S06 - FA-001 Addendum 1.pdf

PDF 360 KB Posted

Attached to
Z1DA--537-19-101 Taylor Elevator Modernization Federal contract opportunity
Solicitation number
36C25220R0063
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12

About this file

This document includes fire alarm system design drawings and notes for an elevator modernization project at a Department of Veterans Affairs medical center. Key details include specifications for a new addressable fire alarm system to be installed that integrates with the existing Siemens system and complies with NFPA standards. The drawings provide a fire alarm riser diagram, device locations, and interface requirements between the fire alarm and elevator control systems. Detector types and locations are indicated for elevator hoistways, machine rooms, and lobbies. Interface relays are specified for primary elevator recall, alternate recall, emergency signaling, and disconnect of main power. The related federal contract opportunity is solicitation number 36C25220R0063 for elevator modernization work at the Jesse Brown VA Medical Center in Chicago, with responses due on February 12, 2020.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--537-19-101 Taylor Elevator Modernization, newest first.
File Type Posted
36C25220R0063_8.docx DOCX document
36C25220R0063 0003.docx DOCX document
S06 - Specs 000115 List of Drawings.pdf PDF
36C25220R0063_7.docx DOCX document
S06 - Addendum1.pdf PDF
S06 - Specs 024119 SelectiveDemolition.pdf PDF
S06 - A-402_Addendum 1.pdf PDF
S06 - A-601_Addendum 1.pdf PDF
S06 - Consolidated RFI Response 537-19-101.pdf PDF
S06 - Specs 000110 TOC 18-401.pdf PDF
S06 - Specs 014500 QualityControl.pdf PDF
36C25220R0063_6.docx DOCX document
36C25220R0063-067.docx DOCX document
36C25220R0063-068.pdf PDF
36C25220R0063-066.pdf PDF
36C25220R0063-064.pdf PDF
36C25220R0063-062.pdf PDF
36C25220R0063-061.pdf PDF
36C25220R0063-063.pdf PDF
36C25220R0063-065.pdf PDF
36C25220R0063-060.pdf PDF
36C25220R0063-059.docx DOCX document
Show all 22

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

FIRE ALARM SYMBOL LEGEND

FIRE ALARM PULL STATION

SYMBOL HEIGHT DESCRIPTION

ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.

TOP: HEIGHT TO TOP OF DEVICE

ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.

F

F

S

FIRE ALARM SPEAKER

FIRE ALARM STROBE

FIRE ALARM PULL SPEAKER AND STROBE

FIRE ALARM DOOR OPEN HOLDER

FIRE ALARM SMOKE DETECTOR

FIRE ALARM CEILING MOUNTED SPEAKER

P

FIRE ALARM DUCT SMOKE DETECTOR

FIRE ALARM HEAT DETECTOR

48"

90"

90"

90"

FIRE ALARM PANEL

FIRE ALARM NAC PANEL

FIRE ALARM ANNUNCIATOR PANEL

FLOW SWITCH

FAP

NAC

FAAP

TAMPER SWITCH

POST INDICATOR VALVEPIV

REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS

F FIRE ALARM BELL90"

XX - CANDELA

XX - CANDELA

XX - WATTAGEF

S

F

S

H

CR

PACS

NC

CARD READER

CCTV CAMERA

PHYSICAL ACCESS CONTROL SYSTEM

NURSE CALL CABINET

GENERAL FIRE ALARM NOTES

1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:

A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.

B. NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.

C. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.

D. NFPA 70 NATIONAL ELECTRICAL CODE.

E. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.

F. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.

G. NFPA 101 LIFE SAFETY CODE.

H. VA FIRE PROTECTION DESIGN MANUAL.

I. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.

J. NFPA 88A STANDARD FOR PARKING STRUCTURES.

K. VA FIRE PROTECTION DESIGN MANUEL

2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).

3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.

4. BEFORE STARTING W ORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.

6. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.

7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.

8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE

ALARM DEVICES. COORDINATE WITH COR.

9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE

LOCATION WITH THE SPRINKLER CONTRACTOR.

10. NEW HEAT DETECTORS SHALL BE 24" FROM SPRINKLER HEADS, CONTRACTOR TOCOORDINATE.

NOTES:

1. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH ACCESS

CONTROL SYSTEM TO ALLOW EGRESS DURING ALARM CONDITIONS.

COORDINATE BETWEEN ACCESS CONTROL SYSTEM AND FIRE ALARM

SYSTEM MANUFACTURERS.

2. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED "RED" EMT

CONDUIT.

3. ALL WIRING SHALL BE AS RECOMMENDED BY MANUFACTURER.

4. PROVIDE SEPERATE OUTPUT SIGNALS TO AIR HANDLER UNIT VFD FOR

INDIVIDUAL UNIT SHUT-DOW N.

5. PROVIDE ELEVATOR RELAYS FOR EACH ELEVATOR.

a. PRIMARY RECALL.

b. ALTERATIVE RECALL.

c. EMERGENCY SHUNT.

d. EMERGENCY SHUNT POWER SUPERVISION.

e. IN CAB NOTIFICATIONS/FIRE FIGHTER.

6. PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.

7. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING SIEMENS

FIRE ALARM SYSTEM

TO ADDITIONAL

INDICATING

APPLIANCES

EXISTING FIRE

ALARM

CONTROL

PANEL (FACP)

STAIRWELL #11

7TH FLOOR

NODE #1

S S S

F F PF

S

F

S

PACS

CONTROLLER

RRR

RR

H

INTERFACE RELAYS INSTALL W ITHIN 3' OF

ELEVATOR CONTROLLER

R1

EQL

R2

EQL

R3

EQL

SHUNT TRIP

BREAKER

R4

EQL

HOT NEUTRAL

120 VAC CIRCUIT

(POWER TO OPERATE

SHUNT TRIP BREAKER)

FROM EMERGENCY

POWER SOURCE

R5

EQL

FIRE ALARM CONTROL UNIT

SCC1 SCC2 SCC3 SCC4

ACTUARION

CAUSES

RECALL TO

ALTERNATE

LEVEL

ACTUARION

CAUSES

RECALL TO

DESIGNATED

LEVEL

ACTUARION

CAUSES

FLASHING

OF

WARNING

SIGNAL

ACTUARION

CAUSES

DISCONNECT

OF MAIN LINE

ELEVATOR

POWER

1DC1

(SUPERVISORY)

ACTUARION

CAUSES

SUPERVISORY

SIGNAL

CONVENTIONAL OR

ADDRESSABLE

ZONE / CIRCUIT

MODULE

H

ELEVATOR

HOISTWAY HEAT

DETECTOR(S)

ELEVATOR

MACHINE ROOM

HEAT DETECTOR(S)

ELEVATOR

HOISTWAY SMOKE

DETECTOR(S)

ELEVATOR MACHINE

ROOM SMOKE

DETECTOR(S)

ELEVATOR LOBBY

SMOKE DETECTOR

5TH FLOOR

ELEVATOR LOBBY

SMOKE DETECTOR

4TH FLOOR

ELEVATOR LOBBY

SMOKE DETECTOR

3RD FLOOR

ELEVATOR LOBBY

SMOKE DETECTOR

2ND FLOOR

(ALTERNATE LEVEL)

ELEVATOR LOBBY

SMOKE DETECTOR

GROUND FLOOR

(DESIGNATED LEVEL)

ELEVATOR LOBBY

SMOKE DETECTOR

BASEMENT

NOTE:

1. FIRE ALARM CIRCUITS ARE TO BE SEDIGNED AND

INSTALLED IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE

ALARM CODE AND NEC 70, NATIONAL ELECTRICAL CODE

R1 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO DESIGNATED LEVEL.

R2 SIGNAL TO ELEVATOR CONTROLLER TO RECALL TO ALTERNATE LEVEL.

R3 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO ALTERNATE LEVEL.

R4 SIGNAL TO ACTIVATE SHUNT TRIP RELAY.

R5 SUPERVISORY RELAY TO MONITOR PRESENCE OF VOLTAGE (POWER) TO OPERATE SHUNT

TRIP BREAKER

SCC1 SUPERVISED CONTROL CIRCUIT FOR OPERATING R1.

SCC2 SUPERVISED CONTROL CIRCUIT FOR OPERATING R2.

SCC3 SUPERVISED CONTROL CIRCUIT FOR OPERATING R3.

SCC4 SUPERVISED CONTROL CIRCUIT FOR OPERATING R4.

IDC1 INITIATING DEVICE CIRCUIT TO SUPERVISE R5 CONTACTS (MONITORING POWER TO OPERATE

SHUNT TRIP BREAKER).

COMPONENT FUNCTION

Engineers Architects

Revisions: Date

Drawing Title

Approved: Project Director

Project Title

Location

VA PROJECT NUMBER

Building Number

Drawing Number

Dwg of

VA FORM 08-6231

Office of Construction and Facilities Management

CONSULTANTS: PROJECT MANAGER

Date Checked Drawn

FULLY SPRINKLERED

ACG Project Number

Headquarters:

Apogee Consulting Group, P.A.

1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.

MICHAEL BLADES & ASSOCIATES, CTO-ELEVATOR CONSULTANTS

/1

/2

:5

:4

A

M

FA001

FIRE ALARM GENERAL NOTES,

SYMBOL LEGEND, AND RISER

1 3ABT

ELEVATOR MODERNIZATION

JESSE BROW N VA MEDICAL CENTER

820 S. DAMEN AVENUE

CHICAGO, ILLINOIS 60612 02/12/2020

ISSUED FOR BID AND CONSTRUCTION

537-19-101A18-401

11A

RSB

Scale: N.T.S.

FIRE ALARM RISER

Scale: N.T.S.

FIRE ALARM INTERFACE WITH ELEVATORS

1 ADDENDUM 01 05/18/2020