Cape Girardeau VA Med Gas Annual 2025.pdf
PDF 953 KB Posted
- Attached to
- Medical Gas Maintenance Service and Inspection
- Solicitation number
- 36C25526Q0384
About this file
This is a Medical Gas Annual Inspection Report for the Cape Girardeau VA Health Care Center, conducted by MGI Medical Gas Installers on September 29, 2025, in compliance with NFPA 99 2024 standards for a Category 1 medical facility.
The inspection tested multiple medical gas systems including oxygen, medical air, medical vacuum, nitrous oxide, nitrogen, carbon dioxide, instrument air, and WAGD across source equipment, master alarms, zone valves, zone verification, cross connections, area alarms, and patient outlets. Overall results showed 47 of 48 patient outlet terminals passed testing (97.9% pass rate), with one vacuum outlet in Procedure Room 2 requiring repair due to leaks without adapter insertion. Source equipment testing identified two failures: the medical air scroll compressor and the vacuum CLAW system both failed testing, resulting in 4 of 6 total source items passing (66.7% pass rate). All master alarm panel signals passed (30 of 30), with two TRI-TECH MED TOUCH panels located in the pre/post nurse station and security office meeting NFPA 99 2024 location requirements. All six zone valves and six area alarms passed inspection. Cross-connection and purity verification testing of ten outlets (approximately 10% of existing outlets per VHA Directive 7515) confirmed individual pressurization and showed oxygen purity at 99.9% and medical air at 21.0%.
Two corrective actions were identified requiring compliance: proper labeling of the medical air fresh air intake line in both the mechanical room and rooftop, and proper labeling of the vacuum exhaust line in both locations. The bulk oxygen system from Taylor Wharton and the oxygen manifold system both passed NFPA 99 2024 code requirements. However, the compressed air system failed due to improper labeling of the fresh air intake line, and the medical vacuum system failed because the exhaust line was improperly labeled as an air intake rather than vacuum exhaust. No future corrections were identified as necessary for patient care continuity.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25526Q0384 0001.pdf | ||
| John J Pershing VA Medical Center Med Gas Annual 2025.pdf | ||
| 36C25526Q0384_1.docx | DOCX document | |
| Pre-Sol 36C25526Q0384_2.docx | DOCX document | |
| 36C25526Q0384 Sources Sought.docx | DOCX document |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
PREPARED BY: BRAYDEN SEGER
TESTING DATES: SEPTEMBER 29TH, 2025
CAPE GIRARDEAU VA HEALTH CARE CENTER
MEDICAL GAS
ANNUAL
INSPECTION
711 S MT AUBURN RD
CAPE GIRARDEAU, MO
ITEMS TESTED/INSPECTED
OXYGEN MEDICAL AIR
MEDICAL
VACUUM
NITROUS
OXIDE
NITROGEN
CARBON
DIOXIDE
INST. AIR WAGD
SOURCE EQUIPMENT P P P
MASTER ALARMS P P P
ZONE VALVES P P P P
ZONE VERIFICATION P P P P
CROSS CONNECTION P P P P
AREA ALARMS P P P P
PATIENT OUTLETS P P P P
PARTICLE ANALYSIS P P
PURITY ANALYSIS P P
MGI MEDICAL GAS VERIFIER: BRAYDEN SEGER
SIGNATURE:
DATE: 9/29/2025
MEDICAL GAS ANNUAL TESTING ANALYSIS
MEDICAL GAS TYPE
SCOPE OF
TESTING/VERIFICATION
NFPA 99 2024 Compliant Medical Gas Annual Inspection for a Category 1 Medical Facility. Includes testing of all medical gas source equipment, medical gas zone valves, medical gas master alarm panels, medical gas area alarm panels, medical gas control panels, medical gas flexible terminals and medical gas terminals and medical gas labeling.
ADDITIONAL COMMENTS
https://qrplanet.com/8lq61w
EXECUTIVE SUMMARY
SIGNALS
PASSED
SIGNALS
FAILED
TOTALS 2 30 30 0
MASTER ALARM PANEL TRI-TECH MED TOUCH 1 15 15 0
MASTER ALARM PANEL TRI-TECH MED TOUCH 1 15 15
2 2 0
SOURCE EQUIPMENT MASTER ALARMS
EQUIPMENT
EQUIPMENT MAKE &
MODEL
ALARM PANEL
COUNT
ALARM SIGNAL
COUNT
TOTAL 6 4 2
MASTER ALARM PANEL ALARMS
CLAWVACUUM 1 0 1
OXYGEN BULK OXYGEN 1 1 0
MEDICAL AIR SCROLL 1 0 1
EXECUTIVE OVERALL SUMMARY-SOURCE
SOURCE EQUIPMENT
GAS TYPE SOURCE TYPE TOTAL COUNT TOTAL PASSED TOTAL FAILED
OXYGEN GAS X GAS MANIFOLD 1 1 0
FAILED REPAIRED FAILED REPAIRED
TOTAL PERCENTAGE OF
OUTLETS TESTED
100.0%
TOTAL OUTLET
FAILURES
TOTAL OUTLETS
REPAIRED
1 0
TOTAL 48 47 1 0
PERCENTAGE 97.9% 2.1% 0.0%
WAGD 4 4 0 0
VACUUM 14 13 1 0
MEDICAL AIR 13 13 0 0
GAS TYPE TOTAL COUNT TOTAL PASSED TOTAL FAILED TOTAL UNAVAILABLE
OXYGEN 17 17 0 0
EXECUTIVE OVERALL SUMMARY-PIPELINE
ZONE VALVES AREA ALARMS
TOTAL VALVES TOTAL ALARMSTOTAL PASSED TOTAL PASSED
0 0
PATIENT OUTLET TERMINALS
6 6
MISSING VALVES MISSING ALARMS
0 00 0
MGI TECHNICIAN: BRAYDEN SEGER
1 SPECIFIC OUTLET REPAIRED BY REPAIR DATE
BACK BOOM VACUUM PROCEDURE ROOM 2 AMICO - DC - CH LEAKS W/OUT ADAPTER INSERTED
CAPE GIRARDEAU VA HEALTH CARE CENTER
END OF OUTLET ISSUES
OUTLET ISSUES
ROOM OUTLET SPECS ISSUE
CAPE GIRARDEAU VA HEALTH CARE CENTER
CORRECTED
CORRECTED
END OF CORRECTIVE ACTIONS
ISSUE NFPA 99 2024 CODE
MEDICAL AIR SOURCE FRESH AIR INTAKE IS IMPROPERLY LABELED
5.1.11.1.1 Piping shall be labeled by stenciling or
adhesive markers that identify the patient medical gas, the support gas, or the vacuum system.
NOTE: CORRECTIVE ACTIONS ARE COMPONENTS OF THE MEDICAL GAS SYSTEM THAT DO NOT MEET THE NFPA 99 2024 CODE AND SHOULD BE UPGRADED OR REPAIRED TO MEET THE
NFPA 99 2024 CODE.
CORRECTIVE
ACTION
THE MEDICAL AIR INTAKE NEEDS TO BE PROPERLY LABELED IN THE MECHANICAL ROOM AS WELL AS THE ROOFTOP TO DIFFERENTIATE IT FROM
OTHER EXHAUST LINES AND INTAKES.
CORRECTIVE ACTIONS
AREA ISSUE NFPA 99 2024 CODE
VACUUM SOURCE VACUUM EXHAUST IS IMPROPERLY LABELED
5.1.11.1.1 Piping shall be labeled by stenciling or
adhesive markers that identify the patient medical gas, the support gas, or the vacuum system.
CORRECTIVE
ACTION
THE VACUUM EXHAUST LINE NEEDS TO BE PROPERLY LABELED IN THE MECHANICAL ROOM AS WELL AS THE ROOFTOP TO DIFFERENTIATE IT
FROM OTHER EXHAUST LINES AND INTAKES.
AREA
NOTE: THESE ARE COMPONENTS OF THE MEDICAL GAS SYSTEM THAT DO NOT MEET THE 2024 NFPA 99 CODE, HOWEVER THEY ARE PERMITTED TO
REMAIN IN USE UNTIL THE AREA(S) ARE UPGRADED OR RENOVATED DUE TO THE ABOVE NOT AFFECTING PATIENT CARE.
END OF FUTURE CORRECTIONS
FUTURE CORRECTIONS
AREA ISSUE NFPA 99 2024 CODE
NONE AT THIS TIME.
FUTURE
CORRECTION
MEDICAL GAS MASTER
ALARM ANALYSIS
MASTER ALARM CODE REQUIREMENTS
Master alarm panels for medical gas and vacuum systems shall each include the following signals:
(NFPA 99 2024 5.1.9.2.4)
(1) Alarm indication when, or just before, changeover occurs in a medical gas system that is supplied by a manifold or other alternating-type bulk system that has as a part of its normal operation a changeover from one portion of the operating supply to another.
(2) Alarm indication for a bulk cryogenic liquid system when the main supply reaches an average day’s supply, indicating low contents.
(3) Alarm indication when, or just before, the changeover to the reserve supply occurs in a medical gas system that consists of one or more units that continuously supply the piping system while another unit remains as the reserve supply and operates only in the case of an emergency.
(4) Alarm indication for cylinder reserve pressure low when the content of a cylinder reserve header is reduced below one average day’s supply.
(5) For bulk cryogenic liquid systems, an alarm when or at a predetermined set point before the reserve supply contents fall to one day’s average supply, indicating reserve low.
(6) Where a cryogenic liquid storage unit is used as a reserve for a bulk supply system, an alarm indication when the gas pressure available in the reserve unit is below that required for the medical gas system to function.
(7) Alarm indication when the pressure in the main line of each separate medical gas system increases 20 percent or decreases 20 percent from the normal operating pressure.
(8) Alarm indication when the medical–surgical vacuum pressure in the main line of each vacuum system drops.
(9) Alarm indication(s) from the local alarm panel(s) as described in 5.1.9.5.2 to indicate when one or more of the conditions being monitored at a site is in alarm.
(10) Medical air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than +2°C (+35°F)
(11) WAGD low alarm when the WAGD vacuum level or flow is below effective operating limits.
(12) An instrument air dew point high alarm from each compressor site to indicate when the line pressure dew point is greater than −30°C (−22°F).
(13) Alarm indication if the primary or reserve production stops on a proportioning system.
CAPE GIRARDEAU VA HEALTH CARE CENTER MGI TECHNICIAN: BRAYDEN SEGER
CAPE GIRARDEAU, MO TESTING DATE: 9/29/2025
VISUAL
STATUS
AUDIBLE
STATUS
LABELED
CORRECTLY
COMMENTS
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
ALARM MAKE AND MODEL: PRE / POST NURSE STATION
COMMENTS
(1) One master alarm panel shall be located in the office or work space of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems.
(2) In order to ensure continuous surveillance of the medical gas and vacuum systems while the facility is in operation, the second master alarm panel shall be located in an area of continuous observation (e.g., the telephone switchboard, security office, or other continuously staffed location).
PASS/FAIL
PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN PASS
TRI-TECH MED TOUCH LOCATION:
PER NFPA 99 2024 WHERE IS THE MASTER ALARM LOCATED OF THE FOLLOWING LOCATIONS LOCATION
MEDICAL AIR LINE PRESSURE LOW PASS
MEDICAL VACUUM LAG IN USE PASS
MEDICAL VACUUM LINE PRESSURE LOW PASS
MEDICAL AIR HIGH DEW POINT PASS
MEDICAL AIR CO HIGH PASS
MEDICAL AIR LINE PRESSURE HIGH PASS
MASTER ALARM ANALYSIS
MASTER ALARM SIGNALS PASS/FAIL
OXYGEN PRIMARY LIQUID LEVEL LOW PASS
OXYGEN SECONDARY LIQUID SUPPLY IN USE PASS
OXYGEN SECONDARY LIQUID LEVEL LOW PASS
OXYGEN SECONDARY LIQUID LOW HEAD PRESSURE PASS
OXYGEN LINE PRESSURE HIGH PASS
OXYGEN LINE PRESSURE LOW PASS
MEDICAL AIR COMP MAINTENANCE REQUIRED PASS
CAPE GIRARDEAU VA HEALTH CARE CENTER MGI TECHNICIAN: BRAYDEN SEGER
CAPE GIRARDEAU, MO TESTING DATE: 9/29/2025
VISUAL
STATUS
AUDIBLE
STATUS
LABELED
CORRECTLY
COMMENTS
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
P P P
ALARM MAKE AND MODEL: SECURITY
COMMENTS
OXYGEN SECONDARY LIQUID SUPPLY IN USE PASS
MASTER ALARM ANALYSIS
MASTER ALARM SIGNALS PASS/FAIL
OXYGEN PRIMARY LIQUID LEVEL LOW PASS
OXYGEN SECONDARY LIQUID LEVEL LOW PASS
OXYGEN SECONDARY LIQUID LOW HEAD PRESSURE PASS
OXYGEN LINE PRESSURE HIGH PASS
OXYGEN LINE PRESSURE LOW PASS
MEDICAL AIR COMP MAINTENANCE REQUIRED PASS
MEDICAL AIR HIGH DEW POINT PASS
MEDICAL AIR CO HIGH PASS
MEDICAL AIR LINE PRESSURE HIGH PASS
MEDICAL AIR LINE PRESSURE LOW PASS
TRI-TECH MED TOUCH LOCATION:
MEDICAL VACUUM LAG IN USE PASS
MEDICAL VACUUM LINE PRESSURE LOW PASS
MEDICAL VACUUM HIGH TEMP SHUTDOWN PASS
PER NFPA 99 2024 WHERE IS THE MASTER ALARM LOCATED OF THE FOLLOWING LOCATIONS LOCATION
(1) One master alarm panel shall be located in the office or work space of the on-site individual responsible for the maintenance of the medical gas and vacuum piping systems.
(2) In order to ensure continuous surveillance of the medical gas and vacuum systems while the facility is in operation, the second master alarm panel shall be located in an area of continuous observation (e.g., the telephone switchboard, security office, or other continuously staffed location).
PASS/FAIL
PASS
MEDICAL GAS AREA
ALARM ANALYSIS
(2) *Critical Care Areas
(2)*Anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is administered shall have the sensors installed either on the source side of any of the individual room zone valve box assemblies or on the patient or use side of each of the individual zone valve box assemblies.
(5) Visual and audible indication that the communication with an alarm-initiating devices is disconnected.
(6) Labeling of each indicator, indication the condition monitored.
(7) Labeling of each alarm panel for its area of surveillance.
(8) Reinitiating of the audible signal if another alarm condition occurs while the audible alarm is silenced.
(9) Power for master, area alarms, sensors, and switches from the life safety branch of the emergency electrical system as described in Chapter 6.
Area Alarms. Area alarm panels shall be provided to monitor all medical gas, medical–surgical vacuum, and piped WAGD systems supplying the following: (NFPA 99 2024 5.1.9.4)
(1) Anesthetizing locations where moderate sedation, deep sedation, or general anesthesia is administered.
Area alarm panels for medical gas systems shall indicate if the pressure in the lines in the area being monitored increases or decreases by 20 percent from the normal line pressure. (NFPA 99 2024 5.1.9.4.2)
Area alarm panels for medical–surgical vacuum systems shall indicate if the vacuum in the area drops to or below 300 mm (12 in.) gauge HgV. (NFPA 99 2024 5.1.9.4.3)
Alarm sensors for area alarms shall be located as follows: (NFPA 99 2024 5.1.9.4.4)
(1)*Critical care areas shall have the alarm sensors installed on the patient or use side of each individual zone valve box assemblies.
AREA ALARM CODE REQUIREMENTS
(1) Separate visual indicators for each condition monitored, except as permitted in 5.1.9.5.2 for local alarms that are displayed on master alarm panels.
(2) Visual indicators that remain in alarm until the situation that has caused the alarm is resolved.
(3) Cancelable audible indication of each alarm condition that produces a sound with a minimum level of
80 dBA at 0.92m (3 ft)
(4) Means to visually indicate a lamp or LED failure
Area alarm systems used for medical gas and vacuum systems shall include the following:
(NFPA 99 2024 5.1.9.1)
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 55 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 24" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 23" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 51 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 24" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 54 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 24" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 52 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 24" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
GAS MONITORED
PRESSURE
READING
LABELING
CORRECT
HIGH
ALARM
SETPOINT
LOW ALARM
SETPOINT
VISUAL
ALARM
FUNCTION
AUDIBLE
ALARM
FUNCTION
MAINLINE
OR ZONE
SENSOR
PASS FAIL
OXYGEN 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
MED AIR 53 PSI PASS 60 PSI 40 PSI PASS PASS ZONE P
VACUUM 24" HG PASS N/A 12" HG PASS PASS ZONE P
FLOOR: 1ST ALARM LOCATION:
END OF 1ST FLOOR AREA ALARM ANALYSIS
AREA ALARM ANALYSIS
1ST FLOOR
AREA MONITORED: COMMENTS
CT SCAN
PROCEDURE ROOM 1 (2011)
OUTSIDE OF CT SCAN ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
PRE-OP / PACU
AREA MONITORED: COMMENTS
PRE-OP / PACU NURSE STATION ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
ENDOSCOPY 2 (2027)
OUTSIDE OF PROCEDURE 1 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
AREA MONITORED: COMMENTS
AREA MONITORED: COMMENTS
OUTSIDE OF ENDOSCOPY 1 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
ENDOSCOPY 1 (2025)
PROCEDURE ROOM 2 (2013)
OUTSIDE OF PROCEDURE 2 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
OUTSIDE OF ENDOSCOPY 2 ALARM MAKE AND MODEL: BEACON MEDAES MEGA 3
MEDICAL GAS
ZONE VALVE ANALYSIS
Zone valves shall be labeled in accordance with 5.1.11.2. (NFPA 99 2024 5.1.4.1.3)
Zone valves shall be so arranged that shutting off the supply of medical gas or vacuum to one zone will not affect the supply of medical gas or vacuum to another zone or the rest of the system.
(NFPA 99 2024 5.1.4.6.3)
A pressure/vacuum indicator shall be provided on the station outlet/inlet side of each zone valve.
(NFPA 99 2024 5.1.4.6.4)
Zone valve boxes shall not be installed behind normally open or normally closed doors or otherwise hidden from plain view. (NFPA 99 2024 5.1.4.6.1)
Zone valves shall be so arranged that shutting off the supply of gas to any one operating room or anesthetizing location will not affect the others. (NFPA 99 2024 5.1.4.6.3)
Zone valve boxes shall be installed where they are visible and accessible at all times.
(NFPA 99 2024 5.1.4.6.1 )
Zone valve boxes shall not be located in closed or locked rooms, areas, or closets.
(NFPA 99 2024 5.1.4.6.1)
Zone valves shall be readily operable from a standing position in the corridor on the same floor they serve. (NFPA 99 2024 5.1.4.6.1)
ZONE VALVE CODE REQUIREMENTS
Zone Valves. All station outlets/inlets shall be supplied through a zone valve as follows:
(NFPA 99 2024 5.1.4.6.1)
(2) The zone valves shall serve only outlets/inlets located on that same story.
(3) The zone valve shall not be located in a room with station outlets/inlets that it controls.
(1) The zone valve shall be placed such that a wall intervenes between the valve and outlets/inlets that it controls.
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 54 PSI PASS PASS 1" BALL PASS PASS P
MED AIR 52 PSI PASS PASS 1" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 53 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 52 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 53 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 54 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 54 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 51 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 54 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 53 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION:
GAS
GAUGE
READING
GAS LABELED
CORRECTLY
ZONE LABELED
CORRECTLY
VALVE SIZE &
TYPE
PROPER
LOCATION
LEAKAGE PASS FAIL
OXYGEN 52 PSI PASS PASS 3/4" BALL PASS PASS P
MED AIR 53 PSI PASS PASS 3/4" BALL PASS PASS P
VACUUM 24" HG PASS PASS 1-1/4" BALL PASS PASS P
FLOOR: 1ST VALVE LOCATION: OUTSIDE OF ENDOSCOPY 2 VALVE MANUFACTURER: BEACON MEDAES
OUTSIDE OF ENDOSCOPY 1 VALVE MANUFACTURER: BEACON MEDAES
COMMENTS
ZONE VALVE ANALYSIS
1ST FLOOR
AREA SERVED: COMMENTS
CT SCAN
PROCEDURE ROOM 1 (2011)
OUTSIDE OF CT SCAN VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
PRE-OP / PACU
INSIDE ENDO SUITE VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
END OF 1ST FLOOR ZONE VALVE ANALYSIS
OUTSIDE OF PROCEDURE 1 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
PROCEDURE ROOM 2 (2013)
OUTSIDE OF PROCEDURE 2 VALVE MANUFACTURER: BEACON MEDAES
AREA SERVED: COMMENTS
ENDOSCOPY 1 (2025)
ENDOSCOPY 2 (2027)
AREA SERVED:
OUTLET ANALYSIS
OTHER GASES 3.5 SCFM
As specified by ±1%, unless otherwise specified
VACUUM 3.0 SCFM N/A
WAGD 3.0 SCFM N/A
NITROUS OXIDE 3.5 SCFM ≥99% nitrous oxide
NITROGEN 5.0 SCFM ≤1% O2 or ≥99% N2
OXYGEN Non-critical 3.5 SCFM Critical 6.0 SCFM ≥99% oxygen
MEDICAL AIR Non-critical 3.5 SCFM Critical 6.0 SCFM 19.5%–23.5% oxygen
Support gas outlets shall deliver 140 SLPM (5.0 SCFM) with a pressure drop of not more than 35 kPa
(5 psi) gauge and static pressure of 1100 kPa to 1275 kPa (160 psi to 185 psi) gauge.
(NFPA 99 2024 5.1.12.4.10.3)
Medical–surgical vacuum inlets shall draw 85 Nl/min (3 SCFM) without reducing the vacuum pressure below 300 mm (12 in.) gauge HgV at any adjacent station inlet. (NFPA 99 2024 5.1.12.4.10.4)
Oxygen and medical air outlets serving critical care areas shall allow a transient flow rate of 170 SLPM
(6 SCFM) for 3 seconds. (NFPA 99 2024 5.1.12.4.10.5)
Medical gas concentration & flow rate requirements. (NFPA 99 2024 Table 5.1.12.4.11)
GAS FLOW RATE CONCENTRATION
OUTLET CODE REQUIREMENTS
Each station outlet/inlet for medical gases or vacuums shall be gas-specific, whether the outlet/inlet is threaded or is a noninterchangeable quick coupler. (NFPA 99 2024 5.1.5.1)
Each outlet/inlet shall be legibly identified in accordance with 5.1.11.3.1. (NFPA 99 2024 5.1.11.3)
Each station outlet/inlet, including those mounted in columns, hose reels, ceiling tracks, or other special installations, shall be designed so that parts or components that are required to be gas specific for compliance with 5.1.5.1 and 5.1.5.9 cannot be interchanged between the station outlet/inlet for different gases. (NFPA 99 2024 5.1.5.7)
All gas outlets with a gauge pressure of 345 kPa (50 psi), including, but not limited to, oxygen, nitrous oxide, medical air, and carbon dioxide, shall deliver 100 SLPM (3.5 SCFM) with a pressure drop of not more than 35 kPa (5 psi) and static pressure of 345 kPa to 380 kPa (50 psi to 55 psi).
(NFPA 99 2024 5.1.12.4.10.2)
OUTLET LOCATION
Le ak ag e w
A d ap te r Le ak ag e w
/o
A d ap te r O p e ra ti o n al
Fl o w
St at ic P re ss u re
C o n ce n tr at io n
C o n d it io n
La b e lin g
PASS FAIL REPAIRED
1ST FLOOR OXY MED AIR
MED
VAC
WAGD
CT SCAN 1 1 1 BEACON 500 CH P P P P P P P
PROCEDURE ROOM 1 2 1 2 1 AMICO DC CH P P P P P P P
PROCEDURE ROOM 2 2 1 2 1 AMICO DC CH P P P P P
ENDOSCOPY 1 2 1 2 1 AMICO DC CH P P P P P P P
ENDOSCOPY 2 2 1 2 1 AMICO DC CH P P P P P P P
PRE-OP / PACU BAY 1 2 2 2 AMICO SB CH P P P P P P P
PRE-OP / PACU BAY 2 2 2 2 AMICO SB CH P P P P P P P
PRE-OP / PACU BAY 3 2 2 2 AMICO SB CH P P P P P P P
PRE-OP / PACU BAY 4 2 2 2 AMICO SB CH P P P P P P P
TOTAL COUNT: 17 13 17 4
OUTLET ANALYSIS
GAS TYPE & OUTLET QUANTITY OUTLET SPECS COMMENTS
BACK BOOM VAC LEAKS W/O
ADAPTER
OUTLET PURITY &
CROSS CONNECT
ANALYSIS
2) Purity verification at 10 percent of the existing outlets annually.
OUTLET PURITY & CROSS CONNECT REQUIREMENTS
VHA DIRECTIVE 7515
1.REASON FOR ISSUE: This Veterans Health Administration (VHA) directiveestablishes policy for the
Department of Veterans Affairs (VA) regarding the safeinstallation, operation, and maintenance of
Medical Gas and Vacuum Systems at VAmedical facilities.
VHA DIRECTIVE 7515(1) A-1 APPENDIX A
(1) Cross connection verification of 10 percent of the existing outlets annually. Testing cannot be repeated on an outlet until all outlets in the hospital have been tested once. Additionally, testing of newly installed outlets must not supersede the testing of existing outlets.
OUTLET LOCATION
O2
AIR
COMMENTS
OUTLETS TESTED OXY MED AIR
MED
VAC
CT SCAN 1 1 1 99.9% 21.0%
ENDO ROOM 1 2 1 1 99.9% 21.0%
PROCEDURE ROOM 2 2 1 2 99.9% 21.0%
PRE-OP 2 2 2 2 99.9% 21.0%
PRE-OP 4 2 2 2 99.9% 21.0%
TOTAL COUNT: 9 7 8
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
INDIVIDUAL
PRESSURIZATION
PASS PASS
OUTLET CROSS-CONNECT &
PURITY TESTING
GAS TYPE & OUTLET
QUANTITY
CROSS-CONNECT
PROCEDURE
PURITY
ANALYSIS
CROSS
CONNECT
PASS/FAIL
CSMEDGAS.COM COMPLIANCE SOLUTIONS 1-833-5MEDGAS
MEDICAL GAS SOURCE
EQUIPMENT ANALYSIS
LOCATION BULK PAD
AREA(S) OF FACILITY SERVED ENTIRE FACILITY
BULK SUPPLIER TAYLOR WHARTON
SYSTEM TYPE LIQUID X HP IN-BUILDING RESERVE
PRIMARY LIQUID LEVEL 72"
PRIMARY PRESSURE 51 PSI
RESERVE LIQUID LEVEL N/A
RESERVE PRESSURE 1950 PSI
PRIMARY FINAL LINE PRESSURE 53 PSI
RESERVE FINAL LINE PRESSURE 53 PSI
SOURCE VALVE PRESSURE 52 PSI
MAIN VALVE PRESSURE 52 PSI
SOURCE VALVE TYPE BALL VALVE
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION INSIDE SOILED UTILITY ROOM BY EOSC
EOSC VALVE SIZE 2"
EOSC LOCATION(S) OUTSIDE OF MANIFOLD ROOM
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
Proper fill circuit (inlet, strainer, check valve, purge valve, supports)
BULK OXYGEN
SOURCE EVALUATION DATA
NFPA 99 2024 SCHEMATIC
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Enclosure (min 6' height) non-combustible, proper ventilation & 2 lockable entries/exits
Containers permanently anchored & cylinders adequately secured
Noncombustible pad w/3' maintenance clearance, accessible for delivery & pad adequately sized for vehicles
Top & bottom fill, hose purge, & vent valves present
Piped w/brazed copper, brass, or stainless & no flex connects/fittings wear & leaks
Reserve and primary check valves in place for reserve to feed automatically
Reserve economizer in place to feed upstream final regulators
Drainage prevented towards (buildings, drains, etc.) & from hazards
Labeling: pipeline, source/main valves & "Oxygen-No Smoking, No Open Flames"
Vaporizer appears adequately sized & isolation valves arranged for service w/o supply interruption
Emergency Supply (3' clearance) or (IBER) w/2 checks, secured, & labeled
Distance from the following: 1' - all structures (Type I & II), * 50' - wood framed Type III, IV, or V building types, * 50' - Public assembly or nearest non- ambulatory patient, * 5' -
Property lines & overhead electrical wiring, 10' building openings, * 10' - public sidewalks & parked vehicles, * 15' - Hazardous piping materials & below ground flammable liquid tanks, * 25' - 0-1000 gal flammable liquids/liquefied gas, below ground flammable liquid fill or vent, 0-25,000 scf flammable gases, or slow burning solids, * 50' - >1000 gal flammable liquids/liquefied gas, >25,000 scf flammable gases, or rapidly burning solids, 3' - combustible surfaces (asphalt & expansion joint filler) where liquid oxygen may fall, 8' - Sewer or drain openings to delivery connects, reliefs, mobile supply equipment, & liquid withdrawal connects, Walls may not form a 3-4 sided court.
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
LOCATION MANIFOLD ROOM
AREA(S) OF FACILITY SERVED EMERGENCY RESERVE FOR ENTIRE FACILITY
MANUFACTURER BEACON MEDAES
MODEL NUMBER 4107213324
SERIAL NUMBER HOP811925
SYSTEM TYPE HIGH PRESSURE X HIGH PRESSURE
CYLINDERS ON RIGHT BANK 4
CYLINDERS ON LEFT BANK 4
RIGHT BANK PRESSURE 1800 PSI
LEFT BANK PRESSURE 1800 PSI
CHANGE OVER PRESSURE 200 PSI
LINE PRESSURE 53 PSI
SOURCE VALVE TYPE BALL VALVE
SOURCE VALVE LOCATION ABOVE MANIFOLD
PRESSURE SWITCH LOCATION SOILED UTILITY ROOM BY LOADING DOCK
PASS FAIL N/A
P
P
P
P
N/A
P
P
P
P
P
P
P
P
P
P
P
ADDITIONAL COMMENTS
Cylinders secured with racks or chains
Headers have header valve and check valves
Cylinders prevented from reaching temperatures in excess 130°F. and lower than 20°F.
Door Labeling: CAUTION, Medical Gases, No Smoking or Open Flame, Room May Have Insufficient Oxygen Open Door & Allow Room to Ventilate before
Entering
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS PASS
Electrical devices protected in room
System visibly complies with above schematic per NFPA 99.
Secured with lockable doors or gates or otherwise secured.
1 hour fire rated door and walls.
Source valve labeled per NFPA 99.
Proper natural ventilation
Proper mechanical ventilation
Manifold power supplied from emergency power
Automatic bank alternation
Warning lights when banks alternate
Relief Valves vented outside, pipe size, turned down, & screened
No flammable materials, cylinders containing flammable gases, or containers containing flammable liquids
NFPA 99 2024 CHECKLIST
OXYGEN MANIFOLD SYSTEM
SOURCE EVALUATION DATA
NFPA 99 2024 SCHEMATIC
LOCATION MECHANICAL ROOM LINE PRESSURE
AREA(S) OF FACILITY SERVED ENTIRE FACILITY DRYER TYPE
MANUFACTURER POWEREX DRYER INFO
MODEL NUMBER STD0502S0025952 DEW POINT MONITOR INFO
SERIAL NUMBER (M)6/18/2021-S25952-5241 CO MONITOR INFO
SYSTEM TYPE SCROLL SOURCE VALVE LOCATION
CONFIGURATION DUPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL POWEREX SL016502AV PUMP 1 HOURS
HORSEPOWER 5 H.P. PUMP 2 HOURS
LEAD ON/OFF 80 PSI / 110 PSI PUMP 3 HOURS
LAG ON/OFF 95 PSI / 105 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) NEG 22 DEG F NEG 76 DEG F
DEW POINT (CS MONITOR) NEG 22 DEG F NEG 55 DEG F
CARBON MONOXIDE (MONITOR ON SYSTEM) N/A
CARBON MONOXIDE (CS MONITOR) N/A
OXYGEN N/A
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
P
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS PASS
ADDITIONAL COMMENTS
System automatically alternates the pumps evenly
Duplexed dryer system
1/4" sample port installed
Source valve in proper location and labeled
Mainline and intake piping properly labeled
Each pump has an isolation valve so a pump can be serviced without interruption of the system
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more instrument air compressors or a standby header
System is supplied with flexible connectors on inlet and outlet sides of the compressors
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag and dew point alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain, pressure gauge, sight glass, pressure relief, & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
N/A
NFPA 99 2024 SCHEMATIC COMPRESSED AIR PURITY ANALYSIS
COMMENTS
N/A
COMPRESSED AIR SYSTEM
SOURCE EVALUATION DATA
55 PSI
DESICCANT
TRIDENT DRYSPELL
PDPM 100
N/A
AT SOURCE
N/A
LOCATION MECHANICAL ROOM LINE PRESSURE
AREA(S) OF FACILITY SERVED ENTIRE FACILITY DRYER TYPE
MANUFACTURER POWEREX DRYER INFO
MODEL NUMBER MSD03A34K DEW POINT MONITOR INFO
SERIAL NUMBER (H)6/12/2021-S25952-3172 CO MONITOR INFO
SYSTEM TYPE SCROLL SOURCE VALVE LOCATION
CONFIGURATION DUPLEX PRESSURE SWITCH LOCATION
PUMP MAKE AND MODEL POWEREX SL014003AV PUMP 1 HOURS
HORSEPOWER 3 HP PUMP 2 HOURS
LEAD ON/OFF 105 / 95 PSI PUMP 3 HOURS
LAG ON/OFF 95 / 85 PSI PUMP 4 HOURS
ELEMENT NFPA LIMIT READING PASS/FAIL
DEW POINT (MONITOR ON SYSTEM) 35 DEG F -28 DEG F PASS
DEW POINT (CS MONITOR) 35 DEG F -32 DEG F PASS
CARBON MONOXIDE (MONITOR ON SYSTEM) 10 PPM 0 PPM PASS
CARBON MONOXIDE (CS MONITOR) 10 PPM 0 PPM PASS
CARBON DIOXIDE 500 PPM 97 PPM PASS
METHANE 25 PPM 0 PPM PASS
CHLOROFORM 2 PPM 0 PPM PASS
OXYGEN 19.5%-23.5% 21.2% PASS
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
P
P
PIntake turned down and screened
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS FAIL
ADDITIONAL COMMENTS
FRESH AIR INTAKE LINE IS IMPROPERLY LABELED AS MEDICAL AIR MAINLINE.
Intake above roof level, >20' above ground, 10 ft from doors, windows, other openings, and 25' from exhausts
System is equipped with manual disconnects
System is equipped with a local lag, dew point and CO alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain, pressure gauge, sight glass, pressure relief, & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System automatically alternates the pumps evenly
Duplexed dryer system
1/4" sample port installed
Source valve in proper location and labeled
Mainline and intake piping properly labeled
System power supplied from emergency power
N/A
NFPA 99 2024 SCHEMATIC MEDICAL AIR PURITY ANALYSIS
COMMENTS
NFPA 99 2024 CHECKLIST
System visibly complies with above schematic per NFPA 99.
Indoors in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical air compressors
System is supplied with flexible connectors on inlet and outlet sides of the compressors
N/A
MEDICAL AIR SYSTEM
SOURCE EVALUATION DATA
100 PSI
DESICCANT
TRIDENT DRYSPELL +
POWEREX PDPM1001AJ
ENMET CO-GUARD
ABOVE SOURCE
ABOVE SOURCE
LOCATION MECHANICAL ROOM
AREA(S) OF FACILITY SERVED ENTIRE FACILITY
MANUFACTURER POWEREX
MODEL NUMBER CVTD0303V4K1HT
SERIAL NUMBER (H)5/27/2021-S000025952-3130
SYSTEM TYPE CLAW
CONFIGURATION DUPLEX
PUMP MAKE AND MODEL BUSCH MM1144.BVZ6.BAXX
HORSEPOWER 3 HP
LEAD ON/OFF 22/18" HG
LAG ON/OFF 19/16" HG
LINE PRESSURE 25" HG
SOURCE VALVE LOCATION AT SOURCE
PRESSURE SWITCH LOCATION AT SOURCE
PUMP 1 HOURS 13449
PUMP 2 HOURS 11083
PUMP 3 HOURS N/A
PUMP 4 HOURS N/A
PASS FAIL N/A
P
P
P
P
P
P
P
P
P
P
P
P
FAIL
ADDITIONAL COMMENTS
EXHAUST IS IMPROPERLY LABELED AS AN AIR INTAKE AND NOT VACUUM EXHAUST.
System automatically alternates the pumps evenly
Source valve in proper location and labeled
Mainline and exhaust piping properly labeled
Exhaust is turned down and screened
Exhaust ≥25' from doors, windows, intakes, building openings & public assembly & copper or stainless, no dips, drip legs installed, & sufficient diameter
MEETS ALL NFPA 99 2024 CODE REQUIREMENTS
Each pump has an isolation valve so a pump can be serviced without interruption of the system
System visibly complies with above schematic per NFPA 99.
Located in a dedicated mechanical equipment area, adequately ventilated and with any required utilities
System has two or more medical vacuum pumps
System has flexible connectors
System has antivibration mountings
System power supplied from emergency power
System is equipped with manual disconnects
System is equipped with a local lag alarm
The local alarms are wired to the master alarm panel
Receiver tank is supplied with an Auto drain & ASME label
There is a receiver bypass valve so the receiver can be serviced without interruption of the system
NFPA 99 2024 CHECKLIST
MEDICAL VACUUM SYSTEM
SOURCE EVALUATION DATA
NFPA 99 2024 SCHEMATIC
END OF REPORT
"Your Med Gas Experts"
CAPE GIRARDEAU VA HEALTH CARE CENTER