S06 36C25222B0022 0003 Att4_Appx A - FHCC Asbestos Hazmat Testing Report.pdf

PDF 4 MB Posted

Attached to
Z1DA--Project 556-20-013 Renovate Bldg 134 CLC 3A/C at the Captain James A. Lovell FHCC in North Chicago, IL
Solicitation number
36C25222B0022
Issued by

About this file

This document contains an asbestos survey report for Building 134 at the Captain James A. Lovell Federal Health Care Center in North Chicago, IL. The survey identified several asbestos containing materials throughout the building including floor tiles, ceiling tiles, mastic, pipe insulation, and transite boards. Regulated asbestos containing materials were found in quantities exceeding thresholds that require abatement under applicable EPA, OSHA and state regulations prior to any renovation that could disturb the materials. The report provides location details and quantity estimates of identified asbestos containing materials to inform future abatement work. It also outlines regulatory requirements and limitations of the survey.

View the file

Other files

File Type Posted
36C25222B0022 0003.docx DOCX document
S06 36C25222B0022 0003 Att3_SOL_Att08 556-20013 VAAR 852.219-77 Certification.pdf PDF
S06 36C25222B0022 0003 Att5_Spec 015719 - Temporary Environmental Controls.pdf PDF
S06 36C25222B0022 0003 Att1_Roof Warranties Bldg 134 B135 B187.pdf PDF
S06 36C25222B0022 0003 Att2_Roof Warranty Bldg 134 Courtyard 3 season metal roof.pdf PDF
S06 36C25222B0022 0002 Att3 DWG E401-A - THIRD FLOOR FA PLAN - A WING.pdf PDF
S06 36C25222B0022 0002 Att2 DWG Pt Lift Details 11JUL22.pdf PDF
36C25222B0022 0002.docx DOCX document
S06 36C25222B0022 0002 Att4 DWG E401-C - THIRD FLOOR FA PLAN - C WING.pdf PDF
S06 36C25222B0022 0002 Att1 Spec 117300 Ceiling Mounted Pt Lift 12JUL22.pdf PDF
S06_36C25222B0022 0001 Att3 Wage Rates.R1 SAM IL20220008 2022.07.08.pdf PDF
S06_36C25222B0022 0001 Att2 Site Visit Sign-In-Sheet 2022.07.11.pdf PDF
36C25222B0022 0001.docx DOCX document
S06_36C25222B0022 0001 Att1 Site Visit Sign-In-Sheet 2022.07.05.pdf PDF
S02 Att06 556-20-013 Drawings Volume 4 of 4_2021.12.23.pdf PDF
S02 Att01 556-20-013 SPECS Volume 1 of 2_Rev2 2022.06.02.pdf PDF
S02 Att07 Wage Rates SAM IL20220020 2022.02.25 current as of 2022.06.28.pdf PDF
36C25222B0022_3.docx DOCX document
S02 Att03 556-20-013 Drawings Volume 1 of 4_2021.12.23.pdf PDF
S02 Att04 556-20-013 Drawings Volume 2 of 4_2021.12.23.pdf PDF
S02 Att05 556-20-013 Drawings Volume 3 of 4_2021.12.23.pdf PDF
S02 Att02 556-20-013 SPECS Volume 2 of 2_Rev2 2022.06.02.pdf PDF
Show all 22

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ASBESTOS & HAZMAT TESTING REPORT FOR 35% SD SUBMISSION

CAPT. JAMES LOVELL FED. HEALTH CARE CENTER

RENOVATE BUILDING 134 – WINGS 3A & 3C CLC

PROJECT 556-20-013

Date: May 25, 2021

Items: Summary Results of Asbestos & HazMat Survey and Cost Estimate

Inspector: Brett Brumbaugh, Castle Hill Associates

Findings: Asbestos and Universal Wastes are present in the work area No lead-based paint is present in the work area

ASBESTOS CONTAINING

MATERIALS

LOCATIONS QUANTITY

Pipe insulation on straight runs and elbows

Inaccessible wall chases for Bathroom A303, A310, Janitor Closet A312, and Lounge A316

~120 lf

Pipe insulation on mud fittings on fiberglass insulated piping

Roof drains in A301, A306, A314;

Inaccessible wall chases for Bathroom A303, A310, Janitor Closet A312, and Lounge A316

~ 36 fittings

Transite cement sheets behind recessed radiators

A301, A302, A304, A305, A306, A306A, A307, A309, A313, A316

12 each = 96 sf

UNIVERSAL WASTE MATERIAL LOCATIONS QUANTITY

Fluorescent light tubes A301, A302, A303, A304, A305, A306, A306A, A307, A308, A309, A310, A311, A312, A313, A316, and corridor

120 tubes

Batteries in exit lights Corridors 3 each

Estimator: Brett Brumbaugh

Notes: Based on 2022 construction and bidding (normal working hours)

EXCLUDES:

• Overtime or shift work.

INCLUDES:

• Bonds, insurance, contractor overhead and profit

• Prevailing wage rates for Chicago, IL

Cost Index: Chicago, IL

Description Material Quantity Unit Cost Amount

Section 02 82 11

Asbestos Removal Pipe insulation on straight runs and elbows 120 55.00 $6,600.00

Pipe insulation mud fittings 36 55.00 $1,980.00

Transite sheets 96 25.00 $2,400.00

OSHA Testing CPIH (day) 3 900.00 $2,700.00

VA VPIH Air Monitoring (day) 3 900.00 $2,700.00

Section 02 84 16

Tubes and Batteries 120 5.00 $600.00

TOTAL COSTS $16,980.00

ASBESTOS SAMPLING REPORT

for

N. CHICAGO, IL

PROJECT:

PROJECT 556-20-013

Assessment Date:

MAY 17, 2021

CONSULTANT:

CASTLE HILL ASSOCIATES, LLC

1197 FARNSWORTH RD., UNIT E

WATERVILLE, OH 43566

567-952-0212 www.CASTLEHILLASSOCIATES.com http://www.castlehillassociates.com/

TABLE OF CONTENTS

• ASBESTOS & LEAD PAINT SAMPLING SUMMARY

• ABESTOS BULK SAMPLING DESCRIPTIONS AND LAB RESULTS

• LEAD PAINT XRF READINGS AND RESULTS

• ASBESTOS LABORATORY REPORT

• ASBESTOS LABORATORY CERTIFICATIONS

• INSPECTOR CERTIFICATIONS

• PREVIOUS ASBESTOS SURVEY REPORT

ASBESTOS INSPECTION SUMMARY

On May 17, 2021, Brett Brumbaugh performed an asbestos survey prior to the gut-rehab renovation project in Building 135, 3rd Floor “A” Wing of the Capt. James Lovell Fed. Health Care Center in N.

Chicago, IL. Bulk samples were collected of suspect asbestos containing materials in the renovation area. Prior to this sampling, Castle Hill was provided with previous sampling results, and was informed that asbestos is known to be located in the pipe insulation and transite board in the “A” wing. There were 9 additional bulk samples taken as part of this survey with the materials identified in the report included in this submission.

Bulk sampling as part of this project was based upon the appearance, texture, and location of the suspect materials. All bulk samples were analyzed utilizing current EPA methods for PLM (Polarized Light Microscopy) by EMSL Analytical in Plymouth, MI. This lab is accredited by the NIST, NVLAP program (National Institute of Standards and Technology, National Voluntary Laboratory Accreditation Program) and also an American Industrial Hygiene Association (AIHA) accredited laboratory.

ASBESTOS INSPECTION FINDINGS

As a result of this inspection, current sampling, and previous surveys/sampling, it has been determined that asbestos containing materials are present in the renovation area of the building. As part of the planned renovations, these materials must be removed in accordance with current Federal, State, and Local asbestos regulations in addition to the VA standards and guidelines for asbestos removal.

LEAD-BASED PAINT FINDINGS

There was no lead-based paint identified in the renovation areas in the renovation areas.

UNIVERSAL WASTES FINDINGS

There were universal wastes identified in the renovation area (fluorescent light tubes and batteries in exit light fixtures).

Respectfully Submitted, Brett L. Brumbaugh, REPA, CESCO State of Illinois Asbestos Inspector - License # 100-09972 EPA Lead Paint Risk Assessor - EPA License # LBP-R-I216003-1 mjones Cloud+ mjones

ASBESTOS SAMPLING PROTOCOL

The bulk samples were collected from locations that were selected to be representative of the building materials. Sampling was accomplished using the simplified sampling scheme referenced in the AHERA regulations and found in the “Pink Book”. Locations of individual samples are referenced on this report.

The samples were either collected with a coring tool designed for asbestos sampling or placed into a plastic bag for laboratory analysis. The samples were analyzed via polarized light microscopy with dispersion staining, using the “Interim method for the Determination of Asbestos in Bulk Insulation Samples” found in Appendix A to Subpart F in 40 CFR Part 763.

The regulations require specific numbers of samples be obtained per homogeneous area. For example when sampling for joint compound or asbestos in hard plaster (sprayed-on or troweled-on surfacing materials) samples are to be taken based on the following increments: 0 to 1000 square feet of material, 3 samples are necessary. From 1001 to 5000 square feet, 5 samples are necessary, over 5000 square feet 7 samples are required. If during analysis any samples are found to contain asbestos, the entire homogeneous area is delineated as asbestos containing material. In the case of pipe insulation or other types of manufactured materials, the regulations require only enough samples to ascertain whether asbestos is present. In this case, the minimum amount of samples to collect and analyze is usually three.

The sampling performed in this inspection followed these sampling guidelines.

ASBESTOS GLOSSARY OF TERMS

Friable asbestos material: means any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 section 1, Polarized Light Microscopy, that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

Category I Non-friable Asbestos Containing Material (ACM) means asbestos containing packings, gaskets, resilient floor coverings, and asphalt roofing products containing more that 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, Section 1, Polarized Light Microscopy.

Category II Non-friable ACM means any material, excluding Category I non-friable ACM, containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy that when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

Regulated Asbestos Containing Material (RACM): means (a) Friable asbestos material, (b) Category I non-friable ACM that has become friable, (c) category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or (d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material expected in the course of demolition or renovation operations regulated by this subpart.

ASBESTOS BULK SAMPLE DESCRIPTIONS & RESULTS

Facility: Capt. James Lovell Fed. Health Care Center – N. Chicago, IL Project: 556-17-016 Renovate Building 135 for HR Area: Building 135, 3rd Floor, “A” Wing Sampling Date: May 17, 2021 Analysis Date: May 18, 2021 Laboratory: EMSL Analytical – Plymouth, MI Sampler: Brett Brumbaugh

SAMPLE

HA MATERIAL DESCRIPTION SAMPLE LOCATION LABORATORY

ANALYSIS RESULT

1 A Black tar behind transite in radiator areas 306 No Asbestos Detected

2 A Black tar behind transite in radiator areas 321 No Asbestos Detected

3 A Black tar behind transite in radiator areas 319 No Asbestos Detected

4 B Hard plaster (base & finish coats) Elevator lobby No Asbestos Detected

5 B Hard plaster (base & finish coats) A314 No Asbestos Detected

6 B Hard plaster (base & finish coats) A307 No Asbestos Detected

7 C Drywall joint compound A301 No Asbestos Detected

8 C Drywall joint compound Hallway by elevators No Asbestos Detected

9 C Drywall joint compound A309 No Asbestos Detected

Note: Asbestos containing materials are defined by containing greater than 1% asbestos.

mjones Cloud+ mjones Cloud+ mjones Cloud+ mjones

LEAD PAINT XRF TESTING DATA

Project: Capt. James Lovell VAMC - N. Chicago, IL

Project: Renovate Bldg. 134 - Wings 3A & 3C CLC 556-20-013

Inspector: Brett Brumbaugh

Date: 5/17/2021

XRF Mfg.: Viken Detection

Model: Pb200i

Type: XRF Lead Paint Analyzer

Serial # 2757

Reading # Building Area Component Paint Color Pb Conc.

mg/cm2 Result

1 3rd Fl. A Wing - Room A316 Metal door frame White -0.1 Negative

2 3rd Fl. A Wing - Room A316 Wood door White 0.2 Negative

3 3rd Fl. A Wing - Room A316 Plaster wall White 0.0 Negative

4 3rd Fl. A Wing - Room A316 Metal door frame White 0.6 Negative

5 3rd Fl. A Wing - Room A316 Metal radiator cover White 0.3 Negative

6 3rd Fl. A Wing - Room A316 Metal window trim White 0.0 Negative

7 3rd Fl. A Wing - Hall by A316 Metal door frame Tan 0.4 Negative

8 3rd Fl. A Wing - Hall by A316 Plaster wall White 0.0 Negative

9 3rd Fl. A Wing - Stairwell Metal door frame White 0.5 Negative

10 3rd Fl. A Wing - Stairwell Cinder block wall White -0.1 Negative

11 3rd Fl. A Wing - Room A311 Ceramic wall tile White 0.1 Negative

12 3rd Fl. A Wing - Lobby Drywall wall White 0.1 Negative

13 3rd Fl. A Wing - Room A308 Metal door White -0.2 Negative

14 3rd Fl. A Wing - Room A306 Plaster wall White 0.2 Negative

15 3rd Fl. A Wing - Elevator Lobby Ceramic wall tile White 0.2 Negative

16 3rd Fl. A Wing - Elevator Lobby Wood door White 0.0 Negative

ASBESTOS LABORATORY REPORT

EMSL Analytical, Inc.

15111 Northville Rd Plymouth, MI 48170

Tel/Fax: (734) 668-6810 / (734) 668-8532 http://www.EMSL.com / annarborlab@emsl.com

082101182EMSL Order:

Customer ID: CHAS42

Customer PO: VA

Project ID:

Attention: Phone:Brett Brumbaugh (567) 952-0212

Fax:Castle Hill Associates, LLC

Received Date:218-A Mechanic St. 05/18/2021 10:30 AM

Analysis Date:Waterville, OH 43566 05/18/2021

Collected Date:

Project: JAMES LOVELL VA - BLDG. 134

Test Report: Asbestos Analysis of Bulk Materials via EPA 600/R-93/116 Method using Polarized

Light Microscopy

Sample Description Appearance % Fibrous % Non-Fibrous

Non-Asbestos Asbestos

% Type

082101182-0001

None DetectedNon-fibrous (Other)84%Cellulose16%Black

Fibrous

Homogeneous

Tar

082101182-0002

None DetectedNon-fibrous (Other)84%Cellulose16%Black

Fibrous

Homogeneous

Tar

082101182-0003

None DetectedMica

Non-fibrous (Other)

5%

95%

White

Non-Fibrous

Homogeneous

Plaster

082101182-0004

None DetectedMica

Non-fibrous (Other)

4%

96%

White

Non-Fibrous

Homogeneous

Plaster

082101182-0005

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Texture

082101182-0005A

None DetectedMica

Non-fibrous (Other)

3%

97%

White

Non-Fibrous

Homogeneous

Joint Compound

082101182-0006

None DetectedNon-fibrous (Other)100%White

Non-Fibrous

Homogeneous

Texture

082101182-0006A

None DetectedMica

Non-fibrous (Other)

2%

98%

White

Non-Fibrous

Homogeneous

Joint Compound

Analyst(s)

Conner Frymier (8) Ryan Shannon, Laboratory Manager or Other Approved Signatory

EMSL maintains liability limited to cost of analysis . Interpretation and use of test results are the responsibility of the client. This report relates only to the samples reported above, and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations . The report reflects the samples as received.

Results are generated from the field sampling data (sampling volumes and areas, locations, etc.) provided by the client on the Chain of Custody. Samples are within quality control criteria and met method specifications unless otherwise noted. The above analyses were performed in general compliance with Appendix E to Subpart E of 40 CFR (previously EPA 600/M4-82-020 “Interim Method”) but augmented with procedures outlined in the 1993 (”final”) version of the method. This report must not be used by the client to claim product certification, approval, or endorsement by NVLAP, NIST or any agency of the federal government. Non- friable organically bound materials present a problem matrix and therefore EMSL recommends gravimetric reduction prior to analysis . Unless requested by the client, building materials manufactured with multiple layers (i.e. linoleum, wallboard, etc.) are reported as a single sample. Estimation of uncertainty is available on request.

Samples analyzed by EMSL Analytical, Inc. Plymouth, MI NVLAP Lab Code 101048-4

Initial report from: 05/19/2021 09:21:02

Page 1 of 1ASB_PLM_0008_0001 - 1.78 Printed: 5/19/2021 9:21 AM

OrderID: 082101182

LABORATORY CERTIFICATIONS

INSPECTOR CERTIFICATIONS

PREVIOUS ASBESTOS SURVEY REPORT

Tropical Environmental, Inc.

10976 Fairbluff Ave.

Huntley, IL. 60142

(224) 569-3277 (224) 569-3278 fax www.TropicalEnvironmental.com

December 19, 2011

Mr. Royal Eckstein Captain James A. Lovell FHCC 3001 Green Bay Road North Chicago, Illinois 60064

RE: U.S. Department of Veterans Affairs (VA)

Captain James A. Lovell Federal Health Care Center Building # 134

Dear Mr. Eckstein:

Tropical Environmental, Inc. (Tropical) performed a limited asbestos assessment of the above referenced location in general accordance with:

• The Commercial and Public Buildings Asbestos Abatement Act (225 ILCS 207) enforced by the Illinois Department of Public Health (IDPH)

• The Asbestos Hazard Emergency Response Act (40 CFR 763) enforced by the U.S.

Environmental Protection Agency (USEPA), and

• The Asbestos Hazard Communication requirements (29 CFR 1910.1001(i) enforced by the U.S. Occupational Safety and Health Administration (OSHA).

Tropical performed the limited survey to identify and sample suspect asbestos-containing materials (ACM) in the facility. Samples of suspect asbestos-containing material (ACM) were submitted to a National Voluntary Laboratory Accreditation Program (NVLAP) certified laboratory for analysis. Laboratory results indicate that some of the suspect material contains asbestos. Please refer to the attached report for details on the survey.

Please feel free to contact me at (224) 269-3277 or by email at info@tropicalenvironmental.com with any comments or questions regarding Tropical’s investigation and this report.

Sincerely, Mark Haines President mailto:info@tropicalenvironmental.com

Table of Contents Page

Executive Summary

1.1 Project Purpose and Background

2.0 Asbestos Survey

2.1 Asbestos Survey Methodology

2.2 Asbestos Results

2.3 Applicable Regulations

3.0 Findings and Recommendations

4.0 Limitations

5.0 References & Definitions

Appendices

Appendix A: Asbestos Survey Analytical Summary Table Appendix B: Asbestos Laboratory Results, Laboratory Certifications and Chain-of-Custodies Appendix C: Tropical Employee Certifications Appendix D: Material/Sample Location Drawings Appendix E: Photographs of ACM Positives

Asbestos Survey

Building # 134 North Chicago, IL www.TropicalEnvironmental.com

Executive Summary

Tropical Environmental, Inc. (Tropical) was retained by the VA to provide an Asbestos Survey of all buildings, as defined by VA representatives, located on the Captain James A. Lovell Federal Health Care Center Campus in North Chicago, IL. The field assessment and sampling was performed from July 19, 2011 to October 5, 2011.

Building 134 is a brick clad, three story structure with a basement. The building was constructed in 1961 and used as nursing home care. The building has approximately 120,000 square feet of floor space. Suspect fire-doors were noted throughout and shall be presumed ACM.

Tropical performed a visual survey of building materials and collected representative samples of homogeneous suspect ACM, in accordance with EPA requirements, guidelines and standard industry practices. The samples were submitted to a National Voluntary Laboratory Accreditation Program (NVLAP) accredited laboratory for bulk analysis.

This report addresses the asbestos survey completed for Building #134.

Based on the bulk sampling and laboratory analyses, suspect materials were reported to contain asbestos, including the following:

HSA

Sample

Material Description

Material Condition

Material Quantity

Material Location

Laboratory Results

FT3

9”X9”

BROWN

W/TAN

STREAKS

FLOOR TILE

AND

ASSOCIATED

MASTIC

NONFRIABLE

77 SF

CLOSETS IN

C3, C6, C7, C16L, A6B, AND OUTSIDE

A1

PC 1.3%- PC

2.4 %

CHRYSOTILE

http://www.tropicalenvironmental.com/

Building # 134 www.TropicalEnvironmental.com

HSA

Sample

Material Description

Material Condition

Material Quantity

Material Location

Laboratory Results

FT7

9”X9” BLACK

W/WHITE

STREAKS

FLOOR TILE

AND

ASSOCIATED

MASTIC

NONFRIABLE

307 SF ROOM C2

PC 1.3%- PC

4.4%

CHRYSOTILE

LN1

BLUE

SPLOTCHY

LINOLEUM

NONFRIABLE 1100 SF ROOM B2A 0.3%-9.2%

CHRYSOTILE

PF

HARD

FITTINGS ON

FIBERGLASS

FRIABLE

UNABLE

TO

QUANTIFY

THROUGHOUT

10%

CHRYSOTILE

10%

AMOSITE

PI PIPE

INSULATION FRIABLE

UNABLE

TO

QUANTIFY

TRHOUGHOUT

CRAWLSPACE

PC TRACE -

30%

Based on the bulk sampling and laboratory analyses, suspect materials were reported to contain asbestos at less than 1%, including the following:

HSA

Sample #

Material Description

Material Condition

Material Quantity

Material Location

Laboratory Results

FT2

12”X12” OFF

WHITE

W/BROWN

SPLOTCHES

FLOOR TILE

NONFRIABLE 7191 SF BASEMENT

CORRIDORS

<0.25% - 0.3%

CHRYSOTILE

VF

BROWN

VINYL

FLOOR WITH

DOT

PATTERN

NONFRIABLE

1200 SF

ROOMS

A14,C12

CORRIDOR

NEXT TO C4

0.3%

Building # 134

Photographs of the ACM are included in Appendix E.

Every attempt was made to thoroughly evaluate and assess the presence and condition of suspect ACM throughout the building. Any suspect ACM identified during renovation that is not specifically listed in this report should be assumed positive until it can be thoroughly evaluated, assessed, sampled, and analyzed prior to disturbance, in accordance with applicable regulatory standards.

Building # 134 www.TropicalEnvironmental.com

1.0 Introduction

Tropical Environmental, Inc. (Tropical) was retained by the VA to provide an Asbestos Survey of all buildings, as defined by VA representatives, located on the Captain James A. Lovell Federal Health Care Center Campus in North Chicago, IL. The field assessment and sampling was performed from July 19, 2011 to October 5, 2011.

This report addresses the asbestos survey completed for Building #134.

The asbestos survey was performed by Illinois Department of Public Health (IDPH) licensed asbestos inspectors Mr. Mark Haines, license #100-00919, and Ms. Terri Lewis, license #100- 07366.

1.1 Project Purpose and Background

The asbestos survey was conducted to identify accessible asbestos containing materials in the building.

1.2 Scope of Work

Tropical performed an asbestos survey to determine and quantify ACM in accessible areas. The ACM survey included the following activities:

• Visual inspection of all accessible areas of the building, as identified by VA representatives to be included in the scope of this project.

• Collection of bulk samples of identified suspect ACM per homogeneous materials in accessible areas of the building.

• NVLAP accredited laboratory analysis of suspect ACM bulk samples by polarized light microscopy (PLM) to first positive result per homogeneous material.

• Preparation of a final report that includes sample locations of representative ACM and the laboratory’s analytical report.

Building # 134 www.TropicalEnvironmental.com

2.0 Asbestos Survey

2.1 Asbestos Survey Methodology

Only currently certified and licensed inspector(s) and (if appropriate) trainee(s) were utilized for this inspection.

The inspector(s) first reviewed supplied building documents, if applicable, which may have included the asbestos management plan, previous inspection reports, blue prints, and as built drawings, etc. A property/structure(s) walk-thru was then conducted to locate, identify, measure and separate previously identified asbestos containing materials and suspect asbestos containing materials into homogeneous areas. The material’s current condition was also evaluated during the walk-thru. Material conditions were evaluated utilizing the following terminology, Good, Damaged & Significantly Damaged.

Samples were collected using EPA approved methods specifically designed for sample collection. Samples were taken utilizing the randomly distributive manner method while simultaneously applying amended water. Samples were immediately placed in a pre-labeled re-sealable plastic bag. To prevent accidental exposure, sample containers are made of a durable plastic designed to provide and airtight seal. The sampling instrument was subsequently wiped with a clean moist cloth to decontaminate the tool, prevent the potential release of asbestos fibers, and prevent cross contamination of subsequent samples. Following the collection of each sample, the sample location was patched as appropriate. Sample areas were touched to determine friability.

The following chart, as detailed by 40 CFR 763.86, is typically used (and in certain cases, required) for sampling surfacing building materials for asbestos content:

< 1000 s/f 3 samples 1000 – 5000 s/f 5 samples >5000 s/f 7 samples

9 samples are recommended by the EPA for all samples

A group letter or combination of letter and number was assigned to each homogenous material.

This combination serves as a prefix to identify materials of similar composition, texture, color, and date of installation. Each sample was then assigned a sample number such as 01, 02, 03, etc.

All samples were identified on a signed and dated Chain-of-Custody document, which accompanied the samples to the laboratory.

Building # 134

To ensure both quality and objectivity, an independent laboratory was used. Laboratories are selected based on their current accreditations. The laboratory chosen participates in the National Voluntary Laboratory Accreditation Program (NVLAP) for quality control procedures (NVLAP Lab Code: 101202-0). As specified in 40 CFR Chapter I (1-1-87 edition) Part 763, Subpart F, Appendix A.

Suspected asbestos samples were analyzed using polarized light microscopy (PLM) / dispersion staining techniques in accordance with the EPA Method documents “US EPA 600/M4-82-020, 1982” & “US EPA 600/R-93/118, 1993”. Detection limits for this type of analysis are approximately one percent (by volume). All samples were analyzed by International Asbestos Testing Laboratories of Mt. Laurel, New Jersey (IATL), a National Voluntary Laboratory Accreditation Program (NVLAP) accredited asbestos laboratory. Laboratory accreditations are provided in Appendix B.

Some materials may not be accurately identified and/or quantified by PLM. As an example, the original fabrication of vinyl floor tile routinely involved milling of asbestos fibers to extremely small sizes. As a result, these fibers may go undetected under the standard PLM method.

Transmission Electron Microscopy (TEM) is required for a more definitive analysis of these materials. These types of flooring materials that are reported by laboratory analysis to be non-asbestos by PLM analysis are routinely submitted to an accredited laboratory for analysis under TEM for verification of asbestos content. One hundred and fifty-eight (158) samples were tested with TEM analysis for this building.

2.2 Asbestos Results

ASBESTOS CONTAINING MATERIALS

Suspect asbestos containing materials were identified and sampled in accordance with the above-referenced survey methodology. Laboratory results for suspect materials that were identified and sampled are included in Appendix A, entitled “Table I, Asbestos Survey Analytical Summary.”

Please reference the material location included on the drawings provided in Appendix D.

According to the AHERA Model Accreditation Plan, non-suspect material such as fiberglass, foam rubber and plastics do not warrant sampling.

2.3 Applicable Regulations

EPA's National Emission Standard for Hazardous Air Pollutants (NESHAP) (40 CFR 61, Building # 134 www.TropicalEnvironmental.com

Subpart M) categorizes asbestos-containing thermal system insulation (TSI) and sprayed-on or troweled-on asbestos as regulated ACM (RACM). Miscellaneous materials (floor tile and floor tile mastic) are classified as Category I Non-Friable Asbestos; and transite material is classified as Category II Non-Friable Asbestos, unless the material is made friable during demolition.

Friable ACM is material that can be crumbled, pulverized, or reduced to a powder by hand.

NESHAP requires at least ten working days’ notification prior to any renovation or demolition activity that will disturb greater than 160 square feet or 260 linear feet of ACM materials. ACM removed during abatement must be disposed of at a landfill approved by the EPA to receive asbestos wastes. NESHAP states that regulated asbestos-containing material (RACM), including friable ACM and non-friable ACM that has become or has a high probability of becoming friable, present in quantities exceeding 260 lineal feet on pipes or 160 square feet on facility components must be removed prior to the commencement of any demolition activities.

NESHAP also states that Category 1 non-friable ACM does not need to be removed prior to demolition if it is not in poor condition and has become friable. Friable materials (with the exception of roofing products) and transite are typically required to be removed prior to a demolition. Asbestos containing floor tile and mastic are typically required to be removed from concrete prior to recycling. Agencies such as Cook County require all asbestos containing materials be removed prior to demolition. If a facility is demolished by intentional burning, all regulated asbestos containing materials including Category I and Category II non-friable ACM must be removed before burning.

The Occupational Safety and Health Administration (OSHA) Construction Industry Standard (29 CFR 1926.1101) categorizes the removal of asbestos containing materials by “class” of material.

Specific requirements for the removal of OSHA classified materials include, but are not limited to, regulated work areas, air monitoring, engineering controls, work practices, personal protective equipment, notification and training.

The U.S. Department of Transportation (DOT) requires special procedures for packaging, labeling and transportation of asbestos wastes to disposal facilities. Other regulations may apply depending upon the contractor’s means and methods.

Tropical recommends the use of certified and licensed asbestos personnel for all planned disturbance of known and suspect asbestos containing products. In accordance with IDPH, IEPA, U.S.EPA and OSHA regulations asbestos containing materials must be removed by and disposed of by a certified/licensed asbestos abatement personnel/contractor.

Building # 134

3.0 Findings and Recommendations

Suspect materials identified, sampled and analyzed as part of this survey were reported to contain asbestos in regulated quantities.

Materials identified in this report as ACM must be handled in accordance with applicable regulations as provided herein, and must be abated if they will be impacted by any planned renovation activity.

The owner or operator of a demolition or renovation activity and prior to the commencement of the demolition or renovation shall thoroughly inspect the affected facility or part of the facility where the demolition or renovation operation will occur for the presence of asbestos, including Category I and Category II non-friable ACM.

It shall be at the owner’s discretion that a copy of this report is provided to any contractor bidding on work in the area(s) covered by this assessment. The owner may also elect to provide a copy of the report to the contractor on site during any renovation and/or demolition activities.

Contractors should use caution and be advised and directed that during renovation or demolition of a structure that concealed materials may be discovered, therefore, should suspect materials not identified in this inspection become exposed or made aware, you should cease operations that may disturb, dislodge or disrupt the material until it is sampled and analyzed for its possible asbestos content.

Although the efforts and intentions of our inspector(s) are always to sample all suspect materials, due to the nature of sampling, (destructive sampling, limited sample locations, visual assumption, etc.) some materials (such as floor tile/linoleum mastic/adhesive) may be excluded from the sampling process. These materials shall be assumed positive for asbestos unless sampled and analyzed otherwise. The client assumes and retains all responsibility and authority to conduct further sampling and analysis at their expense.

If additional suspect asbestos containing materials are identified during the renovation, those materials should be assumed to be positive for asbestos until they can be assessed, sampled, and analyzed by a NVLAP accredited laboratory.

Building # 134 www.TropicalEnvironmental.com

4.0 Limitations

The conclusions of this report are Tropical’s professional opinions, based solely upon visual site observations and interpretations of laboratory analyses, as described in this report. The opinions presented herein apply to the site conditions existing at the time of Tropical’s investigation and interpretation of current regulations pertaining to asbestos. Therefore, Tropical’s opinions and recommendations may not apply to future conditions that may exist at the site, which we have not had the opportunity to evaluate. It should be noted that conditions change and that materials constantly degrade. All applicable federal, state and local regulations should always be verified prior to any work that will disturb or dislodge materials confirmed, assumed or presumed to contain asbestos, Tropical’s assessment was limited to observation, sampling and the analysis of suspect asbestos containing products in accessible portions of the area(s) covered by this survey. Materials in the building that are not considered building materials, are unusual or de minimis, or were inaccessible, due to common construction techniques, to the inspector were excluded from the inspection. As a result, additional asbestos containing building materials may be present in inaccessible areas (e.g. between walls, ceiling spaces enclosed by wallboard, interior of fire doors, etc.) of the structure that were not observed during the survey.

This inspection report is designed to assist the client in the understanding of the regulations regarding asbestos, however, it should not be used as a substitution for obtaining and familiarizing yourself with, including the compliance of, all asbestos related regulations including, but not limited to, 40 CFR, Chapter 61, Subpart M (National Emission Standard for Asbestos) prior to the start of any renovation or demolition activity that will disturb or dislodge asbestos containing materials or suspect/assumed asbestos containing materials.

This report has been prepared for the exclusive use of the intended client, for the specific application to the defined property as addressed in this report. Any additional user of this report shall determine the suitability of the material contained herein for their intended use, and any such user assumes all risks and liability in connection therewith. No claim is made that these findings will remain applicable to future site activities and conditions. Interpretations by any such user from information contained in this report or the drawing of conclusions by any such user from information contained in this report shall be undertaken solely at the risk of said party.

At all times during the performance of the inspection, safety was a priority. Due to the emphasis on safety, there were no injuries, there was no building contamination, and there were no asbestos exposures to either Tropical Environmental, Inc personnel or building occupants.

Building # 134 www.TropicalEnvironmental.com

The asbestos survey was conducted in a manner consistent with that level of care and skill ordinarily exercised by members of the environmental profession under similar conditions. No other warranty or guarantee, express or implied, is included or intended in this Report or otherwise.

Building # 134 www.TropicalEnvironmental.com

5.0 References & Definitions

Illinois Department of Public Health (IDPH)

Asbestos Abatement Act, 105 ILCS 105

Asbestos Abatement for Public and Private Schools and Commercial and Public Buildings in Illinois, 77 Illinois Administrative Code 855

Commercial and Public Building Asbestos Abatement Act, 225 ILCS 207

United States Environmental Protection Agency (USEPA)

Asbestos Hazard Emergency Response Act (AHERA), 40 CFR, Part 763

National Emission Standards for Hazardous Air Pollutants (NESHAP), Asbestos, 40 CFR, Part 61, November 20, 1990

Guidance for Controlling Asbestos-Containing Materials in Buildings (EPA 560/5-85/024), June

Illinois Environmental Protection Agency (IEPA)

Emission Standards and Limitations for Stationary sources, Asbestos 35 IAC, Part 228

United States Occupational Safety and Health Administration (OSHA)

Occupational Exposure to Asbestos, Final Rule, 29 CFR, Pars 1910 and 1926 (August 10, 1994)

Cook County Department of Environmental Control (CCDEC)

Cook County Environmental Control Act

Asbestos Containing Products means, according to the U.S. EPA Method 600/R-93/116, Regulated Asbestos Containing Materials (RACM) are those materials found to contain greater than 1% asbestos per volume of bulk material sampled, by PLM. The term is not intended to include de minimis or inaccessible materials that do not present a risk of harm to public health and that generally would not be the subject of enforcement actions if brought to the attentions of appropriated regulatory agencies.

Building # 134

Asbestos Types are Chrysotile (white asbestos making up approximately 95% of all asbestos used in the United States), Amosite (brown asbestos making up approximately 5% of all asbestos used in the United States), Crocidolite (blue asbestos making up approximately less than 5% of all asbestos used in the United States), and rarely found in buildings are Anthophyllite, Tremolite & Actinolite.

Category I Non-friable Asbestos-Containing Material (ACM) means asbestos-containing packing, gaskets, resilient floor covering, and asphalt roofing products containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy.

Category II Non-friable ACM means any material, excluding Category I nonfriable ACM containing more than 1 percent asbestos as determined using the methods specified in appendix E, subpart E, 40 CFR part 763, section 1, Polarized Light Microscopy that, when dry, cannot be crumbled, pulverized, or reduced to powder by hand pressure.

Damaged means less than 25% localized damage or less than10% distributed damage.

Demolition means the wrecking or taking out of any load-supporting structural member of a facility together with any related handling operations or the intentional burning (i.e. practice burns) of any facility.

Facility means any institutional, commercial, public, industrial, or residential structure, installation, or building (including any structure, installation, or building containing condominiums or individual dwelling units operated as a residential cooperative, but excluding residential buildings having four or fewer dwelling units); any ship; and any active or inactive waste disposal site. For purposes of this definition, any building, structure, or installation that contains a loft used as a dwelling is not considered a residential structure, installation, or building. Any structure, installation, or building that was previously subject to the Asbestos NESHAP is not excluded, regardless of its current use or function.

Friable Asbestos Material means any material containing more than 1 percent asbestos as determined using the method specified in appendix E, subpart E, 40 CFR part 763 section 1, Polarized Light Microscopy, that, when dry, can be crumbled, pulverized, or reduced to powder by hand pressure.

Homogeneous Area -- an area of surfacing materials, thermal surface insulation, or miscellaneous material that is uniform in color and texture and has the same installation date.

Miscellaneous Material means interior building material on structural components, structural members or fixtures, such as floor and ceiling tiles, and does not include surfacing material or thermal system insulation.

Multi-layered Material means a material that has a presence of discrete individual layers. EPA does not

Building # 134 www.TropicalEnvironmental.com regard a sheet of “plasterboard,” sheetrock,” “wallboard,” or “gypsum board” by itself a multi-layered material.

Polarized Light Microscopy means an optical microscopy technique for analyzing bulk samples for asbestos in which the sample is illuminated with polarized light (light which vibrates in only one plane) to distinguish between different types of asbestos fibers by their shape and unique optical properties.

Potential Significant Damage means circumstances in which:

1) Friable ACBM is in an area regularly used by building occupants, including maintenance personnel, in the course of their normal activities.

2) There are indications that there is a reasonable likelihood that the material or its covering will become significantly damaged, deteriorated, or delaminated due to factors such as changes in building use, changes in operations and maintenance practices, changes in occupancy, or recurrent damage.

3) The material is subject to major or continuing disturbance, due to factors including, but not limited to, accessibility or, under certain circumstances, vibration or air erosion.

Regulated Asbestos-Containing Material (RACM), as defined in 40 CFR 61.141, means

(a) Friable asbestos material,

(b) Category I non-friable ACM that has become friable,

(c) Category I non-friable ACM that will be or has been subjected to sanding, grinding, cutting, or abrading, or

(d) Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder by the forces expected to act on the material in the course of demolition or renovation operations.

Renovation means altering a facility or one or more facility components in any way, including the stripping or removal of Regulated Asbestos Containing Materials (RACM) from a facility component. A renovation could be, but not limited to, any interior renovation or remodel not affecting load-supporting structural members or a roof replacement.

Significantly Damaged means 25% (or greater) localized damage or 10% (or greater) distributed damage.

Surfacing means any material that was sprayed-on or troweled-on, or otherwise applied to surfaces, such as acoustical plaster on ceilings and fireproofing materials on structural members, or other materials on surfaces for acoustical, fireproofing, or other purposes.

Thermal Systems Insulation means material applied to pipes, fittings, boilers, breeching, tanks, ducts, or other interior structural components to prevent heat loss or gain, or water condensation, or for other purposes.

Building # 134 www.TropicalEnvironmental.com

Transmission Electron Microscopy means a method of microscopic analysis, which utilizes an electron beam that is focused onto a thin sample. As the beam penetrates (transmits) through the sample, the difference densities produces an image on a fluorescent screen from which samples can be identified and counted. Also used for analyzing air samples for asbestos.

Key to Common Asbestos Related Abbreviations

ACM ........................................ Asbestos-Containing Material

ACBM ................................. Asbestos-Containing Building Material

AHERA............................. Asbestos Hazard Emergency Response Act

CFR ..........................................Code of Federal Regulations

DOT ......................................... Department of Transportation

EPA ..................................... Environmental Protection Agency

FR ................................................... Federal Register

HEPA ....................................... High Efficiency Particulate Air

HVAC ....................... Heating, Ventilating and Air Conditioning Systems

IDPH ................................... Illinois Department of Public Health

LEA ............................................. Local Education Agency

MAP ............................................ Model Accreditation Plan

NESHAP ............... National Emission Standards for Hazardous Air Pollutants

NIOSH ...................... National Institute of Occupational Safety and Health

NIST .......................... National Institute for Standards and Technology

NVLAP .................... National Voluntary Laboratory Accreditation Program

OSHA .......................... Occupational Safety and Health Administration

APPENDIX A

Asbestos Survey Analytical Summary

INSPECTORS: Terri Lewis and Mark Haines

DATE: 8/4/2011

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

1 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

Room C1

Room C10

Room C11

Room B3

Room A301

Corridor outside Room B3A corridor outside Room A12

Corridor outside Room A14

Corridor outside Room A2

Corridor outside Room A5

Corridor outside Room A6B

Corridor outside Room C9A

NAD

Room B3A

Room A13A

Room C13

Room A309

Ceiling tile, 2x4 (2x2 pattern), sm. Fissures/ho

Carpet Adhesive, blue carpet

Carpet Adhesive, orange carpet

Carpet Adhesive, blue, green & purple carpet

MMCT1

X

CA2 MM

CA3 MM

CONDITION

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

ASBESTOS RESULTSMATERIAL TYPE

CA1 MM Carpet Adhesive, gold carpet Room A13

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

HSA ID

CA4 MM

Notes

FRIABILITY ACCESS

ASSESSMENT

CATEGORY

Quantity

NAD

NAD

X

X

X

NAD

NAD

X

X

X

X

X

X X

X

X

X

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

2 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

CONDITION

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

6 = ACBM with potential for significant damage.

ASBESTOS RESULTSMATERIAL TYPE

MATERIAL DESCRIPTION & DRAWING

MAP INDICATOR SYMBOL

HSA ID Notes

FRIABILITY ACCESS

ASSESSMENT

CATEGORY

Quantity

Room A13

Room A13A

Room B13B

Room B3B

NAD

NAD

NADRoom C100

NAD

Room A13A

Room A6

Room A6

Ceiling tile, 2x4, fissured/dots

Ceiling tile, 1x1, white w/ holes

CT6

MMCT2

CT5

Ceiling tile, 2x2, white, smooth

MM Ceiling tile, 2x4, deep fissured

Room C2

Room C15B

NAD

Ceiling tile, 1x1, white w/ fissures (patch) NAD

Ceiling tile, 1x1, white, rough

XCT7 MM

CT4 MM

CT3 MM

MM

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

3 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

CONDITION

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

HSA ID Notes

FRIABILITY ACCESS

ASSESSMENT

CATEGORY

Quantity

Corridor outside Room A105

Corridor outside Room C123

Corridor outside Room C120

Corridor outside Room C115

Brown/silver foil paper

Room C108

Room C117

Closet outside Room A1

Room A1

NAD

NAD

Room A1

Ceiling tile, 2x2, textured rough

Room A2

Fire Stopping

Corridor outside Room C106

DI Duct insulation (horse hair/canvas cover)

Ceiling tile, 2x2, textured rough

MM

EBM MM

MM

FS

NAD

NAD

Room A305

CT8 MM

Exposed baseboard mastic

X

X

X

X

X

X

X

X

X

X

X

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

4 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

CONDITION

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

HSA ID Notes

FRIABILITY ACCESS

ASSESSMENT

CATEGORY

Quantity

Outside elevators across from Room A11

Corridor outside Room C3

Corridor outside Room C15A

Yellow mastic

Room C1

Yellow mastic

Floor tile, 12x12, off white, brown splotches

Yellow mastic

Floor tile, 12x12, blue splotchy Chrysotile - Trace Detected @ <0.25% - Per TEM report

Tan mastic

Corridor outside Room C6

Corridor outside Room A14

Tan mastic

Floor tile, 12x12, blue splotchy

Tan mastic

Corridor outside Room C16 Chrysotile - 0.3% Per TEM report

Corridor outside Room C14 NAD

Floor tile, 9x9, brown w/ tan streaks Chrysotile - PC 2.3%

Black mastic Chrysotile - PC 1.2%

Floor tile, 9x9, brown w/ tan streaks Chrysotile - PC 2.1%

Black mastic Chrysotile - PC 1.3%

Floor tile, 9x9, brown w/ tan streaks Chrysotile - PC 2.4%

Black mastic Chrysotile - PC 1.3%

77 sf

7,191 sf

Floor tile, 12x12, blue splotchy

Floor tile, 12x12, off white, brown splotches

4MMFT2

FT1 MM

Floor tile, 12x12, off white, brown splotches

Floor tile, 12x12, blue splotchy

MMFT3

Corridor outside Room A9

Corridor outside Room C1

Corridor outside Room C12

Room A2

Corridor outside Room A6A

Corridor outside Room C17A

NAD

Corridor outside Room C16C

Closet outside Room A1

NAD

X

X

X

X

X

X

X

X

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

5 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

CONDITION

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

HSA ID Notes

FRIABILITY ACCESS

ASSESSMENT

CATEGORY

Quantity

Floor tile, 12x12, bright light blue splotchy

Tan mastic

Tan mastic

Floor tile, 9x9, black, w/ white streaks Chrysotile - PC 4.1%

Black mastic Chrysotile - PC 2.1%

Floor tile, 9x9, black, w/ white streaks Chrysotile - PC 3.8%

Black mastic Chrysotile - PC 1.3%

Floor tile, 9x9, black, w/ white streaks Chrysotile - PC 4.4%

Black mastic Chrysotile - PC 1.5%

Floor tile, 12x12, green w/ white stripes

Tan mastic

Floor tile, 12x12, green w/ white stripes

Tan mastic

Floor tile, 12x12, green w/ white stripes

Tan mastic

Floor tile, 12x12, off white w/ multi colored spe

Tan mastic

Floor tile, 12x12, off white w/ multi colored spe

Tan mastic

Floor tile, 12x12, off white w/ multi colored spe

Tan mastic

Floor tile, 12x12, bright light blue splotchy

MM

NAD

NAD

NADFT9 XRoom C114 X 5

FT8

307 sfRoom C2

Room C62MM

FT7 MM

FT6 MM

Room A4

Room A3

X

X

X

X

X

X

X

X

X

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

6 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low 2-Medium 3-High NAD - No Asbestos Detected

1 2 3 4 N F 1 2 3

CONDITION

7 = Any remaining friable ACBM or friable suspected ACBM.

1 = Damaged or significantly damaged TSI ACM. 3 = Significantly damaged friable surfacing ACM.

SAMPLE # MATERIAL SAMPLE LOCATION

CONDITION: 1-No damage 2-Slighly Damaged 3-Damaged 4-Significantly Damaged

5 = ACBM with potential for damage.

2 = Damaged friable surfacing ACM. 4 = Damaged or significantly damaged friable miscellaneous ACM.

MATERIAL TYPE: Thermal System Insulation (TSI), Surfacing Material (SM), Miscellaneous Material (MM)

AHERA Assessment Categories:

HSA ID Notes

FRIABILITY ACCESS

ASSESSMENT

CATEGORY

Quantity

Floor tile, 12x12, light tan splotchy

Tan mastic

Floor tile, 12x12, light tan splotchy

Tan mastic

Floor tile, 12x12, light tan splotchy

Tan mastic

Yellow mastic

Floor tile, 12x12, light green splotchy

Yellow mastic

Floor tile, 12x12, gray splotchy

Tan mastic

Corridor outside Room A312

Corridor outside Room B333

Corridor outside Room B332

Corridor outside Room B317

Room B313

Corridor outside Room A306

Linoleum, blue, splotchy Chrysotile - 9.2%

Tan mastic NAD

Chrysotile - 0.3%

Chrysotile - 8.3%

Chrysotile - 7.7%

Chrysotile - 9.2%

Floor tile, 12x12, gray splotchy

Linoleum, blue, splotchy

Floor tile, 12x12, light green splotchy

MM

FT11 MM

FT10 MM

FT12 NAD

Room C115

NAD

Room C115

Room B2A

NAD

Corridor outside Room A302

X Per TEM Results

X X

1,078 sfLN1 MM

X

X

X

X

X

X

X

X

X

TABLE 1

ASBESTOS SURVEY ANALYTICAL SUMMARY

BUILDING: 134

7 OF 11 Last Modified By: cwesthoff On: 12/13/11

KEY:

ACCESSIBILITY: 1-Low…

This is the start of the file's text. The full file is on GovTribe.