John J Pershing VA Medical Center Med Gas Annual 2025.pdf
PDF 1 MB Posted
- Attached to
- Medical Gas Maintenance Service and Inspection
- Solicitation number
- 36C25526Q0384
About this file
This document is a Medical Gas Annual Inspection Report for John J Pershing Medical Center in Poplar Bluff, Missouri, conducted by MGI Inc. (Medical Gas Installers) on September 30, 2025.
The inspection verified NFPA 99 2024 compliance for a Category 1 medical facility across all medical gas systems. Testing covered source equipment (1 bulk oxygen system, 2 reciprocating medical air compressors, 2 lube vane vacuum pumps, and 1 scroll lab air compressor), master alarm panels (2 Beacon MEDAES units with 46 total signals tested), zone valves (21 total across the facility), area alarms (21 alarms across multiple floors), and 358 patient outlet terminals (122 oxygen, 117 medical air, 116 vacuum, 3 dental air). All tested components passed inspection with zero failures. The outlet cross-connect and purity testing covered 7 outlets (approximately 10% of existing outlets per VHA Directive 7515) with all samples demonstrating 99.9% oxygen concentration and 21.3% medical air concentration. Source equipment evaluations confirmed proper operation of bulk oxygen supply, two independent medical air compressor systems, two medical vacuum systems, and the lab air system, with all alarm functions, pressure switches, isolation valves, and safety features meeting code requirements. No corrective actions, outlet issues, or future corrections were identified during the inspection.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Cape Girardeau VA Med Gas Annual 2025.pdf | ||
| 36C25526Q0384 0001.pdf | ||
| 36C25526Q0384_1.docx | DOCX document | |
| Pre-Sol 36C25526Q0384_2.docx | DOCX document | |
| 36C25526Q0384 Sources Sought.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PREPARED BY: BRAYDEN SEGER
TESTING DATES: SEPTEMBER 30TH, 2025
JOHN J PERSHING MEDICAL CENTER
MEDICAL GAS
ANNUAL
INSPECTION
1500 N WESTWOOD BLVD
POPLAR BLUFF, MO 63901
ITEMS TESTED/INSPECTED
OXYGEN MEDICAL AIR
MEDICAL
VACUUM
NITROUS
OXIDE
NITROGEN
CARBON
DIOXIDE
LAB AIR WAGD
SOURCE EQUIPMENT P P P P
MASTER ALARMS P P P P
ZONE VALVES P P P P
ZONE VERIFICATION P P P P
CROSS CONNECTION P P P P
AREA ALARMS P P P P
PATIENT OUTLETS P P P P
PARTICLE ANALYSIS P P P
PURITY ANALYSIS P P P
MGI MEDICAL GAS VERIFIER: BRAYDEN SEGER
SIGNATURE:
DATE: 9/30/2025
MEDICAL GAS ANNUAL TESTING ANALYSIS
MEDICAL GAS TYPE
SCOPE OF
TESTING/VERIFICATION
NFPA 99 2024 Compliant Medical Gas Annual Inspection for a Category 1 Medical Facility. Includes testing of all medical gas source equipment, medical gas zone valves, medical gas master alarm panels, medical gas area alarm panels, medical gas control panels, medical gas flexible terminals and medical gas terminals and medical gas labeling.
ADDITIONAL COMMENTS
https://qrplanet.com/8lq61w
EXECUTIVE SUMMARY
SIGNALS
PASSED
SIGNALS
FAILED
LAB AIR SCROLL 1 1 0
EXECUTIVE OVERALL SUMMARY-SOURCE
SOURCE EQUIPMENT
GAS TYPE SOURCE TYPE TOTAL COUNT TOTAL PASSED TOTAL FAILED
MEDICAL AIR RECIPROCATING 2 2 0
OXYGEN BULK OXYGEN 1 1 0
2 2 0
SOURCE EQUIPMENT MASTER ALARMS
EQUIPMENT
EQUIPMENT MAKE &
MODEL
ALARM PANEL
COUNT
ALARM SIGNAL
COUNT
TOTAL 8 8 0
MASTER ALARM PANEL ALARMS
MASTER ALARM PANEL
BEACON MEDAES TOTAL
ALERT
1 23 23 0
MASTER ALARM PANEL
BEACON MEDAES TOTAL
ALERT
1 23 23
TOTALS 2 46 46 0
VACUUM LUBE VANE 2 2 0
FAILED REPAIRED FAILED REPAIRED
PASSED
PATIENT OUTLET TERMINALS
21 21
MISSING VALVES MISSING ALARMS
0 0 0 00 0
EXECUTIVE OVERALL SUMMARY-PIPELINE
ZONE VALVES AREA ALARMS
TOTAL VALVES TOTAL ALARMSTOTAL PASSED
OXYGEN 122 122 0 0
GAS TYPE TOTAL COUNT TOTAL PASSED TOTAL FAILED TOTAL UNAVAILABLE
VACUUM 116 116 0 0
DENTAL AIR 3 3 0 0
PERCENTAGE 100.0% 0.0% 0.0%
TOTAL 358 358 0 0
TOTAL PERCENTAGE OF
OUTLETS TESTED
100.0%
TOTAL OUTLET
FAILURES
TOTAL OUTLETS
REPAIRED
0 0
MEDICAL AIR 117 117 0 0
MGI TECHNICIAN: BRAYDEN SEGER
1 SPECIFIC OUTLET REPAIRED BY REPAIR DATE
NO ISSUES FOUND
END OF OUTLET ISSUES
OUTLET ISSUES JOHN J PERSHING MEDICAL CENTER
ROOM OUTLET SPECS ISSUE
JOHN J PERSHING MEDICAL CENTER
CORRECTED
END OF CORRECTIVE ACTIONS
NOTE: CORRECTIVE ACTIONS ARE COMPONENTS OF THE MEDICAL GAS SYSTEM THAT DO NOT MEET THE NFPA 99 2024 CODE AND SHOULD BE UPGRADED OR REPAIRED TO MEET THE
NFPA 99 2024 CODE.
CORRECTIVE ACTIONS
AREA ISSUE NFPA 99 2024 CODE
NONE FOUND.
CORRECTIVE
ACTION
NOTE: THESE ARE COMPONENTS OF THE MEDICAL GAS SYSTEM THAT DO NOT MEET THE 2024 NFPA 99 CODE, HOWEVER THEY ARE PERMITTED TO
REMAIN IN USE UNTIL THE AREA(S) ARE UPGRADED OR RENOVATED DUE TO THE ABOVE NOT AFFECTING PATIENT CARE.
END OF FUTURE CORRECTIONS
FUTURE CORRECTIONS
AREA ISSUE NFPA 99 2024 CODE
NONE FOUND.
FUTURE
CORRECTION
MEDICAL GAS MASTER
ALARM ANALYSIS
MASTER ALARM CODE REQUIREMENTS
Master alarm panels for medical gas and vacuum systems shall each include the following signals:
(NFPA 99 2024 5.1.9.2.4)
(1) Alarm indication when, or just before, changeover occurs in a medical gas system that is supplied by a manifold or other alternating-type bulk system that has as a part of its normal operation a changeover from one portion of the operating supply to another.
(2) Alarm indication for a bulk cryogenic liquid system when the main supply reaches an average day’s supply, indicating low contents.
(3) Alarm indication when, or just before, the changeover to the reserve supply occurs in a medical gas system that consists of one or more units that continuously supply the piping system while another unit remains as the reserve supply and operates only in the case of an emergency.
(4) Alarm indication for cylinder reserve pressure low when the content of a cylinder reserve header is reduced below one average day’s supply.
(5) For bulk cryogenic liquid systems, an alarm when or at a predetermined set point before the reserve supply contents fall to one day’s average supply, indicating reserve low.
(6) Where a cryogenic liquid storage unit is used as a reserve for a bulk supply system, an alarm indication when the gas pressure available in the reserve unit is below that required for the medical gas system to function.
(7) Alarm indication when the pressure in the main line of each separate medical gas system increases 20 percent or decreases 20 percent from the normal operating pressure.
(8) Alarm indication when the medical–surgical vacuum pressure in the main line of each vacuum system drops.
(9) Alarm indication(s) from the local alarm panel(s) as described in 5.1.9.5.2 to indicate when one or more of the conditions being monitored at a site is in alarm.
(10) Medical air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than +2°C (+35°F)
(11) WAGD low alarm when the WAGD vacuum level or flow is below effective operating limits.
(12) An instrument air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than −30°C (−22°F).
(13) Alarm indication if the primary or reserve production stops on a proportioning system.
JOHN J PERSHING MEDICAL CENTER MGI TECHNICIAN: BRAYDEN SEGER
POPLAR BLUFF, MO 63901 TESTING DATE: 9/30/2025
VISUAL
STATUS
AUDIBLE
STATUS
LABELED
CORRECTLY
COMMENTS
P TESTED & MAINTAINED BY BULK PROVIDER
P TESTED & MAINTAINED BY BULK PROVIDER
P TESTED & MAINTAINED BY BULK PROVIDER
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
ALARM MAKE AND MODEL: 3RD FLOOR NURSE STATION
COMMENTS
OXYGEN LINE PRESSURE HIGH PASS
OXYGEN LINE PRESSURE LOW PASS
MEDICAL AIR COMP MAINTENANCE REQUIRED (MAIR 1) PASS
OXYGEN SECONDARY LIQUID SUPPLY IN USE N/A
OXYGEN SECONDARY LIQUID LEVEL LOW N/A
MASTER ALARM ANALYSIS
MASTER ALARM SIGNALS PASS/FAIL
OXYGEN PRIMARY LIQUID LEVEL LOW N/A
MEDICAL AIR HIGH DEW POINT (MAIR 1) PASS
MEDICAL AIR CO HIGH (MAIR 1) PASS
MEDICAL AIR LINE PRESSURE HIGH PASS
MEDICAL AIR COMP MAINTENANCE REQUIRED (MAIR 2) PASS
MEDICAL AIR HIGH DEW POINT (MAIR 2) PASS
MEDICAL AIR CO HIGH (MAIR 2) PASS
MEDICAL AIR LINE PRESSURE LOW PASS
LAB AIR HIGH DEW POINT PASS
LAB AIR COMPRESSOR SYSTEM MALFUNCTION PASS
R/D LAB AIR SERVICE ALERT PASS
LAB AIR LINE PRESSURE HIGH PASS
LAB AIR LINE PRESSURE LOW PASS
MEDICAL VACUUM LINE PRESSURE LOW PASS
MEDICAL VACUUM LAG IN USE (VAC 1) PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN (VAC 1) PASS
MEDICAL VACUUM LAG IN USE (VAC 2) PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN (VAC 2) PASS
BEACON MEDAES TOTAL ALERT LOCATION:
PER NFPA 99 2024 WHERE IS THE MASTER ALARM LOCATED OF THE FOLLOWING LOCATIONS LOCATION
(1) One master alarm panel shall be located in the office or work space of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems.
(2) In order to ensure continuous surveillance of the medical gas and vacuum systems while the facility is in operation, the second master alarm panel shall be located in an area of continuous observation (e.g., the telephone switchboard, security office, or other continuously staffed location).
PASS/FAIL
PASS
JOHN J PERSHING MEDICAL CENTER MGI TECHNICIAN: BRAYDEN SEGER
POPLAR BLUFF, MO 63901 TESTING DATE: 9/30/2025
VISUAL
STATUS
AUDIBLE
STATUS
LABELED
CORRECTLY
COMMENTS
P TESTED & MAINTAINED BY BULK PROVIDER
P TESTED & MAINTAINED BY BULK PROVIDER
P TESTED & MAINTAINED BY BULK PROVIDER
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
ALARM MAKE AND MODEL: ER CHECK-IN DESK
COMMENTS
PASS/FAIL
PASS
BEACON MEDAES TOTAL ALERT LOCATION:
PER NFPA 99 2024 WHERE IS THE MASTER ALARM LOCATED OF THE FOLLOWING LOCATIONS LOCATION
(1) One master alarm panel shall be located in the office or work space of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems.
(2) In order to ensure continuous surveillance of the medical gas and vacuum systems while the facility is in operation, the second master alarm panel shall be located in an area of continuous observation (e.g., the telephone switchboard, security office, or other continuously staffed location).
R/D LAB AIR SERVICE ALERT PASS
LAB AIR LINE PRESSURE HIGH PASS
LAB AIR LINE PRESSURE LOW PASS
MEDICAL VACUUM LINE PRESSURE LOW PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN (VAC 2) PASS
MEDICAL VACUUM LAG IN USE (VAC 1) PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN (VAC 1) PASS
MEDICAL VACUUM LAG IN USE (VAC 2) PASS
LAB AIR HIGH DEW POINT PASS
LAB AIR COMPRESSOR SYSTEM MALFUNCTION PASS
MEDICAL AIR CO HIGH (MAIR 2) PASS
MEDICAL AIR LINE PRESSURE HIGH PASS
MEDICAL AIR LINE PRESSURE LOW PASS
MEDICAL AIR CO HIGH (MAIR 1) PASS
MEDICAL AIR COMP MAINTENANCE REQUIRED (MAIR 2) PASS
MEDICAL AIR HIGH DEW POINT (MAIR 2) PASS
OXYGEN LINE PRESSURE LOW PASS
MEDICAL AIR COMP MAINTENANCE REQUIRED (MAIR 1) PASS
MEDICAL AIR HIGH DEW POINT (MAIR 1) PASS
OXYGEN SECONDARY LIQUID LEVEL LOW N/A
OXYGEN LINE PRESSURE HIGH PASS
OXYGEN SECONDARY LIQUID SUPPLY IN USE N/A
MASTER ALARM ANALYSIS
MASTER ALARM SIGNALS PASS/FAIL
OXYGEN PRIMARY LIQUID LEVEL LOW N/A
MEDICAL GAS AREA
ALARM ANALYSIS
(2) *Critical Care Areas
AREA ALARM CODE REQUIREMENTS
(1) Separate visual indicators for each condition monitored, except as permitted in 5.1.9.5.2 for local alarms that are displayed on master alarm panels.
(2) Visual indicators that remain in alarm until the situation that has caused the alarm is resolved.
(3) Cancelable audible indication of each alarm condition that produces a sound with a minimum level of
80 dBA at 0.92m (3 ft)
(4) Means to visually indicate a lamp or LED failure
Area alarm systems used for medical gas and vacuum systems shall include the following:
(NFPA 99 2024 5.1.9.1)
(2)*Anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is administered shall have the sensors installed either on the source side of any of the individual room zone valve box assemblies or on the patient or use side of each of the individual zone valve box assemblies.
(5) Visual and audible indication that the communication with an alarm-initiating devices is disconnected.
(6) Labeling of each indicator, indication the condition monitored.
(7) Labeling of each alarm panel for its area of surveillance.
(8) Reinitiating of the audible signal if another alarm condition occurs while the audible alarm is silenced.
(9) Power for master, area alarms, sensors, and switches from the life safety branch of the emergency electrical system as described in Chapter 6.
Area Alarms. Area alarm panels shall be provided to monitor all medical gas, medical–surgical vacuum, and piped WAGD systems supplying the following: (NFPA 99 2024 5.1.9.4)
(1) Anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is administered.
Area alarm panels for medical gas systems shall indicate if the pressure in the lines in the area being monitored increases or decreases by 20 percent from the normal line pressure. (NFPA 99 2024 5.1.9.4.2)
Area alarm panels for medical–surgical vacuum systems shall indicate if the vacuum in the area drops to or below 300 mm (12 in.) gauge HgV. (NFPA 99 2024 5.1.9.4.3)
Alarm sensors for area alarms shall be located as follows: (NFPA 99 2024 5.1.9.4.4)
(1)*Critical care areas shall have the alarm sensors installed on the patient or use side of each individual zone valve box assemblies.
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
MED AIR 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
FLOOR: GROUND ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 25" HG PASS N/A 12" HG N/A PASS ZONE P
FLOOR: GROUND ALARM LOCATION:
END OF GROUND FLOOR AREA ALARM ANALYSIS
ACROSS FROM URGENT CARE BREAK ROOM ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
OUTSIDE OF BIOMED ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
URGENT CARE: LL12, LL13, LL14,
LL15, LL16, LL17, LL25, LL38
AREA ALARM ANALYSIS
GROUND FLOOR
AREA MONITORED: COMMENTS
BIOMED: GR-034
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 55 PSI PASS 60 PSI 40 PSI N/A N/A ZONE
VACUUM 23" HG PASS N/A 12" HG N/A N/A ZONE
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI N/A N/A ZONE
MED AIR 55 PSI PASS 60 PSI 40 PSI N/A N/A ZONE
VACUUM 25" HG PASS N/A 12" HG N/A N/A ZONE
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 23" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
INSIDE DENTAL DEPARTMENT ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
AREA ALARM ANALYSIS
1ST FLOOR
AREA MONITORED: COMMENTS
DENTAL CLINIC ROOMS: 1E-113,
1E-114, 1E-116, 1E-129, 1E-130, 1E-130A
MEDICAL AIR AND
VACUUM ARE FOR
FUTURE USE: ALARM
AUDIBLE/VISUAL
SIGNALS NOT ABLE TO
BE TESTED
ROOM 1A-144
FOR FUTURE USE:
ALARM AUDIBLE/VISUAL
SIGNALS NOT ABLE TO
BE TESTED
AREA MONITORED: COMMENTS
END OF 1ST FLOOR AREA ALARM ANALYSIS
EXAM ROOMS: 1A-053, 1A-061,
1A-062
NEXT TO EXAM 1A-061 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
HALLWAY OUTSIDE 1A-144 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 26" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 2ND ALARM LOCATION:
END OF 2ND FLOOR AREA ALARM ANALYSIS
ACROSS FROM 2A-063 BONE DENSITY ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA ALARM ANALYSIS
2ND FLOOR
AREA MONITORED: COMMENTS
2A CT: 2002 & 2005
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 22" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN N/A PASS 60 PSI 40 PSI N/A N/A ZONE
MED AIR N/A PASS 60 PSI 40 PSI N/A N/A ZONE
VACUUM N/A PASS N/A 12" HG N/A N/A ZONE
FLOOR: 3RD ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 23" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 25" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
DENTAL AIR 100 PSI PASS 120 PSI 80 PSI PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 25" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
BEACON MEDAES MEGA 3
ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
AREA MONITORED: COMMENTS
3E: 3E-110E, 110F
AREA MONITORED: COMMENTS
ENDOSCOPE SUITE
ACROSS FROM 3E-110E SCOPE STORAGE
ENDOSCOPY RECOVERY: 3A-
OUTSIDE OF 3A-116 ENDO RECOVERY ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
OUTSIDE OF SCOPE CLEANING ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
ACROSS FROM NURSE STATION ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
3A: 3A-154
NEXT TO 3A-154 ALARM MAKE AND MODEL:
AREA MONITORED: COMMENTS
3A & 3C: 3A-037, 3C-041A, 3C-041B
AREA ALARM SHOULD
READ 3A-037, 3C-041A,
& 3C-041B
AREA ALARM ANALYSIS
3RD FLOOR
AREA MONITORED: COMMENTS
3A: 3A-003 & 3A-004
3B: 3B-009, 3B-011, 3B-012, 3B-014, 3B-017, 3B-018, 3B-
020, 3B-023, 3B-24, 3B-029, 3B-030, 3B-033
POWER IS OFF
UNDER CONSTRUCTION
ACROSS FROM NURSE STATION ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
OUTSIDE OF 3A-004
AREA ALARM ANALYSIS
3RD FLOOR
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 3RD ALARM LOCATION:
COMMENTS
3F: 3F-121, 3F-124, 3F-125, 3F-127, 3F-133, 3F-136, 3F-
138, 3F-141, 3F-144, 3F-
146, 3F-147, 3F-149
NEXT TO 3F-124 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
END OF 3RD FLOOR AREA ALARM ANALYSIS
AREA MONITORED:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 23" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 21" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 26" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 26" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 23" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
OUTSIDE OF 4A-080 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
ACROSS FROM 4F-104 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
4A-080
AREA MONITORED: COMMENTS
4B: 4B-009, 4B-012, 4B-018, 4B-020, 4B-024, 4B-027
ACROSS FROM 4B-009
4F: 4F-086, 4F-089, 4F-093, 4F-095, 4F-101, 4F-104
OUTSIDE OF 4A-003 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
4A: 4A-109, 4A-110, 4A-059, 4A-065
OUTSIDE OF 4A-110 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
AREA ALARM ANALYSIS
4TH FLOOR
AREA MONITORED: COMMENTS
4A: 4A-003, 4A-004, 4A-048, 4A-051
ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
4E: 4E-073 & 4E-076
NEXT TO 4E-072 ELECTRICAL CLOSET ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA ALARM ANALYSIS
4TH FLOOR
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 24" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 4TH ALARM LOCATION:
AREA MONITORED: COMMENTS
4C: 4C-037 & 4C-038
NEXT TO 4A-045 STAFF ROOM ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
END OF 4TH FLOOR AREA ALARM ANALYSIS
MEDICAL GAS
ZONE VALVE ANALYSIS
Zone valves shall be readily operable from a standing position in the corridor on the same floor they serve. (NFPA 99 2024 5.1.4.6.1)
ZONE VALVE CODE REQUIREMENTS
Zone Valves. All station outlets/inlets shall be supplied through a zone valve as follows:
(NFPA 99 2024 5.1.4.6.1)
(2) The zone valves shall serve only outlets/inlets located on that same story.
(3) The zone valve shall not be located in a room with station outlets/inlets that it controls.
(1) The zone valve shall be placed such that a wall intervenes between the valve and outlets/inlets that it controls.
Zone valves shall be labeled in accordance with 5.1.11.2. (NFPA 99 2024 5.1.4.1.3)
Zone valves shall be so arranged that shutting off the supply of medical gas or vacuum to one zone will not affect the supply of medical gas or vacuum to another zone or the rest of the system.
(NFPA 99 2024 5.1.4.6.3)
A pressure/vacuum indicator shall be provided on the station outlet/inlet side of each zone valve.
(NFPA 99 2024 5.1.4.6.4)
Zone valve boxes shall not be installed behind normally open or normally closed doors or otherwise hidden from plain view. (NFPA 99 2024 5.1.4.6.1)
Zone valves shall be so arranged that shutting off the supply of gas to any one operating room or anesthetizing location will not affect the others. (NFPA 99 2024 5.1.4.6.3)
Zone valve boxes shall be installed where they are visible and accessible at all times.
(NFPA 99 2024 5.1.4.6.1 )
Zone valve boxes shall not be located in closed or locked rooms, areas, or closets. (NFPA 99 2024
5.1.4.6.1)
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 53 PSI PASS PASS 1-1/4" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 1" BALL PASS PASS P
VACUUM 26" HG PASS PASS 2" BALL PASS PASS P
FLOOR: GROUND VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
MED AIR 53 PSI PASS PASS 3/4" BALL PASS PASS P
FLOOR: GROUND VALVE LOCATION:
COMMENTS
END OF GROUND FLOOR ZONE VALVE ANALYSIS
ACROSS FROM URGENT CARE BREAK ROOM VALVE MANUFACTURER: BEACON MEDAES
BIOMED: GR-034
NOTE: OUTLETS CAPPED
IN 35 & 36
OUTSIDE OF BIOMED VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED:
ZONE VALVE ANALYSIS
GROUND FLOOR
AREA SERVED: COMMENTS
URGENT CARE: LL12, LL13, LL14, LL15,
LL16, LL17, LL25, LL38
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 51 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 50 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 26" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 50 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 52 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 26" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 24" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
AREA SERVED: COMMENTS
END OF 1ST FLOOR ZONE VALVE ANALYSIS
NEXT TO EXAM 1A-061 VALVE MANUFACTURER: BEACON MEDAES
PRIMARY CARE: 1A-053, 1A-061, 1A-062
AREA SERVED: COMMENTS
ROOM 1A-144 - FOR FUTURE USE
FOR FUTURE USE.
CAPPED ABOVE CEILING.
OUTSIDE OF ROOM 1A-144 VALVE MANUFACTURER: BEACON MEDAES
OUTSIDE DENTAL ENTRANCE VALVE MANUFACTURER: BEACON MEDAES
ZONE VALVE ANALYSIS
1ST FLOOR
AREA SERVED: COMMENTS
DENTAL CLINIC ROOMS: 1E-113, 1E-114,
1E-116, 1E-129, 1E-130, 1E-130A
MEDICAL AIR AND
VACUUM ARE FOR
FUTURE USE
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 49 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 53 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 26" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 2ND VALVE LOCATION:
END OF 2ND FLOOR ZONE VALVE ANALYSIS
ZONE VALVE ANALYSIS
2ND FLOOR
AREA SERVED: COMMENTS
2A CT: 2002 & 2005
ACROSS FROM 2A-063 BONE DENSITY VALVE MANUFACTURER: BEACON MEDAES
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 51 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 53 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 23" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 0 PSI PASS PASS 1" BALL PASS PASS
MED AIR 0 PSI PASS PASS 3/4" BALL PASS PASS
VACUUM 0" HG PASS PASS 3/4" BALL PASS PASS
FLOOR: 3RD VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 51 PSI PASS PASS 1" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 23" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 48 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 26" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
DENTAL AIR 100 PSI PASS PASS 3/4" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 54 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 51 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
AREA SERVED: COMMENTS
3A: 3A-154
NEXT TO 3A-154 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
3A & 3C: 3A-037, 3C-041A, 3C-041B
ZONE VALVE SHOULD
READ 3A-037, 3C-041A, &
3C-041B
NEXT TO 3A-045 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
ENDOSCOPY: 3E-111, 3E-111B, 3E-111C,
3E-113
OUTSIDE OF ENDO ENTRANCE VALVE MANUFACTURER: BEACON MEDAES
OUTSIDE OF 3A-004 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
3B: 3B-009, 3B-011, 3B-012, 3B-014, 3B-
017, 3B-018, 3B-020, 3B-023, 3B-24, 3B-
029, 3B-030, 3B-033
AREA UNDER
CONSTRUCTION.
HANDLES ARE REMOVED
AND ZONE VALVES ARE
TAGGED OUT
ACROSS FROM NURSE STATION VALVE MANUFACTURER: BEACON MEDAES
ZONE VALVE ANALYSIS
3RD FLOOR
AREA SERVED: COMMENTS
3A: 3A-003 & 3A-004
AREA SERVED: COMMENTS
3E: 3E-110E
ACROSS FROM 3E-110E SCOPE STORAGE VALVE MANUFACTURER: BEACON MEDAES
ZONE VALVE ANALYSIS
3RD FLOOR
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 54 PSI PASS PASS 1" BALL PASS PASS P
MED AIR 51 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 26" HG PASS PASS 1" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 23" HG PASS PASS 1" BALL PASS PASS P
FLOOR: 3RD VALVE LOCATION:
END OF 3RD FLOOR ZONE VALVE ANALYSIS
AREA SERVED: COMMENTS
ENDO RECOVERY: 3A-116
OUTSIDE OF 3A-116 ENDO RECOVERY VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
3F: 3F-121, 3F-124, 3F-125, 3F-127, 3F-
133, 3F-136, 3F-138, 3F-141, 3F-144, 3F-
146, 3F-147, 3F-149
NEXT TO 3F-124 VALVE MANUFACTURER: BEACON MEDAES
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 53 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 24" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 51 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 21" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 50 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 55 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 23" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 23" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 53 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 25" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 50 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 52 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/2" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
AREA SERVED: COMMENTS
4F: 4F-086, 4F-089, 4F-093, 4F-095, 4F-
101, 4F-104
ACROSS FROM 4F-104 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
4A-080
OUTSIDE OF 4A-080 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
4E: 4E-073 & 4E-076
NEXT TO 4E-072 ELECTRICAL CLOSET VALVE MANUFACTURER: BEACON MEDAES
ZONE VALVE ANALYSIS
4TH FLOOR
AREA SERVED: COMMENTS
4A: 4A-003, 4A-004, 4A-048, 4A-051
OUTSIDE OF 4A-003 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
4A: 4A-109, 4A-110, 4A-059, 4A-065
OUTSIDE OF 4A-110 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
4B: 4B-009, 4B-012, 4B-018, 4B-020, 4B-
024, 4B-027
ACROSS FROM 4B-009 VALVE MANUFACTURER: BEACON MEDAES
ZONE VALVE ANALYSIS
4TH FLOOR
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 1/2" BALL PASS PASS P
MED AIR 56 PSI PASS PASS 1/2" BALL PASS PASS P
VACUUM 21" HG PASS PASS 3/4" BALL PASS PASS P
FLOOR: 4TH VALVE LOCATION:
END OF 4TH FLOOR ZONE VALVE ANALYSIS
AREA SERVED: COMMENTS
4C: 4C-037 & 4C-038
NEXT TO 4A-045 STAFF ROOM VALVE MANUFACTURER: BEACON MEDAES
OUTLET ANALYSIS
OUTLET CODE REQUIREMENTS
Each station outlet/inlet for medical gases or vacuums shall be gas-specific, whether the outlet/inlet is threaded or is a noninterchangeable quick coupler. (NFPA 99 2024 5.1.5.1)
Each outlet/inlet shall be legibly identified in accordance with 5.1.11.3.1. (NFPA 99 2024 5.1.11.3)
Each station outlet/inlet, including those mounted in columns, hose reels, ceiling tracks, or other special installations, shall be designed so that parts or components that are required to be gas specific for compliance with 5.1.5.1 and 5.1.5.9 cannot be interchanged between the station outlet/inlet for different gases. (NFPA 99 2024 5.1.5.7)
All gas outlets with a gauge pressure of 345 kPa (50 psi), including, but not limited to, oxygen, nitrous oxide, medical air, and carbon dioxide, shall deliver 100 SLPM (3.5 SCFM) with a pressure drop of not more than 35 kPa (5 psi) and static pressure of 345 kPa to 380 kPa (50 psi to 55 psi).
(NFPA 99 2024 5.1.12.4.10.2)
Support gas outlets shall deliver 140 SLPM (5.0 SCFM) with a pressure drop of not more than 35 kPa (5 psi) gauge and static pressure of 1100 kPa to 1275 kPa (160 psi to 185 psi) gauge.
(NFPA 99 2024 5.1.12.4.10.3)
Medical–surgical vacuum inlets shall draw 85 Nl/min (3 SCFM) without reducing the vacuum pressure below 300 mm (12 in.) gauge HgV at any adjacent station inlet. (NFPA 99 2024 5.1.12.4.10.4)
Oxygen and medical air outlets serving critical care areas shall allow a transient flow rate of 170 SLPM
(6 SCFM) for 3 seconds. (NFPA 99 2024 5.1.12.4.10.5)
Medical gas concentration & flow rate requirements. (NFPA 99 2024 Table 5.1.12.4.11)
GAS FLOW RATE CONCENTRATION
OXYGEN Non-critical 3.5 SCFM Critical 6.0 SCFM ≥99% oxygen
MEDICAL AIR Non-critical 3.5 SCFM Critical 6.0 SCFM 19.5%–23.5% oxygen
NITROUS OXIDE 3.5 SCFM ≥99% nitrous oxide
NITROGEN 5.0 SCFM ≤1% O2 or ≥99% N2
OTHER GASES 3.5 SCFM
As specified by ±1%, unless otherwise specified
VACUUM 3.0 SCFM N/A
WAGD 3.0 SCFM N/A
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e w
/o
A d ap te r O p er at io n al
Fl o w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io
La b el in g
PASS FAIL REPAIRED BY
GROUND FLOOR OXYGEN MEDICAL AIR VACUUM
BIOMED GD-035 1 BEACON DC CH P P P P P P P
URGENT CARE
LL12 2 2 2 AMICO SB CH P P P P P P P
LL13 2 2 2 AMICO SB CH P P P P P P P
LL14 2 2 2 AMICO SB CH P P P P P P P
LL15 2 2 2 AMICO SB CH P P P P P P P
LL16 2 2 2 AMICO SB CH P P P P P P P
LL17 2 2 2 AMICO SB CH P P P P P P P
LL25 2 2 2 AMICO SB CH P P P P P P P
LL38 2 2 2 AMICO SB CH P P P P P P P
TOTAL COUNT: 16 17 16
GAS TYPE & OUTLET QUANTITY OUTLET SPECS COMMENTS
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p er at io w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io el in g
PASS FAIL REPAIRED BY
2ND FLOOR OXYGEN MEDICAL AIR VACUUM
CT 2002 1 1 1 BEACON SB DISS P P P P P P P
CT 2005 1 1 1 BEACON SB DISS
TOTAL COUNT: 2 2 2
OUTLET ANALYSIS
ROOM IS UNDER CONSTRUCTION
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p er at io w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io el in g
PASS FAIL REPAIRED BY
1ST FLOOR OXYGEN MEDICAL AIR VACUUM
DENTAL CLINIC
1E-113 1 ALLIED 400 CH P P P P P P P
1E-114 1 ALLIED 400 CH P P P P P P P
1E-116 1 ALLIED 400 CH P P P P P P P
1E-129 1 ALLIED 400 CH P P P P P P P
1E-130 1 ALLIED 400 CH P P P P P P P
1E-130A 1 ALLIED 400 CH P P P P P P P
1A-053 1 1 1 BEACON SB CH P P P P P P P
1A-061 1 1 1 ALLIED 400 CH P P P P P P P
1A-062 1 1 1 ALLIED 400 CH P P P P P P P
TOTAL COUNT: 9 3 3
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p er at io w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io el in g
PASS FAIL REPAIRED BY
3RD FLOOR OXYGEN MEDICAL AIR VACUUM
3A-003 4 4 4 AMICO SB CH P P P P P P P
3A-004 4 4 4 AMICO SB CH P P P P P P P
3B-009
3B-011
3B-012
3B-014
3B-017
3B-018
3B-020
3B-023
3B-024
3B-029
3B-030
3B-033
3A-037 2 2 2 AMICO SB CH P P P P P P P
3C-041A 4 4 4 AMICO SB CH P P P P P P P
3C-041B 4 4 4 AMICO SB CH P P P P P P P
3A-154 PROCEDURE 4 4 4 AMICO SB CH P P P P P P P
3E-110E 3 BEACON DC CH P P P P P P P
3E-111 - BED 1 2 2 2 ALLIED 400 CH P P P P P P P
3E-111 - BED 2 2 2 2 ALLIED 400 CH P P P P P P P
3E-111 - BED 3 2 2 2 ALLIED 400 CH P P P P P P P
3E-111 - BED 4 2 2 2 ALLIED 400 CH P P P P P P P
3E-111B 4 4 4 AMICO SB CH P P P P P P P
3E-111C 4 4 4 AMICO SB CH P P P P P P P
3E-113 2 2 2 ALLIED 400 CH P P P P P P P
3A-116 ENDO RECOVERY 4 4 4 AMICO SB CH P P P P P P P
TOTAL COUNT: 44 47 44
DENTAL AIR
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
OUTLET ANALYSIS
GAS TYPE & OUTLET QUANTITY OUTLET SPECS COMMENTS
ROOM IS UNDER CONSTRUCTION
ROOM IS UNDER CONSTRUCTION
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p er at io w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io el in g
PASS FAIL REPAIRED BY
3RD FLOOR OXYGEN MEDICAL AIR VACUUM
OUTLET ANALYSIS
GAS TYPE & OUTLET QUANTITY OUTLET SPECS COMMENTS
3F-121 1 1 1 BEACON SB CH P P P P P P P
3F-124 1 1 1 BEACON SB CH P P P P P P P
3F-125 1 1 1 BEACON SB CH P P P P P P P
3F-127 1 1 1 BEACON SB CH P P P P P P P
3F-133 1 1 1 BEACON SB CH P P P P P P P
3F-136 1 1 1 BEACON SB CH P P P P P P P
3F-138 1 1 1 BEACON SB CH P P P P P P P
3F-141 1 1 1 BEACON SB CH P P P P P P P
3F-144 1 1 1 BEACON SB CH P P P P P P P
3F-146 1 1 1 BEACON SB CH P P P P P P P
3F-147 1 1 1 BEACON SB CH P P P P P P P
3F-149 1 1 1 BEACON SB CH P P P P P P P
TOTAL COUNT: 12 12 12
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e ap te r O p er at io w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io el in g
PASS FAIL REPAIRED BY
4TH FLOOR OXYGEN MEDICAL AIR VACUUM
4A-003 2 2 2 AMICO SB CH P P P P P P P
4A-004 1 1 1 AMICO SB CH P P P P P P P
4A-048 1 1 1 AMICO SB CH P P P P P P P
4A-051 2 2 2 AMICO SB CH P P P P P P P
4A-109 1 1 1 AMICO SB CH P P P P P P P
4A-110 1 1 1 AMICO SB CH P P P P P P P
4A-059 1 1 1 AMICO SB CH P P P P P P P
4A-065 1 1 1 AMICO SB CH P P P P P P P
4F-086 2 2 2 AMICO SB CH P P P P P P P
4F-089 2 2 2 AMICO SB CH P P P P P P P
4F-093 1 1 1 AMICO SB CH P P P P P P P
4F-095 2 2 2 AMICO SB CH P P P P P P P
4F-101 1 1 1 AMICO SB CH P P P P P P P
4F-104 2 2 2 AMICO SB CH P P P P P P P
4A-080 1 1 1 AMICO SB CH P P P P P P P
4E-73 2 2 2 AMICO SB CH P P P P P P P
4E-76 1 1 1 AMICO SB CH P P P P P P P
4B-009 1 1 1 AMICO SB CH P P P P P P P
4B-012 2 2 2 AMICO SB CH P P P P P P P
4B-018 2 2 2 AMICO SB CH P P P P P P P
4B-020 2 2 2 AMICO SB CH P P P P P P P
4B-024 2 2 2 AMICO SB CH P P P P P P P
4B-027 2 2 2 AMICO SB CH P P P P P P P
4C-037 2 2 2 AMICO SB CH P P P P P P P
4C-038 2 2 2 AMICO SB CH P P P P P P P
TOTAL COUNT: 39 39 39
OUTLET PURITY &
CROSS CONNECT
ANALYSIS
VHA DIRECTIVE 7515
1.REASON FOR ISSUE: This Veterans Health Administration (VHA) directiveestablishes policy for the
Department of Veterans Affairs (VA) regarding the safeinstallation, operation, and maintenance of
Medical Gas and Vacuum Systems at VAmedical facilities.
VHA DIRECTIVE 7515(1) A-1 APPENDIX A
(1) Cross connection verification of 10 percent of the existing outlets annually. Testing cannot be repeated on an outlet until all outlets in the hospital have been tested once. Additionally, testing of newly installed outlets must not supersede the testing of existing outlets.
2) Purity verification at 10 percent of the existing outlets annually.
OUTLET PURITY & CROSS CONNECT REQUIREMENTS
OUTLET LOCATION
O2
AIR
COMMENTS
OUTLETS TESTED OXY MED AIR
MED
VAC
LL12 2 2 2 99.9% 21.3%
LL25 2 2 2 99.9% 21.3%
3A-004 4 4 4 99.9% 21.3%
3E-111B 4 4 4 99.9% 21.3%
3F-121 1 1 1 99.9% 21.3%
4F-086 2 2 2 99.9% 21.3%
4C-038 2 2 2 99.9% 21.3%
TOTAL COUNT: 17 17 17
OUTLET CROSS-CONNECT &
PURITY TESTING
GAS TYPE & OUTLET
QUANTITY
CROSS-CONNECT
PROCEDURE
PURITY
ANALYSIS
CROSS
CONNECT
STATUS
PASS/FAIL
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
CSMEDGAS.COM COMPLIANCE SOLUTIONS 1-833-5MEDGAS
MEDICAL GAS SOURCE
EQUIPMENT ANALYSIS
LOCATION BULK TANK FARM
AREA(S) OF FACILITY SERVED ENTIRE FACILITY
BULK SUPPLIER OZARC GAS
SYSTEM TYPE LIQUID X HP - 10 X 10
PRIMARY LIQUID LEVEL 75"
PRIMARY PRESSURE 180 PSI
RESERVE LIQUID LEVEL N/A
RESERVE PRESSURE 1550 PSI
PRIMARY FINAL LINE PRESSURE 180 PSI
RESERVE FINAL LINE PRESSURE 190 PSI
SOURCE VALVE PRESSURE 51 PSI
MAIN VALVE PRESSURE 51 PSI
SOURCE VALVE TYPE BALL JOINT
SOURCE VALVE LOCATION SOILED UTILITY ROOM
PRESSURE SWITCH LOCATION GD-041 EQUIPMENT STORAGE
EOSC VALVE SIZE 2"
EOSC LOCATION(S) EXTERIOR WALL NEAR BULK
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Piped w/brazed copper, brass, or stainless & no flex connects/fittings wear & leaks
Reserve and primary check valves in place for reserve to feed automatically
Reserve economizer in place to feed upstream final regulators
Drainage prevented towards (buildings, drains, etc.) & from hazards
Labeling: pipeline, source/main valves & "Oxygen-No Smoking, No Open Flames"
Vaporizer appears adequately sized & isolation valves arranged for service w/o supply interruption
Emergency Supply (3' clearance) or (IBER) w/2 checks, secured, & labeled
Distance from the following: 1' - all structures (Type I & II), * 50' - wood framed Type III, IV, or V building types, * 50' - Public assembly or nearest non- ambulatory patient, * 5' -
Property lines & overhead electrical wiring, 10' building openings, * 10' - public sidewalks & parked vehicles, * 15' - Hazardous piping materials & below ground flammable liquid tanks, * 25' - 0-1000 gal flammable liquids/liquefied gas, below ground flammable liquid fill or vent, 0-25,000 scf flammable gases, or slow burning solids, * 50' - >1000 gal flammable liquids/liquefied gas, >25,000 scf flammable gases, or rapidly burning solids, 3' - combustible surfaces (asphalt & expansion joint filler) where liquid oxygen may fall, 8' - Sewer or drain openings to delivery connects, reliefs, mobile supply equipment, & liquid withdrawal connects, Walls may not form a 3-4 sided court.
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
Proper fill circuit (inlet, strainer, check valve, purge valve, supports)
BULK OXYGEN
SOURCE EVALUATION DATA
NFPA 99 2024 SCHEMATIC
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Enclosure (min 6' height) non-combustible, proper ventilation & 2 lockable entries/exits
Containers permanently anchored & cylinders adequately secured
Noncombustible pad w/3' maintenance clearance, accessible for delivery & pad adequately sized for vehicles
Top & bottom fill, hose purge, & vent valves present
LOCATION BASEMENT MECHANICAL ROOM LINE PRESSURE
AREA(S) OF FACILITY SERVED ENTIRE FACILITY DRYER TYPE
MANUFACTURER POWEREX DRYER INFO
MODEL NUMBER MTD050525 DEW POINT MONITOR INFO
SERIAL NUMBER (H)11/30/2018-6183006-287 CO MONITOR INFO
SYSTEM TYPE RECIPROCATING SOURCE VALVE LOCATION
CONFIGURATION DUPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL BALDOR EM3312T PUMP 1 HOURS
HORSEPOWER 5 HP PUMP 2 HOURS
LEAD ON/OFF 105/95 PSI PUMP 3 HOURS
LAG ON/OFF 95/85 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) 35 DEG F -19 DEG F PASS
DEW POINT (CS MONITOR) 35 DEG F -21 DEG F PASS
CARBON MONOXIDE (MONITOR ON SYSTEM) 10 PPM 0 PPM PASS
CARBON MONOXIDE (CS MONITOR) 10 PPM 0 PPM PASS
CARBON DIOXIDE 500 PPM 103 PPM PASS
METHANE 25 PPM 0 PPM PASS
CHLOROFORM 2 PPM 0 PPM PASS
OXYGEN 19.5%-23.5% 21.3% PASS
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
N/A
MEDICAL AIR SYSTEM
SOURCE EVALUATION DATA
110 PSI
DESICCANT
POWEREX PDM11003AJ
POWEREX DK964700AJ
ENMET CO-GUARD
BEHIND SOURCE
BEHIND SOURCE
System power supplied from emergency power
N/A
NFPA 99 2024 SCHEMATIC MEDICAL AIR PURITY ANALYSIS
COMMENTS
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical air compressors
System is supplied with flexible connectors on inlet and outlet sides of the compressors
Intake above roof level, >20' above ground, 10 ft from doors, windows, other openings, and 25' from exhausts
System is equipped with manual disconnects
System is equipped with a local lag, dew point and CO alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain, pressure gauge, sight glass, pressure relief, & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System automatically alternates the pumps evenly
Duplexed dryer system
1/4" sample port installed
Source valve in proper location and labeled
Mainline and intake piping properly labeled
Intake turned down and screened
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
LOCATION BASEMENT MECHANICAL ROOM LINE PRESSURE
MANUFACTURER BEACON MEDAES DRYER INFO
MODEL NUMBER 4107005549 DEW POINT MONITOR INFO
SERIAL NUMBER HOP401608 CO MONITOR INFO
SYSTEM TYPE DUPLEX SOURCE VALVE LOCATION
CONFIGURATION DUPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL BEACON MEDAES AIA2498719 PUMP 1 HOURS
HORSEPOWER 10 HP PUMP 2 HOURS
LEAD ON/OFF 105/95 PSI PUMP 3 HOURS
LAG ON/OFF 95/85 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) 35 DEG F -11 DEG C PASS
DEW POINT (CS MONITOR) 35 DEG F -13 DEG C PASS
CARBON MONOXIDE (MONITOR ON SYSTEM) 10 PPM 0 PPM PASS
CARBON MONOXIDE (CS MONITOR) 10 PPM 0 PPM PASS
CARBON DIOXIDE 500 PPM 114 PPM PASS
METHANE 25 PPM 0 PPM PASS
CHLOROFORM 2 PPM 0 PPM PASS
OXYGEN 19.5%-23.5% 21.3% PASS
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PIntake turned down and screened
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
Intake above roof level, >20' above ground, 10 ft from doors, windows, other openings, and 25' from exhausts
System is equipped with manual disconnects
System is equipped with a local lag, dew point and CO alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain, pressure gauge, sight glass, pressure relief, & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System automatically alternates the pumps evenly
Duplexed dryer system
1/4" sample port installed
Source valve in proper location and labeled
Mainline and intake piping properly labeled
System power supplied from emergency power
N/A
NFPA 99 2024 SCHEMATIC MEDICAL AIR PURITY ANALYSIS
COMMENTS
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical air compressors
System is supplied with flexible connectors on inlet and outlet sides of the compressors
N/A
MEDICAL AIR SYSTEM
SOURCE EVALUATION DATA
96 PSI
DESICCANT
BEACON MEDAES SF72
INTERNAL
INTERNAL
BEHIND SOURCE
BEHIND SOURCE
LOCATION BASEMENT MECHANICAL ROOM
MANUFACTURER ALLEN-BRADLEY
MODEL NUMBER 4000054719
SERIAL NUMBER CA 1786010-01
SYSTEM TYPE LUBE VANE
CONFIGURATION DUPLEX
PUMP MAKE AND MODEL FLOWSERVE 4000054719
HORSEPOWER 4.2 HP
LEAD ON/OFF 22/18" HG
LAG ON/OFF 19/16" HG
LINE PRESSURE 22" HG
SOURCE VALVE LOCATION BEHIND SOURCE
PRESSURE SWITCH LOCATION BEHIND SOURCE
PUMP 1 HOURS 7088
PUMP 2 HOURS 7123
PUMP 3 HOURS N/A
PUMP 4 HOURS N/A
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
NFPA 99 2024 CHECKLIST
MEDICAL VACUUM SYSTEM
SOURCE EVALUATION DATA
NFPA 99 2024 SCHEMATIC
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System visibly complies with above schematic per NFPA 99.
Located in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical vacuum pumps
System has flexible connectors
System has antivibration mountings
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
PASS
ADDITIONAL COMMENTS
System automatically alternates the pumps evenly
Source valve in proper location and labeled
Mainline and exhaust piping properly labeled
Exhaust is turned down and screened
Exhaust ≥25' from doors, windows, intakes, building openings & public assembly & copper or stainless, no dips, drip legs installed, & sufficient diameter
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS
LOCATION BASEMENT MECHANICAL ROOM
MANUFACTURER ALLEN-BRADLEY
MODEL NUMBER 4000054719
SERIAL NUMBER CA 1786010-01
SYSTEM TYPE LUBE VANE
CONFIGURATION DUPLEX
PUMP MAKE AND MODEL FLOWSERVE 4000054719
HORSEPOWER 4.2 HP
LEAD ON/OFF 22/18" HG
LAG ON/OFF 19/16" HG
LINE PRESSURE 21" HG
SOURCE VALVE LOCATION BEHIND VACUUM SYSTEM 1
PRESSURE SWITCH LOCATION BEHIND VACUUM SYSTEM 1
PUMP 1 HOURS 6865
PUMP 2 HOURS 6857
PUMP 3 HOURS N/A
PUMP 4 HOURS N/A
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PASS
ADDITIONAL COMMENTS
System automatically alternates the pumps evenly
Source valve in proper location and labeled
Mainline and exhaust piping properly labeled
Exhaust is turned down and screened
Exhaust ≥25' from doors, windows, intakes, building openings & public assembly & copper or stainless, no dips, drip legs installed, & sufficient diameter
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System visibly complies with above schematic per NFPA 99.
Located in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical vacuum pumps
System has flexible connectors
System has antivibration mountings
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
NFPA 99 2024 CHECKLIST
MEDICAL VACUUM SYSTEM
SOURCE EVALUATION DATA
NFPA 99 2024 SCHEMATIC
LOCATION PENTHOUSE LINE PRESSURE
MANUFACTURER ATLAS-COPCO DRYER INFO
MODEL NUMBER SF8+ DEW POINT MONITOR INFO
SERIAL NUMBER API775262 CO MONITOR INFO
SYSTEM TYPE SCROLL SOURCE VALVE LOCATION
CONFIGURATION DUPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL N/A PUMP 1 HOURS
HORSEPOWER 9.92 HP PUMP 2 HOURS
LEAD ON/OFF 100/110 PSI PUMP 3 HOURS
LAG ON/OFF 85/95 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) NEG 22 DEG F -32 DEG C PASS
DEW POINT (CS MONITOR) NEG 22 DEG F -30 DEG C PASS
CARBON MONOXIDE (MONITOR ON SYSTEM) 10 PPM 0 PPM PASS
CARBON MONOXIDE (CS MONITOR) 10 PPM 0 PPM PASS
OXYGEN 19.5%-23.5% 21.3%
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
N/A
LAB AIR SYSTEM
SOURCE EVALUATION DATA
108 PSI
DESICCANT
ATLAS COPCO 1624 7324 80
INTERNAL
INTERNAL
ABOVE SOURCE
WALL ACROSS FROM SOURCE
N/A
NFPA 99 2024 SCHEMATIC LAB AIR PURITY ANALYSIS
COMMENTS
Each pump has an isolation valve so a pump can be serviced without interruption of the system
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated…
This is the start of the file's text. The full file is on GovTribe.