This document contains details regarding a federal contract opportunity for repair work at the Tomah VA Medical Center in Tomah, Wisconsin. The solicitation number is 36C25222B0017 and involves repairs to seal, tuck-point, replace the roof and exterior wood and venting, replace heat tape and gutter lines, and restore and paint the cupola of Building 400. The period of performance is 120 calendar days with an estimated price range between $2,000,000 and $5,000,000. This is a 100% service-disabled veteran-owned small business set-aside to be issued by the Department of Veterans Affairs Veterans Health Administration VISN 12. The pre-bid conference will be held after the solicitation is posted to SAM.gov on or around February 2, 2022, with bid opening scheduled for March 21, 2022.
View the file
Other files
Show all 14
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
No. RFI From COMMENT Response 39 Sam Klumpers Can a specification section for 23 09 be provided? (NOTE: this isn’t really essential if I get the following answered) 40 Sam Klumpers How many points are desired? Each heat tape should be a point.
41 Sam Klumpers Can existing controllers be used or will new controllers be required?
a. Will we need to provide new control panels or expansion modules?
Install new controllers in new panels.
42 Sam Klumpers Is control wiring done by the controls contractor? Yes, It needs to be done by the control contractor.
43 Sam Klumpers Who will furnish and install relays?
a. Will relays be in panels?
Electrical Contractor
44 Sam Klumpers How will snow and ice be detected?
a. Is one global sensor okay or is one required per section of heat tape?
b. It seems that more than just using outside air temperature is desired. Please confirm.
c. If snow sensors are required is there a certain standard/type that is desired? If so could a specification be provided for this?
d. If snow sensors are desired where would they be located? If near the heat tape how are they to be mounted? Could a detail be provided?
e. Is there any special conduit requirement for outdoors?
A. One global sensor is ok.
B. I would stick with just outdoor temp, activate heat tape anytime outdoor temp is below 36 degrees.
C. No snow sensors.
D. No snow sensors.
E. Any conduit installed outdoors needs to be rated for outdoor use along with connectors and boxes.
45 Sam Klumpers Will graphics be required? Yes, provide Graphics.
46 Sam Klumpers Will the standard extensive commissioning process be required? Yes 47 Sam Klumpers Will status of the heat tape be required? Yes, Provide status.
48 Sam Klumpers Will conduit for all control wiring be required? Yes, All control wire to be installed in conduit.
49 Sam Klumpers Who should the control contractor be bidding to?
a. Since there is no Mechanical Contractor (Division 23) should we be bidding directly to the GC?
Control contractor should bid to the GC.
Tomah VAMC Repair Water Intrusion B400 - 676-22-113 36C25222B0017 Pre-Bid RFIs