Requirements for Identification and Replacement of A307 Bolts MemO.pdf
PDF 379 KB Posted
- Attached to
- Z2NB--Project No. 539-20-101 - Replace Fort Thomas Boilers. Federal contract opportunity
- Solicitation number
- 36C25024B0075
About this file
This is an urgent Department of Veterans Affairs (VA) memorandum dated December 13, 2024, addressing requirements for identifying and replacing ASTM A307 bolts on steam and hot water piping systems at all VA medical centers (VAMCs). The memo states that ASTM A307 bolts, previously specified in VHA Master Specifications for use on steam and hot water pipe flanges, lack the necessary material strength at elevated temperatures and must be replaced with ASTM A193 bolts.
The memo establishes two critical deadlines: VISN Capital Asset Managers must provide a list of impacted construction projects to the Office of Healthcare Engineering by January 3, 2025, and all VAMCs must complete surveys of existing steam and hot water piping systems by June 18, 2025. Network Directors must immediately ensure all VAMCs review specifications for projects in design and construction, modify contracts to remove A307 bolts where specified, and develop interim safety measures for facilities where these bolts are identified, particularly in high and medium pressure systems operating over 50 pounds per square inch.
View the file
Other files for this federal contract opportunity
| File | Type | Posted |
|---|---|---|
| 36C25024B0075 0012.docx | DOCX document | |
| 36C25024B0075 0011.docx | DOCX document | |
| 36C25024B0075 0010.docx | DOCX document | |
| RFIs and Answers.pdf | ||
| Drawings ADDENDUM 1.pdf | ||
| Revised and Final Specs.pdf | ||
| 36C25024B0075 0009.pdf | ||
| 36C25024B0075 0008.pdf | ||
| 36C25024B0075 0007.pdf | ||
| 36C25024B0075 0006.docx | DOCX document | |
| 36C25024B0075 0005.docx | DOCX document | |
| 36C25024B0075 0004.docx | DOCX document | |
| 36C25024B0075 0003.docx | DOCX document | |
| 36C25024B0075 0002.docx | DOCX document | |
| Site Visit Sign In .pdf | ||
| 36C25024B0075 0001.docx | DOCX document | |
| Attachment II - Specifications.pdf | ||
| 36C25024B0075_1.docx | DOCX document | |
| Attachment VI - JAs.pdf | ||
| Attachment III - Drawings I.pdf | ||
| Attachment I - DBA WD.pdf | ||
| Attachment V - Limitation on Subcontracting Cert.pdf | ||
| Attachment VII - RFI Form.pdf | ||
| Attachment IV - Drawings II.pdf | ||
| Attachment VIII - EMR Form.pdf |
Show all 25
On GovTribe
Work with this file on GovTribe
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Department of Veterans Affairs
Memorandum
Date:
From: Acting Assistant Under Secretary for Health for Support (19)
Subj: URGENT: For Action: Requirements for Identification and Replacement of A307
Bolts on Steam and Hot Water Piping Systems (VIEWS 12473639)
To: Veterans Integrated Service Network (VISN) Directors (10N1-23)
1. PURPOSE: This memorandum provides notification and information on requirements for the identification and replacement of American Society for Testing and Materials (ASTM) A307 bolts (all grades) on steam and hot water piping systems for all Department of Veterans Affairs (VA) medical centers (VAMC).
2. BACKGROUND: Veterans Health Administration (VHA) Master Specifications for Hydronic Piping (Specification 23 21 13, Section 2.3) and Steam and Condensate Heating Piping (Specification 23 22 13, Section 2.3) indicate ASTM A307 bolts for use on steam and hot water pipe flanges. However, the ASTM A307 bolt (all grades) is considered a general-purpose bolt and does not possess the necessary material strength at elevated temperatures for use on steam and hot water piping systems.
These specifications are being updated to indicate ASTM A193 bolts as the appropriate fastener for steam and hot water piping systems. The current VHA Master Specifications can be accessed at:
https://www.cfm.va.gov/TIL/spec.asp.
All VAMCs must complete a survey of their existing steam and hot water piping systems and develop a replacement plan, prioritizing high and medium pressure steam and hot water piping systems operating over 50 pounds per square inch. If ASTM A307 bolts (all grades) are identified, an Interim Safety Measure must be developed to ensure the safety of staff and the facility until replacement is complete.
3. DECISION: Effective immediately, Network Directors must ensure all VAMCs in their VISN review their specifications for projects in design and correct any references to ASTM A307 bolts, and for projects in construction, assess if ASTM A307 bolts are specified for use on any steam or hot water piping system. If ASTM A307 bolts are indicated, the construction contract must be modified to remove the ASTM A307 bolts. VISN Capital Asset Managers (CAM) must provide a list of impacted construction projects via email to the Office of Healthcare Engineering (OHE) at VHAHealthcareEng@va.gov by Friday, January 3, 2025.
All VAMCs must develop a plan to survey existing steam and hot water piping systems by Wednesday, June 18, 2025, and notify their VISN CAM upon completion of the survey.
Page 2.
Subj: For Action: Requirements for Identification and Replacement of A307 Bolts on Steam and Hot Water Piping Systems (VIEWS 12473639)
4. For additional information or questions regarding this memorandum, please contact OHE at VHAHealthcareEng@va.gov.