S06 - FA-001 Addendum 1.pdf
PDF 360 KB Posted
- Attached to
- Z1DA--537-19-101 Taylor Elevator Modernization Federal contract opportunity
- Solicitation number
- 36C25220R0063
About this file
This document includes fire alarm system design drawings and notes for an elevator modernization project at a Department of Veterans Affairs medical center. Key details include specifications for a new addressable fire alarm system to be installed that integrates with the existing Siemens system and complies with NFPA standards. The drawings provide a fire alarm riser diagram, device locations, and interface requirements between the fire alarm and elevator control systems. Detector types and locations are indicated for elevator hoistways, machine rooms, and lobbies. Interface relays are specified for primary elevator recall, alternate recall, emergency signaling, and disconnect of main power. The related federal contract opportunity is solicitation number 36C25220R0063 for elevator modernization work at the Jesse Brown VA Medical Center in Chicago, with responses due on February 12, 2020.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25220R0063_8.docx | DOCX document | |
| 36C25220R0063 0003.docx | DOCX document | |
| S06 - Specs 000115 List of Drawings.pdf | ||
| 36C25220R0063_7.docx | DOCX document | |
| S06 - Addendum1.pdf | ||
| S06 - Specs 024119 SelectiveDemolition.pdf | ||
| S06 - A-402_Addendum 1.pdf | ||
| S06 - A-601_Addendum 1.pdf | ||
| S06 - Consolidated RFI Response 537-19-101.pdf | ||
| S06 - Specs 000110 TOC 18-401.pdf | ||
| S06 - Specs 014500 QualityControl.pdf | ||
| 36C25220R0063_6.docx | DOCX document | |
| 36C25220R0063-067.docx | DOCX document | |
| 36C25220R0063-068.pdf | ||
| 36C25220R0063-066.pdf | ||
| 36C25220R0063-064.pdf | ||
| 36C25220R0063-062.pdf | ||
| 36C25220R0063-061.pdf | ||
| 36C25220R0063-063.pdf | ||
| 36C25220R0063-065.pdf | ||
| 36C25220R0063-060.pdf | ||
| 36C25220R0063-059.docx | DOCX document |
Show all 22
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM SYMBOL LEGEND
FIRE ALARM PULL STATION
SYMBOL HEIGHT DESCRIPTION
ALL HEIGHTS ARE TO CENTER OF DEVICE UNLESS NOTED OTHERWISE.
TOP: HEIGHT TO TOP OF DEVICE
ANY HEIGHTS INDICATED IN PLANS SHALL SUPERCEDE THOSE LISTED HERE.
F
F
S
FIRE ALARM SPEAKER
FIRE ALARM STROBE
FIRE ALARM PULL SPEAKER AND STROBE
FIRE ALARM DOOR OPEN HOLDER
FIRE ALARM SMOKE DETECTOR
FIRE ALARM CEILING MOUNTED SPEAKER
P
FIRE ALARM DUCT SMOKE DETECTOR
FIRE ALARM HEAT DETECTOR
48"
90"
90"
90"
FIRE ALARM PANEL
FIRE ALARM NAC PANEL
FIRE ALARM ANNUNCIATOR PANEL
FLOW SWITCH
FAP
NAC
FAAP
TAMPER SWITCH
POST INDICATOR VALVEPIV
REMOTE LIGHT/TEST SWITCH FOR DUCT DETECTORS
F FIRE ALARM BELL90"
XX - CANDELA
XX - CANDELA
XX - WATTAGEF
S
F
S
H
CR
PACS
NC
CARD READER
CCTV CAMERA
PHYSICAL ACCESS CONTROL SYSTEM
NURSE CALL CABINET
GENERAL FIRE ALARM NOTES
1. PROVIDE FIRE ALARM SYSTEM AND COMPONENTS COMPLYING WITH THE LATEST:
A. NFPA 13- STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS.
B. NFPA 14- STANDARD FOR THE INSTALLATION OF STANDPIPE AND HOSE SYSTEM.
C. NFPA 20- STANDARD FOR THE INSTALLATION OF STATIONARY PUMPS FOR FIRE PROTECTION.
D. NFPA 70 NATIONAL ELECTRICAL CODE.
E. NFPA 72 NATIONAL FIRE ALARM AND SIGNALING CODE.
F. NFPA 90A STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS.
G. NFPA 101 LIFE SAFETY CODE.
H. VA FIRE PROTECTION DESIGN MANUAL.
I. ANSI S3.41 AUDIBLE EMERGENCY EVACUATION SIGNAL.
J. NFPA 88A STANDARD FOR PARKING STRUCTURES.
K. VA FIRE PROTECTION DESIGN MANUEL
2. FIRE ALARM SYSTEM SHALL COMPLY WITH FACTORY MUTUAL RESEARCH CORPORATION (FM).
3. PROVIDE FIRE ALARM WIRING IN CONDUIT, FACTORY PAINTED RED.
4. BEFORE STARTING W ORK, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
5. NOTIFY COR REGARDING DEFICIENCIES AND NON-OPERATING COMPONENTS. VA WILL MAKE REPAIRS.
6. WHEN WORK IS COMPLETE, TEST EXISTING FIRE ALARM SYSTEM IN WORK AREA AND ADJACENT AREAS.
7. MAKE REPAIRS TO RESOLVE INCORRECT SYSTEM OPERATIONS AT NO ADDITIONAL COST.
8. THE FIRE ALARM SYSTEM VENDOR/CONTRACTOR SHALL TERMINATE, TEST AND PROGRAM ALL NEW FIRE
ALARM DEVICES. COORDINATE WITH COR.
9. CONNECT SPRINKLER SYSTEM SUPERVISORY DEVICES TO THE FIRE ALARM SYSTEM. COORDINATE
LOCATION WITH THE SPRINKLER CONTRACTOR.
10. NEW HEAT DETECTORS SHALL BE 24" FROM SPRINKLER HEADS, CONTRACTOR TOCOORDINATE.
NOTES:
1. FIRE ALARM SYSTEM SHALL BE INTERCONNECTED WITH ACCESS
CONTROL SYSTEM TO ALLOW EGRESS DURING ALARM CONDITIONS.
COORDINATE BETWEEN ACCESS CONTROL SYSTEM AND FIRE ALARM
SYSTEM MANUFACTURERS.
2. ALL FIRE ALARM WIRING SHALL BE IN FACTORY PAINTED "RED" EMT
CONDUIT.
3. ALL WIRING SHALL BE AS RECOMMENDED BY MANUFACTURER.
4. PROVIDE SEPERATE OUTPUT SIGNALS TO AIR HANDLER UNIT VFD FOR
INDIVIDUAL UNIT SHUT-DOW N.
5. PROVIDE ELEVATOR RELAYS FOR EACH ELEVATOR.
a. PRIMARY RECALL.
b. ALTERATIVE RECALL.
c. EMERGENCY SHUNT.
d. EMERGENCY SHUNT POWER SUPERVISION.
e. IN CAB NOTIFICATIONS/FIRE FIGHTER.
6. PROVIDE POWER AMPLIFIERS FOR ALL SPEAKERS.
7. THE NEW FIRE ALARM SYSTEM SHALL MATCH THE EXISTING SIEMENS
FIRE ALARM SYSTEM
TO ADDITIONAL
INDICATING
APPLIANCES
EXISTING FIRE
ALARM
CONTROL
PANEL (FACP)
STAIRWELL #11
7TH FLOOR
NODE #1
S S S
F F PF
S
F
S
PACS
CONTROLLER
RRR
RR
H
INTERFACE RELAYS INSTALL W ITHIN 3' OF
ELEVATOR CONTROLLER
R1
EQL
R2
EQL
R3
EQL
SHUNT TRIP
BREAKER
R4
EQL
HOT NEUTRAL
120 VAC CIRCUIT
(POWER TO OPERATE
SHUNT TRIP BREAKER)
FROM EMERGENCY
POWER SOURCE
R5
EQL
FIRE ALARM CONTROL UNIT
SCC1 SCC2 SCC3 SCC4
ACTUARION
CAUSES
RECALL TO
ALTERNATE
LEVEL
ACTUARION
CAUSES
RECALL TO
DESIGNATED
LEVEL
ACTUARION
CAUSES
FLASHING
OF
WARNING
SIGNAL
ACTUARION
CAUSES
DISCONNECT
OF MAIN LINE
ELEVATOR
POWER
1DC1
(SUPERVISORY)
ACTUARION
CAUSES
SUPERVISORY
SIGNAL
CONVENTIONAL OR
ADDRESSABLE
ZONE / CIRCUIT
MODULE
H
ELEVATOR
HOISTWAY HEAT
DETECTOR(S)
ELEVATOR
MACHINE ROOM
HEAT DETECTOR(S)
ELEVATOR
HOISTWAY SMOKE
DETECTOR(S)
ELEVATOR MACHINE
ROOM SMOKE
DETECTOR(S)
ELEVATOR LOBBY
SMOKE DETECTOR
5TH FLOOR
ELEVATOR LOBBY
SMOKE DETECTOR
4TH FLOOR
ELEVATOR LOBBY
SMOKE DETECTOR
3RD FLOOR
ELEVATOR LOBBY
SMOKE DETECTOR
2ND FLOOR
(ALTERNATE LEVEL)
ELEVATOR LOBBY
SMOKE DETECTOR
GROUND FLOOR
(DESIGNATED LEVEL)
ELEVATOR LOBBY
SMOKE DETECTOR
BASEMENT
NOTE:
1. FIRE ALARM CIRCUITS ARE TO BE SEDIGNED AND
INSTALLED IN ACCORDANCE WITH NFPA 72, NATIONAL FIRE
ALARM CODE AND NEC 70, NATIONAL ELECTRICAL CODE
R1 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO DESIGNATED LEVEL.
R2 SIGNAL TO ELEVATOR CONTROLLER TO RECALL TO ALTERNATE LEVEL.
R3 SIGNAL TO ELEVATOR CONTROLLER FOR RECALL TO ALTERNATE LEVEL.
R4 SIGNAL TO ACTIVATE SHUNT TRIP RELAY.
R5 SUPERVISORY RELAY TO MONITOR PRESENCE OF VOLTAGE (POWER) TO OPERATE SHUNT
TRIP BREAKER
SCC1 SUPERVISED CONTROL CIRCUIT FOR OPERATING R1.
SCC2 SUPERVISED CONTROL CIRCUIT FOR OPERATING R2.
SCC3 SUPERVISED CONTROL CIRCUIT FOR OPERATING R3.
SCC4 SUPERVISED CONTROL CIRCUIT FOR OPERATING R4.
IDC1 INITIATING DEVICE CIRCUIT TO SUPERVISE R5 CONTACTS (MONITORING POWER TO OPERATE
SHUNT TRIP BREAKER).
COMPONENT FUNCTION
Engineers Architects
Revisions: Date
Drawing Title
Approved: Project Director
Project Title
Location
VA PROJECT NUMBER
Building Number
Drawing Number
Dwg of
VA FORM 08-6231
Office of Construction and Facilities Management
CONSULTANTS: PROJECT MANAGER
Date Checked Drawn
FULLY SPRINKLERED
ACG Project Number
Headquarters:
Apogee Consulting Group, P.A.
1151 Kildaire Farm Road, Suite 120 Cary, North Carolina 27511 www.acg-pa.com 919-858-7420 U.S. Department of Veterans Affairs# © COPYRIGHT Apogee Consulting Group, P.A.
MICHAEL BLADES & ASSOCIATES, CTO-ELEVATOR CONSULTANTS
/1
/2
:5
:4
A
M
FA001
FIRE ALARM GENERAL NOTES,
SYMBOL LEGEND, AND RISER
1 3ABT
ELEVATOR MODERNIZATION
JESSE BROW N VA MEDICAL CENTER
820 S. DAMEN AVENUE
CHICAGO, ILLINOIS 60612 02/12/2020
ISSUED FOR BID AND CONSTRUCTION
537-19-101A18-401
11A
RSB
Scale: N.T.S.
FIRE ALARM RISER
Scale: N.T.S.
FIRE ALARM INTERFACE WITH ELEVATORS
1 ADDENDUM 01 05/18/2020