PN 674A4-22-245_100ptc_VOL 2_23-12-07_MH.pdf
PDF 5 MB Posted
- Solicitation number
- 36C25726R0032
About this file
This is a comprehensive set of mechanical engineering construction documents for the U.S. Department of Veterans Affairs (VA) Consolidate Engineering Building 17 project located at 4800 Memorial Drive in Waco, Texas. The documents cover mechanical systems including HVAC, piping, controls, and demolition plans across multiple building levels. Key systems include a new air handling unit (17-AHU-1) with chilled water and steam heating capabilities, multiple exhaust fans, terminal units with hot water reheat, split system air conditioners, and a dust collection system. The project involves replacing existing mechanical equipment, with detailed plans for system modifications, including steam and hot water piping, air distribution, and control systems. The documents provide extensive technical specifications, equipment schedules, typical details, and installation guidelines, indicating a comprehensive renovation of the building's mechanical infrastructure.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25726R0032 0005.docx | DOCX document | |
| 36C25726R0032 0004_Consolidated Engineering Building 17.docx | DOCX document | |
| 36C25726R0032 0003.docx | DOCX document | |
| PN 674A4-22-245_100ptc_VOL 2_23-12-07_EL (1).pdf | ||
| 36C25726R0032 0002.docx | DOCX document | |
| PN 674A4-22-245_100ptc_VOL 2_23-12-07_FA.pdf | ||
| PN 674A4-22-245_100ptc_VOL 2_23-12-07_PL.pdf | ||
| Site visit sign in sheet 25_12_30.pdf | ||
| 36C25726R0032 0001.docx | DOCX document | |
| Attachment 1 Drawings PN 674A4-22-245_100ptc_VOL 1_23-12-07.pdf | ||
| Attachment 4 Itemized Cost Breakdown.xlsx | XLSX spreadsheet | |
| 36C25726R0032_2.docx | DOCX document | |
| Attachment 3 09-16368 Waco Bldg. 17 Report.pdf | ||
| Attachment 2 Specs PN674A4-22-254_100ptc_SPECS_12-08.pdf |
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
HVAC GENERAL NOTES
A. PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL BE CONCEALED
IN A FURRED CHASE OR ABOVE THE SUSPENDED CEILING. REF
SPECIFICATION 23 05 11.
B. THE FIRST FIGURE OF DUCT SIZE INDICATES DIMENSION OF FACE SHOWN
OR INDICATED. DUCT SIZES ARE NET INSIDE DIMENSIONS IN INCHES UNO.
REF SPECIFICATION 23 31 00.
C. REFER TO ARCHITECTURAL CEILING PLANS FOR CEILING TYPES IN EACH
SPACE. MINIMUM 18"X18" ACCESS PANELS ARE REQUIRED IN HARD CEILINGS
FOR VALVES, TRAPS, DAMPERS, CLEANOUTS, CONTROLS, AND SO FORTH.
COORDINATE FINAL LOCATIONS IN THE FIELD FOR BEST ACCESS. REF
SPECIFICATION 08 31 13.
D. TOTAL STATIC PRESSURE NOTED IN THE SCHEDULES INCLUDES DUCT
SYSTEM, TERMINAL UNITS, FILTERS, COILS, AND SO FORTH.
E. FOR TYPICAL STEAM AND WATER PIPING CONNECTIONS TO EQUIPMENT,
SEE EQUIPMENT DETAILS AND RESPECTIVE SPECIFICATIONS.
F. WATER PIPE CONNECTIONS TO AIR HEATING AND COOLING COILS SHALL BE
MADE TO PROVIDE COUNTER FLOW BETWEEN WATER AND AIR.
G. WALL TYPE EXHAUST REGISTERS NOTED AS "BR" ON DRAWINGS ARE TO BE
INSTALLED WITH BOTTOM ELEVATION OF REGISTER AT 7" ABOVE FINISHED
FLOOR.
H. PRESSURES LISTED ARE GAGE PRESSURE UNLESS NOTED OTHERWISE.
I. CONTROL SYSTEM EQUIPMENT SHALL BE COMPATIBLE WITH EXISTING
BUILDING MANAGEMENT SYSTEM CONTROLS. EXTEND EXISTING CONTROL
SYSTEM TO INCLUDE CONTROLS AND SEQUENCES SHOWN. REF
SPECIFICATION 23 09 23.
J. COORDINATE EXISTING FIRE SPRINKLER HEADS AND LIGHTS WITH DUCTS
AND DIFFUSERS.
K. SUBMIT COMPLETE CONSOLIDATED AND COORDINATED SHOP DRAWINGS
FOR NEW SYSTEMS, AND FOR EXISTING SYSTEMS THAT ARE IN THE SAME
AREAS. DO NOT INSTALL EQUIPMENT FOUNDATIONS, EQUIPMENT, OR PIPING
UNTIL COORDINATION/SHOP DRAWINGS HAVE BEEN APPROVED. REF
SPECIFICATION 01 33 23 AND 22 05 11.
L. OTHER THAN EQUIPMENT CONNECTIONS, MINIMUM HYDRONIC PIPE SIZE
SHALL BE 3/4". MINIMUM DUCT SIZE SHALL BE 8"X6".
M. PROVIDE LINE SIZE SERVICE VALVES AT POINTS OF CONNECTION TO
EXISTING MECHANICAL PIPING.
N. REFER TO GI SHEET SERIES FOR ADDITIONAL SYMBOLS AND LEGENDS,
WHERE NOT OTHERWISE DEFINED HERE.
GENERAL NOTES
A. PROVIDE TEMPORARY CONSTRUCTION PARTITIONS AND INFECTION
CONTROL BARRIERS AS APPLICABLE AROUND THE PROJECT AREA
CONSISTENT WITH THE CONTRACTOR'S PHASING PLAN AS APPROVED BY
THE VHA. REFER TO SPECIFICATION 01 35 26.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
7:
A M
M-001
MECHANICAL ABBREVIATIONS &
NOTES
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
A
A/E ARCHITECT / ENGINEER
AAV AUTOMATIC AIR VENT
ACCH AIR COOLED CHILLER
ACCU AIR-COOLED CONDENSING UNIT
ACD AUTOMATIC CONTROL DAMPER, MODULATING
ACD-TP AUTOMATIC CONTROL DAMPER, TWO POSITION
ACU AIR CONDITIONING UNIT
AD ACCESS DOOR
AF AFTER FILTER
AFCV AIR FLOW CONTROL VALVE
AFF ABOVE FINISHED FLOOR
AFMD AIR FLOW MEASURING DEVICE
AHU AIR HANDLING UNIT
AMP AMPERE
AP ACCESS PANEL
APD AIR PRESSURE DROP
ARCH ARCHITECTURE
ARI AIR CONDITIONING AND REFRIGERATION INSTITUTE
AS AIR SEPARATOR
ASHRAE AMERICAN SOCIETY OF HEATING, REFRIGERATION, AND
AIR CONDITIONING ENGINEERS
ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS
B
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BASC BUILDING AUTOMATION SYSTEM CONTRACTOR
BD BUTTERFLY DAMPER
BDD BACKDRAFT DAMPER
BDR BASE BOARD RADIATOR
BFP BACKFLOW PREVENTER
BFT BOILER PLANT FIRE TUBE
BG BOTTOM GRILLE
BHP BRAKE HORSEPOWER
BHW HOT WATER HEATING BOILER
BHX BOILER BLOWDOWN HEAT EXCHANGER
BLDG BUILDING
BOD BASIS OF DESIGN
BR BOTTOM REGISTER
BSC BIOLOGICAL SAFETY CABINETS
BT BLOWOFF TANK
BTC BLOWOFF TANK CONTROL VALVE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BWT BOILER PLANT WATER TUBE
C
CAP CAPACITY
CC COOLING COIL
CCD COOLING COIL CONDENSATE DRAIN
CD CONDENSATE DRAIN
CENT CENTRIFUGAL
CFH CUBIC FEET PER HOUR
CFM CUBIC FEET PER MINUTE
CFP CHEMICAL FEED PUMP
CFT CUBIC FEET
CG CEILING GRILLE
CH CHILLER
CHP CHILLED WATER PUMP
CHR CHILLED WATER RETURN
CHS CHILLED WATER SUPPLY
CI CAST IRON
CKT CIRCUIT
CLG COOLING
CM CARBON MONOXIDE
CO2 CARBON DIOXIDE
COMP COMPRESSOR UNIT
COP COEFFICIENT OF PERFORMANCE
CP CONDENSATE PUMP
CS CONDENSATE STORAGE TANK
CSG CLEAN STEAM GENERATOR
CT COOLING TOWER
CTRL CONTROL
CU CONDENSING UNIT
CUH CABINET UNIT HEATER
CUP CENTRAL UTILITY PLANT
CV CONSTANT VOLUME
CV CONTROL VALVE
CWCC CHILLED WATER COOLING COIL
CWP CONDENSER WATER PUMP
CWR CONDENSER WATER RETURN (TO COOLING TOWER)
CWS CONDENSER WATER SUPPLY (FROM COOLING TOWER)
D
D DAMPER
DB DECIBEL
DBT DRY BULB TEMPERATURE
DC DUST COLLECTOR
DCW DOMESTIC COLD WATER
DDC DIRECT DIGITAL CONTROLS
DEG DEGREES
DEMO DEMOLISH
MECHANICAL ABBREVIATIONS
DF DIFFUSER
DI DEIONIZED WATER
DIA DIAMETER
DN DOWN
DP DEW POINT TEMPERATURE
DP DIFFERENTIAL PRESSURE
DPS DIFFERENTIAL PRESSURE SENSOR
DX DIRECT EXPANSION
DXCC DIRECT EXPANSION COOLING COIL
E
E EXISTING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
EAT-DB ENTERING AIR TEMPERATURE DRY BULB
EC ELECTRONICALLY COMMUTATED
ECC ENGINEERING CONTROL CENTER
ECM ELECTRONICALLY COMMUTATED MOTOR
ECU EVAPORATIVE CONDENSER UNIT
EDH ELECTRIC DUCT HEATER
EER ENERGY EFFICIENCY RATIO
EF EXHAUST FAN
EFF EFFICIENCY
EG EXHAUST GRILLE
EGS EMERGENCY GAS SHUTOFF
EH EXHAUST HOOD
EJ EXPANSION JOINT
EMD END OF MAIN DRIP (STEAM)
ENT ENTERING
ER EXHAUST REGISTER
ERC ELECTRIC REHEAT COIL
ERP ELECTRIC RADIANT PANEL
ERW ENERGY RECOVERY WHEEL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
ETO ETHYLENE OXIDE
EUH ELECTRIC UNIT HEATER
EWC EVAPORATIVE WATER COOLER
EWT ENTERING WATER TEMPERATURE
F
F FAHRENHEIT
F&T FLOAT AND THERMOSTATIC
F/S FIRE SMOKE DAMPER
FA FIRE ALARM
FC FLEXIBLE CONNECTION
FCU FAN COIL UNIT (4 PIPE)
FCUC FAN COIL UNIT COOLING ONLY
FCUH FAN COIL UNIT HEATING ONLY
FD FLOOR DRAIN
FD FIRE DAMPER
FF FILTER FEEDER
FHX FLUE GAS/FEEDWATER HEAT EXCHANGER
FM FLOW METER
FOHX FUEL OIL HEAT EXCHANGER
FOP FUEL OIL PUMP
FOT FUEL OIL TANK
FPM FEET PER MINUTE
FPS FEET PER SECOND
FPTU FAN POWERED TERMINAL UNIT
FR FLOOR REGISTER
FRP FIBER REINFORCED POLYESTER
FS FLOW SWITCH
FSTAT FREEZESTAT
FT FEET
FT WG FEET WATER GAUGE
FT-LB FOOT-POUND
FTR FINNED TUBE RADIATION
FV FACE VELOCITY
G
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GH GRAVITY HOOD
GHW GLYCOL HEATING WATER
GPD GALLONS PER DAY
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GPR GAS PRESSURE REGULATOR
GS GALVANIZED STEEL
GWB GYPSUM WALL BOARD
H
H HUMIDIFIER
HAC HOUSEKEEPING AID CLOSET
HB HOSE BIBB
HC HEATING COIL
HD HEAD
HOA HAND/OFF/AUTOMATIC
HP HEAT PUMP
HP HORSEPOWER
HPDT HIGH PRESSURE DRIP TRAP
HPR HIGH PRESSURE RETURN (STEAM CONDENSATE)
HPS HIGH PRESSURE SUPPLY (STEAM)
HR HOUR
HRC HEAT RECOVERY COIL
HRD HEAT RECOVERY DEVICE
HRW HEAT RECOVERY WHEEL
HSTAT HUMIDISTAT
HTG HEATING
HTM HUMIDIFIER TERMINAL
HUM HUMIDIFIER UNIT MOUNTED
HVD HOISTWAY VENT DAMPER
HVLS HIGH VOLUME, LOW SPEED FAN
HVU HEATING AND VENTILATING UNIT
HW HOT WATER
HWC HOT WATER COIL
HWHC HOT WATER HEATING COIL
HWP HEATING WATER PUMP
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HWUH HOT WATER UNIT HEATER
HX HEAT EXCHANGER
HZ HERTZ
I
I/O INPUT/OUTPUT
IAQ INDOOR AIR QUALITY
IBT INVERTED BUCKET TRAP
ICU INTENSIVE CARE UNIT
ID INSIDE DIAMETER
IDU INDOOR UNIT
IFB INTEGRAL FACE AND BYPASS
IN INCHES
IN HG INCHES OF MERCURY
IN WC INCHES OF WATER COLUMN
IN WG INCHES OF WATER, GAUGE
IN-LB INCH-POUND
IOM INSTALLATION AND OPERATION MANUAL
IPLV INTEGRATED PART LOAD VALUE
IRH INFRARED HEATER
IS INSECT SCREEN
IU INDUCTION UNIT
IV INLET VANES
K
KEA KITCHEN EXHAUST AIR
KW KILOWATT
KWH KILOWATT HOURS
L
LAT LEAVING AIR TEMPERATURE
LAT-DB LEAVING AIR TEMPERATURE DRY BULB
LB POUND
LF LINEAR FOOT (FEET)
LGT LEAVING GLYCOL TEMPERATURE
LH LATENT HEAT
LLHX LIQUID TO LIQUID HEAT EXCHANGER
LPG LIQUID PROPANE GAS
LPR LOW PRESSURE RETURN (STEAM CONDENSATE)
LPS LOW PRESSURE STEAM
LSD LINEAR SLOT DIFFUSER
LTCP LOCAL TEMPERATURE CONTROL PANEL
LVG LEAVING
LVR LOUVER
LWT LEAVING WATER TEMPERATURE
M
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MAU MAKEUP AIR UNIT
MAV MANUAL AIR VENT
MAX MAXIMUM
MB MIXING BOX
MBH 1000 BTUH
MCA MINIMUM CIRCUIT AMPACITY
MEP MECHANICAL ELECTRICAL PLUMBING
MER MECHANICAL EQUIPMENT ROOM
MERV MINIMUM EFFICIENCY REPORTING VALUE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MOCP MAXIMUM OVERCURRENT PROTECTION
MOV MOTOR OPERATED VALVE
MPR MEDIUM PRESSURE RETURN (STEAM CONDENSATE)
MPS MEDIUM PRESSURE STEAM
MRI MAGNETIC RESONANCE IMAGING UNIT
MTD MEAN TEMPERATURE DIFFERENCE
MUA MAKEUP AIR
MV MECHANICAL VENT
MVD MANUAL VOLUME DAMPER
MZ MULTI-ZONE
N
NA NOT APPLICABLE
NC NOISE CRITERIA
NC NORMALLY CLOSED
NG NATURAL GAS
NGFM NATURAL GAS FLOW METER
NO NORMALLY OPEN
NOAA NATIONAL OCEANIC & ATMOSPHERIC ADMINISTRATION
NOM NOMINAL
NPLV NON-STANDARD PART LOAD VALUE
NPS NOMINAL PIPE SIZE
NPSH NET POSITIVE SUCTION HEAD
NPSHA NPSH AVAILABLE
NTS NOT TO SCALE
O
OA OUTSIDE AIR
OAG OUTSIDE AIR GRILLE
OAI OUTSIDE AIR INTAKE
OAL OUTSIDE AIR LOUVER
OD OUTER DIAMETER
ODU OUTDOOR UNIT
OFM OIL FLOWMETER
OH OVER HEAD
OR OPERATING ROOM
P
P PUMP
P&ID PROCESS & INSTRUMENTATION DIAGRAM
P/T PRESSURE/TEMPERATURE
PC PUMPED CONDENSATE
PCF POUNDS PER CUBIC FOOT
PD PRESSURE DROP
PF PRE-FILTER
PG PRESSURE GAUGE
PGW PROPYLENE GLYCOL-WATER SOLUTION
PH PHASE
PHC PREHEAT COIL
PPM PARTS PER MILLION
PRESS PRESSURE
PRV PRESSURE REGULATING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH, ABSOLUTE
PSIG POUNDS PER SQUARE INCH, GAGE
PSS PRIMARY SECONDARY SYSTEM
PSV PRESSURE SAFETY VALVE
PTAC PACKAGED TERMINAL AIR CONDITIONER
Q
QTY QUANTITY
R
RA RETURN AIR
RAD REFRIGERANT AIR DRYER
RAF RADIO FREQUENCY
RAHX ROTARY AIR HEAT EXCHANGER
RAT RETURN AIR TEMPERATURE
RCCH REMOTE CONDENSER CHILLER
RCP RADIANT CEILING PANEL
RD REFRIGERANT DISCHARGE
REA RELIEF AIR
REF REFERENCE OR REFER TO
RF RETURN FAN
RG RETURN GRILLE
RH RELATIVE HUMIDITY
RHC REHEAT COIL
RHG REFRIGERANT HOT GAS
RL REFRIGERANT LIQUID LINE
RLA RUN LOAD AMPERE
RO REVERSE OSMOSIS
RPM REVOLUTIONS PER MINUTE
RR RETURN REGISTER
RS REFRIGERANT SUCTION
RTU ROOFTOP UNIT
RV RELIEF VALVE
S
SA SUPPLY AIR
SAD SOUND ATTENUATING DEVICE
SAT SUPPLY AIR TEMPERATURE
SC SHADING COEFFICIENT
SCFM STANDARD CUBIC FEET PER MINUTE
SCR SILICON CONTROLLED RECTIFIER
SD SMOKE DETECTOR
SD SUPPLY AIR DIFFUSER
SDPR SMOKE DAMPER
SDR SMOKE DAMPER (RETURN)
SDS SMOKE DAMPER (SUPPLY)
SEN SENSIBLE HEAT
SF SUPPLY FAN
SFT STEAM FLASH TANK
SG SUPPLY AIR GRILLE
SH STEAM HUMIDIFIER
SHC STEAM HEATING COIL
SIM SIMILAR
SOO SEQUENCE OF OPERATION
SP STATIC PRESSURE
SP GR SPECIFIC GRAVITY
SPD SUPPLY PROCESS AND DISTRIBUTION
SPRV STEAM PRESSURE REDUCING VALVE
SPS STATIC PRESSURE SENSOR
SQ FT SQUARE FOOT
SQ IN SQUARE INCHES
SR SUPPLY AIR REGISTER
SSHX STEAM TO STEAM HEAT EXCHANGER
SSR SOLID SEPARATOR
SST STAINLESS STEEL
ST STEAM TRAP
STRUCT STRUCTURAL
SUH STEAM UNIT HEATER
SVS STEAM VENT SILENCER
SWHX STEAM TO WATER HEAT EXCHANGER
T
T&PCV TEMPERATURE AND PRESSURE CONTROL VALVE
TAB TESTING, ADJUSTING, AND BALANCING
TD TEMPERATURE DIFFERENCE
TDH TOTAL DYNAMIC HEAD
TDS TOTAL DISSOLVED SOLIDS
TG TRANSFER GRILLE
TP TRAP
TR TOP REGISTER
TSP TOTAL STATIC PRESSURE
TSTAT THERMOSTAT
TU TERMINAL UNIT
TWU THRU-WALL UNIT
U
UC UNIT COOLER
UCT UNDERCUT
UF UNDER FLOOR
UH UNIT HEATER
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
V
V VALVE
VAC VOLTAGE ALTERNATING CURRENT
VAV VARIABLE AIR VOLUME
VD VOLUME DAMPER (MANUAL OPPOSED BLADE)
VFD VARIABLE FREQUENCY DRIVE
VHA VETERANS HEALTH ADMINISTRATION
VI VIBRATION ISOLATOR
VIV VARIABLE INLET VANES
VP VACUUM PUMP
VPS VARIABLE PRIMARY SYSTEM
VR VACUUM (STEAM CONDENSATE) RETURN
VSD VARIABLE SPEED DRIVE
W
W WASTE
WAG WASTE ANESTHESIA GAS
WB WET BULB
WC WATER COOLED
WCCH WATER COOLED CHILLER
WCCU WATER COOLED CONDENSING UNIT
WCPU WATER COOLED HEAT PUMPS
WF WATER FILTER
WFCV WATER FLOW CONTROL VALVE
WFE WELDING FUME EXTRACTOR
WFM WATER FLOWMETER
WFMD WATER FLOW MEASURING DEVICE
WG WATER GAGE
WPD WATER SIDE PRESSURE DROP
X
XP EXPLOSION-PROOF
Y
YR YEAR
Number: Revision: Date:
0 100% CONSTRUCTION DOCUMENTS 12/08/2023
T
TT
M
MT
PT
TT
FT
IT
CT
SD
PDT
TSL
HS
M
LC
LT
PDS
TSH
EPT
AT
CO2
AT
CO
AT
OC
LTCP
VFD
PSH
PSL
26-SF 3
26-TU-1-1
H4
H7
A
BDD
FD
VD
N
1/24
F/S DPR
AV
MV
RH
SCH
SH
TH
PS
RC
WB
CSH
SS
VR
CTPS
CTPD
FWPS
FWPD
CF
FWS
BWS
CBD
BO
TC
A
OFL
HW
SW
CW
FOR
FOS
LPG(I)
NG(I)
NG
HPS
HPR
MPS
MPR
LPS
LPR
PC
HWS
HWR
GHS
GHR
V
SWS
SWR
CWR
CHR
GCR
RL
RS
RHG
CWS
CHS
GCS
MW
D
GRR
GRS
D
R
FC
10x8
M
DETAIL REFERENCE
DRAWING NUMBER WHERE SHOWN
SECTION REFERENCE
TYPICAL UNIT NUMBER
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED.
SUPPLY FAN NUMBER 3 IN BUILDING NUMBER 26
EQUIPMENT ABBREVIATION (EG SUPPLY FAN)
ITEM NUMBER (TERMINAL UNIT NUMBER 1)
ITEM (TERMINAL UNIT SHOWN)
SERVED BY AIR HANDLER UNIT NUMBER 1
DRAWING NUMBER WHERE DRAWN
BUILDING NUMBER WHERE EQUIPMENT IS LOCATED
* TYPE NUMBERS REFER TO MANUFACTURER'S STANDARDIZATION SOCIETY STANDARD PRACTICE SP-58
TEST PLUG (P/T PORT)
AUTOMATIC AIR VENT
MANUAL AIR VENT
QUICK-COUPLE HOSE CONNECTOR
CONNECT TO EXISTING
LIMIT OF DEMOLITION
AIR SEPARATOR
EXISTING DUCT TO BE REMOVED
LOUVER (REF SPECIFICATION 08 90 00)
FLEXIBLE DUCTWORK (INSULATED)
DUCT WITH SOUND LINING
MANUAL VOLUME DAMPER
FIRE DAMPER
BACK DRAFT DAMPER
COMBINATION FIRE/SMOKE DAMPER
AUTOMATIC CONTROL DAMPER
2'x2' RADIANT CEILING PANEL
2'x4' RADIANT CEILING PANEL
SUPPLY DUCT (UP & DOWN)
EXHAUST DUCT (UP & DOWN)
RETURN DUCT (UP & DOWN)
ROUND AND SQUARE 4-WAY CEILING DIFFUSERS
SQUARE 3-WAY CEILING DIFFUSERS
SQUARE 2-WAY CEILING DIFFUSERS
SQUARE 1-WAY CEILING DIFFUSERS
LINEAR SLOT DIFFUSER
SUPPLY REGISTER OR GRILLE (WALL TYPE)
EXHAUST OR RETURN CEILING
REGISTER OR GRILLE
EXHAUST OR RETURN REGISTER
OR GRILLE (WALL TYPE)
VANED ELBOW & AIR SPLIT TYPE DUCT TAKE-OFF
(REF MK SHEET SERIES)
CONNECT NEW DUCT TO EXISTING DUCT
INCLINED RISE, IN DIRECTION OF AIR FLOW
INCLINED DROP, IN DIRECTION OF AIR FLOW
LIMIT OF DEMOLITION
FLEXIBLE CONNECTION, EQUIPMENT,
VIBRATION, OR SEISMIC
VANED ELBOW (PROVIDE ALL SQUARE OR
RECTANGULAR ELBOWS WITH VANES EVEN IF
SYMBOL IS MISSING)
VANED ELBOW (SHORT RADIUS)
STANDARD RADIUS ELBOW (LONG RADIUS)
NEW DUCT (INSIDE DIMENSIONS, INCHES):
WIDTH x DEPTH (RECTANGULAR)
WIDTH / DEPTH (FLAT OVAL)
DIAMETER Ø (ROUND)
EXISTING DUCT TO REMAIN
GENERIC VALVE (REF SPEC FOR TYPE)
GLOBE VALVE
3/4" HOSE ADAPTER
CHECK VALVE
WYE STRAINER (WITH BALL VALVE & HOSE CONNECTION)
FLEXIBLE PIPE CONNECTOR
ANGLE GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CONTROL VALVE
CONTROL BUTTERFLY VALVE
THREE-WAY CONTROL VALVE
PRESSURE REGULATING (IE REDUCING) VALVE
PRESSURE SAFETY VALVE / RELIEF VALVE
WATER FLOW BALANCE VALVE
GATE VALVE WITH GLOBE-VALVED BYPASS
PLUG VALVE
CONTROL VALVE (CV) - FLOAT-OPERATED
FLOW METER
ROOM THERMOSTAT/TRANSMITTER - WALL MOUNT
ROOM HUMIDISTAT (MOISTURE)/TRANSMITTER -
WALL MOUNT
TEMPERATURE TRANSMITTER
TEMPERATURE TRANSMITTER, AVERAGING ELEMENT
MOISTURE (HUMIDITY) TRANSMITTER
PRESSURE TRANSMITTER
FLOW TRANSMITTER
CURRENT TRANSMITTER
CONDUCTIVITY TRANSMITTER
SMOKE DETECTOR
PRESSURE DIFFERENTIAL TRANSMITTER
PRESSURE DIFFERENTIAL SWITCH
HAND SWITCH (HAND-OFF-AUTO SWITCH)
VALVE OR DAMPER ACTUATOR
TEMPERATURE SWITCH, LOW (FREEZESTAT)
TEMPERATURE SWITCH, HIGH
LEVEL CONTROLLER
LEVEL TRANSMITTER
PRESSURE SWITCH HIGH
PRESSURE SWITCH LOW
ELECTRONIC TO PNEUMATIC TRANSDUCER
CARBON DIOXIDE TRANSMITTER
CARBON MONOXIDE TRANSMITTER
OCCUPANCY SENSOR
LOCAL TEMPERATURE CONTROL PANEL
VARIABLE SPEED MOTOR CONTROLLER
CONTROLS SYMBOLS
GENERAL SYMBOLS AND TAGS
HVAC SYMBOLS PIPING SYMBOLSPIPING SYMBOLSHVAC SYMBOLS
FLOOR-SUPPORTED PIPE STAND
RISER CLAMP (TYPE 42)*
WALL BRACKET (TYPE 31, 32, 33)*
CONSTANT SUPPORT HANGER (TYPE 54, 55, 56)*
SLIDING SUPPORTS (TYPE 35)*
TRAPEZE HANGER (PROVIDE U-BOLT PIPE ATTACHMENT
TO TRAPEZE EXCEPT WHERE RH ARE INDICATED)
HOT WATER
ROLLER-TYPE HANGER
VARIABLE SPRING-TYPE HANGER (TYPE 51)*
SPRING CUSHION-TYPE HANGER (TYPE 48 OR 49)*
CLEVIS-TYPE HANGER
HIGH PRESSURE STEAM (60 PSIG AND ABOVE)
HIGH PRESSURE STEAM CONDENSATE RETURN
MEDIUM PRESSURE STEAM (16 PSIG THRU 59 PSIG)
MEDIUM PRESSURE STEAM CONDENSATE RETURN
LOW PRESSURE STEAM (15 PSIG AND BELOW)
LOW PRESSURE STEAM CONDENSATE RETURN
CONDENSATE PUMP DISCHARGE
HEATING WATER SUPPLY
HEATING WATER RETURN
GLYCOL-WATER HEATING SUPPLY
GLYCOL-WATER HEATING RETURN
SOLAR WATER SUPPLY
SOLAR WATER RETURN
REFRIGERANT LIQUID
REFRIGERANT SUCTION
REFRIGERANT HOT GAS
CONDENSER WATER SUPPLY (FROM TOWER)
CONDENSER WATER RETURN (TO TOWER)
CHILLED WATER SUPPLY
CHILLED WATER RETURN
GLYCOL-WATER CHILLED SUPPLY
GLYCOL-WATER CHILLED RETURN
MAKE-UP WATER
DRAIN LINE
VENT LINE
GLYCOL-WATER RUN AROUND SUPPLY
GLYCOL-WATER RUN AROUND RETURN
FEEDWATER PUMP DISCHARGE
FEEDWATER PUMP SUCTION
CONDENSATE TRANSFER PUMP DISCHARGE
CONDENSATE TRANSFER PUMP SUCTION
VACUUM CONDENSATE RETURN
TUBE CLEANER WATER SUPPLY
BOILER BLOWOFF
CONTINUOUS BLOWDOWN
BOILER WATER SAMPLE
FEEDWATER SAMPLE (FROM DEAERATOR)
CHEMICAL FEED
OVERFLOW
COMPRESSED AIR
NATURAL GAS MAIN FUEL
NATURAL GAS IGNITER FUEL
LIQUEFIED PETROLEUM GAS IGNITER FUEL
FUEL OIL SUPPLY
FUEL OIL RETURN
COLD WATER (CITY WATER)
SOFTENED WATER
THERMOMETER
PRESSURE GAGE
FLOW ELEMENT
SIGHT GLASS
THERMOSTATIC TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
FLOAT & THERMOSTATIC TRAP SET
INCLUDING PIPING ACCESSORIES SEE DETAIL
INVERTED BUCKET TRAP SET INCLUDING
PIPING ACCESSORIES SEE DETAIL
DIRECTION OF PIPE PITCH (DOWN)
DIRECTION OF FLOW
ANCHOR
REDUCER OR INCREASER
ECCENTRIC REDUCER
TOP CONNECTION, 45° OR 90°
BOTTOM CONNECTION, 45° OR 90°
SIDE CONNECTION
CAPPED OUTLET
RISE OR DROP IN PIPE
UNION
PIPE UP
PIPE DOWN
POINT OF CHANGE IN DUCT CONSTRUCTION BY STATIC
PRESSURE CLASS. THE NUMBER ASSIGNS PRESSURE
CLASS (IN OF WATER) WHICH WILL ACCOMMODATE
MAXIMUM OPERATING PRESSURE IN THE DUCT
SUBSECTION. THE SYMBOL CONTINUES THE
ASSIGNMENT UNTIL THE DUCT TERMINATES OR
ANOTHER SYMBOL APPEARS. A "N" SUPERSCRIPT
INDICATES NEGATIVE PRESSURE.
FE
DEMOLISHED EQUIPMENT (SHAPE VARIES, REF:
SYMBOLS, TAGS, & NOTES)
(E) EXISTING COMPONENT
(X) DEMOLISHED COMPONENT
PIPE TO BE DEMOLISHED
MS MOISTURE (HUMIDITY) SWITCH
FSH FLOW SWITCH HYDRONIC
DS DOOR SWITCH
PR PILOT RELAY
MOTOR STARTER
WELDED STAINLESS STEEL DUCT
PROVIDE FLEXIBLE SHAFT WRAP A MINIMUM OF 10 FT ON
BOTH SIDES OF FIRE BARRIER PENETRATIONS. THE FIRE
RESISTIVE RATING OF THE WRAP SHALL BE EQUIVALENT TO
THAT OF THE BARRIER PENETRATED. WRAP ENTIRETY OF
RISERS WITHIN SHAFTS SHARED WITH ENVIRONMENTAL AIR
DUCTS.
AIR DEVICE MARK
AIR DEVICE CFM1,200
SD-1
GUIDE
WM WATER FLOW METER
SENSOR WELL / O-LET
NEW PIPING
EXISTING PIPING
MV MECHANICAL VENT LINE
CD CONDENSATE DRAIN LINE
AFMD AIR FLOW MEASUREMENT DEVICE
PUMP TRAP SET INCLUDING PIPING
ACCESSORIES SEE DETAIL
STANDARD BRANCH SUPPLY OR
RETURN, NO SPLITTER (45° TAP)
DUCT-MOUNTED COIL (HOT WATER
OR STEAM COIL)
DUCT-MOUNTED COIL (ELECTRIC)
SDPR
SMOKE DAMPER
## GENERAL EQUIPMENT FURNISHED BY OTHERS; REF MQ
SHEET SERIES FOR CONNECTION SCHEDULE
DOUBLE-LINED VALVE
(REFER TO SPECS FOR TYPE)
# MI7##
DETAIL
SHEET
EQUIPMENT APPLICABLE P&ID, SOO, &
POINT LIST REFERENCE
NEW EQUIPMENT (SHAPE VARIES, REF: SYMBOLS, TAGS,
& NOTES. SCHEDULED ITEMS ARE NEW UNO)
SD DUCT SMOKE DETECTOR, UL268A. PROVIDE PER
NFPA 90A AND SPECIFICATION 28 31 00.
COORDINATE WITH FA CONTRACTOR.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
7:
A M
M-002
MECHANICAL SYMBOLS CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12Number: Revision: Date:
A. PROVIDE SCHEDULED BASIS OF DESIGN OR APPROVED EQUAL. REFER TO
SPECIFICATIONS 01 33 23 AND 23 05 11 FOR FURTHER REQUIREMENTS.
B. SELECT EQUIPMENT FOR SCHEDULED PERFORMANCE AT 460 FT ELEVATION.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTIONS 23 73 00 AND 23 74 13.
2. REFER TO MQ SHEET SERIES FOR
DEFAULT COMPONENT LOCATIONS
AND MINIMUM DIMENSIONS, UNO.
3. PROVIDE MIXING BOX.
4. PROVIDE WITH FACTORY SUPPLIED
ROOF CURB.
5. REFER TO FAN SCHEDULE FOR FAN
CIRCUIT POWER.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 34 00.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 13.
2. BASIS OF DESIGN BELL AND
GOSSETT SU-43-2.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 34 00.
2. REFER TO AHU SCHEDULE THIS
SHEET FOR RELATED
COMPONENTS. POWER FOR FAN IS
A PART OF THE SINGLE POINT
POWER ABOVE.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 82 16.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 40 00.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 13.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 36 00.
2. PROVIDE WITH FACTORY SOUND
ATTENUATOR.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 34 00.
2. SPARK RESISTANT CONSTRUCTION.
REMARKS:
1. SPARK RESISTANT CONSTRUCTION.
2. PROVIDE WITH DIRECT DRIVE FAN,
AIRFLOW AND DELTA P
CONTROLLERS, EXPLOSION
PROTECTION. INSTALL PER
MANUFACTURER'S
RECOMMENDATION.
3. REFER ALSO TO SPECIFICATION
SECTION 23 34 00.
REMARKS:
1. PROVIDE WITH FLEXIBLE 13' FUME
EXTRACTION ARM EQUIPPED WITH
ARC SENSOR, LAMP KIT, AND
ASSOCIATED FAN.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
8:
A M
MQ601
EQUIPMENT SCHEDULES CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
EXHAUST FAN (EF) SCHEDULE
MARK LOCATION AREA SERVED
AIRFLOW
(CFM)
ESP
(IN WG)
FAN MOTOR
BAS
CONTROLS
BOD MFR AND MODEL REMARKS
TYPE DRIVE
ELECTRICAL SPEED
CONTROLHP VAC Φ MCA MOCP
17-GEF-1 ROOF 148A, 148, 148B 3221 0.5
CENTRIFUGAL -
UPBLAST
BELT 3/4 208 3 4.4 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK CUBE-200 1
17-GEF-2 ROOF
132, 132A, 131, 136, 136B, 134, 1790 0.5
CENTRIFUGAL -
UPBLAST
DIRECT 1/2 208 3 3 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
CUE-120-A
17-GEF-3 ROOF 110, 117 510 0.5
CENTRIFUGAL -
UPBLAST
DIRECT 1/4 208 1 4.00 7.27
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
CUE-099-A
17-GEF-4 ROOF 125, 126 1040 0.5
CENTRIFUGAL -
UPBLAST
DIRECT 1/4 208 3 3 15
VFD -
REMOTE
VARIABLE
SPEED
GREENHECK
CUE-130-B
HEAT EXCHANGER (HX) SCHEDULE
MARK LOCATION
AREA/SYSTEM
SERVED
HX TYPE
COLD SIDE STEAM PRESSURE (PSIG)
STEAM
TRAP MARK
REMARKSEWT
(°F)
LWT
(°F)
GPM
WPD
(FT WG)
ENTERING
CONTROL
VALVE
ENTERING
HX
17-HX-1 BASEMENT BLDG 17 SHELL & TUBE 150 180 30 0.52 30 25 ST-1 1, 2
17-HX-2 BASEMENT BLDG 17 SHELL & TUBE 150 180 30 0.52 30 25 ST-3 1, 2
AIR HANDLING UNIT (AHU) SUMMARY SCHEDULE
MARK LOCATION
AREA AND/OR
BLDG SERVED
SUPPLY
AIRFLOW
(CFM)
OUTSIDE
AIRFLOW
(CFM)
SUPPLY
FAN
RETURN
FAN
EXHAUST
FAN
PRE-
FILTER
AFTER-
FILTER
HEAT
RECOVERY
PREHEAT
COIL
COOLING
COIL
REHEAT
COIL
HUMIDIFIER
OVERALL
HEIGHT (IN)
OVERALL
LENGTH (IN)
OVERALL
WIDTH (IN)
POWER
BOD MFR
AND MODEL
REMARKS
VAC PH MCA MOCP
17-AHU-1
LEVEL
2/ROOF
BUILDING 17 19410 6688 17-SF-1 17-RF-1 - 17-PF-1 17-AF-1 - 17-PH-1 17-CC-1 - 17-H-1 99.5 169 546 115 1 20 30
TRANE
CUSTOM
AHU
1, 2, 3, 4, 5
AHU SUPPLY FAN SCHEDULE
MARK
TOTAL
AIRFLOW
(CFM)
ESP (IN WG) TYPE FAN QTY VFD
ELECTRICAL DATA (TOTAL ARRAY UNO)
REMARKSMOTOR HP
(EACH)
VAC PH FLA MOCP
17-SF-1 19410 2.19
DIRECT
DRIVE
2 YES 15 460 3 37 80 1,2
AHU RETURN FAN SCHEDULE
MARK
TOTAL
AIRFLOW
(CFM)
ESP
(IN WG)
TYPE
FAN
QTY
VFD
ELECTRICAL DATA (TOTAL ARRAY UNO)
REMARKSMOTOR HP
(EACH)
VAC PH MCA MOCP
17-RF-1 15440 0.39 DIRECT DRIVE 1 Y 7.5 460 3 11.5 20 1,2
AHU PREHEAT COIL SCHEDULE
MARK
HEATING
AIRFLOW
(CFM)
MAX FV
(FPM)
APD
(IN WG)
EAT-DB
(°F)
LAT-DB
(°F)
MIN
CAPACITY
(MBH)
STEAM
PSIG ENT
CNTRL
VALVE
PSIG
ENT
COIL
STEAM
FLOW
(LB/H)
17-PH-1 15531 450 0.027 48.1 93.8 261 30 25 281
AHU COOLING COIL SCHEDULE
MARK
AIRFLOW
(CFM)
MAX FV
(FPM)
APD (IN WG)
EAT-DB
(°F)
EAT-WB
(°F)
LAT-DB
(°F)
LAT-WB
(°F)
SEN
MBH
TOTAL
MBH
CHILLED WATER (CHW)
GLYCOL
EWT
(°F)
LWT
(°F)
FLOW
(GPM)
WPD
(FT WG)
17-CC-1 19410 450 0.501 85 70 55 54.3 615 1016 - 42 57 171 9.06
AHU PRE-FILTER SCHEDULE
MARK
MERV
RATING
AIRFLOW
(CFM)
MAX
FINAL APD
(IN WG)
THICKNESS
(IN)
FILTER/RACK
TYPE
17-PF-1 7+14 19410 1+1.2 2+6 CARTRIDGE
AHU HUMIDIFIER SCHEDULE
MARK TYPE
DESIGN HUMIDIFICATION
AIRFLOW
(CFM)
EA-DP (°F) LA-DP (°F)
STEAM
SOURCE
PSIG ENT
CONTROL VALVE
PSIG ENT
COIL
STEAM
LOAD (LB/H)
17-H-1
DISPERSION
TUBE
15531 11.7 47 MPS 30 25 241.3
TERMINAL UNIT (TU) SCHEDULE
MARK TYPE
MAX
CFM
MIN
CFM
MAX
TOTAL
APD
(IN WG)
REHEAT COIL
SINGLE POINT
ELECTRICAL
BOD MFR
AND MODEL REMARKSSOURCE
HTG
CFM
EAT
(°F)
LAT
(°F) MBH
EWT
(°F) GPM
WPD
(FT WG) VAC PH
MAX
LOAD
(VA)
17-TU-1
SINGLE
DUCT
220 70 0.5 HW 70 55 91 2.66 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-2
SINGLE
DUCT
150 70 0.5 HW 70 55 85 2.10 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-3
SINGLE
DUCT
240 70 0.5 HW 70 55 93 2.82 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-4
SINGLE
DUCT
150 70 0.5 HW 70 55 85 2.14 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-5
SINGLE
DUCT
160 70 0.5 HW 70 55 85 2.20 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-6
SINGLE
DUCT
350 290 0.5 HW 290 55 85 8.23 180 0.55 0.20 120 1 15 PRICE SDV 1, 2
17-TU-7
SINGLE
DUCT
950 300 0.5 HW 300 55 88 10.39 180 0.69 0.44 120 1 15 PRICE SDV 1, 2
17-TU-8
SINGLE
DUCT
300 250 0.5 HW 250 55 85 6.01 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-9
SINGLE
DUCT
180 170 0.5 HW 170 55 85 4.01 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-10
SINGLE
DUCT
120 110 0.5 HW 110 55 85 2.61 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-11
SINGLE
DUCT
681 560 0.5 HW 641 55 85 12.58 180 0.84 0.63 120 1 15 PRICE SDV 1, 2
17-TU-12
SINGLE
DUCT
340 90 0.5 HW 90 55 89 3.23 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-14
SINGLE
DUCT
130 110 0.5 HW 110 55 85 2.40 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-15
SINGLE
DUCT
360 300 0.5 HW 300 55 85 7.21 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-16
SINGLE
DUCT
140 70 0.5 HW 70 55 85 1.90 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-17
SINGLE
DUCT
110 90 0.5 HW 90 55 85 2.16 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-18
SINGLE
DUCT
230 210 0.5 HW 210 55 85 5.00 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-19
SINGLE
DUCT
170 160 0.5 HW 160 55 85 3.76 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-21
SINGLE
DUCT
210 190 0.5 HW 190 55 85 4.48 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-22
SINGLE
DUCT
270 70 0.5 HW 70 55 90 2.58 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-23
SINGLE
DUCT
100 70 0.5 HW 70 55 85 1.65 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-24
SINGLE
DUCT
100 70 0.5 HW 70 55 85 1.56 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-25
SINGLE
DUCT
100 70 0.5 HW 70 55 85 1.66 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-26
SINGLE
DUCT
260 170 0.5 HW 170 55 85 4.03 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-27
SINGLE
DUCT
540 190 0.5 HW 190 55 93 7.63 180 0.50 0.18 120 1 15 PRICE SDV 1, 2
17-TU-28
SINGLE
DUCT
150 100 0.5 HW 100 55 85 2.66 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-29
SINGLE
DUCT
100 70 0.5 HW 70 55 85 1.65 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-30
SINGLE
DUCT
260 250 0.5 HW 250 55 85 5.54 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-31
SINGLE
DUCT
220 200 0.5 HW 200 55 85 5.19 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-32
SINGLE
DUCT
740 430 0.5 HW 430 55 86 9.77 180 0.65 0.40 120 1 15 PRICE SDV 1, 2
17-TU-33
SINGLE
DUCT
190 180 0.5 HW 180 55 85 4.24 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-34
SINGLE
DUCT
990 990 0.5 HW 990 55 86 18.6 180 0.88 0.68 120 1 15 PRICE SDV 1, 2
17-TU-35
SINGLE
DUCT
230 220 0.5 HW 220 55 85 6.42 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-36
SINGLE
DUCT
2620 1950 0.5 HW 1950 55 85 38.6 180 2.26 0.73 120 1 15 PRICE SDV 1, 2
17-TU-37
SINGLE
DUCT
670 550 0.5 HW 550 55 85 13.26 180 0.88 0.68 120 1 15 PRICE SDV 1, 2
17-TU-38
SINGLE
DUCT
1290 1240 0.5 HW 1240 55 85 24.5 180 1.93 0.46 120 1 15 PRICE SDV 1, 2
17-TU-39
SINGLE
DUCT
310 300 0.5 HW 300 55 85 8.68 180 0.58 0.22 120 1 15 PRICE SDV 1, 2
17-TU-40
SINGLE
DUCT
110 110 0.5 HW 110 55 85 2.36 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-41
SINGLE
DUCT
110 110 0.5 HW 110 55 85 2.36 180 0.50 0.17 120 1 15 PRICE SDV 1, 2
17-TU-42
SINGLE
DUCT
310 300 0.5 HW 300 55 85 8.68 180 0.50 0.22 120 1 15 PRICE SDV 1, 2
17-TU-43
SINGLE
DUCT
1870 1800 0.5 HW 1800 55 85 34.2 180 2.61 0.95 120 1 15 PRICE SDV 1, 2
17-TU-44
SINGLE
DUCT
1340 730 0.5 HW 730 55 85 19.44 180 1.30 0.23 120 1 15 PRICE SDV 1, 2
AIR CURTAIN (AC) SCHEDULE
MARK LOCATION AREA SERVED
MIN HEATING
CAPACITY(MBH)
FAN MOTOR
BOD MFR AND MODEL REMARKS
TYPE DRIVE
ELECTRICAL SPEED
CONTROLHP VAC Φ
17-AC-1 153 RECEIVING 18.4 ELECTRIC DIRECT 1/2 208 3 VFD BERNER IDC12 1
17-AC-2 153 RECEIVING 18.4 ELECTRIC DIRECT 1/2 208 3 VFD BERNER IDC12 1
17-AC-3 148B WELDING 14.4 ELECTRIC DIRECT 1/2 208 3 VFD BERNER IDC12 1,2
DUST COLLECTOR (DC) SCHEDULE
MARK LOCATION AREA SERVED
MINIMUM
AIRFLOW
(CFM)
FAN MOTOR
BOD MFR AND MODEL REMARKS
TYPE DRIVE
ELECTRICAL SPEED
CONTROLHP VAC Φ
17-DC-1
PLAN SOUTH
EXTERIOR
CARPENTRY SHOP 6575 CENTRIFUGAL DIRECT 30 208 3 VFD
DONALDSON TORIT
36-30
1,2,3
WELDING FUME EXTRACTOR (WFE) SCHEDULE
MARK LOCATION AREA SERVED
MERV
RATING
TYPE
MOTOR
BOD MFR AND MODEL REMARKSELECTRICAL SPEED
CONTROLHP VAC Φ
17-WFE-1 148B WELDING 14
WALL MOUNTED
EXTRACTION UNIT
1 208 3 -
LINCOLN ELECTRIC
PRISM
A. PROVIDE SCHEDULED BASIS OF DESIGN OR APPROVED EQUAL. REFER TO
SPECIFICATIONS 01 33 23 AND 23 05 11 FOR FURTHER REQUIREMENTS.
B. SELECT EQUIPMENT FOR SCHEDULED PERFORMANCE AT 460 FT ELEVATION.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 23.
2. MULTIPLEX PUMP AND VENTED
RECEIVER PACKAGE. SIZE PUMP
MODULES FOR N+1 REDUNDANCY
SUCH THAT THE SCHEDULED
CAPACITY IS MET GIVEN FAILURE OF
1 MODULE.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 13.
2. MAX WIDE OPEN VALVE FLOW AT
SET PRESSURE + 5 PSIG SHALL BE
LESS THAN ASSOCIATED SAFETY
RELIEF VALVE.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 13.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 13.
2. FOR PUMP TRAPS, SCHEDULED
INLET PRESSURE IS MOTIVE
PRESSURE AND DP IS MOTIVE
MINUS BACK PRESSURE.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 81 00.
2. IDU POWERED BY ASSOCIATED
OUTDOOR UNIT.
3. PROVIDE SECONDARY DRAIN PANS
FOR INDOOR UNITS.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 21 23.
REMARKS:
1. REFER ALSO TO SPECIFICATION:
A. 23 21 13 FOR EXPANSION TANKS,
AIR SEPARATORS, BUFFER
TANKS.
B. 23 25 00 FOR FILTERS FEEDERS
AND GLYCOL MAKEUP SYSTEMS.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 82 00.
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 37 00.
2. MATCH RUN-OUT TO NECK SIZE
UNLESS OTHERWISE TAGGED.
3. BLACK SHADED CELLS INDICATE
NECK SIZES NOT APPLICABLE TO
GIVEN AIR DEVICE.
4. S1R-#, # INDICATES NOMINAL FRAME
DIAMETER
REMARKS:
1. REFER ALSO TO SPECIFICATION
SECTION 23 22 13 AND MK SHEET
SERIES DETAILS.
2. BOD IS ARMSTRONG HAFT.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
GENERAL NOTES
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
8:
A M
MQ602
EQUIPMENT SCHEDULES CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
SPLIT SYSTEM AIR CONDITIONER OUTDOOR UNIT (ODU) SCHEDULE
MARK
INDOOR
UNIT
SERVED
STAGES
COOLING REQUIREMENTS HEATING REQUIREMENTS ELECTRICAL DATA
BOD MFR AND
MODEL
REMARKSMIN NET
CAPACITY
(MBH)
MIN
EER / SEER
AMBIENT
TEMP
(°F)
MIN NET
CAPACITY
(MBH)
MIN COP
AMBIENT
TEMP
(°F)
VAC PH MCA MOCP
17-ODU-1
17-IDU-1,
17-IDU-2
- 27.0 3.40 99.2 - - - 208 1 30 40 CARRIER RAV 1
17-ODU-2
17-IDU-1,
17-IDU-2
- 27.0 3.40 99.2 - - - 208 1 30 40 CARRIER RAV 1
17-ODU-3 17-IDU-3 - 5.95 3.40 99.2 - - - 208 1 15 15 CARRIER 38MARB 1
STEAM TRAP (ST) SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
CAPACITY AT
MIN DP
MIN DP
(PSIG)
MIN INLET
PRESSURE
(PSIG)
TRAP TYPE REMARKS
ST-DS
DRIP
STATIONS
LPS,MPS,HPS AS
APPLICABLE
REF 23 22 13 REF 23 22 13 REF 23 22 13 IB 1
ST-1 17-HX-1 MPS 973 1/4 25 F&T 1
ST-2 17-HX-2 MPS 973 1/4 25 F&T 1
ST-3 17-SDWH-1 LPS 4615 1/4 10 F&T 1
ST-4 17-PH-1 MPS 979 1/4 25 F&T 1
ST-5 17-H-1 MPS 111 5 25 IB 1
STEAM PRESSURE RELIEF SAFETY VALVE (SV) SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
MIN
CAPACITY
(LB/HR)
SET
PRESSURE
(PSIG)
NORMAL
LINE
PRESSURE
(PSIG)
BASIS OF
DESIGN
REMARKS
17-SV-1 BASEMENT MPS 818 35 30
SPIRAX SARCO
17-SV-2 BASEMENT LPS 1846 20 15
SPIRAX SARCO
STEAM PRESSURE REDUCING VALVE (SPRV) SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
MIN
CAPACITY
(LB/HR)
PRESSURE
IN
(PSIG)
PRESSURE
OUT
(PSIG)
REMARKS
17-SPRV-1 BASEMENT MPS 818 55 30 1, 2
17-SPRV-2 BASEMENT LPS 1846 55 15 1, 2
STEAM CONDENSATE PUMP (SCP) SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
PUMP TYPE
CONTINUOUS
LOAD
(LB/HR)
DISCHARGE
PRESSURE
(PSIG)
RECEIVER &
VENT FLASH
STEAM
CAPACITY
(LB/HR)
ELECTRICAL/MOTOR DATA
BOD MFR
AND MODEL
REMARKS
HP VAC PH
MAX
RPM
SPEED
CONTROL
17-SCP-1 BASEMENT
STEAM CONDENSATE
RETURN
CENTRIFUGAL 6660 20 281 3 208 3 3500 -
BELL &
GOSSETT
CC SERIES
1,2
HYDRONIC PUMP SCHEDULE
MARK LOCATION
AREA AND/OR BLDG
SERVED
SYSTEM PUMP TYPE FLUID GPM
HEAD
(FT WG)
NPSHA
(FT WG)
FLUID
TEMP
(°F)
MIN %
EFF
ELECTRICAL/MOTOR DATA
BASIS OF DESIGN REMARKS
HP VAC PH
MAX
RPM
SPEED
CONTROL
17-CHP-1 BASEMENT BLDG 17 CHW
BASE MOUNTED, END
SUCTION
WATER 179.6 31.9 - 45 72 2 208 3 1800 VFD BELL AND GOSSETT E-1510 1
17-CHP-2 BASEMENT BLDG 17 CHW
BASE MOUNTED, END
SUCTION
WATER 179.6 31.9 - 45 72 2 208 3 1800 VFD BELL AND GOSSETT E-1510 1
17-HWP-1 BASEMENT BLDG 17 HW INLINE WATER 30 45 - 150 47 1.5 208 1 1800 ECM BELL AND GOSSETT E-90 1
17-HWP-2 BASEMENT BLDG 17 HW INLINE WATER 30 45 - 150 47 1.5 208 1 1800 ECM BELL AND GOSSETT E-90 1
MISCELLANEOUS HYDRONIC EQUIPMENT SCHEDULE
MARK DESCRIPTION LOCATION
SYSTEM AND/OR
SERVICE
TYPE
VOLUME
(GAL)
FLOW
(GPM)
WPD
(FT WG)
CONNECTION
SIZE
(NPS)
ELECTRICAL REMARKS
17-AS-1
AIR
SEPARATOR
BASEMENT HW TANGENTIAL NA 28.8 0.04 3 NA 1
17-AS-2
AIR
SEPARATOR
BASEMENT CHW TANGENTIAL NA 179.6 1.61 3 NA 1
17-ET-1
EXPANSION
TANK
BASEMENT HW DIAPHRAGM 7.80 NA NA 3/4 NA 1
17-ET-2
EXPANSION
TANK
BASEMENT CHW DIAPHRAGM 13.1 NA NA 1 NA 1
17-FF-1
FILTER
FEEDER
BASEMENT HW
SIDE STREAM
BYPASS
5 1.37 - - NA 1
17-FF-2
FILTER
FEEDER
BASEMENT CHW
SIDE STREAM
BYPASS
5 8.55 - - NA 1
HEATING WATER UNIT HEATER (HWUH) SCHEDULE
MARK DESCRIPTION
FLOW RATE
(GPM)
HHW COIL
(MBH)
COIL
PRESSURE
DROP
HEATING
(CFM)
HEATING COIL
EAT (°F)
HEATING COIL
LAT (°F)
MOTOR HP VOLTAGE PHASE
BOD MFGR AND
MODEL
REMARKS
17-UH-1
HORIZONTAL
DELIVERY
1.23 9.75 0.20 630 60 91 1/25 115 1 MODINE HSB 1
17-UH-3
HORIZONTAL
DELIVERY
0.5 6.19 0.50 340 28.2 93 1/60 115 1 MODINE HSB 1
17-UH-4
HORIZONTAL
DELIVERY
0.51 7.66 0.50 340 28.2 93 1/60 115 1 MODINE HSB 1
SPLIT SYSTEM AIR CONDITIONER INDOOR UNIT (IDU) SCHEDULE
MARK AREA SERVED TYPE
SUPPLY
CFM
OA
CFM
ESP
(IN WG)
COOLING REQUIREMENTS HEATING REQUIREMENTS ELECTRICAL REQUIREMENTS
BOD MFR AND
MODEL
REMARKS
SOURCE
SEN
MBH
TOTAL
MBH
EAT-
DB
(°F)
EAT-
WB
(°F)
LAT-
DB
(°F)
LAT-
WB
(°F)
SOURCE
TOTAL
MBH
EAT-
DB
(°F)
LAT-
DB
(°F)
FAN
HP
(QTY)
VAC PH MCA MOCP
SPEED
CONTROL
17-IDU-2 IT ROOM HIGH WALL DUCTLESS 990 0 - 17-ODU-1 26.59 27.0 79 61 55 50 - - - - 1/10 208 1 - - ECM CARRIER RAV 1,2,3
17-IDU-1 IT ROOM HIGH WALL DUCTLESS 990 0 - 17-ODU-1 26.59 27.0 79 61 55 50 - - - - 1/10 208 1 - - ECM CARRIER RAV 1,2,3
17-IDU-3
ELECTRICAL
ROOM
DUCTED 190 0 - 17-ODU-2 5.95 6.19 79 61 55 50 - - - - - 208 1 - - ECM CARRIER 40MBDQ 1,2,3
AIR DEVICE SCHEDULE
MARK
TYPE
DESCRIPTION
MOUNTING
PANEL / FRAME
SIZE
NECK SIZE MAX CFM
MAX NC MAX APD
BOD MFR AND
MODEL
REMARKS6Ø
6X6 8Ø 8X8
10Ø 10X10
12Ø 12X12
14Ø 14X14
E2-A
EXHAUST -
LOUVERED
FACE
SURFACE /
LAY-IN
24"X24" 100 225 350 525 725 13 0.1 PRICE 500/600 1,2,3
E6-A
EXHAUST -
STANDARD
WALL TYPE
SURFACE /
DUCT
18"X6" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3
E6-B
EXHAUST -
STANDARD
WALL TYPE
SURFACE /
DUCT
36"X12" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3
R2-A
RETURN -
LOUVERED
FACE
SURFACE /
LAY-IN
24"X24" 100 225 350 525 725 13 0.1 PRICE 500/600 1,2,3
R6-A
RETURN -
STANDARD
WALL TYPE
SURFACE /
DUCT
18"X6" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3
R6-B
RETURN -
STANDARD
WALL TYPE
SURFACE /
DUCT
36"X12" 100 200 350 525 730 25 0.1 PRICE 90 SERIES 1,2,3
S1R-6
SUPPLY -
ROUND CONE
LOUVER
SURFACE /
DUCT
REF CFM &
NECK SIZE
140 210 325 450 635 25 0.1 TITUS TMR 1,2,3,4
S1R-10
SUPPLY -
ROUND CONE
LOUVER
SURFACE /
DUCT
REF CFM &
NECK SIZE
140 210 325 450 635 25 0.1 TITUS TMR 1,2,3,4
S1R-14
SUPPLY -
ROUND CONE
LOUVER
SURFACE /
DUCT
REF CFM &
NECK SIZE
140 210 325 450 635 25 0.1 TITUS TMR 1,2,3,4
S3-A
SUPPLY -
PERFORATED
FACE
SURFACE /
LAY-IN
24"X24" 100 200 300 390 470 25 0.1 PRICE AMCD 1,2,3
S4-A
SUPPLY - SLOT
DIFFUSER/PLEN
UM
SURFACE /
LAY-IN
24"L, 1X1" SLOT 100 110 -1 -1 -1 25 0.15 TITUS FL 1,2,3
S4-C
SUPPLY - SLOT
DIFFUSER/PLEN
UM
SURFACE /
LAY-IN
48"L, 1X1" SLOT 160 210 -1 -1 -1 25 0.15 TITUS FL 1,2,3
S6-A
SUPPLY -
REGISTER
SURFACE /
DUCT
12"X8" 100 200 350 525 730 25 0.1 TITUS 300FL 1,2,3
S6-B
SUPPLY -
REGISTER
SURFACE /
DUCT
18"X6" 100 200 350 525 730 25 0.1 TITUS 300FL 1,2,3
STEAM FLASH TANK (SFT) SCHEDULE
MARK LOCATION
SYSTEM AND/OR
SERVICE
TYPE
MAX RETURN
PRESSURE
(PSIG)
CONDENSATE
(LB/HR)
REMARKS
17-SFT-1 BASEMENT BLDG 17 MPR HORIZONTAL 35 2063 1,2
A. REFER TO M-001 AND M-002 FOR MECHANICAL SYMBOLS, ABBREVIATIONS,
AND GENERAL NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL
PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE
SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE
LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND
SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.
MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP
ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL
REMAIN IN SERVICE FOLLOWING DEMOLITION.
A
21 3 4 5 6 7 8 9 10 11 12
A'
B'
C'
D'
1' 2' 3' 4'
A'''
A''
3" ø
C D
3"ø MPS
3" ø
M P
S
1(X) 17-P-3
(X)
17-ET-3
/F1 MD111 /F1 MD111
(E) 6"ø CHR
(E) 6"ø CHS
2" ø
M P
R
4" ø
M P
S
5 5
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:0
5:
P M
MD110
DEMOLITION PLANS - BASEMENT
NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
DEMOLITION HVAC PLANS - BASEMENT - NORTH
F1
1. DEMOLISH EXISTING WATER TANKS AND ASSOCIATED PLUMBING BACK TO
MAIN.
2. DEMOLISH ANY REMAINING MECHANICAL EQUIPMENT LOCATED IN THE
BASEMENT. PROVIDE RFI FOR ANY EQUIPMENT TO BE DEMOLISHED THAT
IS NOT IDENTIFIED PRIOR TO REMOVAL.
3. DEMOLISH EXISTING PUMP AND ASSOCIATED PLUMBING BACK TO MAIN.
4. EXISTING MECHANICAL PIPING EXTENDS THROUGHOUT CRAWLSPACE.
CONTRACTOR SHALL VERIFY PIPING IN THE CRAWL SPACE AND REMOVE.
5. DEMOLISH FULL EXTENT OF MECHANICAL PIPING TO MECHANICAL
EQUIPMENT.
6. EXISTING STEAM PIPING TO REMAIN.
7. PRIOR TO DEMOLITION, CONDUCT EXISTING CONDITION TEST AND
BALANCE REPORT ON CHILLED WATER AND STEAM MAINS SERVING
BUILDING PER SPECIFICATION 23 05 93.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL
PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE
SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE
LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND
SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.
MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP
ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL
REMAIN IN SERVICE FOLLOWING DEMOLITION.
A
B
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
3" ø
M P
S
2"ø MPS
4"ø MPS
4"ø HPS
3" ø
M P
S
3"ø MPS
(X) HX
2" ø
M P
R
4" ø
M P
S
/F1 MD110 /F1 MD110
2" ø
L P
R
2"ø MPS
2" ø
M P
S 2" ø M
P S 2"ø LPR
2" ø
L P
R
4"ø HPS
1/
2" ø
M P
S
2" ø
L P
R
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
7:
A M
MD111
DEMOLITION PLANS - BASEMENT
SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
DEMOLITION HVAC PLANS - BASEMENT - SOUTH
F1
1. DEMOLISH EXISTING WATER TANKS.
2. DEMOLISH EXISTING COMPRESSOR AND ASSOCIATED PIPING.
3. DEMOLISH EXISTING INLINE PUMPS.
4. DEMOLISH EXISTING STEAM CONDENSATE PUMP AND RECEIVER.
5. DEMOLISH EXISTING EXPANSION TANKS.
6. DEMOLISH ANY REMAINING MECHANICAL EQUIPMENT OR PIPING LOCATED
IN THE BASEMENT. PROVIDE RFI FOR ANY EQUIPMENT TO BE DEMOLISHED
THAT IS NOT IDENTIFIED PRIOR TO REMOVAL.
7. EXISTING STEAM PIPING TO REMAIN.
8. PRIOR TO DEMOLITION, CONDUCT EXISTING CONDITION TEST AND
BALANCE REPORT ON CHILLED WATER AND STEAM MAINS SERVING
BUILDING PER SPECIFICATION 23 05 93.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL
PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE
SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE
LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND
SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.
MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP
ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL
REMAIN IN SERVICE FOLLOWING DEMOLITION.
A
21 3 4 5 6 7 8 9 10 11 12
A'
B'
C'
D'
1' 2' 3' 4'
A'''
A''
(E )4
0x
(E )3
6x
(E )2
4x
(E )2
0x
(E )2
0x
(E )2
0x
(E )2
0x x1
(E )3
0x
(E )2
4x
(E)48x20
(E)20x10
(E )2
0x
(E )2
0x
(E)20x10 (E)24x12
(E)24x12 (E)24x12
(E )1
2x
(E )1
8x
(E)18x10
(E )1
2x
(E )1
2x
(E)12x12
(E )1
2x
(E )1
2x
(E)8ø
(E)8ø
(E)8ø
(E)40x20
(E )3
0x
(E )3
0x
(E )8 ø (E
)8 ø
(E)40x20
(X) AC
(E) 2"ø MPS
(E) 1"ø MPR
(E) 1"ø MPR
(E)12x12
(E )2
0x
(E)12x12
6"ø MPR
6"ø MPR
4" ø
C H
R
1"ø MPS
1"ø MPS
1"ø MPS
1"ø MPS
2"ø NG
1 1/2"ø MPR
1"ø MPS
1"ø MPR
2"ø MPS
2"ø MPR
/F1 MD113 /F1 MD113
4" ø
C H
S 4" ø C
H R
3"ø MPS
3"ø MPS
3"ø MPS
3"ø MPS
6"ø CHS
6"ø CHR
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
7:
A M
MD112
DEMOLITION PLANS - LEVEL 1
NORTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
DEMOLITION HVAC PLANS - LEVEL 1 - NORTH
F1
1. DEMOLISH EXISTING EXHAUST FAN.
2. DEMOLISH EXISTING DUCT WORK AT THIS APPROXIMATE LOCATION.
3. DEMOLISH EXISTING SOAP STATION AND ASSOCIATED PIPING.
4. DEMOLISH CHS/R PIPING FROM EXISTING AIR HANDLING UNITS BACK TO
MAIN.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL
PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE
SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE
LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND
SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.
MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP
ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL
REMAIN IN SERVICE FOLLOWING DEMOLITION.
A
B
C
D
21 3 4 5 6 7 8 9 10 11 12
A'
1' 2' 3' 4'
A''
(E )2
0x
(E )3
0x
(E )3
0x
(E)30x20
(E )1
2x
(E)48x24
(X) AHU-2
(X) AHU-1
(X) EF-7
(X) UH-1
(E
1" ø
M P
S
(E
3/ 4" ø M
P R
(E) 2"ø MPS
(E) 1"ø MPR
(E) 1"ø MPR
(E)12x12
18x12
3/4"ø MPS
3/4"ø MPR
1/
4" ø
M P
R
4" ø
C H
R
4" ø
C H
S
2"ø MPS2"ø MPR
6"ø CHR 6"ø CHS
1"ø MPS
1"ø MPS
1"ø MPS
1"ø MPS
2"ø MPS
2"ø MPR
/F1 MD112 /F1 MD112
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
SOUTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEERS: STAMP:
Approved: Project Director
Phase Project Title
Location
Issue Date Checked Drawn
Project Number
Drawing Number
Building Number
SEE REVISION
SCHEDULE
R E
V
IS
IO
N
S C
H E
D U
L E
C :\R ev it
\2 2.
_M
E C
H -P
LU
M
_R
_H M al et z.
rv t
/7 /2
:5
7:
A M
MD113
DEMOLITION PLANS - LEVEL 1
SOUTH
CONSOLIDATE ENGINEERING
BLDG. 17
4800 MEMORIAL DR., WACO TX 76711
674A4-22-254
MR HM
100% CONSTRUCTION
DOCUMENTS
VEG 22.12
3/16" = 1'-0"
DEMOLITION HVAC PLANS - LEVEL 1 - SOUTH
F1
1. DEMOLISH AHU AND ASSOCIATED PIPING.
2. DEMOLISH GRILLES SERVED BY EXPOSED DUCT ABOVE.
3. DEMOLISH EXISTING CART WASH ASSEMBLY, DRAIN, AND ASSOCIATED
PLUMBING PIPING AND EXTERIOR EXHAUST.
4. EXISTING PASS THROUGH VENT TO REMAIN.
(X) AHU-6
(X) AHU-7
(X) AHU-5
(X) AHU-3
(X) AHU-9
(X) AHU-8
(X) AHU-4
(X) EF-4
(X) EF-5
(X) EF-3
(X) EF-2
(X) EF-6
1"ø CD
2"ø CHR
2"ø CHS
1"ø MPR 2"ø MPS
3" ø
C H
S
3" ø
C H
R
1/
4" ø
C D
1 1/4"ø MPR
2"ø MPS
1/
4" ø
M P
R
1/
2" ø
M P
S
2"ø CD
6"ø CHS
6"ø CHR
6" ø
C H
S
2" ø
C D
6" ø
C H
R
3" ø
C H
R
2" ø
C D
3" ø
C H
S
2"ø MPS 2"ø MPR
1 1/4"ø MPR
2"ø MPS
1/
2" ø
M P
S
1/
4" ø
M P
R
2"ø CD
6"ø CHS
6"ø CHR
3" ø
C H
S
2" ø
C D
3" ø
C H
R 2" ø N
G
2"ø NG
A
21 3 4 5 6 7 8 9 10 11 12
A'
B'
C'
D'
1' 2' 3' 4'
A'''
A''
3/4"ø NG
A. REFER TO M-001 AND M-002 FOR MECHANICAL SYMBOLS, ABBREVIATIONS,
AND GENERAL NOTES.
B. FIELD VERIFY EXISTING CONDITIONS AND REPORT DISCREPANCIES TO THE
VHA COR BEFORE PROCEEDING WITH WORK.
C. REFER TO GI SHEET SERIES LIFE SAFETY PLANS FOR LEGEND AND DETAILED
LOCATIONS OF RATED CONSTRUCTION REQUIRING ADDITIONAL MEP
PENETRATION SEALING MEASURES IN ACCORDANCE WITH THE
SPECIFICATIONS. IN THE EVENT OF A CONFLICTING OR AMBIGUOUS WALL
PATTERN SHOWN ON MEP PLANS, RATINGS FROM THE LIFE SAFETY PLAN
SHALL GOVERN.
D. REFER TO SPECIFICATIONS 01 00 00 AND 23 05 11 FOR SELECTIVE
DEMOLITION AND REPAIR REQUIREMENTS. PATCH OPENINGS REMAINING IN
EXISTING CONSTRUCTION FOLLOWING DEMOLITION OF MECHANICAL
PENETRATIONS NOT REPLACED IN KIND. MATCH AESTHETICS AND LIFE
SAFETY RATINGS OF THE SURROUNDING CONSTRUCTION. ENGAGE
LICENSED AND SITE-APPROVED ROOFING CONTRACTOR TO PATCH AND
SEAL WHERE ITEMS ARE REMOVED THROUGH THE EXISTING ROOF.
MAINTAIN EXISTING WARRANTIES.
E. REFER TO HAZARDOUS MATERIAL SURVEY IN THE SPECIFICATIONS. DO NOT
PROCEED WITH DEMOLITION OR DISTURBANCE OF ITEMS CONTAINING
HAZARDOUS MATERIALS UNTIL ABATEMENT HAS BEEN PERFORMED IN
ACCORDANCE WITH THE SPECIFICATIONS.
F. REFER TO GC SHEET SERIES FOR PROJECT PHASING PLAN AND NARRATIVE.
G. PROVIDE SERVICE VALVES OR DAMPERS AT LIMITS OF DEMOLITION. CAP
ENDS WHERE NOT RECONNECTED IN NEW WORK. EXISTING SYSTEMS SHALL
REMAIN IN SERVICE FOLLOWING DEMOLITION.
7' -6
5'
1"
5'
3/
8'
1/
1/
1"
0'
1"
0'
1"
0'
0'
1"
0'
1"
0'
9" 6"
3"
3"
1' -6
1'
6"
1/
2"
2' 1'
6"
1"
3' 2'
1'
3/ 4"
4'
2' 1'
1/
2"
6' 4'
2'
3/ 8"
8'
4'
3/
8' 4'
2'
1/ 4"
8'
4'
1/ 8"
KEY PLAN
GENERAL NOTES
SHEET KEYNOTES
P la n N or th
True North
NORTH
BLDG 17
Drawing Title
VA FORM 08 - 6231
F
CONSULTANTS:
750 W HAMPDEN AVE
SUITE 300
ENGLEWOOD, CO 80110
(720) 550-6307
WWW.VALHALLAENGINEERING.COM
10987654321
10987654321
E
D
C
B
A
F
E
D
C
B
A
ARCHITECT/ENGINEER…