36C25621R0109 FIRE STOPPING 078400.doc

DOC document 33 KB Posted

Attached to
Z1DZ-- Proj No 520-22-113 Access Control &Security Systems Upgrade Federal contract opportunity
Solicitation number
36C25621R0109
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16

About this file

This document includes a federal contract solicitation and project specifications for an access control and security system upgrade. The Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 16 is seeking proposals for Project No. 520-22-113 to upgrade the access control and security systems at the Gulf Coast Veterans Health Care System facility in Biloxi, Mississippi. The 100% set-aside contract for service-disabled veteran-owned small businesses has an estimated value between $1-2 million. Interested vendors must register in the System for Award Management and Vendor Information Pages databases. The solicitation will be issued on August 6th with proposals due around September 6th. The contract award is expected within 30 days thereafter and work must be completed within 180 days of the notice to proceed. The specifications document provides technical requirements for firestopping and smoke sealing related to the security upgrade work.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DZ-- Proj No 520-22-113 Access Control &Security Systems Upgrade, newest first.
File Type Posted
520-22-113 Pre-Award RFI Register 01 Sep 21.pdf PDF
36C25621R0109 0004.docx DOCX document
VHA Directive 1193 COVID 2019 Vaccination August 13 2021.pdf PDF
36C25621R0109 0003.docx DOCX document
S04 Site Visit Sign-In Sheets - Proj 520-22-113.pdf PDF
36C25621R0109 0002.docx DOCX document
36C25621R0109 0001.docx DOCX document
36C25621R0109 REQ ELEC INSTALL 260511.doc DOC document
36C25621R0109 EXHIBIT C.docx DOCX document
36C25621R0109 Earth Moving Short Form 312011.doc DOC document
36C25621R0109 Drawings 07152021.pdf PDF
36C25621R0109 CONSTRUCTION WASTE MNGT 017419.doc DOC document
36C25621R0109 COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY 280500.docx DOCX document
36C25621R0109 SOW.docx DOCX document
36C25621R0109 Signage 101400.docx DOCX document
36C25621R0109 MS20210050 04022021 Mod 2.pdf PDF
36C25621R0109 ICRA .pdf PDF
36C25621R0109 EXHIBIT B.docx DOCX document
36C25621R0109 RFP.docx DOCX document
36C25621R0109 LED Signage Site Drawings.pdf PDF
36C25621R0109 EXHIBIT F.docx DOCX document
36C25621R0109 EXHIBIT E.docx DOCX document
36C25621R0109 EXHIBIT D.docx DOCX document
36C25621R0109 Demolition 024100.doc DOC document
36C25621R0109 Shop Drawings 013323 .doc DOC document
36C25621R0109 Safety Requirements 013526.doc DOC document
36C25621R0109 REQ FOR COM INSTALL 270511.doc DOC document
36C25621R0109 J_A_Redacted.pdf PDF
36C25621R0109 General Requirements 010000 .doc DOC document
36C25621R0109 EXHIBIT A.docx DOCX document
Show all 30

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

520-22-113

SECTION 07 84 00

FIRESTOPPING

PART 1 GENERAL

1.1 DESCRIPTION

A.

Closures of openings in walls, floors, and roof decks against penetration of flame, heat, and smoke or gases in fire resistant rated construction.

B.

Closure of openings in walls against penetration of gases or smoke in smoke partitions.

1.2 RELATED WORK(NOT APPLICABLE)

1.3 SUBMITTALS

A.

Submit in accordance with Section 01 33 23, SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES.

B.

Manufacturers literature, data, and installation instructions for types of firestopping and smoke stopping used.

C.

List of FM, UL, or WH classification number of systems installed.

D.

Certified laboratory test reports for ASTM E814 tests for systems not listed by FM, UL, or WH proposed for use.

1.4 DELIVERY AND STORAGE

A.

Deliver materials in their original unopened containers with manufacturer’s name and product identification.

B.

Store in a location providing protection from damage and exposure to the elements.

1.5 warranty

Firestopping work subject to the terms of the Article “Warranty of Construction”, FAR clause 52.246-21, except extend the warranty period to five years.

1.6 QUALITY ASSURANCE

FM, UL, or WH or other approved laboratory tested products will be acceptable.

1.7 APPLICABLE PUBLICATIONS

A.

Publications listed below form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.

B.

American Society for Testing and Materials (ASTM):

E84-10 Surface Burning Characteristics of Building Materials

E814-11 Fire Tests of Through-Penetration Fire Stops

C.

Factory Mutual Engineering and Research Corporation (FM):

Annual Issue Approval Guide Building Materials

D.

Underwriters Laboratories, Inc. (UL):

Annual Issue Building Materials Directory

Annual Issue Fire Resistance Directory

1479-10 Fire Tests of Through-Penetration Firestops

E.

Warnock Hersey (WH):

Annual Issue Certification Listings

PART 2 - PRODUCTS

2.1 FIRESTOP SYSTEMS

A.

Use either factory built (Firestop Devices) or field erected (through-Penetration Firestop Systems) to form a specific building system maintaining required integrity of the fire barrier and stop the passage of gases or smoke. No mixing of more than one fire stop product is allowed for use in any one penetration.

B.

Through-penetration firestop systems and firestop devices tested in accordance with ASTM E814 or UL 1479 using the "F" or "T" rating to maintain the same rating and integrity as the fire barrier being sealed. "T" ratings are not required for penetrations smaller than or equal to 100 mm (4 in) nominal pipe or 0.01 m2 (16 sq. in.) in overall cross sectional area.

C.

Products requiring heat activation to seal an opening by its intumescence shall exhibit a demonstrated ability to function as designed to maintain the fire barrier.

D.

Firestop sealants used for firestopping or smoke sealing shall have following properties:

1.

Contain no flammable or toxic solvents.

2.

Have no dangerous or flammable out gassing during the drying or curing of products.

3.

Water-resistant after drying or curing and unaffected by high humidity, condensation or transient water exposure.

4.

When used in exposed areas, shall be capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.

E.

Firestopping system or devices used for penetrations by glass pipe, plastic pipe or conduits, unenclosed cables, or other non-metallic materials shall have following properties:

1.

Classified for use with the particular type of penetrating material used.

2.

Penetrations containing loose electrical cables, computer data cables, and communications cables protected using firestopping systems that allow unrestricted cable changes without damage to the seal.

3.

Intumescent products which would expand to seal the opening and act as fire, smoke, toxic fumes, and, water sealant.

F.

Maximum flame spread of 25 and smoke development of 50 when tested in accordance with ASTM E84.

G.

FM, UL, or WH rated or tested by an approved laboratory in accordance with ASTM E814.

H.

Materials to be asbestos free.

2.2 SMOKE STOPPING IN SMOKE PARTITIONS

A.

Use silicone sealant in smoke partitions as specified in Section 07 92 00, JOINT SEALANTS.

B.

Use mineral fiber filler and bond breaker behind sealant.

C.

Sealants shall have a maximum flame spread of 25 and smoke developed of 50 when tested in accordance with E84.

D.

When used in exposed areas capable of being sanded and finished with similar surface treatments as used on the surrounding wall or floor surface.

PART 3 - EXECUTION

3.1 EXAMINATION

Submit product data and installation instructions, as required by article, submittals, after an on site examination of areas to receive firestopping.

3.2 PREPARATION

A.

Remove dirt, grease, oil, loose materials, or other substances that prevent adherence and bonding or application of the firestopping or smoke stopping materials.

B.

Remove insulation on insulated pipe for a distance of 150 mm (six inches) on either side of the fire rated assembly prior to applying the firestopping materials unless the firestopping materials are tested and approved for use on insulated pipes.

3.3 INSTALLATION

A.

Do not begin work until the specified material data and installation instructions of the proposed firestopping systems have been submitted and approved.

B.

Install firestopping systems with smoke stopping in accordance with FM, UL, WH, or other approved system details and installation instructions.

C.

Install smoke stopping seals in smoke partitions.

3.4 CLEAN-UP AND ACCEPTANCE OF WORK

A.

As work on each floor is completed, remove materials, litter, and debris.

B.

Do not move materials and equipment to the next-scheduled work area until completed work is inspected and accepted by the Resident Engineer.

C.

Clean up spills of liquid type materials.

- - - E N D - - -

07 84 00 - 4

File details come from the government source that posted it. Updated .