P01-537-26-200 AHU-AC21 Schedule-ADDENDUM 1.pdf
PDF 87 KB Posted
- Solicitation number
- 36C25226R0051
About this file
This document is a revised Air Handling Unit (AHU) specification schedule for equipment tag AC-21, presented as Addendum #1 to a contract solicitation.
The schedule specifies a single rooftop-mounted AHU (AC-21) with a capacity of 28,740 CFM and external static pressure of 3.5 inches water gauge (in. W.G.), with total static pressure of 6.47 in. W.G. The unit operates on 208-volt, 3-phase, 60-hertz power and features a plug fan with 444-inch diameter operating at 95 feet per minute. The cooling coil is configured with 8 rows at 11 fins per inch, handling 1,375 MBH sensible cooling and 2,190 MBH total cooling capacity, with entering air conditions of 95°F dry bulb/75°F wet bulb and leaving air conditions of 53.5°F dry bulb/53.5°F wet bulb. The heating coil operates with 8 rows at 11 fins per inch, designed for -10°F entering water temperature and 88.1°F leaving air temperature, providing 3,248 MBH capacity at 325 GPM. Pre-filters consist of MERV 7 (PF-1) and MERV 13 (PF-2) options. The AHU is based on Carrier 39M Outdoor AHU, Temtrol PF Series AHU, or York custom-made AHU designs, utilizing 30% glycol for the heating coil circuit. Air friction loss is specified at 0.325 inches water gauge, and water friction loss is 325 feet water gauge equivalent.
View the file
Other files
Show all 15
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Revised AHU AC-21 Schedule_ADDENDUM#1.
AHU AC-21 SCHEDULE
Tag
Location
Fan
Cfm
PRESSURE
IN. W.G.
PRESSU
RE IN,
WG,
MOTOR
FAN
COOLING COIL
HEATING COIL
PRE-FILTERS
BASED ON
REMARKS
Ext, S.P.
Total
S.P.
BHP/HP
Volts/Ph/Hz Diam
In
RPM Type Face GPM Area.
EAT
DB/WB
LAT
DB/WB
SC MBH TC MBH No. of
Rows/fpi
EW
T
°F
LWT
°F
Face Area Sq. Ft.
EWT
°F
LWT
°F
No. of
Row s/fpi
EAT
°F
LAT
°F
Capacity
MBH
GPM AIR FRICT.
INCH WG
WTR FRICT.
FT. WG
PF-1 = MERV 7.
PF-2 = MERV 13.
CARRIER 39M
OUTDOOR AHU
TEMTROL PF
SERIES AHU
YORK CUSTOM-
MADE AHU
30% GLYCOL
AC-21 Roof 28,740 3.5 6.47
208/3ɸ/60
Plug
Fan
444 95/75 53.5/53.5 1375 2190 8/11 40 55
180 160 8/11 -10 88.1 3248 325
File details come from the government source that posted it. Updated .