This is a comprehensive set of mechanical engineering construction documents for the U.S. Department of Veterans Affairs (VA) Consolidate Engineering Building 17 project located at 4800 Memorial Drive in Waco, Texas. The documents cover mechanical systems including HVAC, piping, controls, and demolition plans across multiple building levels. Key systems include a new air handling unit (17-AHU-1) with chilled water and steam heating capabilities, multiple exhaust fans, terminal units with hot water reheat, split system air conditioners, and a dust collection system. The project involves replacing existing mechanical equipment, with detailed plans for system modifications, including steam and hot water piping, air distribution, and control systems. The documents provide extensive technical specifications, equipment schedules, typical details, and installation guidelines, indicating a comprehensive renovation of the building's mechanical infrastructure.

View the file

Other files

Show all 14

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

HVAC GENERAL NOTES

A. PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED

IN A FURRED CHASE OR ABOVE THE SUSPENDED CEILING. REF

SPECIFICATION 23 05 11.

B. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN

OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS IN INCHES UNO.

REF SPECIFICATION 23 31 00.

C. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH

SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS

FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.

COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF

SPECIFICATION 08 31 13.

D. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT

SYSTEM, TERMINAL UNITS, FILTERS, COILS, AND SO FORTH.

E. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT,

SEE EQUIPMENT DETAILS AND RESPECTIVE SPECIFICATIONS.

F. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE

MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.

G. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE

INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED

FLOOR.

H. PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE.

I. CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING

BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL

SYSTEM TO INCLUDE CONTROLS AND SEQUENCES SHOWN. REF

SPECIFICATION 23 09 23.

J. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DUCTS

AND DIFFUSERS.

K. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS

FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME

AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING

UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF

SPECIFICATION 01 33 23 AND 22 05 11.

L. OTHER THAN EQUIPMENT CONNECTIONS, MINIMUM HYDRONIC PIPE SIZE

SHALL BE 3/4". MINIMUM DUCT SIZE SHALL BE 8"X6".

M. PROVIDE LINE SIZE SERVICE VALVES AT POINTS OF CONNECTION TO

EXISTING MECHANICAL PIPING.

N. REFER TO GI SHEET SERIES FOR ADDITIONAL SYMBOLS AND LEGENDS,

WHERE NOT OTHERWISE DEFINED HERE.

GENERAL NOTES

A. PROVIDE TEMPORARY CONSTRUCTION PARTITIONS AND INFECTION

CONTROL BARRIERS AS APPLICABLE AROUND THE PROJECT AREA

CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY

THE VHA. REFER TO SPECIFICATION 01 35 26.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

7:

A M

M-001

MECHANICAL ABBREVIATIONS &

NOTES

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

A

A/E ARCHITECT / ENGINEER

AAV AUTOMATIC AIR VENT

ACCH AIR COOLED CHILLER

ACCU AIR-COOLED CONDENSING UNIT

ACD AUTOMATIC CONTROL DAMPER, MODULATING

ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION

ACU AIR CONDITIONING UNIT

AD ACCESS DOOR

AF AFTER FILTER

AFCV AIR FLOW CONTROL VALVE

AFF ABOVE FINISHED FLOOR

AFMD AIR FLOW MEASURING DEVICE

AHU AIR HANDLING UNIT

AMP AMPERE

AP ACCESS PANEL

APD AIR PRESSURE DROP

ARCH ARCHITECTURE

ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE

AS AIR SEPARATOR

ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND

AIR CONDITIONING ENGINEERS

ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS

B

B BOILER

BAS BUILDING AUTOMATION SYSTEM

BASC BUILDING AUTOMATION SYSTEM CONTRACTOR

BD BUTTERFLY DAMPER

BDD BACKDRAFT DAMPER

BDR BASE BOARD RADIATOR

BFP BACKFLOW PREVENTER

BFT BOILER PLANT FIRE TUBE

BG BOTTOM GRILLE

BHP BRAKE HORSEPOWER

BHW HOT WATER HEATING BOILER

BHX BOILER BLOWDOWN HEAT EXCHANGER

BLDG BUILDING

BOD BASIS OF DESIGN

BR BOTTOM REGISTER

BSC BIOLOGICAL SAFETY CABINETS

BT BLOWOFF TANK

BTC BLOWOFF TANK CONTROL VALVE

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BWT BOILER PLANT WATER TUBE

C

CAP CAPACITY

CC COOLING COIL

CCD COOLING COIL CONDENSATE DRAIN

CD CONDENSATE DRAIN

CENT CENTRIFUGAL

CFH CUBIC FEET PER HOUR

CFM CUBIC FEET PER MINUTE

CFP CHEMICAL FEED PUMP

CFT CUBIC FEET

CG CEILING GRILLE

CH CHILLER

CHP CHILLED WATER PUMP

CHR CHILLED WATER RETURN

CHS CHILLED WATER SUPPLY

CI CAST IRON

CKT CIRCUIT

CLG COOLING

CM CARBON MONOXIDE

CO2 CARBON DIOXIDE

COMP COMPRESSOR UNIT

COP COEFFICIENT OF PERFORMANCE

CP CONDENSATE PUMP

CS CONDENSATE STORAGE TANK

CSG CLEAN STEAM GENERATOR

CT COOLING TOWER

CTRL CONTROL

CU CONDENSING UNIT

CUH CABINET UNIT HEATER

CUP CENTRAL UTILITY PLANT

CV CONSTANT VOLUME

CV CONTROL VALVE

CWCC CHILLED WATER COOLING COIL

CWP CONDENSER WATER PUMP

CWR CONDENSER WATER RETURN (TO COOLING TOWER)

CWS CONDENSER WATER SUPPLY (FROM COOLING TOWER)

D

D DAMPER

DB DECIBEL

DBT DRY BULB TEMPERATURE

DC DUST COLLECTOR

DCW DOMESTIC COLD WATER

DDC DIRECT DIGITAL CONTROLS

DEG DEGREES

DEMO DEMOLISH

MECHANICAL ABBREVIATIONS

DF DIFFUSER

DI DEIONIZED WATER

DIA DIAMETER

DN DOWN

DP DEW POINT TEMPERATURE

DP DIFFERENTIAL PRESSURE

DPS DIFFERENTIAL PRESSURE SENSOR

DX DIRECT EXPANSION

DXCC DIRECT EXPANSION COOLING COIL

E

E EXISTING

EA EXHAUST AIR

EAT ENTERING AIR TEMPERATURE

EAT-DB ENTERING AIR TEMPERATURE DRY BULB

EC ELECTRONICALLY COMMUTATED

ECC ENGINEERING CONTROL CENTER

ECM ELECTRONICALLY COMMUTATED MOTOR

ECU EVAPORATIVE CONDENSER UNIT

EDH ELECTRIC DUCT HEATER

EER ENERGY EFFICIENCY RATIO

EF EXHAUST FAN

EFF EFFICIENCY

EG EXHAUST GRILLE

EGS EMERGENCY GAS SHUTOFF

EH EXHAUST HOOD

EJ EXPANSION JOINT

EMD END OF MAIN DRIP (STEAM)

ENT ENTERING

ER EXHAUST REGISTER

ERC ELECTRIC REHEAT COIL

ERP ELECTRIC RADIANT PANEL

ERW ENERGY RECOVERY WHEEL

ESP EXTERNAL STATIC PRESSURE

ET EXPANSION TANK

ETO ETHYLENE OXIDE

EUH ELECTRIC UNIT HEATER

EWC EVAPORATIVE WATER COOLER

EWT ENTERING WATER TEMPERATURE

F

F FAHRENHEIT

F&T FLOAT AND THERMOSTATIC

F/S FIRE SMOKE DAMPER

FA FIRE ALARM

FC FLEXIBLE CONNECTION

FCU FAN COIL UNIT (4 PIPE)

FCUC FAN COIL UNIT COOLING ONLY

FCUH FAN COIL UNIT HEATING ONLY

FD FLOOR DRAIN

FD FIRE DAMPER

FF FILTER FEEDER

FHX FLUE GAS/FEEDWATER HEAT EXCHANGER

FM FLOW METER

FOHX FUEL OIL HEAT EXCHANGER

FOP FUEL OIL PUMP

FOT FUEL OIL TANK

FPM FEET PER MINUTE

FPS FEET PER SECOND

FPTU FAN POWERED TERMINAL UNIT

FR FLOOR REGISTER

FRP FIBER REINFORCED POLYESTER

FS FLOW SWITCH

FSTAT FREEZESTAT

FT FEET

FT WG FEET WATER GAUGE

FT-LB FOOT-POUND

FTR FINNED TUBE RADIATION

FV FACE VELOCITY

G

GA GAUGE

GAL GALLONS

GALV GALVANIZED

GH GRAVITY HOOD

GHW GLYCOL HEATING WATER

GPD GALLONS PER DAY

GPH GALLONS PER HOUR

GPM GALLONS PER MINUTE

GPR GAS PRESSURE REGULATOR

GS GALVANIZED STEEL

GWB GYPSUM WALL BOARD

H

H HUMIDIFIER

HAC HOUSEKEEPING AID CLOSET

HB HOSE BIBB

HC HEATING COIL

HD HEAD

HOA HAND/OFF/AUTOMATIC

HP HEAT PUMP

HP HORSEPOWER

HPDT HIGH PRESSURE DRIP TRAP

HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)

HPS HIGH PRESSURE SUPPLY (STEAM)

HR HOUR

HRC HEAT RECOVERY COIL

HRD HEAT RECOVERY DEVICE

HRW HEAT RECOVERY WHEEL

HSTAT HUMIDISTAT

HTG HEATING

HTM HUMIDIFIER TERMINAL

HUM HUMIDIFIER UNIT MOUNTED

HVD HOISTWAY VENT DAMPER

HVLS HIGH VOLUME, LOW SPEED FAN

HVU HEATING AND VENTILATING UNIT

HW HOT WATER

HWC HOT WATER COIL

HWHC HOT WATER HEATING COIL

HWP HEATING WATER PUMP

HWR HEATING WATER RETURN

HWS HEATING WATER SUPPLY

HWUH HOT WATER UNIT HEATER

HX HEAT EXCHANGER

HZ HERTZ

I

I/O INPUT/OUTPUT

IAQ INDOOR AIR QUALITY

IBT INVERTED BUCKET TRAP

ICU INTENSIVE CARE UNIT

ID INSIDE DIAMETER

IDU INDOOR UNIT

IFB INTEGRAL FACE AND BYPASS

IN INCHES

IN HG INCHES OF MERCURY

IN WC INCHES OF WATER COLUMN

IN WG INCHES OF WATER, GAUGE

IN-LB INCH-POUND

IOM INSTALLATION AND OPERATION MANUAL

IPLV INTEGRATED PART LOAD VALUE

IRH INFRARED HEATER

IS INSECT SCREEN

IU INDUCTION UNIT

IV INLET VANES

K

KEA KITCHEN EXHAUST AIR

KW KILOWATT

KWH KILOWATT HOURS

L

LAT LEAVING AIR TEMPERATURE

LAT-DB LEAVING AIR TEMPERATURE DRY BULB

LB POUND

LF LINEAR FOOT (FEET)

LGT LEAVING GLYCOL TEMPERATURE

LH LATENT HEAT

LLHX LIQUID TO LIQUID HEAT EXCHANGER

LPG LIQUID PROPANE GAS

LPR LOW PRESSURE RETURN (STEAM CONDENSATE)

LPS LOW PRESSURE STEAM

LSD LINEAR SLOT DIFFUSER

LTCP LOCAL TEMPERATURE CONTROL PANEL

LVG LEAVING

LVR LOUVER

LWT LEAVING WATER TEMPERATURE

M

MA MIXED AIR

MAT MIXED AIR TEMPERATURE

MAU MAKEUP AIR UNIT

MAV MANUAL AIR VENT

MAX MAXIMUM

MB MIXING BOX

MBH 1000 BTUH

MCA MINIMUM CIRCUIT AMPACITY

MEP MECHANICAL ELECTRICAL PLUMBING

MER MECHANICAL EQUIPMENT ROOM

MERV MINIMUM EFFICIENCY REPORTING VALUE

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MOCP MAXIMUM OVERCURRENT PROTECTION

MOV MOTOR OPERATED VALVE

MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)

MPS MEDIUM PRESSURE STEAM

MRI MAGNETIC RESONANCE IMAGING UNIT

MTD MEAN TEMPERATURE DIFFERENCE

MUA MAKEUP AIR

MV MECHANICAL VENT

MVD MANUAL VOLUME DAMPER

MZ MULTI-ZONE

N

NA NOT APPLICABLE

NC NOISE CRITERIA

NC NORMALLY CLOSED

NG NATURAL GAS

NGFM NATURAL GAS FLOW METER

NO NORMALLY OPEN

NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION

NOM NOMINAL

NPLV NON-STANDARD PART LOAD VALUE

NPS NOMINAL PIPE SIZE

NPSH NET POSITIVE SUCTION HEAD

NPSHA NPSH AVAILABLE

NTS NOT TO SCALE

O

OA OUTSIDE AIR

OAG OUTSIDE AIR GRILLE

OAI OUTSIDE AIR INTAKE

OAL OUTSIDE AIR LOUVER

OD OUTER DIAMETER

ODU OUTDOOR UNIT

OFM OIL FLOWMETER

OH OVER HEAD

OR OPERATING ROOM

P

P PUMP

P&ID PROCESS & INSTRUMENTATION DIAGRAM

P/T PRESSURE/TEMPERATURE

PC PUMPED CONDENSATE

PCF POUNDS PER CUBIC FOOT

PD PRESSURE DROP

PF PRE-FILTER

PG PRESSURE GAUGE

PGW PROPYLENE GLYCOL-WATER SOLUTION

PH PHASE

PHC PREHEAT COIL

PPM PARTS PER MILLION

PRESS PRESSURE

PRV PRESSURE REGULATING VALVE

PSI POUNDS PER SQUARE INCH

PSIA POUNDS PER SQUARE INCH, ABSOLUTE

PSIG POUNDS PER SQUARE INCH, GAGE

PSS PRIMARY SECONDARY SYSTEM

PSV PRESSURE SAFETY VALVE

PTAC PACKAGED TERMINAL AIR CONDITIONER

Q

QTY QUANTITY

R

RA RETURN AIR

RAD REFRIGERANT AIR DRYER

RAF RADIO FREQUENCY

RAHX ROTARY AIR HEAT EXCHANGER

RAT RETURN AIR TEMPERATURE

RCCH REMOTE CONDENSER CHILLER

RCP RADIANT CEILING PANEL

RD REFRIGERANT DISCHARGE

REA RELIEF AIR

REF REFERENCE OR REFER TO

RF RETURN FAN

RG RETURN GRILLE

RH RELATIVE HUMIDITY

RHC REHEAT COIL

RHG REFRIGERANT HOT GAS

RL REFRIGERANT LIQUID LINE

RLA RUN LOAD AMPERE

RO REVERSE OSMOSIS

RPM REVOLUTIONS PER MINUTE

RR RETURN REGISTER

RS REFRIGERANT SUCTION

RTU ROOFTOP UNIT

RV RELIEF VALVE

S

SA SUPPLY AIR

SAD SOUND ATTENUATING DEVICE

SAT SUPPLY AIR TEMPERATURE

SC SHADING COEFFICIENT

SCFM STANDARD CUBIC FEET PER MINUTE

SCR SILICON CONTROLLED RECTIFIER

SD SMOKE DETECTOR

SD SUPPLY AIR DIFFUSER

SDPR SMOKE DAMPER

SDR SMOKE DAMPER (RETURN)

SDS SMOKE DAMPER (SUPPLY)

SEN SENSIBLE HEAT

SF SUPPLY FAN

SFT STEAM FLASH TANK

SG SUPPLY AIR GRILLE

SH STEAM HUMIDIFIER

SHC STEAM HEATING COIL

SIM SIMILAR

SOO SEQUENCE OF OPERATION

SP STATIC PRESSURE

SP GR SPECIFIC GRAVITY

SPD SUPPLY PROCESS AND DISTRIBUTION

SPRV STEAM PRESSURE REDUCING VALVE

SPS STATIC PRESSURE SENSOR

SQ FT SQUARE FOOT

SQ IN SQUARE INCHES

SR SUPPLY AIR REGISTER

SSHX STEAM TO STEAM HEAT EXCHANGER

SSR SOLID SEPARATOR

SST STAINLESS STEEL

ST STEAM TRAP

STRUCT STRUCTURAL

SUH STEAM UNIT HEATER

SVS STEAM VENT SILENCER

SWHX STEAM TO WATER HEAT EXCHANGER

T

T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE

TAB TESTING, ADJUSTING, AND BALANCING

TD TEMPERATURE DIFFERENCE

TDH TOTAL DYNAMIC HEAD

TDS TOTAL DISSOLVED SOLIDS

TG TRANSFER GRILLE

TP TRAP

TR TOP REGISTER

TSP TOTAL STATIC PRESSURE

TSTAT THERMOSTAT

TU TERMINAL UNIT

TWU THRU-WALL UNIT

U

UC UNIT COOLER

UCT UNDERCUT

UF UNDER FLOOR

UH UNIT HEATER

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

V

V VALVE

VAC VOLTAGE ALTERNATING CURRENT

VAV VARIABLE AIR VOLUME

VD VOLUME DAMPER (MANUAL OPPOSED BLADE)

VFD VARIABLE FREQUENCY DRIVE

VHA VETERANS HEALTH ADMINISTRATION

VI VIBRATION ISOLATOR

VIV VARIABLE INLET VANES

VP VACUUM PUMP

VPS VARIABLE PRIMARY SYSTEM

VR VACUUM (STEAM CONDENSATE) RETURN

VSD VARIABLE SPEED DRIVE

W

W WASTE

WAG WASTE ANESTHESIA GAS

WB WET BULB

WC WATER COOLED

WCCH WATER COOLED CHILLER

WCCU WATER COOLED CONDENSING UNIT

WCPU WATER COOLED HEAT PUMPS

WF WATER FILTER

WFCV WATER FLOW CONTROL VALVE

WFE WELDING FUME EXTRACTOR

WFM WATER FLOWMETER

WFMD WATER FLOW MEASURING DEVICE

WG WATER GAGE

WPD WATER SIDE PRESSURE DROP

X

XP EXPLOSION-PROOF

Y

YR YEAR

Number: Revision: Date:

0 100% CONSTRUCTION DOCUMENTS 12/08/2023

T

TT

M

MT

PT

TT

FT

IT

CT

SD

PDT

TSL

HS

M

LC

LT

PDS

TSH

EPT

AT

CO2

AT

CO

AT

OC

LTCP

VFD

PSH

PSL

26-SF 3

26-TU-1-1

H4

H7

A

BDD

FD

VD

N

1/24

F/S DPR

AV

MV

RH

SCH

SH

TH

PS

RC

WB

CSH

SS

VR

CTPS

CTPD

FWPS

FWPD

CF

FWS

BWS

CBD

BO

TC

A

OFL

HW

SW

CW

FOR

FOS

LPG(I)

NG(I)

NG

HPS

HPR

MPS

MPR

LPS

LPR

PC

HWS

HWR

GHS

GHR

V

SWS

SWR

CWR

CHR

GCR

RL

RS

RHG

CWS

CHS

GCS

MW

D

GRR

GRS

D

R

FC

10x8

M

DETAIL REFERENCE

DRAWING NUMBER WHERE SHOWN

SECTION REFERENCE

TYPICAL UNIT NUMBER

BUILDING NUMBER WHERE EQUIPMENT IS LOCATED.

SUPPLY FAN NUMBER 3 IN BUILDING NUMBER 26

EQUIPMENT ABBREVIATION (EG SUPPLY FAN)

ITEM NUMBER (TERMINAL UNIT NUMBER 1)

ITEM (TERMINAL UNIT SHOWN)

SERVED BY AIR HANDLER UNIT NUMBER 1

DRAWING NUMBER WHERE DRAWN

BUILDING NUMBER WHERE EQUIPMENT IS LOCATED

* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD PRACTICE SP-58

TEST PLUG (P/T PORT)

AUTOMATIC AIR VENT

MANUAL AIR VENT

QUICK-COUPLE HOSE CONNECTOR

CONNECT TO EXISTING

LIMIT OF DEMOLITION

AIR SEPARATOR

EXISTING DUCT TO BE REMOVED

LOUVER (REF SPECIFICATION 08 90 00)

FLEXIBLE DUCTWORK (INSULATED)

DUCT WITH SOUND LINING

MANUAL VOLUME DAMPER

FIRE DAMPER

BACK DRAFT DAMPER

COMBINATION FIRE/SMOKE DAMPER

AUTOMATIC CONTROL DAMPER

2'x2' RADIANT CEILING PANEL

2'x4' RADIANT CEILING PANEL

SUPPLY DUCT (UP & DOWN)

EXHAUST DUCT (UP & DOWN)

RETURN DUCT (UP & DOWN)

ROUND AND SQUARE 4-WAY CEILING DIFFUSERS

SQUARE 3-WAY CEILING DIFFUSERS

SQUARE 2-WAY CEILING DIFFUSERS

SQUARE 1-WAY CEILING DIFFUSERS

LINEAR SLOT DIFFUSER

SUPPLY REGISTER OR GRILLE (WALL TYPE)

EXHAUST OR RETURN CEILING

REGISTER OR GRILLE

EXHAUST OR RETURN REGISTER

OR GRILLE (WALL TYPE)

VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF

(REF MK SHEET SERIES)

CONNECT NEW DUCT TO EXISTING DUCT

INCLINED RISE, IN DIRECTION OF AIR FLOW

INCLINED DROP, IN DIRECTION OF AIR FLOW

LIMIT OF DEMOLITION

FLEXIBLE CONNECTION, EQUIPMENT,

VIBRATION, OR SEISMIC

VANED ELBOW (PROVIDE ALL SQUARE OR

RECTANGULAR ELBOWS WITH VANES EVEN IF

SYMBOL IS MISSING)

VANED ELBOW (SHORT RADIUS)

STANDARD RADIUS ELBOW (LONG RADIUS)

NEW DUCT (INSIDE DIMENSIONS, INCHES):

WIDTH x DEPTH (RECTANGULAR)

WIDTH / DEPTH (FLAT OVAL)

DIAMETER Ø (ROUND)

EXISTING DUCT TO REMAIN

GENERIC VALVE (REF SPEC FOR TYPE)

GLOBE VALVE

3/4" HOSE ADAPTER

CHECK VALVE

WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)

FLEXIBLE PIPE CONNECTOR

ANGLE GLOBE VALVE

BUTTERFLY VALVE

BALL VALVE

CONTROL VALVE

CONTROL BUTTERFLY VALVE

THREE-WAY CONTROL VALVE

PRESSURE REGULATING (IE REDUCING) VALVE

PRESSURE SAFETY VALVE / RELIEF VALVE

WATER FLOW BALANCE VALVE

GATE VALVE WITH GLOBE-VALVED BYPASS

PLUG VALVE

CONTROL VALVE (CV) - FLOAT-OPERATED

FLOW METER

ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT

ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER -

WALL MOUNT

TEMPERATURE TRANSMITTER

TEMPERATURE TRANSMITTER, AVERAGING ELEMENT

MOISTURE (HUMIDITY) TRANSMITTER

PRESSURE TRANSMITTER

FLOW TRANSMITTER

CURRENT TRANSMITTER

CONDUCTIVITY TRANSMITTER

SMOKE DETECTOR

PRESSURE DIFFERENTIAL TRANSMITTER

PRESSURE DIFFERENTIAL SWITCH

HAND SWITCH (HAND-OFF-AUTO SWITCH)

VALVE OR DAMPER ACTUATOR

TEMPERATURE SWITCH, LOW (FREEZESTAT)

TEMPERATURE SWITCH, HIGH

LEVEL CONTROLLER

LEVEL TRANSMITTER

PRESSURE SWITCH HIGH

PRESSURE SWITCH LOW

ELECTRONIC TO PNEUMATIC TRANSDUCER

CARBON DIOXIDE TRANSMITTER

CARBON MONOXIDE TRANSMITTER

OCCUPANCY SENSOR

LOCAL TEMPERATURE CONTROL PANEL

VARIABLE SPEED MOTOR CONTROLLER

CONTROLS SYMBOLS

GENERAL SYMBOLS AND TAGS

HVAC SYMBOLS PIPING SYMBOLSPIPING SYMBOLSHVAC SYMBOLS

FLOOR-SUPPORTED PIPE STAND

RISER CLAMP (TYPE 42)*

WALL BRACKET (TYPE 31, 32, 33)*

CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*

SLIDING SUPPORTS (TYPE 35)*

TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT

TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)

HOT WATER

ROLLER-TYPE HANGER

VARIABLE SPRING-TYPE HANGER (TYPE 51)*

SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*

CLEVIS-TYPE HANGER

HIGH PRESSURE STEAM (60 PSIG AND ABOVE)

HIGH PRESSURE STEAM CONDENSATE RETURN

MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)

MEDIUM PRESSURE STEAM CONDENSATE RETURN

LOW PRESSURE STEAM (15 PSIG AND BELOW)

LOW PRESSURE STEAM CONDENSATE RETURN

CONDENSATE PUMP DISCHARGE

HEATING WATER SUPPLY

HEATING WATER RETURN

GLYCOL-WATER HEATING SUPPLY

GLYCOL-WATER HEATING RETURN

SOLAR WATER SUPPLY

SOLAR WATER RETURN

REFRIGERANT LIQUID

REFRIGERANT SUCTION

REFRIGERANT HOT GAS

CONDENSER WATER SUPPLY (FROM TOWER)

CONDENSER WATER RETURN (TO TOWER)

CHILLED WATER SUPPLY

CHILLED WATER RETURN

GLYCOL-WATER CHILLED SUPPLY

GLYCOL-WATER CHILLED RETURN

MAKE-UP WATER

DRAIN LINE

VENT LINE

GLYCOL-WATER RUN AROUND SUPPLY

GLYCOL-WATER RUN AROUND RETURN

FEEDWATER PUMP DISCHARGE

FEEDWATER PUMP SUCTION

CONDENSATE TRANSFER PUMP DISCHARGE

CONDENSATE TRANSFER PUMP SUCTION

VACUUM CONDENSATE RETURN

TUBE CLEANER WATER SUPPLY

BOILER BLOWOFF

CONTINUOUS BLOWDOWN

BOILER WATER SAMPLE

FEEDWATER SAMPLE (FROM DEAERATOR)

CHEMICAL FEED

OVERFLOW

COMPRESSED AIR

NATURAL GAS MAIN FUEL

NATURAL GAS IGNITER FUEL

LIQUEFIED PETROLEUM GAS IGNITER FUEL

FUEL OIL SUPPLY

FUEL OIL RETURN

COLD WATER (CITY WATER)

SOFTENED WATER

THERMOMETER

PRESSURE GAGE

FLOW ELEMENT

SIGHT GLASS

THERMOSTATIC TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

FLOAT & THERMOSTATIC TRAP SET

INCLUDING PIPING ACCESSORIES SEE DETAIL

INVERTED BUCKET TRAP SET INCLUDING

PIPING ACCESSORIES SEE DETAIL

DIRECTION OF PIPE PITCH (DOWN)

DIRECTION OF FLOW

ANCHOR

REDUCER OR INCREASER

ECCENTRIC REDUCER

TOP CONNECTION, 45° OR 90°

BOTTOM CONNECTION, 45° OR 90°

SIDE CONNECTION

CAPPED OUTLET

RISE OR DROP IN PIPE

UNION

PIPE UP

PIPE DOWN

POINT OF CHANGE IN DUCT CONSTRUCTION BY STATIC

PRESSURE CLASS. THE NUMBER ASSIGNS PRESSURE

CLASS (IN OF WATER) WHICH WILL ACCOMMODATE

MAXIMUM OPERATING PRESSURE IN THE DUCT

SUBSECTION. THE SYMBOL CONTINUES THE

ASSIGNMENT UNTIL THE DUCT TERMINATES OR

ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT

INDICATES NEGATIVE PRESSURE.

FE

DEMOLISHED EQUIPMENT (SHAPE VARIES, REF:

SYMBOLS, TAGS, & NOTES)

(E) EXISTING COMPONENT

(X) DEMOLISHED COMPONENT

PIPE TO BE DEMOLISHED

MS MOISTURE (HUMIDITY) SWITCH

FSH FLOW SWITCH HYDRONIC

DS DOOR SWITCH

PR PILOT RELAY

MOTOR STARTER

WELDED STAINLESS STEEL DUCT

PROVIDE FLEXIBLE SHAFT WRAP A MINIMUM OF 10 FT ON

BOTH SIDES OF FIRE BARRIER PENETRATIONS. THE FIRE

RESISTIVE RATING OF THE WRAP SHALL BE EQUIVALENT TO

THAT OF THE BARRIER PENETRATED. WRAP ENTIRETY OF

RISERS WITHIN SHAFTS SHARED WITH ENVIRONMENTAL AIR

DUCTS.

AIR DEVICE MARK

AIR DEVICE CFM1,200

SD-1

GUIDE

WM WATER FLOW METER

SENSOR WELL / O-LET

NEW PIPING

EXISTING PIPING

MV MECHANICAL VENT LINE

CD CONDENSATE DRAIN LINE

AFMD AIR FLOW MEASUREMENT DEVICE

PUMP TRAP SET INCLUDING PIPING

ACCESSORIES SEE DETAIL

STANDARD BRANCH SUPPLY OR

RETURN, NO SPLITTER (45° TAP)

DUCT-MOUNTED COIL (HOT WATER

OR STEAM COIL)

DUCT-MOUNTED COIL (ELECTRIC)

SDPR

SMOKE DAMPER

## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF MQ

SHEET SERIES FOR CONNECTION SCHEDULE

DOUBLE-LINED VALVE

(REFER TO SPECS FOR TYPE)

# MI7##

DETAIL

SHEET

EQUIPMENT APPLICABLE P&ID, SOO, &

POINT LIST REFERENCE

NEW EQUIPMENT (SHAPE VARIES, REF: SYMBOLS, TAGS,

& NOTES. SCHEDULED ITEMS ARE NEW UNO)

SD DUCT SMOKE DETECTOR, UL268A. PROVIDE PER

NFPA 90A AND SPECIFICATION 28 31 00.

COORDINATE WITH FA CONTRACTOR.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

7:

A M

M-002

MECHANICAL SYMBOLS CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12Number: Revision: Date:

A. PROVIDE SCHEDULED BASIS OF DESIGN OR APPROVED EQUAL. REFER TO

SPECIFICATIONS 01 33 23 AND 23 05 11 FOR FURTHER REQUIREMENTS.

B. SELECT EQUIPMENT FOR SCHEDULED PERFORMANCE AT 460 FT ELEVATION.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTIONS 23 73 00 AND 23 74 13.

2. REFER TO MQ SHEET SERIES FOR

DEFAULT COMPONENT LOCATIONS

AND MINIMUM DIMENSIONS, UNO.

3. PROVIDE MIXING BOX.

4. PROVIDE WITH FACTORY SUPPLIED

ROOF CURB.

5. REFER TO FAN SCHEDULE FOR FAN

CIRCUIT POWER.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 34 00.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 13.

2. BASIS OF DESIGN BELL AND

GOSSETT SU-43-2.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 34 00.

2. REFER TO AHU SCHEDULE THIS

SHEET FOR RELATED

COMPONENTS. POWER FOR FAN IS

A PART OF THE SINGLE POINT

POWER ABOVE.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 82 16.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 40 00.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 13.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 36 00.

2. PROVIDE WITH FACTORY SOUND

ATTENUATOR.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 34 00.

2. SPARK RESISTANT CONSTRUCTION.

REMARKS:

1. SPARK RESISTANT CONSTRUCTION.

2. PROVIDE WITH DIRECT DRIVE FAN,

AIRFLOW AND DELTA P

CONTROLLERS, EXPLOSION

PROTECTION. INSTALL PER

MANUFACTURER'S

RECOMMENDATION.

3. REFER ALSO TO SPECIFICATION

SECTION 23 34 00.

REMARKS:

1. PROVIDE WITH FLEXIBLE 13' FUME

EXTRACTION ARM EQUIPPED WITH

ARC SENSOR, LAMP KIT, AND

ASSOCIATED FAN.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

8:

A M

MQ601

EQUIPMENT SCHEDULES CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

EXHAUST FAN (EF) SCHEDULE

MARK LOCATION AREA SERVED

AIRFLOW

(CFM)

ESP

(IN WG)

FAN MOTOR

BAS

CONTROLS

BOD MFR AND MODEL REMARKS

TYPE DRIVE

ELECTRICAL SPEED

CONTROLHP VAC Φ MCA MOCP

17-GEF-1 ROOF 148A, 148, 148B 3221 0.5

CENTRIFUGAL -

UPBLAST

BELT 3/4 208 3 4.4 15

VFD -

REMOTE

VARIABLE

SPEED

GREENHECK CUBE-200 1

17-GEF-2 ROOF

132, 132A, 131, 136, 136B, 134, 1790 0.5

CENTRIFUGAL -

UPBLAST

DIRECT 1/2 208 3 3 15

VFD -

REMOTE

VARIABLE

SPEED

GREENHECK

CUE-120-A

17-GEF-3 ROOF 110, 117 510 0.5

CENTRIFUGAL -

UPBLAST

DIRECT 1/4 208 1 4.00 7.27

VFD -

REMOTE

VARIABLE

SPEED

GREENHECK

CUE-099-A

17-GEF-4 ROOF 125, 126 1040 0.5

CENTRIFUGAL -

UPBLAST

DIRECT 1/4 208 3 3 15

VFD -

REMOTE

VARIABLE

SPEED

GREENHECK

CUE-130-B

HEAT EXCHANGER (HX) SCHEDULE

MARK LOCATION

AREA/SYSTEM

SERVED

HX TYPE

COLD SIDE STEAM PRESSURE (PSIG)

STEAM

TRAP MARK

REMARKSEWT

(°F)

LWT

(°F)

GPM

WPD

(FT WG)

ENTERING

CONTROL

VALVE

ENTERING

HX

17-HX-1 BASEMENT BLDG 17 SHELL & TUBE 150 180 30 0.52 30 25 ST-1 1, 2

17-HX-2 BASEMENT BLDG 17 SHELL & TUBE 150 180 30 0.52 30 25 ST-3 1, 2

AIR HANDLING UNIT (AHU) SUMMARY SCHEDULE

MARK LOCATION

AREA AND/OR

BLDG SERVED

SUPPLY

AIRFLOW

(CFM)

OUTSIDE

AIRFLOW

(CFM)

SUPPLY

FAN

RETURN

FAN

EXHAUST

FAN

PRE-

FILTER

AFTER-

FILTER

HEAT

RECOVERY

PREHEAT

COIL

COOLING

COIL

REHEAT

COIL

HUMIDIFIER

OVERALL

HEIGHT (IN)

OVERALL

LENGTH (IN)

OVERALL

WIDTH (IN)

POWER

BOD MFR

AND MODEL

REMARKS

VAC PH MCA MOCP

17-AHU-1

LEVEL

2/ROOF

BUILDING 17 19410 6688 17-SF-1 17-RF-1 - 17-PF-1 17-AF-1 - 17-PH-1 17-CC-1 - 17-H-1 99.5 169 546 115 1 20 30

TRANE

CUSTOM

AHU

1, 2, 3, 4, 5

AHU SUPPLY FAN SCHEDULE

MARK

TOTAL

AIRFLOW

(CFM)

ESP (IN WG) TYPE FAN QTY VFD

ELECTRICAL DATA (TOTAL ARRAY UNO)

REMARKSMOTOR HP

(EACH)

VAC PH FLA MOCP

17-SF-1 19410 2.19

DIRECT

DRIVE

2 YES 15 460 3 37 80 1,2

AHU RETURN FAN SCHEDULE

MARK

TOTAL

AIRFLOW

(CFM)

ESP

(IN WG)

TYPE

FAN

QTY

VFD

ELECTRICAL DATA (TOTAL ARRAY UNO)

REMARKSMOTOR HP

(EACH)

VAC PH MCA MOCP

17-RF-1 15440 0.39 DIRECT DRIVE 1 Y 7.5 460 3 11.5 20 1,2

AHU PREHEAT COIL SCHEDULE

MARK

HEATING

AIRFLOW

(CFM)

MAX FV

(FPM)

APD

(IN WG)

EAT-DB

(°F)

LAT-DB

(°F)

MIN

CAPACITY

(MBH)

STEAM

PSIG ENT

CNTRL

VALVE

PSIG

ENT

COIL

STEAM

FLOW

(LB/H)

17-PH-1 15531 450 0.027 48.1 93.8 261 30 25 281

AHU COOLING COIL SCHEDULE

MARK

AIRFLOW

(CFM)

MAX FV

(FPM)

APD (IN WG)

EAT-DB

(°F)

EAT-WB

(°F)

LAT-DB

(°F)

LAT-WB

(°F)

SEN

MBH

TOTAL

MBH

CHILLED WATER (CHW)

GLYCOL

EWT

(°F)

LWT

(°F)

FLOW

(GPM)

WPD

(FT WG)

17-CC-1 19410 450 0.501 85 70 55 54.3 615 1016 - 42 57 171 9.06

AHU PRE-FILTER SCHEDULE

MARK

MERV

RATING

AIRFLOW

(CFM)

MAX

FINAL APD

(IN WG)

THICKNESS

(IN)

FILTER/RACK

TYPE

17-PF-1 7+14 19410 1+1.2 2+6 CARTRIDGE

AHU HUMIDIFIER SCHEDULE

MARK TYPE

DESIGN HUMIDIFICATION

AIRFLOW

(CFM)

EA-DP (°F) LA-DP (°F)

STEAM

SOURCE

PSIG ENT

CONTROL VALVE

PSIG ENT

COIL

STEAM

LOAD (LB/H)

17-H-1

DISPERSION

TUBE

15531 11.7 47 MPS 30 25 241.3

TERMINAL UNIT (TU) SCHEDULE

MARK TYPE

MAX

CFM

MIN

CFM

MAX

TOTAL

APD

(IN WG)

REHEAT COIL

SINGLE POINT

ELECTRICAL

BOD MFR

AND MODEL REMARKSSOURCE

HTG

CFM

EAT

(°F)

LAT

(°F) MBH

EWT

(°F) GPM

WPD

(FT WG) VAC PH

MAX

LOAD

(VA)

17-TU-1

SINGLE

DUCT

220 70 0.5 HW 70 55 91 2.66 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-2

SINGLE

DUCT

150 70 0.5 HW 70 55 85 2.10 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-3

SINGLE

DUCT

240 70 0.5 HW 70 55 93 2.82 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-4

SINGLE

DUCT

150 70 0.5 HW 70 55 85 2.14 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-5

SINGLE

DUCT

160 70 0.5 HW 70 55 85 2.20 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-6

SINGLE

DUCT

350 290 0.5 HW 290 55 85 8.23 180 0.55 0.20 120 1 15 PRICE SDV 1, 2

17-TU-7

SINGLE

DUCT

950 300 0.5 HW 300 55 88 10.39 180 0.69 0.44 120 1 15 PRICE SDV 1, 2

17-TU-8

SINGLE

DUCT

300 250 0.5 HW 250 55 85 6.01 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-9

SINGLE

DUCT

180 170 0.5 HW 170 55 85 4.01 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-10

SINGLE

DUCT

120 110 0.5 HW 110 55 85 2.61 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-11

SINGLE

DUCT

681 560 0.5 HW 641 55 85 12.58 180 0.84 0.63 120 1 15 PRICE SDV 1, 2

17-TU-12

SINGLE

DUCT

340 90 0.5 HW 90 55 89 3.23 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-14

SINGLE

DUCT

130 110 0.5 HW 110 55 85 2.40 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-15

SINGLE

DUCT

360 300 0.5 HW 300 55 85 7.21 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-16

SINGLE

DUCT

140 70 0.5 HW 70 55 85 1.90 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-17

SINGLE

DUCT

110 90 0.5 HW 90 55 85 2.16 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-18

SINGLE

DUCT

230 210 0.5 HW 210 55 85 5.00 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-19

SINGLE

DUCT

170 160 0.5 HW 160 55 85 3.76 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-21

SINGLE

DUCT

210 190 0.5 HW 190 55 85 4.48 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-22

SINGLE

DUCT

270 70 0.5 HW 70 55 90 2.58 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-23

SINGLE

DUCT

100 70 0.5 HW 70 55 85 1.65 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-24

SINGLE

DUCT

100 70 0.5 HW 70 55 85 1.56 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-25

SINGLE

DUCT

100 70 0.5 HW 70 55 85 1.66 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-26

SINGLE

DUCT

260 170 0.5 HW 170 55 85 4.03 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-27

SINGLE

DUCT

540 190 0.5 HW 190 55 93 7.63 180 0.50 0.18 120 1 15 PRICE SDV 1, 2

17-TU-28

SINGLE

DUCT

150 100 0.5 HW 100 55 85 2.66 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-29

SINGLE

DUCT

100 70 0.5 HW 70 55 85 1.65 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-30

SINGLE

DUCT

260 250 0.5 HW 250 55 85 5.54 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-31

SINGLE

DUCT

220 200 0.5 HW 200 55 85 5.19 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-32

SINGLE

DUCT

740 430 0.5 HW 430 55 86 9.77 180 0.65 0.40 120 1 15 PRICE SDV 1, 2

17-TU-33

SINGLE

DUCT

190 180 0.5 HW 180 55 85 4.24 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-34

SINGLE

DUCT

990 990 0.5 HW 990 55 86 18.6 180 0.88 0.68 120 1 15 PRICE SDV 1, 2

17-TU-35

SINGLE

DUCT

230 220 0.5 HW 220 55 85 6.42 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-36

SINGLE

DUCT

2620 1950 0.5 HW 1950 55 85 38.6 180 2.26 0.73 120 1 15 PRICE SDV 1, 2

17-TU-37

SINGLE

DUCT

670 550 0.5 HW 550 55 85 13.26 180 0.88 0.68 120 1 15 PRICE SDV 1, 2

17-TU-38

SINGLE

DUCT

1290 1240 0.5 HW 1240 55 85 24.5 180 1.93 0.46 120 1 15 PRICE SDV 1, 2

17-TU-39

SINGLE

DUCT

310 300 0.5 HW 300 55 85 8.68 180 0.58 0.22 120 1 15 PRICE SDV 1, 2

17-TU-40

SINGLE

DUCT

110 110 0.5 HW 110 55 85 2.36 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-41

SINGLE

DUCT

110 110 0.5 HW 110 55 85 2.36 180 0.50 0.17 120 1 15 PRICE SDV 1, 2

17-TU-42

SINGLE

DUCT

310 300 0.5 HW 300 55 85 8.68 180 0.50 0.22 120 1 15 PRICE SDV 1, 2

17-TU-43

SINGLE

DUCT

1870 1800 0.5 HW 1800 55 85 34.2 180 2.61 0.95 120 1 15 PRICE SDV 1, 2

17-TU-44

SINGLE

DUCT

1340 730 0.5 HW 730 55 85 19.44 180 1.30 0.23 120 1 15 PRICE SDV 1, 2

AIR CURTAIN (AC) SCHEDULE

MARK LOCATION AREA SERVED

MIN HEATING

CAPACITY(MBH)

FAN MOTOR

BOD MFR AND MODEL REMARKS

TYPE DRIVE

ELECTRICAL SPEED

CONTROLHP VAC Φ

17-AC-1 153 RECEIVING 18.4 ELECTRIC DIRECT 1/2 208 3 VFD BERNER IDC12 1

17-AC-2 153 RECEIVING 18.4 ELECTRIC DIRECT 1/2 208 3 VFD BERNER IDC12 1

17-AC-3 148B WELDING 14.4 ELECTRIC DIRECT 1/2 208 3 VFD BERNER IDC12 1,2

DUST COLLECTOR (DC) SCHEDULE

MARK LOCATION AREA SERVED

MINIMUM

AIRFLOW

(CFM)

FAN MOTOR

BOD MFR AND MODEL REMARKS

TYPE DRIVE

ELECTRICAL SPEED

CONTROLHP VAC Φ

17-DC-1

PLAN SOUTH

EXTERIOR

CARPENTRY SHOP 6575 CENTRIFUGAL DIRECT 30 208 3 VFD

DONALDSON TORIT

36-30

1,2,3

WELDING FUME EXTRACTOR (WFE) SCHEDULE

MARK LOCATION AREA SERVED

MERV

RATING

TYPE

MOTOR

BOD MFR AND MODEL REMARKSELECTRICAL SPEED

CONTROLHP VAC Φ

17-WFE-1 148B WELDING 14

WALL MOUNTED

EXTRACTION UNIT

1 208 3 -

LINCOLN ELECTRIC

PRISM

A. PROVIDE SCHEDULED BASIS OF DESIGN OR APPROVED EQUAL. REFER TO

SPECIFICATIONS 01 33 23 AND 23 05 11 FOR FURTHER REQUIREMENTS.

B. SELECT EQUIPMENT FOR SCHEDULED PERFORMANCE AT 460 FT ELEVATION.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 23.

2. MULTIPLEX PUMP AND VENTED

RECEIVER PACKAGE. SIZE PUMP

MODULES FOR N+1 REDUNDANCY

SUCH THAT THE SCHEDULED

CAPACITY IS MET GIVEN FAILURE OF

1 MODULE.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 13.

2. MAX WIDE OPEN VALVE FLOW AT

SET PRESSURE + 5 PSIG SHALL BE

LESS THAN ASSOCIATED SAFETY

RELIEF VALVE.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 13.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 13.

2. FOR PUMP TRAPS, SCHEDULED

INLET PRESSURE IS MOTIVE

PRESSURE AND DP IS MOTIVE

MINUS BACK PRESSURE.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 81 00.

2. IDU POWERED BY ASSOCIATED

OUTDOOR UNIT.

3. PROVIDE SECONDARY DRAIN PANS

FOR INDOOR UNITS.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 21 23.

REMARKS:

1. REFER ALSO TO SPECIFICATION:

A. 23 21 13 FOR EXPANSION TANKS,

AIR SEPARATORS, BUFFER

TANKS.

B. 23 25 00 FOR FILTERS FEEDERS

AND GLYCOL MAKEUP SYSTEMS.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 82 00.

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 37 00.

2. MATCH RUN-OUT TO NECK SIZE

UNLESS OTHERWISE TAGGED.

3. BLACK SHADED CELLS INDICATE

NECK SIZES NOT APPLICABLE TO

GIVEN AIR DEVICE.

4. S1R-#, # INDICATES NOMINAL FRAME

DIAMETER

REMARKS:

1. REFER ALSO TO SPECIFICATION

SECTION 23 22 13 AND MK SHEET

SERIES DETAILS.

2. BOD IS ARMSTRONG HAFT.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

8:

A M

MQ602

EQUIPMENT SCHEDULES CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT (ODU) SCHEDULE

MARK

INDOOR

UNIT

SERVED

STAGES

COOLING REQUIREMENTS HEATING REQUIREMENTS ELECTRICAL DATA

BOD MFR AND

MODEL

REMARKSMIN NET

CAPACITY

(MBH)

MIN

EER / SEER

AMBIENT

TEMP

(°F)

MIN NET

CAPACITY

(MBH)

MIN COP

AMBIENT

TEMP

(°F)

VAC PH MCA MOCP

17-ODU-1

17-IDU-1,

17-IDU-2

- 27.0 3.40 99.2 - - - 208 1 30 40 CARRIER RAV 1

17-ODU-2

17-IDU-1,

17-IDU-2

- 27.0 3.40 99.2 - - - 208 1 30 40 CARRIER RAV 1

17-ODU-3 17-IDU-3 - 5.95 3.40 99.2 - - - 208 1 15 15 CARRIER 38MARB 1

STEAM TRAP (ST) SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

CAPACITY AT

MIN DP

MIN DP

(PSIG)

MIN INLET

PRESSURE

(PSIG)

TRAP TYPE REMARKS

ST-DS

DRIP

STATIONS

LPS,MPS,HPS AS

APPLICABLE

REF 23 22 13 REF 23 22 13 REF 23 22 13 IB 1

ST-1 17-HX-1 MPS 973 1/4 25 F&T 1

ST-2 17-HX-2 MPS 973 1/4 25 F&T 1

ST-3 17-SDWH-1 LPS 4615 1/4 10 F&T 1

ST-4 17-PH-1 MPS 979 1/4 25 F&T 1

ST-5 17-H-1 MPS 111 5 25 IB 1

STEAM PRESSURE RELIEF SAFETY VALVE (SV) SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

MIN

CAPACITY

(LB/HR)

SET

PRESSURE

(PSIG)

NORMAL

LINE

PRESSURE

(PSIG)

BASIS OF

DESIGN

REMARKS

17-SV-1 BASEMENT MPS 818 35 30

SPIRAX SARCO

17-SV-2 BASEMENT LPS 1846 20 15

SPIRAX SARCO

STEAM PRESSURE REDUCING VALVE (SPRV) SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

MIN

CAPACITY

(LB/HR)

PRESSURE

IN

(PSIG)

PRESSURE

OUT

(PSIG)

REMARKS

17-SPRV-1 BASEMENT MPS 818 55 30 1, 2

17-SPRV-2 BASEMENT LPS 1846 55 15 1, 2

STEAM CONDENSATE PUMP (SCP) SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

PUMP TYPE

CONTINUOUS

LOAD

(LB/HR)

DISCHARGE

PRESSURE

(PSIG)

RECEIVER &

VENT FLASH

STEAM

CAPACITY

(LB/HR)

ELECTRICAL/MOTOR DATA

BOD MFR

AND MODEL

REMARKS

HP VAC PH

MAX

RPM

SPEED

CONTROL

17-SCP-1 BASEMENT

STEAM CONDENSATE

RETURN

CENTRIFUGAL 6660 20 281 3 208 3 3500 -

BELL &

GOSSETT

CC SERIES

1,2

HYDRONIC PUMP SCHEDULE

MARK LOCATION

AREA AND/OR BLDG

SERVED

SYSTEM PUMP TYPE FLUID GPM

HEAD

(FT WG)

NPSHA

(FT WG)

FLUID

TEMP

(°F)

MIN %

EFF

ELECTRICAL/MOTOR DATA

BASIS OF DESIGN REMARKS

HP VAC PH

MAX

RPM

SPEED

CONTROL

17-CHP-1 BASEMENT BLDG 17 CHW

BASE MOUNTED, END

SUCTION

WATER 179.6 31.9 - 45 72 2 208 3 1800 VFD BELL AND GOSSETT E-1510 1

17-CHP-2 BASEMENT BLDG 17 CHW

BASE MOUNTED, END

SUCTION

WATER 179.6 31.9 - 45 72 2 208 3 1800 VFD BELL AND GOSSETT E-1510 1

17-HWP-1 BASEMENT BLDG 17 HW INLINE WATER 30 45 - 150 47 1.5 208 1 1800 ECM BELL AND GOSSETT E-90 1

17-HWP-2 BASEMENT BLDG 17 HW INLINE WATER 30 45 - 150 47 1.5 208 1 1800 ECM BELL AND GOSSETT E-90 1

MISCELLANEOUS HYDRONIC EQUIPMENT SCHEDULE

MARK DESCRIPTION LOCATION

SYSTEM AND/OR

SERVICE

TYPE

VOLUME

(GAL)

FLOW

(GPM)

WPD

(FT WG)

CONNECTION

SIZE

(NPS)

ELECTRICAL REMARKS

17-AS-1

AIR

SEPARATOR

BASEMENT HW TANGENTIAL NA 28.8 0.04 3 NA 1

17-AS-2

AIR

SEPARATOR

BASEMENT CHW TANGENTIAL NA 179.6 1.61 3 NA 1

17-ET-1

EXPANSION

TANK

BASEMENT HW DIAPHRAGM 7.80 NA NA 3/4 NA 1

17-ET-2

EXPANSION

TANK

BASEMENT CHW DIAPHRAGM 13.1 NA NA 1 NA 1

17-FF-1

FILTER

FEEDER

BASEMENT HW

SIDE STREAM

BYPASS

5 1.37 - - NA 1

17-FF-2

FILTER

FEEDER

BASEMENT CHW

SIDE STREAM

BYPASS

5 8.55 - - NA 1

HEATING WATER UNIT HEATER (HWUH) SCHEDULE

MARK DESCRIPTION

FLOW RATE

(GPM)

HHW COIL

(MBH)

COIL

PRESSURE

DROP

HEATING

(CFM)

HEATING COIL

EAT (°F)

HEATING COIL

LAT (°F)

MOTOR HP VOLTAGE PHASE

BOD MFGR AND

MODEL

REMARKS

17-UH-1

HORIZONTAL

DELIVERY

1.23 9.75 0.20 630 60 91 1/25 115 1 MODINE HSB 1

17-UH-3

HORIZONTAL

DELIVERY

0.5 6.19 0.50 340 28.2 93 1/60 115 1 MODINE HSB 1

17-UH-4

HORIZONTAL

DELIVERY

0.51 7.66 0.50 340 28.2 93 1/60 115 1 MODINE HSB 1

SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT (IDU) SCHEDULE

MARK AREA SERVED TYPE

SUPPLY

CFM

OA

CFM

ESP

(IN WG)

COOLING REQUIREMENTS HEATING REQUIREMENTS ELECTRICAL REQUIREMENTS

BOD MFR AND

MODEL

REMARKS

SOURCE

SEN

MBH

TOTAL

MBH

EAT-

DB

(°F)

EAT-

WB

(°F)

LAT-

DB

(°F)

LAT-

WB

(°F)

SOURCE

TOTAL

MBH

EAT-

DB

(°F)

LAT-

DB

(°F)

FAN

HP

(QTY)

VAC PH MCA MOCP

SPEED

CONTROL

17-IDU-2 IT ROOM HIGH WALL DUCTLESS 990 0 - 17-ODU-1 26.59 27.0 79 61 55 50 - - - - 1/10 208 1 - - ECM CARRIER RAV 1,2,3

17-IDU-1 IT ROOM HIGH WALL DUCTLESS 990 0 - 17-ODU-1 26.59 27.0 79 61 55 50 - - - - 1/10 208 1 - - ECM CARRIER RAV 1,2,3

17-IDU-3

ELECTRICAL

ROOM

DUCTED 190 0 - 17-ODU-2 5.95 6.19 79 61 55 50 - - - - - 208 1 - - ECM CARRIER 40MBDQ 1,2,3

AIR DEVICE SCHEDULE

MARK

TYPE

DESCRIPTION

MOUNTING

PANEL / FRAME

SIZE

NECK SIZE MAX CFM

MAX NC MAX APD

BOD MFR AND

MODEL

REMARKS6Ø

6X6 8Ø 8X8

10Ø 10X10

12Ø 12X12

14Ø 14X14

E2-A

EXHAUST -

LOUVERED

FACE

SURFACE /

LAY-IN

24"X24" 100 225 350 525 725 13 0.1 PRICE 500/600 1,2,3

E6-A

EXHAUST -

STANDARD

WALL TYPE

SURFACE /

DUCT

18"X6" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3

E6-B

EXHAUST -

STANDARD

WALL TYPE

SURFACE /

DUCT

36"X12" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3

R2-A

RETURN -

LOUVERED

FACE

SURFACE /

LAY-IN

24"X24" 100 225 350 525 725 13 0.1 PRICE 500/600 1,2,3

R6-A

RETURN -

STANDARD

WALL TYPE

SURFACE /

DUCT

18"X6" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3

R6-B

RETURN -

STANDARD

WALL TYPE

SURFACE /

DUCT

36"X12" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3

S1R-6

SUPPLY -

ROUND CONE

LOUVER

SURFACE /

DUCT

REF CFM &

NECK SIZE

140 210 325 450 635 25 0.1 TITUS TMR 1,2,3,4

S1R-10

SUPPLY -

ROUND CONE

LOUVER

SURFACE /

DUCT

REF CFM &

NECK SIZE

140 210 325 450 635 25 0.1 TITUS TMR 1,2,3,4

S1R-14

SUPPLY -

ROUND CONE

LOUVER

SURFACE /

DUCT

REF CFM &

NECK SIZE

140 210 325 450 635 25 0.1 TITUS TMR 1,2,3,4

S3-A

SUPPLY -

PERFORATED

FACE

SURFACE /

LAY-IN

24"X24" 100 200 300 390 470 25 0.1 PRICE AMCD 1,2,3

S4-A

SUPPLY - SLOT

DIFFUSER/PLEN

UM

SURFACE /

LAY-IN

24"L, 1X1" SLOT 100 110 -1 -1 -1 25 0.15 TITUS FL 1,2,3

S4-C

SUPPLY - SLOT

DIFFUSER/PLEN

UM

SURFACE /

LAY-IN

48"L, 1X1" SLOT 160 210 -1 -1 -1 25 0.15 TITUS FL 1,2,3

S6-A

SUPPLY -

REGISTER

SURFACE /

DUCT

12"X8" 100 200 350 525 730 25 0.1 TITUS 300FL 1,2,3

S6-B

SUPPLY -

REGISTER

SURFACE /

DUCT

18"X6" 100 200 350 525 730 25 0.1 TITUS 300FL 1,2,3

STEAM FLASH TANK (SFT) SCHEDULE

MARK LOCATION

SYSTEM AND/OR

SERVICE

TYPE

MAX RETURN

PRESSURE

(PSIG)

CONDENSATE

(LB/HR)

REMARKS

17-SFT-1 BASEMENT BLDG 17 MPR HORIZONTAL 35 2063 1,2

A. REFER TO M-001 AND M-002 FOR MECHANICAL SYMBOLS, ABBREVIATIONS,

AND GENERAL NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL

PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE

SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE

LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND

SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.

MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP

ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL

REMAIN IN SERVICE FOLLOWING DEMOLITION.

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

3" ø

C D

3"ø MPS

3" ø

M P

S

1(X) 17-P-3

(X)

17-ET-3

/F1 MD111 /F1 MD111

(E) 6"ø CHR

(E) 6"ø CHS

2" ø

M P

R

4" ø

M P

S

5 5

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:0

5:

P M

MD110

DEMOLITION PLANS - BASEMENT

NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION HVAC PLANS - BASEMENT - NORTH

F1

1. DEMOLISH EXISTING WATER TANKS AND ASSOCIATED PLUMBING BACK TO

MAIN.

2. DEMOLISH ANY REMAINING MECHANICAL EQUIPMENT LOCATED IN THE

BASEMENT. PROVIDE RFI FOR ANY EQUIPMENT TO BE DEMOLISHED THAT

IS NOT IDENTIFIED PRIOR TO REMOVAL.

3. DEMOLISH EXISTING PUMP AND ASSOCIATED PLUMBING BACK TO MAIN.

4. EXISTING MECHANICAL PIPING EXTENDS THROUGHOUT CRAWLSPACE.

CONTRACTOR SHALL VERIFY PIPING IN THE CRAWL SPACE AND REMOVE.

5. DEMOLISH FULL EXTENT OF MECHANICAL PIPING TO MECHANICAL

EQUIPMENT.

6. EXISTING STEAM PIPING TO REMAIN.

7. PRIOR TO DEMOLITION, CONDUCT EXISTING CONDITION TEST AND

BALANCE REPORT ON CHILLED WATER AND STEAM MAINS SERVING

BUILDING PER SPECIFICATION 23 05 93.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL

PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE

SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE

LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND

SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.

MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP

ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL

REMAIN IN SERVICE FOLLOWING DEMOLITION.

A

B

C

D

21 3 4 5 6 7 8 9 10 11 12

A'

1' 2' 3' 4'

A''

3" ø

M P

S

2"ø MPS

4"ø MPS

4"ø HPS

3" ø

M P

S

3"ø MPS

(X) HX

2" ø

M P

R

4" ø

M P

S

/F1 MD110 /F1 MD110

2" ø

L P

R

2"ø MPS

2" ø

M P

S 2" ø M

P S 2"ø LPR

2" ø

L P

R

4"ø HPS

1/

2" ø

M P

S

2" ø

L P

R

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

7:

A M

MD111

DEMOLITION PLANS - BASEMENT

SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION HVAC PLANS - BASEMENT - SOUTH

F1

1. DEMOLISH EXISTING WATER TANKS.

2. DEMOLISH EXISTING COMPRESSOR AND ASSOCIATED PIPING.

3. DEMOLISH EXISTING INLINE PUMPS.

4. DEMOLISH EXISTING STEAM CONDENSATE PUMP AND RECEIVER.

5. DEMOLISH EXISTING EXPANSION TANKS.

6. DEMOLISH ANY REMAINING MECHANICAL EQUIPMENT OR PIPING LOCATED

IN THE BASEMENT. PROVIDE RFI FOR ANY EQUIPMENT TO BE DEMOLISHED

THAT IS NOT IDENTIFIED PRIOR TO REMOVAL.

7. EXISTING STEAM PIPING TO REMAIN.

8. PRIOR TO DEMOLITION, CONDUCT EXISTING CONDITION TEST AND

BALANCE REPORT ON CHILLED WATER AND STEAM MAINS SERVING

BUILDING PER SPECIFICATION 23 05 93.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL

PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE

SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE

LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND

SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.

MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP

ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL

REMAIN IN SERVICE FOLLOWING DEMOLITION.

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

(E )4

0x

(E )3

6x

(E )2

4x

(E )2

0x

(E )2

0x

(E )2

0x

(E )2

0x x1

(E )3

0x

(E )2

4x

(E)48x20

(E)20x10

(E )2

0x

(E )2

0x

(E)20x10 (E)24x12

(E)24x12 (E)24x12

(E )1

2x

(E )1

8x

(E)18x10

(E )1

2x

(E )1

2x

(E)12x12

(E )1

2x

(E )1

2x

(E)8ø

(E)8ø

(E)8ø

(E)40x20

(E )3

0x

(E )3

0x

(E )8 ø (E

)8 ø

(E)40x20

(X) AC

(E) 2"ø MPS

(E) 1"ø MPR

(E) 1"ø MPR

(E)12x12

(E )2

0x

(E)12x12

6"ø MPR

6"ø MPR

4" ø

C H

R

1"ø MPS

1"ø MPS

1"ø MPS

1"ø MPS

2"ø NG

1 1/2"ø MPR

1"ø MPS

1"ø MPR

2"ø MPS

2"ø MPR

/F1 MD113 /F1 MD113

4" ø

C H

S 4" ø C

H R

3"ø MPS

3"ø MPS

3"ø MPS

3"ø MPS

6"ø CHS

6"ø CHR

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

7:

A M

MD112

DEMOLITION PLANS - LEVEL 1

NORTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION HVAC PLANS - LEVEL 1 - NORTH

F1

1. DEMOLISH EXISTING EXHAUST FAN.

2. DEMOLISH EXISTING DUCT WORK AT THIS APPROXIMATE LOCATION.

3. DEMOLISH EXISTING SOAP STATION AND ASSOCIATED PIPING.

4. DEMOLISH CHS/R PIPING FROM EXISTING AIR HANDLING UNITS BACK TO

MAIN.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL

PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE

SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE

LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND

SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.

MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP

ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL

REMAIN IN SERVICE FOLLOWING DEMOLITION.

A

B

C

D

21 3 4 5 6 7 8 9 10 11 12

A'

1' 2' 3' 4'

A''

(E )2

0x

(E )3

0x

(E )3

0x

(E)30x20

(E )1

2x

(E)48x24

(X) AHU-2

(X) AHU-1

(X) EF-7

(X) UH-1

(E

1" ø

M P

S

(E

3/ 4" ø M

P R

(E) 2"ø MPS

(E) 1"ø MPR

(E) 1"ø MPR

(E)12x12

18x12

3/4"ø MPS

3/4"ø MPR

1/

4" ø

M P

R

4" ø

C H

R

4" ø

C H

S

2"ø MPS2"ø MPR

6"ø CHR 6"ø CHS

1"ø MPS

1"ø MPS

1"ø MPS

1"ø MPS

2"ø MPS

2"ø MPR

/F1 MD112 /F1 MD112

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

SOUTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

SEE REVISION

SCHEDULE

R E

V

IS

IO

N

S C

H E

D U

L E

C :\R ev it

\2 2.

_M

E C

H -P

LU

M

_R

_H M al et z.

rv t

/7 /2

:5

7:

A M

MD113

DEMOLITION PLANS - LEVEL 1

SOUTH

CONSOLIDATE ENGINEERING

BLDG. 17

4800 MEMORIAL DR., WACO TX 76711

674A4-22-254

MR HM

100% CONSTRUCTION

DOCUMENTS

VEG 22.12

3/16" = 1'-0"

DEMOLITION HVAC PLANS - LEVEL 1 - SOUTH

F1

1. DEMOLISH AHU AND ASSOCIATED PIPING.

2. DEMOLISH GRILLES SERVED BY EXPOSED DUCT ABOVE.

3. DEMOLISH EXISTING CART WASH ASSEMBLY, DRAIN, AND ASSOCIATED

PLUMBING PIPING AND EXTERIOR EXHAUST.

4. EXISTING PASS THROUGH VENT TO REMAIN.

(X) AHU-6

(X) AHU-7

(X) AHU-5

(X) AHU-3

(X) AHU-9

(X) AHU-8

(X) AHU-4

(X) EF-4

(X) EF-5

(X) EF-3

(X) EF-2

(X) EF-6

1"ø CD

2"ø CHR

2"ø CHS

1"ø MPR 2"ø MPS

3" ø

C H

S

3" ø

C H

R

1/

4" ø

C D

1 1/4"ø MPR

2"ø MPS

1/

4" ø

M P

R

1/

2" ø

M P

S

2"ø CD

6"ø CHS

6"ø CHR

6" ø

C H

S

2" ø

C D

6" ø

C H

R

3" ø

C H

R

2" ø

C D

3" ø

C H

S

2"ø MPS 2"ø MPR

1 1/4"ø MPR

2"ø MPS

1/

2" ø

M P

S

1/

4" ø

M P

R

2"ø CD

6"ø CHS

6"ø CHR

3" ø

C H

S

2" ø

C D

3" ø

C H

R 2" ø N

G

2"ø NG

A

21 3 4 5 6 7 8 9 10 11 12

A'

B'

C'

D'

1' 2' 3' 4'

A'''

A''

3/4"ø NG

A. REFER TO M-001 AND M-002 FOR MECHANICAL SYMBOLS, ABBREVIATIONS,

AND GENERAL NOTES.

B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE

VHA COR BEFORE PROCEEDING WITH WORK.

C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED

LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP

PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE

SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL

PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN

SHALL GOVERN.

D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE

DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN

EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL

PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE

SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE

LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND

SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.

MAINTAIN EXISTING WARRANTIES.

E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT

PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING

HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN

ACCORDANCE WITH THE SPECIFICATIONS.

F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.

G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP

ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL

REMAIN IN SERVICE FOLLOWING DEMOLITION.

7' -6

5'

1"

5'

3/

8'

1/

1/

1"

0'

1"

0'

1"

0'

0'

1"

0'

1"

0'

9" 6"

3"

3"

1' -6

1'

6"

1/

2"

2' 1'

6"

1"

3' 2'

1'

3/ 4"

4'

2' 1'

1/

2"

6' 4'

2'

3/ 8"

8'

4'

3/

8' 4'

2'

1/ 4"

8'

4'

1/ 8"

KEY PLAN

GENERAL NOTES

SHEET KEYNOTES

P la n N or th

True North

NORTH

BLDG 17

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307

WWW.VALHALLAENGINEERING.COM

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEER…