOR WILL BE DEMOLISHED BACK TO THE RISER. A NEW NFPA COMPLIANT SYSTEM WILL
BE INSTALLED FOR THE NEW FLOOR LAYOUT.
APPLICABLE CODES & STANDARDS
VA FIRE PROTECTION DESIGN MANUAL (8TH EDITION - 06.01.21)
NFPA 13 - 2019 (OR MOST RECENT)
NFPA 72 - 2019 (OR MOST RECENT)
NFPA 101 - 2021 (OR MOST RECENT)
INTERNATIONAL BUILDING CODE - 2021
HYDRAULIC INFORMATION
THE CONTRACTOR SHALL SCHEDULE A FLOW TEST TO VERIFY UNDERGROUND FLOW AND
PRESSURE. IT MAY BE ASSUMED THAT THE EXISTING FLOW AND PRESSURE IS SUFFICIENT
TO SUPPLY CHANGES TO THE DESIGN. A 10% SAFETY FACTOR SHALL BE APPLIED.
1/16" = 1'-0"
SPRINKLER ZONE PLANS - LEVEL 1
1/16" = 1'-0"
SPRINKLER ZONE PLANS - BASEMENT
FIRE SUPPRESSION ZONES ARE TO MATCH
THE SMOKE ZONES PER THE VA FIRE
PROTECTION DESIGN MANUAL
FIRE SUPPRESSION ZONES ARE TO MATCH
THE SMOKE ZONES PER THE VA FIRE
PROTECTION DESIGN MANUAL
Number: Revision: Date:
0 100% CONSTRUCTION DOCUMENTS 12/08/2023
12" = 1'-0"
EXISTING FIRE PROTECTION WET PIPE RISER
A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
b. STORM DRAINAGE
G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND
PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.
H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.
A
21 3 4 5 6 7 8 9 10 11 12
A'
B'
C'
D'
1' 2' 3' 4'
A''' A''
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FA110
FIRE ALARM PLANS - BASEMENT -
NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE ALARM PLANS - BASEMENT - NORTH
A. REFER TO P-001 FOR PLUMBING SYMBOLS, ABBREVIATIONS, AND GENERAL
NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI-SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
E. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS OH UNO:
a. DOMESTIC WATER
b. MED GAS
c. STORM DRAINAGE
d. VENTS
F. HORIZONTAL PIPING FOR THE FOLLOWING SYSTEMS IS UF UNO:
a. SANITARY SEWER
b. STORM DRAINAGE
G. MAINTAIN A MINIMUM 2' CLEARANCE OF PLUMBING EQUIPMENT AND
PLUMBING PIPING FROM INSTALLED CEILING MOUNTED OVERHEAD FANS.
H. REFER TO SPECIFICATION 22 05 23 FOR PLUMBING VALVES.
A
B
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
BASEMENT
MECHANICAL
BASEMENT SUMP
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FA111
FIRE ALARM PLANS - BASEMENT -
SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE ALARM PLANS - BASEMENT - SOUTH
F
FACP
A
21 3 4 5 6 7 8 9 10 11 12
A'
B'
C'
D'
1' 2' 3' 4'
A''' A''
OPEN OFFICE
OFFICE
OFFICE
OFFICE
WAITING
LOCKSMITH 107
RECEPTION
CONFERENCE ROOM
OFFICE
STAFF TOILET
OFFICE
INTERIOR DESIGN
LIBRARY
OFFICE
OFFICE
INTERIOR DESIGN
OFFICE
PLAN ROOM
VISITOR TOILET
OFFICE
CONFERENCE ROOM
OFFICE
OFFICE
OFFICE
RECEPTION
WAITING
HAC
BREAK / TRAINING
ROOM
C01
CORRIDOR
C04
CORRIDOR
C03A
CORRIDOR
ELECTRICAL
STORAGE
C06
CORRIDOR
BREAK ROOM
WOMENS TOILET
MENS TOILET
136B
MENS SHOWER
ELECTRICAL ROOM
STORAGE
IT ROOM
FIRE RISER
C02
CORRIDOR
NORTH ENTRY
ELECTRICAL SHOP
136A
MENS LOCKERS
C05A
CORRIDOR
HAC
KITCHEN
132B
ENTRYWAY
132A
ENTRYWAY
135B
WOMENS SHOWER
112A
ENGINEERING
TECHNICIAN OFFICE
C05B
CORRIDOR
134A
CHASE
C03B
CORRIDOR
C03C
CORRIDOR
135A
WOMENS LOCKERS
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FA112
FIRE ALARM PLANS - LEVEL 1 -
NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE ALARM PLANS - LEVEL 1 - NORTH
F
A
B
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
PLAN ROOM
HVAC / PLUMBING
SHOP
CARPENTRY SHOP
WELDING SHOP
FIRE RISER
RECEIVING
148B
WELDING
ELECTRICAL SHOP
148A
WELDING STORAGE
144B
CARPENTRY
STORAGE
142B
HVAC/PLUMBING
STORAGE
C05A
CORRIDOR
142A
OFFICE
144A
OFFICE
C05B
CORRIDOR
WATERPROOF.
VERIFY
LOCATION
WITH AHJ.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FA113
FIRE ALARM PLANS - LEVEL 1 -
SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE ALARM PLANS - LEVEL 1 - SOUTH
A
21 3 4 5 6 7 8 9 10 11 12
A'
B'
C'
D'
1' 2' 3' 4'
A''' A''
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FX120
FIRE SUPPRESSION PLANS -
BASEMENT - NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE SUPPRESSION PLANS - BASEMENT - NORTH
B
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FX121
FIRE SUPPRESSION PLANS -
BASEMENT - SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE SUPPRESSION PLANS - BASEMENT - SOUTH
A'
B'
C'
D'
1' 2' 3' 4'
A''' A''
OPEN OFFICE
OFFICE
OFFICE
OFFICE 105
WAITING
LOCKSMITH 107
RECEPTION
CONFERENCE ROOM
OFFICE
STAFF TOILET
OFFICE
INTERIOR DESIGN
LIBRARY
OFFICE
OFFICE
INTERIOR DESIGN
OFFICE
PLAN ROOM
VISITOR TOILET
OFFICE
CONFERENCE ROOM
OFFICE
OFFICE
OFFICE
RECEPTION
WAITING
HAC
BREAK / TRAINING
ROOM
C01
CORRIDOR
C04
CORRIDOR
C03A
CORRIDOR
ELECTRICAL
STORAGE
C06
CORRIDOR
BREAK ROOM
WOMENS TOILET
MENS TOILET
136B
MENS SHOWER
ELECTRICAL ROOM
STORAGE
IT ROOM
FIRE RISER
C02
CORRIDOR
NORTH ENTRY
ELECTRICAL SHOP
136A
MENS LOCKERS
C05A
CORRIDOR
HAC
KITCHEN
132B
ENTRYWAY
132A
ENTRYWAY
135B
WOMENS SHOWER
112A
ENGINEERING
TECHNICIAN OFFICE
C05B
CORRIDOR
134A
CHASE
C03B
CORRIDOR
C03C
CORRIDOR
135A
WOMENS LOCKERS
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FX122
FIRE SUPPRESSION PLANS - LEVEL
1 - NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE SUPPRESSION PLANS - LEVEL 1 - NORTH
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
PLAN ROOM
BREAK / TRAINING
ROOM
C06
CORRIDOR 136B
MENS SHOWER
HVAC / PLUMBING
SHOP
CARPENTRY SHOP
ELECTRICAL ROOM
IT ROOM
WELDING SHOP
FIRE RISER
RECEIVING
148B
WELDING
ELECTRICAL SHOP
148A
WELDING STORAGE
144B
CARPENTRY
STORAGE
142B
HVAC/PLUMBING
STORAGE
136A
MENS LOCKERS
C05A
CORRIDOR
HAC
142A
OFFICE
144A
OFFICE
C05B
CORRIDOR
3 F-002
EXISTING
FIRE RISER
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FX123
FIRE SUPPRESSION PLANS - LEVEL
1 - SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE SUPPRESSION PLANS - LEVEL 1 - SOUTH
A'
B'
C'
D'
1' 2' 3' 4'
A''' A''
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FX124
FIRE SUPPRESSION PLANS - ATTIC
- NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE SUPPRESSION PLANS - ATTIC- NORTH
Number: Revision: Date:
0 100% CONSTRUCTION DOCUMENTS 12/08/2023
ATTIC IS COMBUSTABLE AND FIRE SPRINKLER
PROTECTION IS REQUIRED. CONTRACTOR SHALL
COORDINATE FIRE SUPPRESSION WITH OTHER
DICIPLINES AND PROVIDE A NFPA COMPLIANT
SYSTEM TO PROTECT SPACE.
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\U se rs
\T R ic am or e\
D oc um en ts \2
2.
_M E
C H
-P
LU
M _R
_t ric am or eR
H Q
T H
.r vt
/7
/2
:3 2:
A
M
FX125
FIRE SUPPRESSION PLANS - ATTIC
- SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
BG TR
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
FIRE SUPPRESSION PLANS - ATTIC - SOUTH
Number: Revision: Date:
0 100% CONSTRUCTION DOCUMENTS 12/08/2023
ATTIC IS COMBUSTABLE AND FIRE SPRINKLER
PROTECTION IS REQUIRED. CONTRACTOR SHALL
COORDINATE FIRE SUPPRESSION WITH OTHER
DICIPLINES AND PROVIDE A NFPA COMPLIANT
SYSTEM TO PROTECT SPACE.
File details come from the government source that posted it. Updated .