P01-537-26-200 AHU-AC21 Schedule-ADDENDUM 1.pdf

PDF 87 KB Posted

Attached to
Z1DA--537-26-200 FY26 Facility Cooling Improvements
Solicitation number
36C25226R0051
Issued by

About this file

This document is a revised Air Handling Unit (AHU) specification schedule for equipment tag AC-21, presented as Addendum #1 to a contract solicitation.

The schedule specifies a single rooftop-mounted AHU (AC-21) with a capacity of 28,740 CFM and external static pressure of 3.5 inches water gauge (in. W.G.), with total static pressure of 6.47 in. W.G. The unit operates on 208-volt, 3-phase, 60-hertz power and features a plug fan with 444-inch diameter operating at 95 feet per minute. The cooling coil is configured with 8 rows at 11 fins per inch, handling 1,375 MBH sensible cooling and 2,190 MBH total cooling capacity, with entering air conditions of 95°F dry bulb/75°F wet bulb and leaving air conditions of 53.5°F dry bulb/53.5°F wet bulb. The heating coil operates with 8 rows at 11 fins per inch, designed for -10°F entering water temperature and 88.1°F leaving air temperature, providing 3,248 MBH capacity at 325 GPM. Pre-filters consist of MERV 7 (PF-1) and MERV 13 (PF-2) options. The AHU is based on Carrier 39M Outdoor AHU, Temtrol PF Series AHU, or York custom-made AHU designs, utilizing 30% glycol for the heating coil circuit. Air friction loss is specified at 0.325 inches water gauge, and water friction loss is 325 feet water gauge equivalent.

View the file

Other files

Show all 15

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Revised AHU AC-21 Schedule_ADDENDUM#1.

AHU AC-21 SCHEDULE

Tag

Location

Fan

Cfm

PRESSURE

IN. W.G.

PRESSU

RE IN,

WG,

MOTOR

FAN

COOLING COIL

HEATING COIL

PRE-FILTERS

BASED ON

REMARKS

Ext, S.P.

Total

S.P.

BHP/HP

Volts/Ph/Hz Diam

In

RPM Type Face GPM Area.

EAT

DB/WB

LAT

DB/WB

SC MBH TC MBH No. of

Rows/fpi

EW

T

°F

LWT

°F

Face Area Sq. Ft.

EWT

°F

LWT

°F

No. of

Row s/fpi

EAT

°F

LAT

°F

Capacity

MBH

GPM AIR FRICT.

INCH WG

WTR FRICT.

FT. WG

PF-1 = MERV 7.

PF-2 = MERV 13.

CARRIER 39M

OUTDOOR AHU

TEMTROL PF

SERIES AHU

YORK CUSTOM-

MADE AHU

30% GLYCOL

AC-21 Roof 28,740 3.5 6.47

208/3ɸ/60

Plug

Fan

444 95/75 53.5/53.5 1375 2190 8/11 40 55

180 160 8/11 -10 88.1 3248 325

File details come from the government source that posted it. Updated .