36C25518R0342-A00003002.pdf

PDF 907 KB Posted

Attached to
657-17-185JC Renovate Gastroenterology Procedure Room and Support Space
Solicitation number
36C25518R0342
Issued by

About this file

36C25518R0342 A00003 S05 - PRE-BID RFI'S AND ANSWERS - DRAWING A200 - A00003.pdf

View the file

Other files

File Type Posted
36C25518C0158-000.docx DOCX document
36C25518R0342-A00003000.docx DOCX document
36C25518R0342-A00003001.pdf PDF
36C25518R0342-A00002003.pdf PDF
36C25518R0342-A00002005.pdf PDF
36C25518R0342-A00002002.pdf PDF
36C25518R0342-A00002000.docx DOCX document
36C25518R0342-A00002004.pdf PDF
36C25518R0342-A00002001.pdf PDF
36C25518R0342-A00001001.pdf PDF
36C25518R0342-A00001000.docx DOCX document
36C25518R0342-003.pdf PDF
36C25518R0342-002.pdf PDF
36C25518R0342-001.docx DOCX document
36C25518R0342-000.docx DOCX document
Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

MAX

0' - 7"0' - 6 1/32" Requirement

Per MFR

MAX

0' - 7"

/3

Resilient Contact Surface Bumper

Ancorage Shall be Located to Miss Studs;

Provide Backing Supoort.

MFR Standard End Closure Corner Guard; See Plan for Locations

Wall Assembly; See Plan for P-Type

Door Frame; See Plan for More Information

MFR Standard End Closer

0' - 4 1/16"1-A-200

Sim

R e D o o r s c h e d u le

Notes:

1. Head Similar

2. Provide (3) Anchors MIN per Jamb; (4) at Rated Partitions

3. Refer to Door Schedule for Ratings Required

4. HM Jamb Throat 1/8" Larger than Partition, Caulk and Paint , TYP

Double Stud @ Jamb

Welded HM Frame

X

P-Type;

REF: Plan

Line Of Adjacent Partition (Where

Occurs)

/1

0' - 0 1/2"

/3

0' - 1 13/16" ±Varies

REF:

Schedule

Wall Assembly;

RE: Plan for P-

Type

Stainless Steel Corner Guard

0' - 3 1/2"

/2

F Flush

REF: Schedule

R E

F S c h e d u le

HM

0' - 2" REF: Door Schedule 0' - 2"

R E

F D o o r S c h e d u le

1-A-200

Sim

Hollow Metal

Partition Type Not to ScaleC 3-5/8" Studs

Decking

5/8" GWB

Ceiling Line; RE: RCP

FIN Floor; REF: Schedule

Wall Base; REF: Schedule

MTL Studs @ 16" OC

Sub-floor / Slab

Room Side: GWB 6" Above CLG Corridor Side: GWB Extend to Underside of Decking; Cope Tight to Structure

Sliptrack at Structure TYP

(C2) 7 1/4"

(C) 0' - 4 7/8"

CORRIDOR

SIDE

ROOM

SIDE

Sound Batts

± 0' - 3 1/32"

/2

MIN.

0' - 1 17/32"

Wall Base; RE: Room Finish Schedule

Bottom of Lower Wall Guard to be Flush with Top of Wall Base

Fasteners per MRF Requirements

Continuous Aluminum Retainer

Continuous Impact Bumper

Vinyl Cover; RE: Finish Schedule for More Information

5/8" GWB, TYP.

MTL Stud Blocking per MFR Requirements

± 0' - 1 1/4"

Fasteners Per MFR Requirements

Continuous Aluminum Retainer

Continuous Impact Bumper

Vinyl Cover; RE: Finish schedule for More Information

5/8" GWB, TYP.

MTL Stud Blocking per MFR Requirements

LOWER GUARDRAIL

UPPER HANDRAIL

Note: See Detail for Termination

G

SS1 countertop w/ 4" SS1 backsplash

2' - 6"

1-A-200

Lockable PLAM Cabinet w/ (2) adjustable shelves.

1-A-200

Integral coved base RE: Finish info

Lockable PLAM base cabinet w/ (1) adjustable shelf

SS1 - SEE FINISH SCHEDULE

CABINET PULLS

(VERTICAL

MOUNT; BRUSHED

STAINLESS STEEL

WIRE)

PLAM

DRAWER UNIT

LOCKABLE PLAM BASE CABINET

SCHEDULED BASE

NOTE: DRAWER, CABINET

INTERIOR, & ADJUSTABLE

SHELF TO BE WHITE

MELAMINE

2'-1" U.O.N.

/2

/8

2'-0"

3"

1"

R E

E

L E

V A

T

IO

N

2X FTWD BLOCKING

SEALANT

4" SS1

PLAM Cabinet, Scribe to Wall

/2

Sealant

Extend Side panel at Exposed Ends

Blocking where Required

Clear

10 7/8"

Clear glass in PLAM Frame. Provide concealed lock

F

.V

ACT CLG grid & pads RE: Material Schedule

5/8" GWB on 3 5/8" Mtl Studs

Note: Glass cabinet doors are to be secured with concealed locks. Verify lock type with VA.

1' - 0" 1" 1/2"

HHH

Lockable PLAM Cabinet w/ (2) adjustable shelves.

1-A-200

1" 2' - 6"

E27

Endoscopy Equipment provided and installed by the VA. See Equipment plan

TYP

0' - 0 1/2"

T Y

P

/2

BRACING ABOVE

PER DETAIL

10/A200

L3x3 VERTICAL

ANGLE STRUTS

EACH CORNER

PER DETAIL

10/A200

HOLE IN PLATE

FOR MEP ROUTING

BY EQUIP. MFG.

1" MOUNTING

PLATE BY

EQUIPMENT

MFG.

L6x6x1/2 SUPPORT ANGLE

L3x3x1/4 VERTICAL

ANGLE HANGERS TYP

EA. CORNER OF FRAME

L2x2x3/8 ANGLES TYP

EA SIDE OF FRAME

1" STEEL PLATE

BY BOOM MFG.

3/4" Ø HILTI HY200 ANCHORS

@ 12" o.c. DRILL AND EPOXY

W/3 1/2" EMBEDMENT MIN. 3/16

3-SIDES

TYP

3/16

3-SIDES

TYP

3/16

TYP

/3

MIN.

2' - 0"

W/ EQUIP. MFG.

2' - 0" VERIFY

MIN.

2' - 0"

Drawing Title Project Title

Date

Location

Checked

Building Number

Project Number

Drawing Number

Drawn

Revisions: Date

CONSULTANTS: ARCHITECT/ENGINEERS:

#1 6th FloorApproved: Chief of Service

Approved: Service Line Nurse Mgr.

Approved: Projects Chief

Approved: Infection Control

Approved: Safety Officer

Approved: COR o n e e ig h th in c h o n e fo o t 1

B

A

C

D

E

F th re e in c h e s o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t o n e in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 87 9

F

E

D

C

B

A

97 8654321

1 Memorial Dr. STE 1800 Saint Louis, MO 63102

Tel Fax

314.621.4343 314.621.0261

220 N College Ave Indianapolis, IN 46202

Tel Fax

317.464.9090 317.464.9393

Department of Veteran's Affairs Medical Center John Cochran

Division

4/19/2018 4:45:47 PM

Door and Misc. Details VAJC Renovate GI Procedure Room

1-A-200

657-17-185JC

915 NORTH GRAND BLVD. SAINT

LOUIS, MISSOURI 63106

January 30, 2018

Bid Documents

RD HT

1 1/2" = 1'-0"4 Detail - Crash Rail Termination

3" = 1'-0"1 Detail - HM Door Jamb

3" = 1'-0"5 Detail - Stainless Steel Corner Guard

Door Types Frame Types

3" = 1'-0"6 Detail - Handrail & Crashrail

1/4" = 1'-0"3 Interior Elevation - East

1 1/2" = 1'-0"8 Detail - Base Cabinet w/ Drawer

1 1/2" = 1'-0"7 Detail - Upper Cabinet

1/4" = 1'-0"2 Elevation 1 - a

3/4" = 1'-0"9 TYPICAL PLAN VIEW OF MEDICAL BOOM SUPPORT FRAME

3/4" = 1'-0"10 TYPICAL SECTION @ MEDICAL BOOM SUPPORT FRAME

htaylor HT MO Seal - Sig and Date

Sheets
1-A-200 - Door and Misc. Details

File details come from the government source that posted it.