36C25218B0106-003.pdf
PDF 8 MB Posted
- Solicitation number
- 36C25218B0106
About this file
36C25218B0106 S02 - 695-17-119 SteamTunnelRepair_Drawings_100 FULL SET.pdf
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25218B0106-00005007.pdf | ||
| 36C25218B0106-00005001.pdf | ||
| 36C25218B0106-00005009.pdf | ||
| 36C25218B0106-00005002.pdf | ||
| 36C25218B0106-00005005.pdf | ||
| 36C25218B0106-00005006.pdf | ||
| 36C25218B0106-00005008.pdf | ||
| 36C25218B0106-00005000.docx | DOCX document | |
| 36C25218B0106-00005004.pdf | ||
| 36C25218B0106-00005003.pdf | ||
| 36C25218B0106-00004000.docx | DOCX document | |
| 36C25218B0106-00003000.docx | DOCX document | |
| 36C25218B0106-00002000.docx | DOCX document | |
| 36C25218B0106-00001001.pdf | ||
| 36C25218B0106-00001000.docx | DOCX document | |
| 36C25218B0106-00001002.pdf | ||
| 36C25218B0106-005.pdf | ||
| 36C25218B0106-002.pdf | ||
| 36C25218B0106-004.pdf | ||
| 36C25218B0106-006.pdf | ||
| 36C25218B0106-001.docx | DOCX document | |
| 36C25218B0106-000.docx | DOCX document |
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
NON-SPRINKLERED
C :\U se rs
\e de ci na
\D oc um en ts \1
6.
.0
Tu nn el
M od el _e de ci na gu id on de si gn
.c om
.rv t
9/
/2
8:
:3
AM
GI000
COVER SHEET
RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
1 SEPTEMBER 2017 ETA ETA
100% BID SET
MILWAUKEE VAMC
BLDG 112
CLEMENT J. ZABLOCKI VA MEDICAL CENTER
REPAIR CAMPUS STEAM TUNNEL
100% BID SET
SHEET LIST
SHEET NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
CIVIL
CC001 GENERAL CIVIL NOTES
VF101 EXISTING CONDITIONS
CD101 SITE DEMOLITION PLAN
CS101 SITE PLAN
CS501 SITE DETAILS
CW101 MAINTENANCE OF TRAFFIC PLAN
CW501 SIGNAGE DETAILS
CJ101 EROSION CONTROL PLAN
CJ501 EROSION CONTROL DETAILS
STRUCTURE
SI001 STRUCTURAL GENERAL NOTES
SB101 STEAM TUNNEL PLANS AND SECTIONS
SB301 SECTIONS
Contact: Contact:
Hannah Fleck Engineer
CIVILOWNER ARCHITECT
Mark VandeWoude Structural Engineer
STRUCTURAL
p: 317.800.6388 x 119 e: mvanderwoude@guidondesign.com
LOCATION MAP
VICINITY MAP
BUILDING 112
N
N
Contact:
CLEMENT J. ZABLOCKI
VA MEDICAL CENTER
5000 West National Ave.
Milwaukee, WI 53295 p: 414.384.2000
GUIDON DESIGN INC.
Evan Anderson-Decina Project Manager | Architect
905 North Capitol Avenue Suite 100 Indianapolis, IN 46204 p: 317.800.6388 x 116 e: edecina@guidondesign.com
PROJECT NO: 695-17-119
AND STRUCTURAL SUPPORTS
GUIDON DESIGN INC.
905 North Capitol Avenue Suite 100 Indianapolis, IN 46204
Contact:
RING & DUCHATEAU, LLP
Josh Nickols Engineer
MECHANICAL,
ELECTRICAL &
PLUMBING
17400 West Capitol Drive Brookfield, WI 53045 p: 414.778.7421 e: jnickols@ringdu.com p: 317.800.6388 x 115 e: hfleck@guidondesign.com
GUIDON DESIGN INC.
905 North Capitol Avenue Suite 100 Indianapolis, IN 46204
Revisions: Date:
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
CC001
GENERAL CIVIL NOTES
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
0 2010
N
VF101
EXISTING CONDITIONS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
0 2010
N
CD101
SITE DEMOLITION PLAN
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
0 4020
N
CS101
SITE PLAN
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
CS501
SITE DETAILS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
0 12060
N
CW101CW101
MAINTENANCE OF TRAFFIC
PLAN
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
CW501
SIGNAGE DETAILS
DETOUR
AHEAD
ROAD CLOSED
THRU TRAFFIC
TO
END
DETOUR
DETOUR
ROAD
CLOSED
DETOUR
DO NOT
ENTER
ONE WAY
ONLY
DETOUR
ROAD
NARROWS
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
0 4020
N
CJ101
EROSION CONTROL PLAN
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
Consultant:
NON-SPRINKLERED
BLDG 112RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
(414) 778-1700
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
JIM BEIER, COR, VAMC
Revisions: Date: 01 SEPTEMBER 2017
100% BID SET
KC HF
CJ501
EROSION CONTROL
DETAILS
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE
CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE
BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO INSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING
ERECTION. THIS INCLUDES THE ADDITION OF NECESSARY SHORING, SHEETING, TEMPORARY
BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL,
MECHANICAL, ELECTRICAL AND PLUMBING DRAWINGS AND SPECIFICATIONS.
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL
WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT REQUIREMENT SHALL
APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE
DRAWINGS, SHALL BE MADE WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
CONCRETE MIX DESIGN SUBMITTAL
THE CONTRACTOR SHALL SUBMIT FOR THE REVIEW OF THE STRUCTURAL ENGINEER A MIX DESIGN FOR EACH PROPOSED CLASS OF CONCRETE. EACH MIX DESIGN SHALL BE IDENTIFIED BY A MIX NUMBER OR OTHER UNIQUE IDENTIFICATION. THE CONTRACTOR SHALL NOT VARY FROM THE MIX
DESIGNS NOR USE ANY CONCRETE OTHER THAN THE APPROVED MIX DESIGNS WITHOUT THE
APPROVAL OF THE STRUCTURAL ENGINEER. MIX DESIGN SUBMITTALS SHALL INCLUDE THE
FOLLOWING INFORMATION:
1. MIX DESIGN NUMBER OR UNIQUE IDENTIFICATION AND INTENDED LOCATION OF PLACEMENT.
2. CEMENT TYPE, PROPORTION AND NAME OF MANUFACTURER.
3. FLY ASH PROPORTION (WHEN USED), LABORATORY ANALYSIS CERTIFICATION, AND NAME AND
LOCATION OF SUPPLIER.
4. COURSE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
5. FINE AGGREGATE PROPORTION, GRADATION REPORT, NAME AND LOCATION OF SUPPLIER.
6. MIXING WATER PROPORTION AND SOURCE.
7. ADMIXTURE DOSAGES, PRODUCT NAME(S) AND MANUFACTURER NAME(S).
8. FIBER REINFORCEMENT DOSAGE (WHEN USED), PRODUCT NAME AND MANUFACTURER NAME.
9. DESIGN 28-DAY COMPRESSIVE STRENGTH (F'C).
10. DESIGN SLUMP RANGE.
11. DESIGN AIR-ENTRAINMENT (FOR CONCRETE REQUIRING ENTRAINED AIR).
12. STATISTICAL ANALYSIS OF LABORATORY STRENGTH TEST DATA IN ACCORDANCE WITH "STANDARD
DEVIATION" DETERMINATION OUTLINED IN ACI 318.
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE,
ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND
SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT
OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE
STRUCTURAL ENGINEER. DRAWINGS SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE
RETURNED UNCHECKED.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF SHOP DRAWINGS. FOR HARD COPY OPTION, SUBMIT A MINIMUM OF TWO COPIES OF SHOP DRAWINGS TO THE STRUCTURAL ENGINEER FOR
REVIEW (ONE COPY SHALL BE RETAINED BY THE STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT SHOP DRAWINGS IN ADOBE PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. STRUCTURAL STEEL (INCLUDING DESIGN CALCULATIONS SEALED BY A PROFESSIONAL ENGINEER
REGISTERED IN THE STATE WHERE THE PROJECT IS CONSTRUCTED FOR ALL CONNECTIONS NOT
SPECIFICALLY DETAILED ON THE DRAWINGS)
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED
BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE
APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS,
FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL
MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF
MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY
RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST
CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL SAMPLES, AND UPON APPROVAL IN WRITING
BY CONTRACTING OFFICER.
SUBMIT HARD COPIES OR ELECTRONIC VERSIONS OF PRODUCT DATA. FOR HARD COPY OPTION,
SUBMIT A MINIMUM OF TWO COPIES OF PRODUCT DATA TO THE STRUCTURAL ENGINEER FOR
REVIEW (ONE COPY SHALL BE RETAINED BY THE STRUCTURAL ENGINEER). FOR ELECTRONIC OPTION, SUBMIT PRODUCT DATA IN PDF FORMAT.
1. FIBER REINFORCEMENT FOR CONCRETE
2. CONCRETE CURING COMPOUND
4. CONCRETE JOINT SEALANT
5. WATER STOPS
6. EXPANSION ANCHORS
7. ADHESIVE ANCHORS
8. NON-SHRINK GROUT
CONCRETE
REINFORCED CONCRETE HAS BEEN DESIGNED IN ACCORDANCE WITH THE BUILDING CODE
REQUIREMENTS FOR STRUCTURAL CONCRETE (ACI 318) AND COMMENTARY (ACI 318R).
MIXING, TRANSPORTING, AND PLACING OF CONCRETE SHALL CONFORM TO THE LATEST
EDITION OF THE SPECIFICATIONS FOR STRUCTURAL CONCRETE (ACI 301). READY-MIXED
CONCRETE SHALL CONFORM TO THE REQUIREMENTS OF ASTM C94. IN CASE OF A
DISCREPANCY, THE PLANS AND SPECIFICATIONS SHALL GOVERN.
CEMENT SHALL CONFORM TO ASTM C150, TYPE I, UNO.
FLY ASH SHALL CONFORM TO ASTM C618, CLASS C OR F. THE RATIO OF THE AMOUNT (BY
WEIGHT) OF FLY ASH TO TOTAL CEMENTITIOUS MATERIALS IN THE MIX SHALL NOT EXCEED 25
PERCENT.
NORMAL WEIGHT AGGREGATES SHALL CONFORM TO ASTM C33.
WATER-REDUCING ADMIXTURES SHALL CONFORM TO ASTM C494.
AIR-ENTRAINING ADMIXTURES SHALL CONFORM TO ASTM C260 AND SHALL BE CERTIFIED BY
THE MANUFACTURER TO BE COMPATIBLE WITH OTHER ADMIXTURES.
CALCIUM CHLORIDE ADMIXTURES OR ADMIXTURES CONTAINING MORE THAN 0.1 PERCENT
CHLORIDE IONS SHALL NOT BE USED.
IN COLD WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF
CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF ACI 306R,
COLD WEATHER CONCRETING.
IN HOT WEATHER CONDITIONS, MIXING, PLACING, FINISHING, CURING AND PROTECTION OF
CONCRETE SHALL BE PERFORMED IN ACCORDANCE WITH THE LATEST EDITION OF ACI 305R,
HOT WEATHER CONCRETING.
USE OF CONSTRUCTION JOINTS AT LOCATIONS OTHER THAN THOSE INDICATED ON THE
DRAWINGS SHALL BE SUBMITTED TO THE STRUCTURAL ENGINEER FOR REVIEW.
SLUMP FOR PUMPED CONCRETE SHALL BE MEASURED AT POINT OF DISCHARGE.
NORMAL WEIGHT CONCRETE SHALL BE USED IN THE FOLLOWING AREAS AND SHALL HAVE THE
PROPERTIES AS SHOWN BELOW:
STEAM TUNNEL REPAIR CONCRETE AND TOP SLAB
1. COMPRESSIVE STRENGTH (28 DAYS): 5000 PSI
2. MAXIMUM SLUMP: 4 INCHES
3. MINIMUM CEMENTITIOUS MATERIALS CONTENT: 375 LB./CU. YD.
4. (USE TYPE II SULFATE RESISTANT CEMENT)
5. MAXIMUM SLUMP FOR CONCRETE CONTAINING HIGH-RANGE WATER-REDUCING ADMIXTURE: 8
INCHES (AFTER ADMIXTURE IS ADDED TO CONCRETE WITH 2 TO 4 INCH SLUMP).
6. MAXIMUM WATER/CEMENTITIOUS MATERIALS RATIO: 0.45
7. MAXIMUM COARSE AGGREGATE SIZE: 1 1/2 INCHES
8. AIR CONTENT: 3-6%
SHORING/RE-SHORING
THE SHORING AND/OR RE-SHORING DESIGN FOR CONCRETE FRAME SYSTEMS IS THE
RESPONSIBILITY OF THE CONTRACTOR. TEMPORARY SHORING FOR SLABS, BEAMS, AND GIRDERS
SHALL BE ADEQUATE TO CARRY THE TOTAL WEIGHT OF THE SLAB-BEAM-GIRDER SYSTEM (UNIT
WEIGHT OF CONCRETE CAN BE TAKEN AS 145 PCF) AND ANY TEMPORARY CONSTRUCTION LOADS
TO BE IMPOSED ON THE STRUCTURAL SYSTEM. SHORING FOR A LEVEL SHALL NOT BE REMOVED
UNTIL THE CONCRETE AT THAT LEVEL HAS ATTAINED THE SPECIFIED COMPRESSIVE STRENGTH
(F'C). REMOVAL OF SHORING AND/OR RESHORING SHALL NOT CAUSE OVERSTRESSING OF ANY
STRUCTURAL ELEMENTS. SHORING PLAN TO BE DESIGNED AND STAMPED BY A PROFESSIONAL
ENGINEER AND SUBMITTED DURING CONSTRUCTION PHASE PER THE 033000 SPECIFICATION.
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND
SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000 PSI.
ALL REINFORCING STEEL IN THIS PROJECT SHALL BE EPOXY-COATED, CONFORMING TO ASTM 775.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE
LATEST EDITION OF THE FOLLOWING STANDARDS: ACI 301, ACI 315, ACI 318 AND
ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE
THE FOLLOWING MINIMUM CONCRETE COVER OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT
UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR APPROVED BY THE
STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE
STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT
CORNERS OF ALL WALLS AND GRADE BEAMS. LAP SPLICE CORNER BARS WITH
STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE)
AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE
BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
WELDABLE REINFORCING STEEL
REINFORCING STEEL WHICH IS TO BE WELDED SHALL CONFORM TO ASTM A706. WELDING OF
REINFORCING STEEL, WHEN APPROVED BY THE STRUCTURAL ENGINEER, SHALL CONFORM TO THE LATEST EDITION OF AMERICAN WELDING SOCIETY STANDARD D1.4. ELECTRODES FOR SHOP AND FIELD
WELDING OF REINFORCING STEEL SHALL CONFORM TO ASTM A233, CLASS E90XX.
EPOXY-COATED REINFORCING STEEL
EPOXY COATED REINFORCING STEEL SHALL CONFORM TO ASTM A775 AND SHALL BE USED ONLY
WHERE SHOWN OR NOTED ON THE DRAWINGS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185. FABRIC SHALL
BE SUPPLIED IN FLAT SHEETS AND LAPPED A MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED AS FOLLOWS, UNLESS NOTED OTHERWISE:
SLABS ON GRADE: 2 INCHES DOWN FROM TOP OF SLAB.
SLABS ON METAL DECK: 3/4 INCH DOWN FROM TOP OF SLAB.
FIBER REINFORCEMENT
FIBER REINFORCEMENT SHALL BE 3/4" LONG, VIRGIN (NON-RECYCLED) NYLON OR
POLYPROPYLENE FIBERS, INTRODUCED INTO THE CONCRETE MIX AT THE BATCH PLANT, IN
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. DOSAGE SHALL BE 1.5 POUNDS
PER CUBIC YARD OF CONCRETE.
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR
AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7
DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE
TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE
DISCARDED 90 DAYS AFTER CASTING UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL
BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE
COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF
CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE CYLINDERS SHALL BE
STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE
BUILDING CONCRETE. SPECIAL CURING BOXES ARE NOT PERMITTED FOR THESE TEST
CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, READY-
MIX SUPPLIER AND CONTRACTOR WITHIN 24 HOURS AFTER TESTING.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY70"
FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL
ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN
CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY
THE MANUFACTURER'S REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE
WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-
STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE
COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL HAVE A
MINIMUM COMPRESSIVE STRENGTH (F'C) OF 5,000 PSI IN 28 DAYS.
WATERSTOPS
SELF-EXPANDING STRIP WATER STOPS SHALL BE VOLCLAY WATERSTOP-RX 101 UNLESS NOTED
OTHERWISE. INSTALL IN ACCORDANCE WITH MANUFACTURER'S WRITTEN NSTRUCTIONS.
MASTIC COATING
MASTIC COATING FOR PROTECTION OF INDICATED ITEMS SHALL BE BITUMASTIC 50 COAL TAR
MASTIC BY CARBOLINE OR EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL
ENGINEER. INSTALL AT LOCATIONS INDICATED ON DRAWINGS.
UNLESS NOTED OTHERWISE, APPLY MASTIC TO A COATING THICKNESS OF 18 MILS. PROVIDE
FULL COVERAGE OVER ITEMS INDICATED TO RECEIVE COATING.
STRUCTURAL STEEL
STRUCTURAL STEEL DETAILING, FABRICATION AND ERECTION SHALL CONFORM TO THE ANSI/AISC 360 SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS, LATEST EDITION WITH AMENDMENTS, AND THE AISC 303 CODE OF STANDARD PRACTICE FOR STEEL BUILDINGS AND BRIDGES, LATEST
EDITION WITH AMENDMENTS.
STRUCTURAL STEEL WIDE FLANGE SHAPES SHALL CONFORM TO ASTM A992, 50 KSI.
STRUCTURAL STEEL PLATES AND ROLLED SHAPES OTHER THAN WIDE-FLANGE SHAPES SHALL
CONFORM TO ASTM A36, UNLESS NOTED OTHERWISE.
STRUCTURAL STEEL TUBING SHALL CONFORM TO ASTM A500, GRADE B.
STRUCTURAL PIPE SHALL CONFORM TO ASTM A53, GRADE B.
ANCHOR RODS SHALL CONFORM TO ASTM F1554, GRADE 36, UNLESS NOTED OTHERWISE.
STEEL STUDS SHALL CONFORM TO ASTM A108.
BOLTED CONNECTIONS SHALL CONFORM TO THE SPECIFICATION FOR STRUCTURAL JOINTS
USING ASTM A325 OR A490 BOLTS, APPROVED BY THE RESEARCH COUNCIL ON STRUCTURAL
CONNECTIONS OF THE ENGINEERING FOUNDATION. BOLTED CONNECTIONS FOR STRUCTURAL
STEEL MEMBERS SHALL BE MADE WITH 3/4" DIAMETER A325 BOLTS, UNLESS NOTED OTHERWISE.
BOLTED CONNECTIONS SHALL BE TIGHTENED TO THE SNUG TIGHT CONDITION, EXCEPT BOLTED
CONNECTIONS IN BRACE ELEMENTS ARE TO BE FULLY PRETENSIONED WITH CLASS A FAYING
SURFACES.
WELDING PROCEDURES SHALL CONFORM TO THE LATEST EDITION OF THE AMERICAN WELDING
SOCIETY'S STRUCTURAL WELDING CODE FOR STEEL ANSI/AWS D1.1.
WELDED CONNECTIONS USING ASTM A992 STEEL AS A BASE METAL SHALL BE MADE WITH E70XX
LOW HYDROGEN ELECTRODES. UNLESS OTHERWISE SHOWN OR NOTED ON THE DRAWINGS,
OTHER WELDED CONNECTIONS MAY BE MADE WITH STANDARD E70XX ELECTRODES.
STRUCTURAL STEEL THAT RECEIVES FINISH PAINT SHALL BE SHOP-PRIMED WITH A RUST-
INHIBITING PRIMER, UNLESS NOTED OTHERWISE ON THE DRAWINGS. CONTRACTOR SHALL VERIFY PRIMER IS COMPATIBLE WITH FINISH COAT SYSTEM SPECIFIED BY THE ARCHITECT. COORDINATE
FINISH PAINTING REQUIREMENTS WITH THE ARCHITECT.
STRUCTURAL STEEL THAT IS NOT EXPOSED IN THE FINISHED CONSTRUCTION AND DOES NOT
RECEIVE FINISH PAINT SHALL NOT BE SHOP-PRIMED, UNLESS NOTED OTHERWISE ON THE
DRAWINGS.
STRUCTURAL STEEL NOTED TO BE GALVANIZED SHALL BE HOT-DIP GALVANIZED IN
CONFORMANCE WITH ASTM A123.
DO NOT PAINT OR GALVANIZE THE FOLLOWING SURFACES:
1. SURFACES TO BE WELDED.
2. SURFACES TO RECEIVE BOLTED SLIP-CRITICAL CONNECTIONS.
3. SURFACES TO RECEIVE SHEAR STUD CONNECTIONS.
4. SURFACES TO RECEIVE SPRAYED-ON FIREPROOFING.
ALL ABRASIONS TO GALVANIZED SURFACES OR SURFACES TO RECEIVE AN ARCHITECTURAL FINISH
COAT SHALL BE TOUCHED-UP AFTER ERECTION IS COMPLETE. FOR PAINTED STEEL, USE A
PRIMER EQUIVALENT TO THE SHOP PAINT. FOR GALVANIZED STEEL, USE A ZINC-RICH COLD-
GALVANIZING PAINT.
DESIGN CONNECTIONS NOT SHOWN IN ACCORDANCE WITH THE ASD SPECIFICATION AND MANUAL
OF STEEL CONSTRUCTION. UNLESS NOTED OTHERWISE ON THE DRAWINGS, DESIGN BEAM
CONNECTIONS NOT SHOWN, TO SUPPORT A MINIMUM OF A 10 KIP SHEAR REACTION. PROVIDE NO LESS THAN 2 BOLTS IN ANY SINGLE LINE OF BOLTS, UNLESS SPECIFICALLY INDICATED ON THE
DRAWINGS.
PROVIDE L4X4X1/4 FRAMED OPENINGS FOR ALL ROOF PENETRATIONS 12 INCHES OR LARGER
ALONG ANY SIDE, UNLESS LARGER FRAMING IS INDICATED. REFER TO MECHANICAL AND PLUMBING
DRAWINGS FOR PENETRATIONS. COORDINATE FRAMED OPENING SIZES AND LOCATIONS WITH
THE MECHANICAL AND PLUMBING CONTRACTORS.
GALVANIZE ALL EXPOSED STEEL.
EXISTING STEEL MARKED ON PLANS FOR REUSE SHALL BE CLEANED AND INSPECTED TO CONFIRM
IT IS SUITABLE FOR USE AT NEW LOCATION.
RENOVATION (EXISTING CONDITIONS)
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE VA RECORD DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO NOTIFY THE STRUCTURAL
ENGINEER IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR DISCREPANCIES TO THE STRUCTURAL
ENGINEER PRIOR TO THE FABRICATION AND ERECTION OF ANY NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THIS PROJECT, THAT BECOME DAMAGED, SHALL BE REPLACED WITH NEW MATERIAL OF EQUAL QUALITY AND APPEARANCE, AT THE
CONTRACTOR'S EXPENSE.
ALL WORK SHALL BE PERFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK. ADJACENT
EXISTING CONSTRUCTION SHALL BE PROTECTED FROM DUST, DIRT AND DEBRIS ACCUMULATION AT ALL
TIMES.
TUNNEL REPAIR LOCATIONS
FRAME NUMBER
LOCATION
(STA.) CONCRETE ISSUES REPAIR AREA (SF) PLATE SUPPORTS TO BE REPLACED PLATE DETAIL OTHER NOTES
1 00+04
2 00+12 UPPER GUIDE STEEL PLATE 3/SB101
3 00+20
4 00+24 LOWER GUIDE STEEL PLATE 3/SB101
5 00+28 UPPER GUIDE STEEL PLATE 3/SB101
6 00+32 LOWER GUIDE STEEL PLATE 3/SB101
7 00+36 SPALLING 5 UPPER GUIDE STEEL PLATE 3/SB101
8 00+40 SPALLING/DELAMINATION 5
9 00+53 SPALLING 5
10 00+61 UPPER GUIDE STEEL PLATE 3/SB101
11 00+69 LOWER GUIDE STEEL PLATE 3/SB101
12 00+77 UPPER GUIDE STEEL PLATE 3/SB101
13 00+85 LOWER GUIDE STEEL PLATE 3/SB101
14 00+93 UPPER GUIDE STEEL PLATE 3/SB101
15 01+01 LOWER GUIDE STEEL PLATE 3/SB101
16 01+09 UPPER GUIDE STEEL PLATE 3/SB101
17 01+17 LOWER GUIDE STEEL PLATE 3/SB101
18 01+25
19 01+29 LOWER GUIDE STEEL PLATE 3/SB101
20 01+34 ANCHORS 7/SB101
21 01+42
22 01+51 LOWER GUIDE STEEL PLATE 3/SB101
23 01+59 UPPER GUIDE STEEL PLATE 3/SB101
24 01+68
25 01+76
26 01+84
27 01+93
28 02+00
29 02+08
30 02+16
31 02+24
32 02+32
33 02+40
34 02+48
35 02+56 LEAK AT CONCRETE JOINT - SEAL
36 02+64
37 02+72
38 02+80
39 02+84
40 02+89
41 02+96
42 03+04
43 03+12 ANCHORS 7/SB101
44 03+21
45 03+28 LOWER GUIDE STEEL PLATE 3/SB101
46 03+36
47 03+44 SPALLING 5 LOWER GUIDE STEEL PLATE 3/SB101
48 03+52
49 03+60 SPALLING/DELAMINATION 5 LOWER GUIDE STEEL PLATE 3/SB101
50 03+68 SPALLING/DELAMINATION 15
51 03+76 SPALLING 15
52 03+84 SPALLING 15
53 03+92 SPALLING/DELAMINATION 15 LOWER GUIDE STEEL PLATE 3/SB101
54 04+00 SPALLING/DELAMINATION 15
55 04+08 SPALLING/DELAMINATION 15
56 04+16 SPALLING/DELAMINATION 15 UPPER GUIDE STEEL PLATE 3/SB101
57 04+24 SPALLING/DELAMINATION 15 LOWER GUIDE STEEL PLATE 3/SB101
58 04+32 10
59 04+40 UPPER GUIDE STEEL PLATE 3/SB101 CORRODED PIPES - CLEAN
60 04+48 5 LOWER GUIDE STEEL PLATE 3/SB101
61 04+56 SPALLING 30
62 04+64 SPALLING/DELAMINATION 10
63 04+72 UPPER GUIDE STEEL PLATE 3/SB101
64 04+80 SPALLING 5
65 04+88 SPALLING/DELAMINATION 10 UPPER GUIDE STEEL PLATE 3/SB101
66 04+96 SPALLING/DELAMINATION 30 LOWER GUIDE STEEL PLATE 3/SB101 TOP SLAB REPLACEMENT
67 05+04 SPALLING/DELAMINATION TOP SLAB REPLACEMENT
68 05+12 DETERIORATION TO REBAR 10 LOWER GUIDE STEEL PLATE, ANCHORS 3/SB101, 7/SB101 TOP SLAB REPLACEMENT
69 05+20 DETERIORATION TO REBAR 10 TOP SLAB REPLACEMENT
70 05+28 SPALLING/DELAMINATION ANCHORS 7/SB101 TOP SLAB REPLACEMENT
71 05+36 SPALLING/DELAMINATION 40 TOP SLAB REPLACEMENT
72 05+44 SPALLING/DELAMINATION 15 LOWER GUIDE STEEL PLATE 3/SB101
73 05+52 SPALLING 5 UPPER GUIDE STEEL PLATE 3/SB101
74 05+60 SPALLING 5 LOWER GUIDE STEEL PLATE 3/SB101
75 05+68 SPALLING 5
76 05+76 LOWER GUIDE STEEL PLATE 3/SB101
77 05+84
78 05+92
79 06+00 CONDUIT RUNS THROUGH - SEE CIVIL FOR FIX
80 06+07 SPALLING/DELAMINATION 5
81 06+15 ANCHORS 7/SB101
82 06+24 LOWER GUIDE STEEL PLATE 3/SB101
83 06+31
84 06+40 SPALLING 5
85 06+47 SPALLING 40
86 06+55
87 06+63
88 06+71 ANCHORS 7/SB101
89 06+79
90 06+87
91 06+95
92 07+03
93 07+11
94 07+19
95 07+26
96 07+34 LOWER GUIDE STEEL PLATE 3/SB101
97 07+42
98 07+50
99 07+58
100 07+66
101 07+72
NOTES:
1. FRAMES ARE NUMBERED STARTING WITH "1" CLOSEST TO THE BOILER PLANT ENTRANCE, FINISHING WITH "101" AT THE
ENTRANCE TO THE MAUSOLEUM.
2. FOR DAMAGED CONCRETE SECTIONS NOTED FOR REPAIR, CLEAN DAMAGED SURFACE AND GRIND DOWN TO REMOVE ANY
SPALLING/EFFLUORESCENCE. CLEAN WITH WIRE BRUSH AND ROUGHEN SURFACE TO 1/4" AMPLITUDE. SEAL ANY LEAKS AND ENSURE SURFACE IS DRY BEFORE APPLYING REPAIR MATERIAL. FILL WITH REPAIR GROUT/MORTAR (TO BE APPROVED BY VA)
UNTIL SURFACE IS FLUSH.
3. COVER REPAIRED CONCRETE SURFACE AFTER REPAIR WITH APPROVED SHEETING TEMPORARILY ADHERED TO
SURROUNDING CONCRETE UNTIL CURING PERIOD HAS ENDED.
4. WHERE JOINTS BETWEEN CONCRETE SECTIONS SHOW SIGNS OF LEAKING, APPLY APPROVED HYDRAULIC CEMENT AND
WAIT UNTIL SECTION HAS DRIED TO BEGIN CONCRETE REPAIR.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
NON-SPRINKLERED
C U s e rs
\l la i\ D o c u m e n ts
\1 .1
.0
T u n n e l M o d e l_ lla i.
rv t /1
/2
:1 :2
P
M
SI001
STRUCTURAL GENERAL NOTES
RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
1 SEPTEMBER 2017 MV LL
100% BID SET
MILWAUKEE VAMC
BLDG 112
TRANSFORMERS
CONC WALL
TRANSFORMER
SPRINKLER
CONTROL
BOX
FAN
STEPS
RIM 638.86'
8" PVC E 634.86'
RIM 634.53'
12" E 629.37' 12" W 629.37'
12" RCP N 629.47'
RIM 634.65'
12" E 631.15'
RIM 628.69'
6" NW 625.66'
8" E 625.66'
(TO BOTTOM OF BELL)
RIM 628.29'
8" W 625.44'
8" SW 625.38'
6" E 625.64'
RIM 628.48'
6" W 624.58' +/-
(FILLED WITH DEBRIS)
RIM 629.49'
8" N 624.79' +/- 6" W 624.89' +/- 8" S 624.79'+/-
(FULL OF DEBRIS,
UNKNOWN CONNECTIONS)
RIM 637.20'
8" PVC W 632.94'
12" RCP S 631.99'
RIM 640.17'
12" RCP S 634.16'
12" RCP W 635.09'
RIM 642.82'
6" E 637.66' 6" N 637.74' 6" W 637.82'
N 642.79' +/-
METAL FENCE
C H A
IN
LI
N K
F E N C E
S
IG
N
LANDSCAPING
S
IG
N
LANDSCAPING
BR
IC
K
WA
LL
S
IG
N
TUNNEL
ACCESS
HATCH
METAL CAP
S
IG
N
GAS PUMPS
AND VENT
ON CONC
PAD
SIGN
LA
ND
SC
AP
IN
G
SET BENCHMARK, CHISELED " "
ON WEST SIDE, TOP OF
CONCRETE LIGHT POLE BASE
ELEV = 640.24'
ABANDONED TUNNEL ACCESS
F L O W E R
D R
POWER PLANT DR.
B R
IC
K
ASPHAL
T
ASPHALT
GRAVEL
ASPHALT
ASPH
C O N C R E T E
ASPHALT
ASPHALT
A S P H A L T
C O N C R E T E
CONC
C O N C
CONC
C O N C
CONC
C O N C
C O N C
CONC
C O N C
FOUND
IRON ROD
1 STORY
METAL
BUILDING
BLDG 112
SB101
SB101
TYP
TYP
ABANDONED STEAM PIPE (TO
BE REMOVED) (~01+10)
STEP DOWN (~01+31)
APPROX. LOCATION
FRAME 20 ANCHOR
(~01+40)
ABANDONED WATER LINE
(TO BE REMOVED) (~1+90)
MID-HEIGHT PIPE CROSSING (~ 02+08)
START (~00+00)
BAD SPALL AREA
(APPROX 02+50 -02+60)
APPROX. LOCATION FRAME 43
ANCHOR (~03+20)
APPROX LOCATION OF
JOINT LEAK (~04+35)
APPROX. LOCATION FRAME
70 ANCHOR (~05+30)
APPROX. LOCATION FRAME
81 ANCHOR (~ 06+15)
APPROX. LOCATION FRAME
88 ANCHOR (~ 06+80)
PIPE CROSSING MID-
HEIGHT (~ 07+50)
END OF SCOPE OF
PROJECT ( ~ 07+79 )
TOP SLAB NEEDS
REPLACEMENT IN THIS AREA
SB101
SB101
NOTES:
1. PROVIDE TEMPORARY FALL PROTECTION COVER OVER OPENING DURING CONSTRUCTION
2. PROVIDE TEMPORARY HORIZONTAL BRACING ACROSS TUNNEL WHILE TOP SLAB IS REMOVED CAPABLE
OF WITHSTANDING 5K TENSION OR COMPRESSION FORCE.
3. PROVIDE TEMPORARY WEATHER PROTECTION OVER TUNNEL OPENING DURING CONSTRUCTION AND
REPAIR WORK.
4. STEAM PIPES TO REMAIN OPERATIONAL DURING DURATION OF CONSTRUCTION. CONTRACTOR TO PLACE PROPER SAFEGUARDS IN PLACE TO PROTECT PIPES DURING CONSTRUCTION AND TO PROMOTE SAFETY
OF WORKERS.
BOILER PLANT
MAUSOLEUM
REMOVE EXISTING
TOP PLATE
REMOVE EXISTING
BASE PLATE
EXISTING
CONCRETE
TUNNEL
REMOVE EXISTING
PIPE SUPPORT FRAME
REMOVE EXISTING PIPE
SUPPORT FRAME
REMOVE UPPER GUIDE STEEL
PLATE SUPPORT (SEE REPAIR
TABLE FOR LOCATIONS)
REMOVE LOWER GUIDE STEEL
PLATE SUPPORT (SEE REPAIR
TABLE FOR LOCATIONS)
NOTES:
1. CONTRACTOR TO PROVIDE TEMPORARY PIPE SUPPORT UPON DEMOLITION
2. REPLACE ALL FRAMES LABELED 1-101 (SEE REPAIR TABLE) BETWEEN BOILER
PLANT AND ABOVE-GROUND STEAM VAULT "MAUSOLEUM"
3. DO NOT REMOVE FRAMES BEFORE INSTALLING REPLACEMENT.
CUT BOTTOM STEEL TUBE ANCHOR
TO MOST VIABLE STEEL. REMOVE
WALL PLATE ASSEMBLIES.
LOCATIONS INDICATED IN REPAIR
TABLE
L3x3x1/4 GALVANIZED ANGLE
CONNECTION W/ 3/8" DIA. S.S.
EXPANSION ANCHORS
NEW HSS 3x3x1/4
GALVANIZED STEEL TUBE
COLUMN
NEW HDPE
BEARING PAD
NEW HSS 3x3x1/4 GALVANIZED
STEEL TUBE SUPPORT
NEW LOW FRICTION PIPE
SUPPORT ASSEMBLY TO
REPLACE GUIDE STEEL PLATES
L3x3x1/4 GALVANIZED ANGLE
CONNECTION W/ 3/8" DIA. S.S.
EXPANSION ANCHORS
NEW HSS 3x3x1/4
GALVANIZED STEEL
TUBE SUPPORT
EXISTING
CONCRETE
TUNNEL
PROVIDE 1/2" GAP BENEATH TUBE
COLUMN FOR POTENTIAL DRAINAGE
1/4" 2" MIN
1/4"
NEW 3/8" x 9" x 9" GALV. STEEL
PLATE W/ (4) 1/2" DIA. S.S.
EXPANSION ANCHORS
1/4
SB101
NOTE:
1. REPLACE FRAMES 1-101 (SEE REPAIR TABLE) BETWEEN BOILER PLANT AND ABOVE-
GROUND STEAM VAULT "MAUSOLEUM"
2. INSTALL FRAMES 6"-12" HORIZONTALLY FROM ORIGINAL FRAMES. DO NOT REMOVE
ORIGINAL FRAMES UNTIL NEW ASSEMBLIES ARE COMPLETELY INSTALLED.
1/4 3" CUT, REMOVE, AND REPLACE TOP SLAB
1'
DRILL AND EPOXY #5 "L" BARS @ 12"
O.C. W/ 12" EMBEDMENT
12"
24"
CONT. #5 BARS @ 12" O.C. TOP & BOTT.
6' - 7 1/2"
#5 BARS @ 12" OC
TOP & BOTT
NOTE:
1. CONTRACTOR TO FIELD-VERIFY ALL DIMENSIONS
2. PIPES AND SUPPORTS NOT SHOWN FOR CLARITY
ROUGHEN SURFACE TO 1/4"
AMPLITUDE AND APPLY
BONDING AGENT, TYP
2" PROTECTION BOARD
WATERPROOFING
EXISTING CONCRETE
TUNNEL
CONTINUOUS HYDROPHILIC
WATER STOP
SLOPE PROTECTION BOARD FOR DRAINAGE
ETCH FRAME NUMBER INTO FACE
OF STEEL COLUMN AT 2 SIDES. (SEE
REPAIR TABLE FOR DESIGNATED
FRAME NUMBERS)
EXISTING TUNNEL TOP SLAB
NEW TUNNEL TOP SLAB
CONTINUOUS HYDROPHILIC
WATERSTOP
ROUGHEN EXISTING SURFACE TO 1/4"
AMPLITUDE AND APPLY BONDING AGENT
#5 BARS @ 12"
EPOXY-DOWEL REBAR INTO
EXISTING W/ 6" MIN EMBEDMENT.
1/2" x 9" x 10" GALV. PLATE W/ (4) 3/8"
DIA. EXPANSION ANCHORS, GALV.
COAT ASSEMBLY W/ MIN. 1/8" LAYER
OF EPOXY AFTER INSTALLATION.
NOTES:
1. SEE REPAIR TABLE FOR ANCHOR LOCATIONS.
2. ADDITIONAL STEEL AND SUPPORTS NOT SHOWN FOR CLARITY
1/4 3@121/2" x 1'-0" x 1'-5" GALV. STEEL PLATE
WELDED TO ANCHOR TUBES.
GALV. SHIM PLATES AS REQUIRED
1/2" x 4" x 8" GALV. PLATE 1/4 3"
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
NON-SPRINKLERED
C U s e rs
\l la i\ D o c u m e n ts
\1 .1
.0
T u n n e l M o d e l_ lla i.
rv t /1
/2
:1 :2
P
M
SB101
STEAM TUNNEL PLANS AND
SECTIONSRING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
1 SEPTEMBER 2017 MV LL
100% BID SET
MILWAUKEE VAMC
BLDG 112
SCALE: 1" = 20'-0"SB101
1 TUNNEL PLAN
N
SCALE: 3/4" = 1'-0"SB101
2 TYPICAL EXIST TUNNEL SECTION
SCALE: 3/4" = 1'-0"SB101
3 TYPICAL REPAIR SECTION
SCALE: 3/4" = 1'-0"SB101
6 TOP SLAB REPLACEMENT/WATERPROOFING DETAIL
SCALE: 3" = 1'-0"SB101
4 FRAME LABEL DETAIL
SCALE: 3/4" = 1'-0"SB101
5 CONNECTION TO EXISTING TOP SLAB
SCALE: 3/4" = 1'-0"SB101
7 ANCHOR
00+00
FACE OF TUNNEL AT
BUILDING 112
1 2 3 4 5 6 7 8
SB101
SB101
01+00
9 10 11 12 13 14 15 16 17 18 19 20
21 22 23 24 25 26 27
ABANDONED STEAM PIPE. CUT AND REMOVE.
INFILL OPENINGS IN WALLS W/ 4000 PSI CONCRETE
MIX. SEAL WITH WATERPROOF JOINT MATERIAL.
ABANDONED WATER LINE. CUT AND REMOVE WITHIN TUNNEL
EXTENTS. INFILL OPENINGS WITH 4000 PSI CONCRETE MIX. SEAL WITH
WATERPROOF JOINT MATERIAL
02+00 02+79
28 29 30
37 38
Level 1 100' - 0"
SB101
03+00
04+00 05+00 05+50
BEGINNING OF
WATERPROOFING
EXCAVATION
03+55
04+95 05+40
AREA OF TOP SLAB
REPLACEMENT
41 42 43 44
45 46 47 48 49 50 51
52 53 54 55 56 57 58 59 60 61 62 63 64 65
66 67 68 69 70 71 72
06+00
END OF
WATERPROOFING
EXCAVATION
05+80
72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88
07+00
07+79
END OF WORK AT TUNNEL
INTERFACE WITH ABOVE-
GROUND VAULT
89 90 91 92 93 94 95 96 97
99 100 101
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
GUIDON DESIGN INC.
905 N. CAPITOL AVE. SUITE 100 | INDIANAPOLIS, IN. 46204
317.800.6388 | WWW.GUIDONDESIGN.COM
SUSTAINABLE ARCHITECTURE + ENGINEERING
PROJECT LEAD
Architect, Structural Engineer, Civil Engineer
NON-SPRINKLERED
C U s e rs
\l la i\ D o c u m e n ts
\1 .1
.0
T u n n e l M o d e l_ lla i.
rv t /1
/2
:1 :2
P
M
SB301
SECTIONS
RING & DuCHATEAU LLP
17400 W. CAPITOL DRIVE
BROOKFIELD, WI 53045
REPAIR CAMPUS STEAM TUNNEL
AND STRUCTURAL SUPPORTS
MILWAUKEE VAMC
695-17-119
1 SEPTEMBER 2017 MV LL
100% BID SET
MILWAUKEE VAMC
BLDG 112
SCALE: 1/8" = 1'-0"SB301
1 STEAM TUNNEL PROFILE SECTION
M A
T C
H
LI
N E
A -A
M A
T C
H
LI
N E
A -A
M A
T C
H
LI
N E
B -B
M A
T C
H
LI
N E
B -B
NOTES:
1. STEAM PIPES TO REMAIN OPERATIONAL DURING DURATION OF CONSTRUCTION.
CONTRACTOR TO PLACE PROPER SAFEGUARDS IN PLACE TO PROTECT PIPES DURING
CONSTRUCTION AND TO PROMOTE SAFETY OF WORKERS.
2. THIS SHEET TO BE PRINTED IN COLOR FOR FULL CONTEXT.
| Sheets |
| GI000 - COVER SHEET |