657-21-114JC Drawings 1-63pgs.pdf

PDF 40 MB Posted

Attached to
Z2DA--657-21-114JC - Correct HVAC Systems for VHA Directive 1116. 2, JC
Solicitation number
36C25525R0051
Issued by

About this file

The file is a set of detailed architectural and engineering drawings for a VA hospital HVAC system improvement project at the John Cochran Division of the VA St. Louis Healthcare System. The project, numbered 657-21-114JC, aims to correct HVAC systems to comply with VHA Directive 1116(2), specifically focusing on Sterile Processing Service (SPS) and Reusable Medical Equipment (RME) storage rooms. The scope involves modifying HVAC systems in multiple rooms across different building levels, including CB18 Scope Storage, CB25 HAC, A131 Supply Room, B121 Storage, B147 Supply, A539/A540 Storage, and A940 Storage.

The comprehensive drawing set includes architectural, mechanical, electrical, plumbing, and fire protection plans spanning basement, levels 1, 5, and 9 of the facility. The project involves installing new air handling units, exhaust fans, supply fans, variable air volume terminals, steam humidifiers, and associated electrical and control systems. The work is designed to ensure proper air changes, temperature control, and pressurization for critical medical storage and processing areas. Romanyk Consulting Corp. is the project's architectural and engineering firm, and the project is being executed for the Department of Veterans Affairs Network Contracting Office, with the St. Louis VAMC as the specific facility.

View the file

Other files

Show all 17

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

VICINITY MAPGENERAL NOTES

1. THESE DRAWINGS SHALL BE USED ONLY FOR THIS SPECIFIC PROJECT/SITE LOCATION. THESE DRAWINGS ARE A

COMPOSITE SET OF CONTRACT DOCUMENTS AND SHALL NOT BE SEPARATED FOR DISTRIBUTION. THE GC SHALL REVIEW

ALL DRAWINGS AND PROVIDE/DISTRIBUTE THE ENTIRE SET TO EACH SUBCONTRACTOR.

2. THE GC SHALL VISIT THE SITE TO INSPECT EXISTING CONDITIONS AND VERIFY WORK BEING PERFORMED BEFORE

SUBMITTING COST QUOTATIONS FOR WORK.

3. NOTIFY THE ARCHITECT PROMPTLY OF ANY ERRORS, OMISSIONS, INCONSISTENCIES, DISCREPANCIES AND CONFLICTS WITHIN THE CONTRACT DOCUMENTS AND ITS ASSOCIATED FIELD/PROJECT CONDITIONS SO THAT A RESOLUTION CAN BE

PROVIDED PRIOR TO CONTINUING WITH WORK.

4. DO NOT SCALE THE DRAWINGS. REQUEST ANY MISSING DIMENSIONS FROM THE ARCHITECT

5. ALL WORK PERFORMED SHALL BE IN STRICT COMPLIANCE WITH GOVERNING FEDERAL, STATE AND LOCAL BUILDING CODE REQUIREMENTS, SHALL BE EXECUTED IN ACCORDANCE WITH ACCEPTED INDUSTRY STANDARDS, AND SHALL CONFORM TO SPECIFIC REGULATIONS AS MANDATED BY THE OWNER, THE ARCHITECT, AND THE AUTHORITIES HAVING JURISDICTION. THE GENERAL CONTRACTOR IS RESPONSIBLE FOR ANY FEES ASSOCIATED WITH PROCURING SUCH PERMITS AND CERTIFICATES

AND SHALL FURNISH COPIES OF PERMITS, INSPECTIONS, AND CERTIFICATES TO THE OWNER.

6. THE GENERAL CONTRACTOR SHALL COORDINATE ALL WORK TO MINIMIZE DISRUPTION OF ANY EXISTING TENANTS OR BUILDING OPERATIONS. THE GENERAL CONTRACTOR SHALL TAKE ADEQUATE PRECAUTIONS TO PROTECT BUILDING OCCUPANTS, MATERIALS, AND EXISTING CONSTRUCTION THROUGHOUT ALL PHASES OF CONSTRUCTION. DAMAGE TO EXISTING-TO-REMAIN CONSTRUCTION OR EQUIPMENT SHALL BE RESTORED TO ORIGINAL CONDITION AT THE

CONTRACTOR'S EXPENSE.

7. THE GENERAL CONTRACTOR SHALL REMOVE ALL TRASH AND DEBRIS FROM THE JOB SITE ON A DAILY BASIS.

8. ANY REQUESTS FOR SUBSTITUTIONS OF ANY SPECIFIED ITEM ARE TO BE SUBMITTED TO THE ARCHITECT IN WRITING AND WILL BE CONSIDERED ONLY IF THE ALTERNATE PROPOSED IS PROVEN TO BE ADVANTAGEOUS TO THE OWNER WITH

RESPECT TO DELIVERY DATE, QUALITY, OR COST.

9. THE MEANS AND METHODS OF CONSTRUCTION, AND TEMPORARY STRUCTURES AND FACILITIES, ARE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE ARCHITECT DOES NOT ASSUME ANY RESPONSIBILITY FOR THE CONTRACTOR'S

MEANS AND METHODS OR FOR TEMPORARY STRUCTURES.

10. DEMOLITION OF EXISTING STRUCTURES IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE CONTRACTOR SHALL

EMPLOY ENGINEERING EXPERTISE AS NEEDED TO ASSIST IN DEMOLITION.

11. JOB SITE SAFETY AND SECURITY ARE THE SOLE RESPONSIBILITY OF THE GENERAL CONTRACTOR. THE GENERAL CONTRACTOR SHALL CONSULT WITH LOCAL FIRE AUTHORITIES TO ASCERTAIN REQUIREMENTS FOR FIRE SUPPRESSION AND SAFETY DURING CONSTRUCTION. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR MEETING OSHA

REGULATIONS DURING CONSTRUCTION.

12. THE GENERAL CONTRACTOR IS SOLELY RESPONSIBLE FOR STORAGE AND PROTECTION OF BUILDING MATERIALS, AND INSTALLED CONSTRUCTION, FROM INCLEMENT WEATHER, THEFT, AND OTHER HAZARDS. THE GC SHALL FOLLOW ALL MANUFACTURER'S RECOMMENDATIONS FOR STORAGE OF MATERIALS. PARTIALLY COMPLETED WALLS SHALL BE COVERED TO PROTECT FROM WATER INTRUSION. DAMAGE, INCLUDING BUT NOT LIMITED TO MOLD, RESULTING FROM WATER INTRUSION DURING CONSTRUCTION SHALL BE REPAIRED AT THE GENERAL CONTRACTOR'S EXPENSE.

ANNOTATION DRAWING SYMBOLS

GRID / COLUMN LINE DESIGNATOR

EQUIPMENT NUMBER

DOOR NUMBER

WALL TYPE

WINDOW TYPE

ROOM NAME / NUMBER

REVISION TAG

PLAN NORTH

TRUE NORTH

NORTH

NORTH ARROW WITH TRUE

NORTH INDICATION

EGRESS ROUTE ID AND

SECTION LENGTH

EGRESS : ?

ROOM OCCUPANCY & AREA

ELEVATION NUMBER

SECTION

INTERIOR ELEVATION

ENLARGEMENT,

DETAIL

SPOT ELEVATION

FLOOR LEVEL &

NAME

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

SHEET KEYNOTE

EXTERIOR ELEVATION

PLATE NUMBER WHERE

SECTION/DETAIL IS DRAWN

INDEX OF DRAWINGS

01-AE101

DISCIPLINE:

G - GENERAL

A - ARCHITECTURE

P - PLUMBING

M - MECHANICAL

E - ELECTRICAL

SHEET TYPE

DESIGNATOR

BUILDING NUMBER

SHEET NUMBER

WITHIN SERIES

PROJECT TEAM

ENRIGHT AVE

DELMAR BLVD G

R

A N

D B

L V

D

N S

PRIN

G A

VE

BELL AVE

WINDSOR

BUILDING NO. TAG01

5T

1T

PROJECT INFORMATION

THE VA ST. LOUIS HEALTH CARE SYSTEM, JOHN COCHRAN DIVISION, WILL CORRECT VARIOUS HVAC SYSTEMS WITHIN BUILDING 01 AT THE JOHN COCHRAN DIVISION OF THE VA ST. LOUIS HEALTHCARE SYSTEM TO ENSURE THEY ARE COMPLIANT WITH VHA DIRECTIVE 1116(2). VHA DIRECTIVE 1116(2) IS RELATED TO STERILE PROCESSING SERVICE (SPS) AND THE STORAGE OF REUSABLE MEDICAL EQUIPMENT (RME). RME IS EQUIPMENT INTENDED FOR REPEATED USE ON DIFFERENT PATIENTS WITH

APPROPRIATE DECONTAMINATION AND OTHER PROCESSING BETWEEN USES.

PROJECT NAME: CORRECT HVAC SYSTEMS FOR VHA DIRECTIVE 1116

PROJECT NUMBER: 657-21-114JC

PROJECT LOCATION: ST. LOUIS VAMC – JOHN COCHRAN DIVISION, 915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

PROJECT PURPOSE/USE: HVAC IMPROVEMENTS

ROOMS IN SCOPE:

• CB18 - SCOPE STORAGE

• CB25 - CLEAN HOUSEKEEPING CLOSET

• A131 - SUPPLY ROOM

• B121 - STORAGE

• A147 - SUPPLY

SCOPE OF WORK SUMMARY:

PROJECT MANAGER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Arlo Wiezcorek, PE arlo.wieczorek@romanykconsulting.com

P: 855.424.3838 ext 324 C: 319.721.4986

MECHANICAL ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com

855.424.3838 x324

319.721.4986 cell

ELECTRICAL ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Yumei Wang P.E, RCDD, CTS, LEED AP Yumei.Wang@RomanykConsulting.com

855.424.3838 x311

402.321.3766 cell

OWNER:

Department of Veterans Affairs Network Contracting Office (NCO) 15 3450 S 4th Street Trafficway, Leavenworth KS 6604

CONTRACTING OFFICER REPRESENTATIVE:

St. Louis VAMC – John Cochran Division 915 North Grand Blvd.

St. Louis, MO 63106

Walter Staas Walter.Staas@va.gov

314.652.4100 x58723

PLUMBING ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com

855.424.3838 x324

319.721.4986 cell

FIRE PROTECTION ENGINEER:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Arlo Wieczorek, PE Arlo.Wieczorek@RomanykConsulting.com

855.424.3838 x324

319.721.4986 cellBUILDING SUMMARY

PLAN NORTH

TRUE NORTH

NORTH

ARCHITECT:

Romanyk Consulting Corp.

3308 Preston Road, Suite 350-164 Plano, Texas 75093

Jim Booher AIA NCARD ASHE LEED AP Jim.Booher@RomanykConsulting.com

855.424.3838 x324

319.721.4986 cell

• A540 - RME STORAGE

• A539(A) - STORAGE

• A940 - STORAGE

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

F

U.S. Department of Veterans Affairs

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

Phase

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6 5 4 3 2 1

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

A/E:

U.S. Department of Veterans Affairs

FULLY SPRINKLERED

Office of Construction and Facilities Management

STAMP

NOT FOR

PERMITTING OR

CONSTRUCTION

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:5

P

M

PROJECT COVER SHEET

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

SEPTEMBER 28, 2023

01-GI-100

657-21-114JC

PROJECT NUMBER - 657-21-114JC

CORRECT HVAC SYSTEMS FOR VHA DIRECTIVE 1116 (2)

100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

100% BID DOCUMENTS

SEPTEMBER 28, 2023

Revisions: Date:

R

EG

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

ES D. BOOHER

1 3 2 67

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:0

P

M

DRAWING INDEX & ABBREVIATIONS

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-101

SHEET # SHEET TITLE

GENERAL

01-GI-100 PROJECT COVER SHEET

01-GI-101 DRAWING INDEX & ABBREVIATIONS

01-GI-102 ICRA DETAILS

01-GI-103 ICRA DETAILS CLASS 1 & 2

01-GI-104 ICRA DETAILS CLASS 3

01-GI-105 CLASS IV ICRA DETAILS

01-GI-106 CLASS IV ALT ICRA DETAILS

01-GI-107 BASEMENT - OVERALL PLAN

01-GI-108 LEVEL 01 - OVERALL PLAN

01-GI-109 LEVEL 05 - OVERALL PLAN

01-GI-110 LEVEL 09 - OVERALL PLANS

01-GI-201 LIFE SAFETY PLAN & INFECTION CONTROL - BASEMENT

01-GI-202 LIFE SAFETY PLAN & INFECTION CONTROL - LEVEL 01

01-GI-203 LIFE SAFETY PLAN & INFECTION CONTROL - LEVEL 05

01-GI-204 LIFE SAFETY PLAN & INFECTION CONTROL - LEVEL 09

ARCHITECTURAL

01-AE-101 OVERALL CEILING PLAN - BASEMENT

01-AE-102 OVERALL CEILING PLAN - LEVEL 01

01-AE-103 OVERALL CEILING PLAN - LEVEL 05

01-AE-104 OVERALL CEILING PLAN - LEVEL 09

01-AE-401 BASEMENT - ENLARGED PLANS

01-AE-402 LEVEL 01 - ENLARGED PLANS

01-AE-403 LEVEL 01 - ENLARGED DEMOLITION PLAN

01-AE-404 LEVEL 01 - ENLARGED PLAN

01-AE-405 LEVELS 05 & 09 - ENLARGED DEMOLITION PLANS

01-AE-406 LEVELS 05 & 09 - ENLARGED PLANS

01-AE-500 CEILING DETAILS & WALL TYPES

01-AE-501 CEILING DETAILS

FIRE PROTECTION

01-FG-001 FIRE PROTECTION LEGENDS, NOTES, AND ABBREVIATIONS

01-FP-101 FIRE PROTECTION ENLARGED PLAN - LEVELS 00, 01, 05 & 09

PLUMBING

01-PG-001 PLUMBING LEGENDS, SCHEDULES AND ABBREVIATIONS

01-PG-002 PLUMBING DETAILS

01-PP-101 PLUMBING ENLARGED PLANS - LEVEL 01

01-PP-102 PLUMBING ENLARGED PLANS - LEVELS 05 & 09

MECHANICAL

01-MG-001 MECHANICAL NOTES, LEGENDS, AND ABBREVIATIONS

01-MG-002 MECHANICAL DETAILS

01-MG-003 MECHANICAL DETAILS

01-MG-004 MECHANICAL SCHEDULES

01-MG-005 MECHANICAL SCHEDULES

01-MG-006 CONTROLS SEQUENCES

01-MG-007 CONTROLS SEQUENCES

01-MG-008 CONTROLS SEQUENCES

01-MG-009 CONTROL SEQUENCES

MECHANICAL

01-MH-101 MECHANICAL ENLARGED HVAC PLANS - LEVEL 00

01-MH-102 MECHANICAL ENLARGED HVAC PLANS - LEVEL 00

01-MH-103 MECHANICAL ENLARGED HVAC PLANS - LEVEL 01

01-MH-104 MECHANICAL ENLARGED HVAC PLANS - LEVEL 01

01-MH-105 MECHANICAL ENLARGED HVAC PLANS - LEVELS 05 & 09

01-MP-101 MECHANICAL ENLARGED PIPING PLANS - LEVEL 00

01-MP-102 MECHANICAL ENLARGED PIPING PLANS - LEVEL 01

01-MP-103 MECHANICAL ENLARGED PIPING PLANS - LEVEL 01

01-MP-104 MECHANICAL ENLARGED PIPING PLANS - LEVEL 01

01-MP-105 MECHANICAL ENLARGED PIPING PLANS - LEVELS 05 & 09

ELECTRICAL

01-EG-001 ELECTRICAL LEGENDS, SCHEDULES, AND ABBREVIATIONS

01-EG-500 ELECTRICAL ONE LINE DIAGRAM

01-EG-501 ELECTRICAL SCHEDULES

01-EG-502 ELECTRICAL SCHEDULES

ELECTRICAL

01-EP-101 ELECTRICAL ENLARGED PLANS - LEVEL 00

01-EP-102 ELECTRICAL ENLARGED PLANS - LEVEL 00

01-EP-103 ELECTRICAL ENLARGED PLANS - LEVEL 01

01-EP-104 ELECTRICAL ENLARGED PLANS - LEVEL 01

01-EP-105 ELECTRICAL ENLARGED PLANS - LEVEL 01

01-EP-106 ELECTRICAL ENLARGED PLANS - LEVEL 05

01-EP-107 ELECTRICAL ENLARGED PLANS - LEVEL 09

Grand total: 63

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

INFECTION CONTROL NOTES

INFECTION CONTROL GENERAL NOTES:

1. ISOLATE EXISTING HVAC SYSTEM IN AREAS WHERE WORK IS TO BE PERFORMED. ALL AIR

VENTS MUST BE SEALED OFF NEAR THE CONSTRUCTION AREA AS REQUIRED AFTER

COORDINATION WITH COR TO ENSURE NON-INTERFERENCE WITH HVAC AND NEGATIVE

PRESSURE SYSTEMS. DUST TO BE CONTROLLED WITHIN THE WORK SITE FROM FLOOR

TO DECK.

2. TRAFFIC CONTROL: DESIGNATED ENTRY AND EXIT PROCEDURES WILL BE DEFINED AND

CLEARLY ARTICULATED WITH CONSTRUCTION SIGNAGE TO BE PROVIDED BY THE

CONTRACTOR. ALL EGRESS WAYS MUST BE MAINTAINED FREE OF DEBRIS AT ALL TIMES.

THEY MUST BE UTILIZED AT SCHEDULED TIMES ONLY AS COORDINATED WITH COR. DUST

MATS MUST BE PLACED AT ENTRANCES/EXITS OF WORK AREA AND REPLACED DAILY OR

MORE FREQUENTLY IF NECESSARY. DEBRIS WHEN TRANSPORTED THROUGH HOSPITAL

AREAS MUST BE COMPLETELY TIGHTLY COVERED TO CONTAIN DUST DURING

TRANSPORT. DEBRIS SHALL BE REMOVED IN EVENINGS OR NON-DUTY TIMES IF POSSIBLE.

ALL CART WHEELS MUST BE CLEANED BEFORE LEAVING THE CONSTRUCTION AREA.

3. CLEANING: THE CONSTRUCTION ZONE AND ADJACENT ENTRY AREA SHALL BE

MAINTAINED IN A CLEAN AND SANITARY MANNER BY THE CONTRACTOR AND WILL BE HIGH

EFFICIENCY PARTICULATE AIR (HEPA) VACUUMED AND WET MOPPED WITH DISINFECTANT

DAILY OR MORE FREQUENTLY AS NEEDED TO MINIMIZE DUST GENERATION. CLOTHING

SHALL BE FREE OF LOOSE SOIL AND DEBRIS UPON EXITING THE CONSTRUCTION ZONE.

PROVIDE PERSONAL PROTECTIVE EQUIPMENT, INCLUDING FACE SHIELDS, GLOVES, AND

N95 RESPIRATORS REQUIRED BY THE SAFETY SPECIFICATION.

4. INFECTION CONTROL CONSTRUCTION PERMIT: CONTRACTOR TO OBTAIN INFECTION

CONTROL PERMIT BEFORE CONSTRUCTION BEGINS.

5. STAGING AREAS WILL BE DESIGNATED BY THE COR. CONTRACTOR TO COORDINATE WITH

THE COR PRIOR TO CONSTRUCTION.

6. THE CONTRACTOR SHALL COORDINATE WITH RISK ASSESSMENT DOCUMENTATION AND

THE COR PRIOR TO IMPLEMENTATION.

7. CONTRACTOR TO PROVIDE PROTECTION ABOVE CEILING WITHIN THE CONTAINMENT AREA,

IF EXISTING WALLS AND/OR PARTITIONS DO NOT EXTEND TO THE STRUCTURE ABOVE.

8. COORDINATE WITH MEP/FP.

9. ICRA PLANS DENOTE TOTAL DEFINED AREAS OF WORK ON ALL AFFECTED LEVELS. THE VA

MAY, BASED ON DYNAMIC UNFORESEEN VARIABLES (PATIENT CENSUS, OTHER PROJECTS, ETC.), REQUIRE THE GENERAL CONTRACTOR TO MODIFY EXTENTS AND AREA SIZES OF ICRA

BARRIERS. ANY SUCH MODIFICATION WILL REQUIRE THE SAME REQUISITE PROVISIONS REQUIRING

CONTAINMENT (ANTE ROOM, WALK-OFF MATS, ETC.) AIR-PRESSURIZATION CRITERIA, AND

IDENTIFICATION AS NOTED ON SHEET GI-103 TO GI-106.

ENVIRONMENTAL CONTROLS:

TYPE OF CONSTRUCTION ACTIVITY - TYPE C:

WORK THAT GENERATES MODERATE TO HIGH LEVEL OF DUST OR REQUIRES DEMOLITION OR

REMOVAL OF ANY FIXED BUILDING COMPONENTS OR ASSEMBLIES.

INCLUDES, BUT IT NOT LIMITED TO:

• SANDING OF WALLS FOR PAINTING FOR WALL COVERING

• REMOVAL OF FLOOR COVERINGS, CEILING TILES AND CASEWORK

• NEW WALL CONSTRUCTION

• MINOR DUCT WORK OR ELECTRICAL WORK ABOVE CEILINGS

• MAJOR CABLING ACTIVITIES

• ANY ACTIVITY WHICH CANNOT BE COMPLETED WITHIN A SINGLE WORKSHIFT.

INFECTION CONTROL PRECAUTIONS FOR CLASS II

DURING CONSTRUCTION PROJECT:

1. PROVIDE ACTIVE MEANS TO PREVENT AIRBORNE DUST FROM DISPERSING INTO ATMOSPHERE.

2. WATER MIST WORK SURFACES TO CONTROL DUST WHILE CUTTING.

3. SEAL UNUSED DOORS WITH DUCT TAPE.

4. BLOCK OFF AND SEAL AIR VENTS.

5. PLACE DUST MAT AT ENTRANCE AND EXIT OF WORK AREA

6. REMOVE OR ISOLATE HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

UPON COMPLETION OF PROJECT:

1. WIPE WORK SURFACES WITH DISINFECTANT.

2. CONTAIN CONSTRUCTION WASTE BEFORE TRANSPORT IN TIGHTLY COVERED CONTAINERS.

3. WET MOP AND/OR VACUUM WITH HEPA FILTERED VACUUM BEFORE LEAVING WORK AREA.

4. REMOVE ISOLATION OF HVAC SYSTEM IN AREAS WHERE WORK IS BEING PERFORMED.

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:0

P

M

ICRA DETAILS

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-102

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

ES D. BOOHER

1 3 2 67

VHASTLSTAASW

Text Box Appendix A: Alternative To Outdoor Exhaust Requirements This Appendix provides an equivalent ICRA control measure to requirements detailed in this VHA ICRA template that would allow interior construction space exhaust.

Interior Construction Space Exhaust:

If the facility is not able to exhaust to the building exterior, the Healthcare Environment and Facilities program office has identified an alternate industry-recognized standard interior exhaust procedure that is accepted as providing an equivalent level of infection prevention and control (IPC), and safety. The alternate interior exhaust procedure is implemented by completing the following:

a.If exhaust is directed indoors, then the system must be HEPA filtered. Prior to start of work, including assembly of the ICRA barriers, initial baseline air sampling measurements for particulate levels must be taken in the planned area of discharge. Once containment is erected and completed, HEPA filtration must then be verified by particulate measurement, using a particle counter with multi-channel capabilities to measure down to 0.3 microns, to confirm that the discharge of the HEPA unit does not exceed the baseline particulate count of the area to which the exhaust is directed. Verification must continue at least three times per day (once every 8 hours), 7 days per week, during the use of the negative air machine and HEPA filter. Any exceedance must trigger a work stoppage and an immediate response and resolution. All particulate measurements, including the baseline measurement, must be documented and retrievable.b.To accommodate the sampling, the negative air pressure machine must be fitted with a 2 ft section of ridged ductwork at the discharge. The sample port for monitoring must be in the ridged ductwork section.c.Vapor generating processes must be assessed and appropriate filtration must be installed to mitigate transmission to the facility.d.Engineering must do a complete flow and pressure analysis and document the area to which the air is being discharged to ensure the flow and pressure relationships in that area are not being adversely impacted by the additional flow. Ideally, this is done as part of the construction package to ensure the design is implementable and no additional HVAC changes are required to accommodate the exhaust from the negative air equipment.e.Install device on exterior of work containment to continually monitor negative pressurization. To ensure proper pressure is continuously maintained, the device(s) shall have a visual pressure indicator, data collection and alarm.f.Exhaust must be directed to Low Risk areas as defined on page 4 in this ICRA template. Ideally this discharge must be located so as not to impinge on high traffic areas or create a nuisance with noise or excessive airflow.NOTE: Exhaust into shared or recirculating HVAC systems, other shared exhaust systems (e.g., bathroom exhaust), chases or above ceiling is not acceptable.

VHASTLSTAASW

Text Box ICRA barriers shall not be built during Medical Center business hours 8:00am-4:30pm M-F. Some areas may have additional time restrictions.

ICRA barriers at all rooms shall be Class IV. There must be an ante room.

All gaps in the containment barrier must be taped and sealed. Taping is to be done in a manner as to not be destructive to existing infrastructure or the contractor is responsible for repair. Taping is to be inspected daily and any gaps resealed or retaped to maintain the required negative air pressure. Negative air outlet shall use a piece of hard flat material in the window with a hole in it for the tubing and use a round flange and attach the tubing with a band clamp or similar VA approved method.

ICRA barriers at long piping runs may be allowed Class II depending on location, length of schedule, and contractors means and methods. Contractor to provide a written proposal for IP to review, but must be prepared to provide a more restrictive barrier at no cost to the government. Work in corridors or common areas shall not be done during Medical Center business hours 8:00am-4:30pm M-F. Some areas may have additional time restrictions.

Doors into ICRA barriers shall be:

· Metal and wipeable to maintain a dust free clean surface. No wood allowed.

· Pre-manufactured temporary wall systems are allowed per VA approval.

· ADA compliant threshold, or no threshold.

· Have a door closer.

· Door must close and latch on its own power while the negative air is operational.

· A door latch and lock compatible with the VA key core.

CL3357 NZD 626 RH CT6 (LFIC LESS CONST. CORE) (Storeroom function) Lock set for JC Large Format Interchangeable Core.

A potential supplier - IDN-H Hoffman Inc. ~314-692-8391.

OUTSIDE OF BUILDING

COVER ALL

RETURNS AT

GRATE

/DIFFUSERS

E

SUPPLY DUCTS EITHER KEEP

RUNNING OR COVER WHEN

RUNNING TO KEEP DUST OUT

OPTIONAL EXHAUST DUCTS

(COVER THE GRATES AND THE

DIFFUSERS)

TAPE ALL SERVICES TO

PROTECT CONTAMINATION

A

O

V

FIRE EXTINGUISHER ON

PORTABLE FLOOR BRACKET

(ILSM MAY REQUIRE MORE

THAN ONE).

PROVIDE STICKY MATS

( CHANGED END OF

SHIFT OR MORE IF

NECESSARY TO

MAINTAIN

CLEANLINESS)>

SUSPENDED PLASTIC

ZIPPER WALL

CURTAIN BARRIER

POST ICRA, ILSM, FIRE

INSPECTION SHEETS

VISIBLE TO PUBLIC

PROVIDE STICKY MATS

( CHANGED END OF SHIFT

OR MORE IF NECESSARY

TO MAINTAIN CLEANLINESS)

INDICATOR MUST BE AT -0.01 OR GREATER

(VERIFY DAILY), IF NOT VERIFY ALL OPENINGS

SUCH AS DOORS ARE CLOSED AND /OR

CHANGE OUT NEGATIVE AIR - PRE FILTER.

F

IE

L D

V E

R

IF

Y

W A

L L

H E

IG

H

T V

E R

IE

S

C E

IL

IN

G H

E

IG

H T

2X4 SUSPENDED

CEILING AS SCHEDULED

3 5/8" INSULATED WALL WITH 16

GA. METAL STUDS AT 16" O.C.

WITH 5/8" GYPSUM BOARD EACH

SIDE. WALL TO EXTEND TO ROOF

4" RUBBER COVE TO MATCH

EXISTING AREA BASE @ BOTH

SIDES

TYPE A

F

IE

L D

V E

R

IF

Y

W A

L L

H E

IG

H

T V

E R

IE

S

C E

IL

IN

G H

E

IG

H T

2X4 SUSPENDED

CEILING AS SCHEDULED

3 5/8" INSULATED WALL WITH 16

GA. METAL STUDS AT 16" O.C.

WITH 5/8" GYPSUM BOARD EACH

SIDE. WALL TO EXTEND TO ROOF

4" RUBBER COVE TO MATCH

EXISTING AREA BASE @ BOTH

SIDES

TYPE B

SUSPENDED PLASTIC

ZIPPER WALL CURTAIN

BARRIER

POST ICRA, ILSM, FIRE

INSPECTION SHEETS

VISIBLE TO PUBLIC

A P

P R

O X

A

.F .F

INDICATOR MUST BE AT -0.01 OR MORE

NEGATIVE (VERIFY DAILY). IF NOT VERIFY ALL

OPENING SUCH AS DOORS ARE CLOSED AND/OR

CHANGED OUT NEGATIVE AIR PRE FILTER

ICRA, ILSM

FIRE WATCH

MISC. FORMS

PAPER CADDY

INDICATOR (REFER TO

PLAN & ELEVATION)

C.O.R. WITH

CONTACT

INFORMATION

XXXX XXX XXXX

XXXX XXX XXXX

XXXX XXX XXXX

XXXX XXX XXXX

CHILLER PLANT AFTER HOURS

CONTACT PHONE XXXX FIRE

EMERGENCY DIAL 911

THIS IS A

RESTRICTED AREA

AREA UNDER

CONSTRUCTION

PERSONNEL ENTERING MUST HAVE : HARD HAT, SAFETY GLASSES, AND PROPER I.D.

COMING SOON!!!!

-DESCRIPTION OF NEWLY PROPOSED OCCUPANCY -

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:1

P

M

ICRA DETAILS CLASS 1 & 2

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-103

1/4" = 1'-0"

TYPICAL CONSTRUCTION LAYOUT - CLASS I & CLASS II

1" = 1'-0"

ICRA WALL TYPES

1/4" = 1'-0"

ICRA ELEVATION

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

CROSS-SECTION 'A-A'

SCALE:

1/2"=1'-0"

CLASS III

EXISTING CONCRETE SLAB

FLOORING

FIRE/U.L. RATED PLASTIC TO

PREVENT DUST INFILTRATION

PRIOR TO CONSTRUCTION

EXISTING SPRINKLER

SYSTEM

EXISTING

WINDOW FRAME

FIRE/U.L. RATED PLASTIC TO

PREVENT DUST INFILTRATION

PRIOR TO CONSTRUCTION

FIRE RATED PLYWOOD

(TEMP GLASS PANEL)

HEPA NEGATIVE

AIR UNIT

HEATED

DETECTOR

CUT-OFF

FINISHED FLOORING TO BE

KEPT CLEAN. FLOORS NOT

BEING REPLACED TO BE

PROTECTED OR COVERED

WITH ROSEN PAPER/FIRE

RATED PLYWOOD

EXISTING WALLEXISTING WALL

COVER ALL RETURNS AT

THE GRATE/DIFFUSERS

A

O

V

E

F L E

A

D U C

OUTSIDE BUILDING

MONTHLY CHANGE

HEPA FILTER

HEPA

NEGATIVE AIR

UNIT

PRE-FILTER

WEEKLY

CHANGED( OR

MORE AS NEEDED)

PROVIDE STICKY MATS

(CHANGED END OF SHIFT

OR MORE IF NECESSARY TO

MAINTAIN CLEANLINESS)

OPTIONAL EXHAUST

DUCTS (COVER THE

GRATES AND THE

DIFFUSERS)

A

SUPPLY, CLOSE OR

COVER WHEN IN USE

TO KEEP DUST OUT

INDICATOR MUST BE AT -0.01 OR MORE

NEGATIVE (VERIFY DAILY), IF NOT VERIFY

ALL OPENING SUCH AS DOORS ARE

CLOSED AND/OR CHANGE OUT NEGATIVE

AIR PRE-FILTER. (TYP REGULATOR

INSTALLATION).

PROVIDE STICKY MATS

(CHANGED END OF SHIFT

OR MORE IF NECESSARY TO

MAINTAIN CLEANLINESS)

SUSPENDED PLASTIC

WALL CURTAIN

SHEETS VISIBLE TO

PUBLIC POST ICRA, ILSM, FIRE

INSPECTION

ABC TYPE FIRE EXTINGUISHER ON PORTABLE

FLOOR BRACKET (ILSM MAY REQUIRE MORE

THAN ONE OR WALL MOUNTED). NEED

INSPECTION TAG AND MONTHLY INSPECTION).

(INITIALS/DATED).

TAPE ALL SERVICES TO

PROTECT AGAINST

CONTAMINATION

FIRE/U.L. RATED PLASTIC TO

PREVENT DUST (INSTALL PRIOR TO

CONSTRUCTION)

EXISTING WALL

FINISHED FLOORING TO BE KEPT CLEAN.

FLOORS NOT BEING REPLACED TO BE

PROTECTED OR COVERED WITH ROSEN

PAPER/FIRE RATED PLYWOOD

HEATED DETECTOR CUT-OFF

HEPA NEGATIVE AIR UNIT

EXISTING WALL

NEGATIVE AIR DUCT

DAMPEREXISTING FIRE SPRINKLER SYSTEM

EXISTING FLOOR

A

O

V

E

F L E X

D U C T

SUPPLY, CLOSE OR

COVER WHEN IN USE

TO KEEP DUST OUT

OPTIONAL EXHAUST

DUCTS (COVER THE

GRATES AND THE

DIFFUSERS)

COVER ALL RETURNS WITH

FIRE RATED PLASTIC AT THE

GRATE/DIFFUSERS SHEETING

AND SECURE WITH DUCT

TAPE.

FIRE RATED PLYWOOD

(REFER TO ELEVATION)

OUTSIDE OF

BUILDING

HEPA FILTER

(MONTHLY

CHANGED)

HEPA NEGATIVE AIR UNIT

PRE-FILTER WEEKLY

CHANGED (OR MORE AS

NEEDED)

TAPE ALL SERVICES TO

PROTECT AGAINST

CONTAMINATION

PROVIDE STICKY MATS

(CHANGED END OF SHIFT

OR MORE IF NECESSARY TO

MAINTAIN CLEANLINESS)

ABC TYPE FIRE EXTINGUISHER ON PORTABLE

FLOOR BRACKET (ILSM MAY REQUIRE MORE

THAN ONE OR WALL MOUNTED). NEED

INSPECTION TAG AND MONTHLY INSPECTION).

(INITIALS/DATED).

PROVIDE STICKY MATS

(CHANGED END OF SHIFT

OR MORE IF NECESSARY TO

MAINTAIN CLEANLINESS)

INDICATOR MUST BE AT -0.01 OR MORE

NEGATIVE (VERIFY DAILY), IF NOT VERIFY

ALL OPENING SUCH AS DOORS ARE

CLOSED AND/OR CHANGE OUT NEGATIVE

AIR PRE-FILTER. (TYP REGULATOR

INSTALLATION).

a a

SUSPENDED PLASTC WALL

SHEETS VISIBLE TO

PUBLIC POST ICRA, ILSM, FIRE

INSPECTION

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:1

P

M

ICRA DETAILS CLASS 3

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-104

NTS

CLASS 3 SECTION B NTS

CLASS 3 ALT

NTS

CLASS 3 SECTION A

NTS

CLASS 3 ICRA PLANS

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

TEMP. ANTE

ROOM

HARD

BARRIER

COVER ALL RETURNS WITH FIRE

RATED PLASTIC AT THE

GRATE/DIFFUSERS SHEETING

AND SECURE WITH DUCT TAPE.

HEPA NEGATIVE

AIR UNIT

TAPE ALL SERVICES

TO PROTECT AGAINST

CONTAMINATION

ABC TYPE FIRE EXTINGUISHER

ON PORTABLE FLOOR BRACKET

(ILSM MAY REQUIRE MORE THAN

ONE OR WALL MOUNTED). NEED

INSPECTION TAG AND MONTHLY

INSPECTION). (INITIALS/DATED).

FIRE RATED

PLYWOOD

(REFER TO

ELEVATION)

A

O

V

PRE-FILTER

WEEKLY CHANGED

(OR MORE AS

NEEDED)

HEPA FILTER

(MONTHLY

CHANGED)

SUPPLY DUCTS - EITHER KEEP

RUNNING OR COVER WITH FIRE

RATED PLASTIC SHEETING AND

SECURE WITH DUCT TAPE TO

KEEP DUST OUT.

SHEETS VISIBLE TO

PUBLIC POST ICRA, ILSM,

FIRE INSPECTION

E

OPTIONAL EXHAUST

DUCTS (COVER THE

GRATES AND THE

DIFFUSERS)

TYPICAL IDEAL CONSTRUCTION LAYOUT CLASS IV

INDICATOR MUST BE AT -0.01 OR MORE

NEGATIVE (VERIFY DAILY), IF NOT VERIFY ALL

OPENING SUCH AS DOORS ARE CLOSED

AND/OR CHANGE OUT NEGATIVE AIR PRE-

FILTER. (TYP REGULATOR INSTALLATION).

BLUE CORE

LOCKSET

(LOCKED AT ALL

TIMES)

OUTSIDE OF

BUILDING

ELEVATION

(REFER TO ELEV.

DETAIL)

PROVIDE STICKY MATS

(CHANGED END OF SHIFT OR

MORE IF NECESSARY TO

MAINTAIN CLEANLINESS)

TYPE B

TYPE A

A A

EXISTING WINDOW FRAME

FIRE RATED PLYWOOD

(TEMP. REMOVE GLASS

PANEL)

HEPA NEGATIVE AIR UNIT

EXISTING FIRE SPRINKLER SYSTEM

EXISTING CONCRETE SLAB

FLOORING

EXISTING WALL

FINISHED FLOORING TO BE

KEPT CLEAN. FLOORS NOT

BEING REPLACED TO BE

PROTECTED OR COVERED

WITH ROSEN PAPER/FIRE

RATED PLYWOOD.

FLEX DUCT

PLASTIC

WINDOW

HEPA NEGATIVE

AIR UNIT

MOBILE CONTAINMENT

CART WITH CANVAS/

ZIPPER SIDE

ENTRY, 1-1/4" SQUARE

TUBE FRAME

FLEX

DUCT

CROSS-SECTION 'A-A' MOBILE CONTAINMENT CART

FIRE/U.L. RATED

PLASTIC TO PREVENT

DUST (INSTALL PRIOR TO

CONSTRUCTION.)

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:2

P

M

CLASS IV ICRA DETAILS

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-105

1/4" = 1'-0"

CLASS 4 PLAN

1/2" = 1'-0"

CLASS 4 SECTIONS

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:2

P

M

CLASS IV ALT ICRA DETAILS

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-106

1/2" = 1'-0"

CLASS IV ALT ICRA DETAILS

COMMITTEE.

BASIS

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

S P

S P

SCOPE OF WORK

GENERAL NOTES

SPECIMEN

AUTOPSY

MECH DOCK

TOILET -

LOCKER

Room

CLOSET

WALK-IN

REF

VIEWING

RM.

BATTERY

CHARGING

MECH

CORRIDOR

CORRIDOR

ELEC

WASH RM.

STORAGE

REF

STORAGE

CLOSET

WASH RM.

MECH

STAIR 05

EQUIP.

STORAGE

GAS

STORAGE

CHEMICAL

STORAGE

VAULT

VAULT

SUPPLIES

H004

CORRIDOR

FOOD/ BEV

STORAGE

VESTIBULE

EMS

STORAGE

VOL

SERVICE

STORAGE

EMS

STORAGE

SERVICE

ELEVATOR

LOBBY

VESTIBULE

FOOD/ BEV

WALK-IN

REF.

STORAGE

STORAGE

SILVER

RECOV.

EMS

OFFICE 342

OFFICE

CORRIDOR

CORRIDOR

A002A

MECH. RM.

MECH. RM.

TOILET,

MALE

MAIL RM.

STAIR 02

A016A

ELEC

CORRIDOR

WAITING

RM.

OFFICE

EXAM

EXAM

OFFICE

CONTROL

SIMULATOR

RM.

OI&T

RECEPTION

TOILET

OFFICE

CORRIDOR

LOCKER

LOCKER

TOILET

WORK AREA

MAZE

THERAPY

ROOM 1

CONTROL

AREA

CONTROL

LINEAR

ACCELERATOR

MAZE

CORRIDOR

VESTIBULE

MOLD SHOP

MECH. RM.

ELEC

TOILET

OUT-PATIENT

WAITING

OFFICE

OFFICE

PATIENT

DRESSING/

TOILET

CORRIDOR

PATIENT

INJECTION

CORRIDOR

STORAGE

LABORATORY

CONTROL

RM.

PET/ CT

EXAM392

EXAM

MECH

WORK RM.

A020

ELEC. RM.

CONFERENCE

RM.

ELEC

STAIR 12

ELEC RM.

OI&T

ELEC. RM.

MECH. RM.

UTILITY

SERVICE

CORRIDOR

OFFICE

MECH

STAIR 11

STORAGE

B002

CLEAN

MEDICAL

SUPPLY

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

OFFICE

RECEPTION 421

VESTIBULE

CB27

ELEC

CB28

ELEC

STAIR 10

STORAGE

WORK RM.

OFFICE 428

OFFICE

MECH

STORAGE

OI&T

TOILET

TOILET

CORRIDOR

CORRIDOR

CORRIDOR

WAITING

RM.

CORRIDOR

MECH. RM.

TOILET,

MALE

SOUND

BOOTH

EXAM

SOUND

BOOTH 444

LOCKER

FEMALE

SOUND

BOOTH

CORRDOR

CORRIDOR

STORAGE

MANUAL

WASH

CB24

CART WASH

DETERGENT

& WATER

TREATMENT

ANTE RM.

ANTE RM.

CB13

LOCKER RM,

FEMALE

CB14

LOCKER RM,

MALE

HAC

CB17

Room

CB17A

SCOPE

PROCESSING

CB18

SCOPE

STORAGE

CB15A

SHOWER,

FEMALE

CB19

ANTE RM.

CB20

ANTE RM.

S007

STAIR 07

CB21A

SHOWER,

FEMALE

CB22A

SHOWER

MALE

CB25

HAC

CB23

OFFICE CB22

LOCKER

MALE

CB21

LOCKER

FEMALE

ETO

ETO

CASE CART

STORAGE

CB24

SURGICAL

STERILIZER

STORAGE

CB26

PREP/

STERILIZATION

PUMP RM.

OI&T

DECONTAMINATION

OFFICE

OFFICE

OFFICE

OFFICE

CORRIDOR

CORRIDOR

CORRIDOR

HAC

WAITING

RM.

OFFICE

EXAM

EXAM

EXAM

OFFICE

CB03

MECH. RM.

OFFICE

STAFF

ELEC

OI&T

OFFICE

BREAK RM.

STORAGE

CORRIDOR

CORRIDOR

STAIR 06

CB02A

MECH. RM.

CB02

MECH. RM.

GENERATOR

CB03

MECH. RM.

BREAK

ROOM

BIOMED

SHOP

OFFICE

OFFICE

TECH

CB36

BIOMED

SHOP

CB35

EQUIPMENT

STORAGE

H015

ELEVATOR

LOBBY

CONFERENCE

RM.

CORRIDOR

ELEVATOR

LOBBY

STAIR 03

OFFICE

OFFICE

OI&T

LAUNDRY

ELEC

F.E. CLOSET

OFFICE

STORAGE

LOCKER

TOILET,

FEMALE

A017A

OI&T

A017

HAC

B682

F.E. CLOSET

S001

STAIR 01

A019

OFFICE

CLOSET

H008

MAIN

ELEVATOR

LOBBY

FOOD/ BEV.

WALK-IN

FREEZE

WAREHOUSE

WAREHOUSE

MECH.

SPACE

CORRIDOR

LIGHT RM.

TOILET

LOCKER

MACHINE

SHOP

PAINT

STORAGE

PLASTER

SHOP

PAINT SHOP

OFFICE

CARPENTER

SHOP

STORAGE

OFFICE

ELEC SHOP

OFFICE

PLUMB.

SHOP

STAIR 04

PLUMB.

SHOP

HVAC SHOP

CORRIDOR

OFFICE

CORRIDOR

CARPENTER

SHOP

HVAC SHOP

STERILIZER

RECESS

DECONTAMINATION

MECH

ELEV 3

E8

ELEV 8

TELEPHONE

SWITCHGEAR

SERVER RM.

A001

PHONE

A002

PATIENT

CLOTHING

A016

OFFICE /

STORAGE

ELEV 10

TELEPHONE

SWITCHGEAR

OFFICE

WAREHOUSE

CH-CB-5

CHASE

CHASE

CH-CB-7

CHASE

CH-CB-11

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CH-A-1

CHASE

STAIR 7

STAIR 08

STAIR 09

ELEV 1

ELEV 2

ELEV 4

ELEV 5

ELEV 6

E7

ELEV 7

E9

ELEV 9

STORAGE

SUPERVISOR

VAULT

CART

HOLDING

EMS

BREAK

AREA/

LOCKERS

OFFICE

CORRIDOR

RECEIVING

01-AE-401

01-AE-401

01-MH-101

01-MH-101

01-EP-101

01-EP-101

01-EP-101

01-EP-102

01-EP-102

01-EP-102

01-EP-101

01-MH-101

01-MH-101

01-MH-101

01-MH-101

NO SCOPE OF WORK ASSOCIATED WITH THIS AREA

AREA OF WORK

GENERAL CONTRACTOR ACCESS/ROUTE

DEMO WALLS FOR INSPECTION SEE PLUMBING DWGS.

1. G.C. SHALL VERIFY DIMENSIONS OF OWNER FURNISHED EQUIPMENT AND

COORDINATE INSTALLATION WITH ALL TRADES WHERE REQUIRED.

2. EXTEND ALL RATED WALLS TO DECK PER UL ASSEMBLY REQUIREMENTS.

3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS, ETC.

4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD BLOCKING WITHIN WALLS BASED

ON CASEWORK ELEVATIONS AND ALL INTERIOR PARTITION ELEVATIONS.

5. ALL INTERIOR WALLS SHALL RECEIVE 5/8" TYPE 'X' GYPSUM BOARD.

6. G.C. SHALL PROVIDE UL APPROVED FIRE- RESISTIVE PENETRATION SYSTEMS

WHERE PLUMBING IS LOCATED IN A FIRE-RATED PARTITION ASSEMBLY.

7. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED AS NON-RATED SMOKE

PARTITIONS.

8. CONTRACTOR CANNOT WORK IN THE PROJECT AREA MONDAY - FRIDAY

BETWEEN THE HOURS OF 7AM-5PM. EXCEPTIONS MAY BE MADE BUT

PROPOSALS MUST BE SUBMITTED TO THE COR IN WRITING 21 CALENDAR DAYS

IN ADVANCE OF DOING WORK. COR RESERVES THE RIGHT TO ACCEPT OR DENY

ANY PROPOSALS. COR RESERVES THE RIGHT TO STOP WORK DURING THIS TIME

THAT IS DEEMED EXCESSIVE OR DISRUPTIVE TO PATIENT CARE AT NO COST TO

THE GOVERNMENT. WORK DURING REGULAR BUSINESS HOURS WILL BE

ALLOWED WITH WORK ASSOCIATED WITHIN ROOMS A539, A539A, AND A540.

WORK ADJACENT TO THESE ROOMS MAY BE RESTRICTED TO AFTER BUSINESS

HOURS. ANY EXCESSIVE NOISE PERCEIVED OUTSIDE THE CONSTRUCTION

CONTAINMENT BARRIER ABOVE 85 DECIBELS SHALL BE COORDINATED WITH

THE COR. THE COR RESERVES THE RIGHT TO DELAY WORK FOR 1-2 HOURS

SHOULD EXCESSIVE NOISE, VIBRATIONS, OR ANYTHING THE COR HAS DEEMED

EXCESSIVE OR DISRUPTIVE TO A PATIENT CARE PROCEDURE IN PROXIMITY TO

THE CONSTRUCTION CONTAINMENT BARRIER. A PLAN OF ACTION WILL BE

IMMEDIATELY PUT IN PLACE TO AVOID DISRUPTIONS TO THE CONSTRUCTION

SCHEDULE.

PLAN NORTH

TRUE NORTH

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:4

P

M

BASEMENT - OVERALL PLAN

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-107

1/16" = 1'-0"

BASEMENT - OVERALL PLAN

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

DN

S

S P

SCOPE OF WORK

GENERAL NOTES

A120

EXAM

A162E

HEMO DIAL

TREAT BAY

H109B

CORRIDOR

A162F

HEMO DIAL

TREAT BAY

A162G

HEMO DIAL

TREAT BAY

A162H

HEMO DIAL

TREAT BAY

A162J

HEMO DIAL

TREAT BAY

A162A

HEMO DIAL

TREAT BAY

A162B

HEMO DIAL

TREAT BAY

A162C

HEMO DIAL

TREAT BAY

A162D

HEMO DIAL

TREAT BAY

A163A

EXAM

A163B

EXAM

A160

TOILET

A161

ELEC

A156

NURSE

STATION

A159

NOUR.

A158

OFFICE

A157

MED. PREP.

A164

PATIENT

ISO.

A164A

TOILET

A165A

TOILET

S105

STAIR 05

A165

PATIENT

ISO.

A155

MECH. RM.

A154

SOILED

H108

CORRIDOR H108B

SCALE

A166

HAC

A167

EQUIPMENT

REPAIR

A168

PERITONEAL

DIALYSIS

A169A

EXAM

A169B

EXAM

A170A

OFFICE

A170C

DIETITIAN

A170B

IV

TREATMENT

A170D

IV

TREATMENT

A154A

CLEAN

A174A

TOILET

A173A

TOILET

A153

CONFERENCE

RM.

A170F

OFFICE

A170E

SUPPLY

H109C

CORRIDOR

H108D

CORRIDOR

H109A

CORRIDOR

A173B

COATS

A168A

STORAGE

A172A

LOCKER RM.

A173

RECEPTION

A171

DECONTAMINATION

A170G

OFFICE

A172

LOUNGE

A174

WAITING

H109

CORRIDOR

A100

WAITING

RM.

A100A

RECEPTION

A100B

COFFEE

SHOP

A100C

STORAGE

A101A

TOILET

A101

VESTIBULE

A101B

TOILET

A101C

RELEASE

OF

INFORMATION

A101D

OPTICAL

SHOP

H105

CORRIDOR

A177

NEPHROLOGY

A177A

OFFICE

A177B

OFFICE

A177C

OFFICE

A177D

STORAGE

A177E

OFFICE

A177F

CLOSET

A177G

OFFICE

A102

ALARM

PANEL

A103

OFFICE

A135

RECEPTION

A134

WAITING

RM.

A104

SCREEN

A105

SCREEN

A106

LEAD

NURSE

A107

EXAM

A108

OFFICE

A109

OFFICE A110

BREAK

A111

EXAM

A112

EXAMA113

EXAM

A114

EXAM

A115

EXAM

A116

EXAM

A117

TOILET

A118

HAC

A119

ELEC

A110A

TOILET

H101

CORRIDOR

H102

CORRIDOR

A121

EXAM

A122

EXAM

A123

EXAM

A124

OPHTH.

CHIEF

RESIDENT

A125

OPHTH.

CHIEF

RESIDENT

A126

EXAM

A127

LASER

TREATMENT

A128

PROCEDURE

A129

EXAM

A130

EXAM

A131

CLINICAL

MANAGER

A132

EXAM

A133

IMAGING

SUPPLY

A132A

OFFICE,

CHIEF

A131A

ELEC

S102

STAIR 02

H103

CORRIDOR

A137A

ELEC

A136

OI&T

A136A

FIRE ALARM

SYSTEM

S101

STAIR 01A139

NEUROLOGY

CLINICA139F

WAITING

RM.

H123

CORRIDOR

A139E

NURSE

STATION

A139D

EXAM

A139C

EXAM

A139G

EXAM

A139H

EXAM

A139J

EXAM

A139K

EXAM

A139B

EXAM

A139A

EXAM

B100

AMBASSADOR

SUITE

B100A

MECH. RM.

B100B

OFFICE

B100D

OFFICE

B100E

OFFICE

B100F

OFFICE

B100G

OFFICE

B100H

OFFICE

B100I

ELEC.

CLOSET

B100J

OI&T S112

STAIR 12

H100A

INFORMATION

H100

LOBBY

B102B

MED. PREP.

B102A

MED. PREP.

B102

WAITING

RM.

B102D

ALCOVE

B102E

OFFICE

B102F

AGENT

CASHIER

H118

CORRIDOR

B103C

EQUIPMENT

STORAGE

B106

CONFERENCE

RM.

B107

ARMORY

B108

OFFICE,

CHIEF

C101

LOCKER RM.

C102

EVIDENCE

C103

OFFICE

C104

OFFICE

C105

OFFICE

C106

OFFICE

C107

HOLDING

CELL

C108

CONTROL

H122

ELEVATOR

LOBBY

H120

CORRIDOR

C146

TOILET,

MALE

B105

OI&T

B103

HAC

B104

CHUTE

A180

OFFICE

A181

OFFICE

A182

MECH. RM.

A183

OFFICE

A184

OFFICE

A185

OFFICE

A186

OFFICE

A187

OFFICEA188

OFFICEA189

EXAMA190

EXAM

A191

STORAGE

A192

STORAGE

A193

FIRE ALARM

A148

STORAGE

A149

OI&T

A149A

STORAGE

H111A

STORAGE

H111

ELEVATOR

LOBBY

H110

ELEVATOR

LOBBY

A140

OFFICE

A141

INTAKE

A142

INTAKE

A143

OFFICE

A144

EXAM A145

OFFICE

A146

OFFICE

A147

OFFICE

A151

TOILET

A150

OFFICE

H113

CORRIDOR

B145

OFFICE

B146

WAITING

RM.

B147

SUPPLY

B148

BREAK RM.

B149

OFFICE

B150

CONSULT

RM.

B149A

OFFICE

B149B

OFFICE

B121

STORAGEB122

TOILET,

FEMALE

S103

STAIR 03

B122A

TOILET

B124

PROCEDURE

RM.

B125

OFFICE

B126

EXAM

B127

EXAM

B128

EXAM

B129

EXAM

B130

MECH. RM.

B131

EXAM

B132

EXAM

B133

EXAM

B134

EXAM

B135

EXAM

B136

EXAM

B137

TOILET

B138

EXAM

B139

EXAM

B140

EXAM

B141

EXAM

B142

EXAM

B143

OFFICE

B144

OFFICE

S104

STAIR 04

B142A

ELEC

H117

CORRIDOR

B119A

WAITING

ROOM

B119

WAITING

ROOM

B111

OFFICE

H124

CORRIDOR

B112

EXAM

B113

EXAM

B114

EXAM

B116

EXAM

B117

EXAM

B118

EXAM

B117A

OFFICE

C149

OFFICE

C138

LOCKER RM.

C140

ELIGIBILITY

C141

OFFICE

C141A

OFFICE

H125

CORRIDOR

C110

WAITING

RM.

C109

OFFICE

C109A

TRIAGE

C112

CONTROL

RM.

C113

TRIAGE

E125

TRIAGE

E126

TOILET

E127

ANTE RM.

E128

PATIENT

ISO.

E133

EXAM

TREATMENT

E101

EXAM

TREAT.

BAYS

E102

EXAM

E103

NURSE

STATION

E104

EXAM

E105

EXAM

E106

EXAM

E107

EXAM

E108

CLEAN

EQUIPMENT

E109

EXAM

E110

EXAM

E111

TOILET

E112

CLEAN

UTILITY

E113

SOIL

UTILITY

E114

CLEAN

LINEN

E115

AMBUL.

ATTEND.

E116

MED. PREP.

E117

OFFICE /

NOUR.

E118

LOCKER RM.

E119

TOILET

E120

LOCKER RM.

E121

HAC

E122

SECURE

HOLD

E123

SECURE

HOLD

C115

TOILET

C118

TOILET

C117

ELEC

E124

WAITING

RM.

E134

NURSE

STATION

E135

TOILET

E121A

ALCOVE

H134

CORRIDOR

H135

CORRIDOR

H132

CORRIDOR

H126

CORRIDOR

C111B

EXAM

C111A

EXAM

C114

CONFERENCE

RM.

C116

OFFICE

C119

OFFICE

C120

OFFICE

H128

CORRIDOR

C121

OFFICE

C122

FILE RM.

C123

OFFICE

C124

OFFICE

C125

OFFICE

C126

OFFICE

C127

OFFICE

C128

WAITING

C129

OFFICE

C122A

OFFICE

C130

OFFICE

C131

OFFICE

C132

OFFICE

C134

OFFICE

H133

CORRIDOR

C136

OI&T

C137

STORAGE

C148

OFFICE

C150

EXAM

C151

EXAM

C152

EXAM

H127

CORRIDOR

H130

CORRIDOR

H131

CORRIDOR

S106

STAIR 06

C173

OFFICE

C173A

TOILET

D143

EXAM

D120

EXAM

D121

EXAM

D122

EXAM

D123

OFFICE

D124

OFFICE D125

EXAM

D126

EXAM

D127

EXAM

D128

TOILET

D129

OFFICE C180

OFFICE

C179

OFFICE

C178

OFFICE

C177

TOILET

C176

EXAM

D174

EXAM

H141

CORRIDOR

H142

CORRIDOR

H140

CORRIDOR

S109

STAIR 09

D130

EXAM

D131

EXAM

D132

OFFICE

D133

OFFICE

D134

OFFICE

D135

OFFICE

D136A

OFFICE

D142

EXAM

D136B

CLEAN

SUPPLIES

D141

EXAM

D140

HAC

D139

EXAM

D138

EXAM

D137

EXAM

D136

NURSE

STATION

D101A

WAITING

RM.

D116

OFFICE

D117

OFFICE

D118

EXAM

H139

CORRIDOR

D112

OFFICE

D102

EXAM

D119

OFFICE

D111

OFFICE D110

OFFICE

CH-D-1

CHASE

S110

STAIR 10

H137

CORRIDOR

D144

ELEC

D145

OI&T

D146

OFFICE

H136

CORRIDOR

D103

BREAK RM.

D104

TOILET

D105

WORK RM.

D115

TOILET

D114

EXAM

D113

EXAM

D106

HAC

D107

EXAM

D108

EXAM

S108

STAIR 08

H138

CORRIDOR

E110A

STORAGEE110B

STORAGE

D147

OFFICE

D148

OFFICE,

CHIEF

H138A

CORRIDOR

D109

OFFICE

E112A

OXYGEN

STORAGE

C114A

STORAGE

H127A

CORRIDOR

H114A

CORRIDOR

H119

CORRIDOR

H113C

CORRIDOR

C146A

HAC

B120A

ELEC

H113A

CORRIDOR

A101E

BREAK RM.

H109E

CORRIDOR

H109D

CORRIDOR

A170I

OI&T

A103A

TOILET

H110B

F.E. CLOSET

A139I

STORAGE

H125B

ENTRYWAY

C109B

VESTIBULE

C175

EXAM

H125A

VESTIBULE

D101

NURSE

STATION

ELEV 10

S107A

VESTIBULE

S107

STAIR 07

H113B

F.E. CLOSET

H103A

F.E. CLOSET

A175

SUPPLY

F.E. CLST

H117A

F.E. CLOSET

C178A

CLOSET

Room

ELEV 1

ELEV 2

ELEV 3

ELEV 4

ELEV 5

ELEV 6

ELEV 7

ELEV 8

ELEV 9

CH-C-1

CHASE

CH-C-2

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CH-B-3

CHASE

CH-B-1

CHASE

CH-B-2

CHASE

CH-B-4

CHASE

CH-B-5

CHASE CH-B-6

CHASE

CH-A-12

CHASE

CH-B-7

CHASE

CH-C-3

CHASE

CH-B-8

CHASE

CH-B-9

CHASE

CH-C-4

CHASE

CH-C-5

CHASE

CH-D-5

CHASE

CH-D-2

CHASE

CH-C-7

CHASE

CH-C-8

CHASE CH-E-1

CHASE

CH-C-6

CHASE

CH-D-3

CHASE

CH-D-4

CHASE

CH-E-2

CHASE

01-AE-403

01-AE-404

01-AE-402

01-AE-402

01-MH-104

01-MH-104

01-MH-104

01-MH-103

01-MH-103

01-EP-103

01-EP-103

01-EP-103

01-EP-105

01-EP-105

01-EP-104

01-EP-104

NO SCOPE OF WORK ASSOCIATED WITH THIS AREA

AREA OF WORK

GENERAL CONTRACTOR ACCESS/ROUTE

DEMO WALLS FOR INSPECTION SEE PLUMBING DWGS.

1. G.C. SHALL VERIFY DIMENSIONS OF OWNER FURNISHED EQUIPMENT AND

COORDINATE INSTALLATION WITH ALL TRADES WHERE REQUIRED.

2. EXTEND ALL RATED WALLS TO DECK PER UL ASSEMBLY REQUIREMENTS.

3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS, ETC.

4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD BLOCKING WITHIN WALLS BASED

ON CASEWORK ELEVATIONS AND ALL INTERIOR PARTITION ELEVATIONS.

5. ALL INTERIOR WALLS SHALL RECEIVE 5/8" TYPE 'X' GYPSUM BOARD.

6. G.C. SHALL PROVIDE UL APPROVED FIRE- RESISTIVE PENETRATION SYSTEMS

WHERE PLUMBING IS LOCATED IN A FIRE-RATED PARTITION ASSEMBLY.

7. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED AS NON-RATED SMOKE

PARTITIONS.

8. CONTRACTOR CANNOT WORK IN THE PROJECT AREA MONDAY - FRIDAY

BETWEEN THE HOURS OF 7AM-5PM. EXCEPTIONS MAY BE MADE BUT

PROPOSALS MUST BE SUBMITTED TO THE COR IN WRITING 21 CALENDAR DAYS

IN ADVANCE OF DOING WORK. COR RESERVES THE RIGHT TO ACCEPT OR DENY

ANY PROPOSALS. COR RESERVES THE RIGHT TO STOP WORK DURING THIS TIME

THAT IS DEEMED EXCESSIVE OR DISRUPTIVE TO PATIENT CARE AT NO COST TO

THE GOVERNMENT. WORK DURING REGULAR BUSINESS HOURS WILL BE

ALLOWED WITH WORK ASSOCIATED WITHIN ROOMS A539, A539A, AND A540.

WORK ADJACENT TO THESE ROOMS MAY BE RESTRICTED TO AFTER BUSINESS

HOURS. ANY EXCESSIVE NOISE PERCEIVED OUTSIDE THE CONSTRUCTION

CONTAINMENT BARRIER ABOVE 85 DECIBELS SHALL BE COORDINATED WITH

THE COR. THE COR RESERVES THE RIGHT TO DELAY WORK FOR 1-2 HOURS

SHOULD EXCESSIVE NOISE, VIBRATIONS, OR ANYTHING THE COR HAS DEEMED

EXCESSIVE OR DISRUPTIVE TO A PATIENT CARE PROCEDURE IN PROXIMITY TO

THE CONSTRUCTION CONTAINMENT BARRIER. A PLAN OF ACTION WILL BE

IMMEDIATELY PUT IN PLACE TO AVOID DISRUPTIONS TO THE CONSTRUCTION

SCHEDULE.

PLAN NORTH

TRUE NORTH

G ra p h ic S ca le

/2

0"

G ra p h ic S ca le

/3 2"

0"

' G ra p h ic S ca le

/1 6"

0"

' G ra p h ic S ca le

/8

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

/8

0"

' G ra p h ic

S ca le

/2

0"

G ra p h ic S ca le

/4

0"

G ra p h ic S ca le

0"

Romanyk Consulting Focusing on what matters

VA FORM 08 - 6231

F

E

D

C

B

A

F

E

D

C

B

A

910 7 6 5 4 3 2 1

ARCHITECT/ENGINEER OF RECORDCONSULTANT

8910 7 6

Romanyk Consulting Corp. www.romanykconsulting.com 3308 Preston Road, Suite 350-164, Plano, Texas 75093

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

U.S. Department of Veterans Affairs

Phase

STAMP

5 4 3 2 1

Office of Construction and Facilities Management

FULLY SPRINKLERED

B

IM

/V

IS

N

S t L o u is C o rr e c t H

V A

C t o m e e t D ir e c ti v e

/S tL

M O

-A C

S

-1

J C

M

E P

V

.r v t

/2

/2

:0

:1

P

M

LEVEL 01 - OVERALL PLAN

SEPTEMBER 28, 2023

657-21-114JC100% BID DOCUMENTS CORRECT HVAC SYSTEMS FOR

VHA DIRECTIVE 1116 (2)

JB MR

657 - ST. LOUIS, MO

915 NORTH GRAND BLVD., ST. LOUIS, MO 63106

01-GI-108

1/16" = 1'-0"

LEVEL 01 - OVERALL PLAN

ISTERED ARCHITECT

S

TATE OF TEXAS

J

AM

SP SP

SCOPE OF WORK

GENERAL NOTES

D502B

CART

ELEVATOR

EQUIPMENT

D502A

CART

ELEVATOR

EQUIPMENT

D502L

STORAGE

D502J

STORAGE

PLUMBING

SHOP

D502H

STORAGE

MASON

SHOP

S508

STAIR 08

D502G

STORAGE

CARPENTRY

SHOP

D502K

STORAGE

IHCG SHOP

D502F

STORAGE

ELECTRIC

SHOP D502E

STORAGE

PIPE SHOP

D502D

STORAGE

A/C SHOP

H517

CORRIDOR

STORAGE

A/C SHOP

B538

MECH. RM.

D505A

Room

D505

MECH. RM.

A554

ELEC

A571A

NOUR.

A565A

ANTE RM.

A556A

OFFICE

A556

OFFICE

A557

CONFERENCE

RM.

A556B

HALLWAY

A555A

TOILET

A558A

TOILET

A558

OFFICE

A555

OFFICE

A553

OFFICE

A553A

TOILET

A552A

STRETCH

A559

OFFICE

A552

OFFICE

A560

HAC

A559A

TOILET

A561

OFFICE

S505

STAIR 05

A550

OFFICE

A549A

TOILET

A549

WAITING

A548

WAITING

A548A

TOILET

A547

OFFICE,

DIETICIAN

A572

OFFICE

A573

MED. PREP.

A570

OFFICE

A569

OFFICE

A570A

ANTE RM.

A570B

TOILET

A568

OFFICE

A569A

TOILET

A568A

OFFICE

HALLWAY

A567B

OFFICE

A567

OFFICEA566A

TOILET

A567A

HALLWAY

A566

OFFICEA565B

TOILET

A565

OFFICE

A562

CLEAN

A564

SOILED

A564A

CRASH

CART

A563

ELEC

H505

CORRIDOR

H504

CORRIDOR

A571

NURSE

STATION

A578

TLT

A577A

TOILET

A576

OFFICE

A574

TOILET

A575

OFFICE

A544C

TOILET

H507

SERVICE

ELEVATOR

LOBBY

H503

CORRIDOR

A544B

LOCKER

A544

PHYSICIAN

WORK RM.

A501A

OFFICE

A501

OFFICE

A502

OFFICE

A509

OFFICE

A510

OFFICE

A511

OFFICE

A510A

TOILET

A512

OFFICE

A513

OFFICE

A512A

TOILET

A542

LAB

A541

STORAGE

B546

OFFICE

B544

OFFICE

B545

TOILET

A536B

ELEC

A544A

CLOSET

H506

ELEVATOR

LOBBY

B502

OFFICE

B501

OFFICE

A540A

STORAGE

A539

STORAGE

A535

OFFICE

S501

STAIR 01

A538

PHYSICIAN

WORK RM.

A536

ELECA536A

OI&T

A535A

TOILET

A537A

DATA

H501

CORRIDOR

A508A

TOILET

A508

OFFICE

A507A

TOILET

A507

OFFICE

A504

COPY

A503

HAC

A506A

TOILET

A505

NOUR.

A506

OFFICE

A517

OFFICE

A516

OFFICE

A515

OFFICE

A514

OFFICE

A516A

TOILET

A514A

TOILET

A521

STRG

A519

SOILED

A520

ELEC

A517A

TOILET

A518

STORAGE

A532

TOILET

A531

OFFICE

A533

OFFICE

B524D

EXAM

A524C

EXAM

A524A

EXAM

A524B

EXAM

B524

WAITING

RM. B524E

RECEPTION

A522

OFFICE

A523A

OFFICE

A523

HALLWAY

A523B

OFFICE

A527

HAC

S502

STAIR 02

A525

TOILET,

MALE

A526

OFFICE

H502A

F.E. CLOSET

A530

OFFICE

A529

OFFICE

H502

CORRIDOR

A543

PULMONARY

RESPIRATORY

THERAPY

A543B

OFFICE

B542

OFFICE

B541

OFFICE

H508

CORRIDOR

B503

BRONCHOSCOPY

SUITE

CORRIDOR

B528

STORAGE

B529

TOILET

B530

TOILET

B526

PREP /

RECOVERY

B527

MECH

B525

CONTROL

B523

EP LAB

H516

CORRIDOR

ELECTRO-

PHYSIOLOGY

C513

STERILIZER

C528

HAC

B532

MALE

LOCKER

HAC

B538A

TOILET

LOCKER

FEMALE

B533

OFFICE

B534

CATHETER

READING

B537

SOILED

B536

ELEC

S503

STAIR 03

H508A

F.E. CLOSET

B504

BREAK RM.

B522

TOILET

B520

WAITING

RM.

B521

HOLDING

B519

CONSULT

B511

CONTROL 1

B512

CONTROL 2

B509

SCRUB

B513

STORAGE

B510

CARDIAC

CATH. LAB 1

B508

PREP

B505

STORAGE

B506

MECH

B507

OI&T

B504B

Room

H509

CORRIDOR

H510A

CORRIDOR

H514

ELEVATOR

LOBBY

B531

TOILET

H513A

CORRIDOR

H513

CORRIDOR

H512A

SUPPLY

C520

LOCKER

C520A

TOILET

C519

BREAK

C518A

TOILET

C518

LOCKERC516

SOILED

C500B

STORAGE

C500C

OFFICE

C500D

HAC

C501A

ANTE RM.

C501

RECOVERY

ISOLATION

H510B

CORRIDOR

C500A

STORAGE

C504

RECOVERY

C503

RECOVERY

C502

RECOVERY

C510A

ANTE

C510

ISOLATION

RECOVERY

C509

RECOVERY

H511

CORRIDOR

C507

RECOVERY

C506

RECOVERY

C505

RECOVERY

C511A

TOILET

C511

TOILET

H512

CORRIDOR

C512

STORAGE

C524

OI&T

C514A

SCRUB

C522

OI&T

C521

ELEC

C515

CLEAN RM.

C514

STORAGE

B543

TOILET

B517

STORAGE

B518

HAC

H506A

F.E. CLOSET

B514

SCRUB

C508

RECOVERY

H510

CORRIDOR

H515

CORRIDOR

S506

STAIR 06

D502

MECH. RM.

STORAGE

D502C

STORAGE

BMET

S507

STAIR 07

ELEV 1

ELEV 2

ELEV 3

ELEV 4

ELEV 5

ELEV 6

ELEV 7

ELEV 8

ELEV 9

S509

STAIR 09

A577

STORAGE

CHASE

CHASE

CHASE

CHASE

CHASE

C512A

ENTRY

CHASE

A544D

CLOSET

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE 164

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

CHASE

A525A

MECH

CHASE

CHASE

B515

PREP/RECOV

B516

CARDIAC

CATH LAB 2

01-AE-405

01-AE-406

01-MH-105

01-MH-105

01-EP-106

01-EP-106

01-EP-106

A539

STORAGE

01-MP-105

NO SCOPE OF WORK ASSOCIATED WITH THIS AREA

AREA OF WORK

GENERAL CONTRACTOR ACCESS/ROUTE

DEMO WALLS FOR INSPECTION SEE PLUMBING DWGS.

1. G.C. SHALL VERIFY DIMENSIONS OF OWNER FURNISHED EQUIPMENT AND

COORDINATE INSTALLATION WITH ALL TRADES WHERE REQUIRED.

2. EXTEND ALL RATED WALLS TO DECK PER UL ASSEMBLY REQUIREMENTS.

3. G.C. SHALL INSTALL IN-WALL METAL BACKING FOR ALL PARTITION-MOUNTED

EQUIPMENT, ACCESSORIES, PARTITION STOPS, ETC.

4. G.C. SHALL INSTALL FIRE-RETARDANT WOOD BLOCKING WITHIN WALLS BASED

ON CASEWORK ELEVATIONS AND ALL INTERIOR PARTITION ELEVATIONS.

5. ALL INTERIOR WALLS SHALL RECEIVE 5/8" TYPE 'X' GYPSUM BOARD.

6. G.C. SHALL PROVIDE UL APPROVED FIRE- RESISTIVE PENETRATION SYSTEMS

WHERE PLUMBING IS LOCATED IN A FIRE-RATED PARTITION ASSEMBLY.

7. ALL CORRIDOR WALLS SHALL BE CONSTRUCTED AS NON-RATED SMOKE

PARTITIONS.

8. CONTRACTOR CANNOT WORK IN THE PROJECT AREA MONDAY - FRIDAY

BETWEEN THE HOURS OF 7AM-5PM. EXCEPTIONS MAY BE MADE BUT

PROPOSALS MUST BE SUBMITTED TO THE COR IN WRITING 21 CALENDAR DAYS

IN ADVANCE OF DOING WORK. COR RESERVES THE RIGHT TO ACCEPT OR DENY

ANY…