About this file

This solicitation is for a multi-phase project to upgrade the existing fire alarm system at the Louis Stokes Veterans Affairs Medical Center in Cleveland, Ohio. Phase 1 involves installing a new campus fiber loop and NotifierA head end units, which will be fully tested prior to proceeding. Phase 2 consists of tracing conduits and wiring of existing field devices such as strobes, horns, pull stations, and smoke detectors, rewiring as needed and reprogramming devices to report to the correct NotifierA control panel located in each smoke compartment or zone. The project magnitude is between $2,000,000 and $5,000,000 and must be completed within 425 calendar days of receiving the notice to proceed. Bidders must register on SAM.gov and ensure their registration remains accurate, complete and unexpired through the bid opening date. Questions regarding this solicitation must be submitted in writing to the contracting officer by the specified deadline.

View the file

Other files

File Type Posted
36C25020B0065 0010.docx DOCX document
WD Cuyahoga 07.30.2021.pdf PDF
280500 - COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY. - Revised 7-26 -2021.pdf PDF
36C25020B0065 0009.docx DOCX document
36C25020B0065 0008.docx DOCX document
36C25020B0065 0007.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part7.pdf PDF
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part6.pdf PDF
36C25020B0065 0006.docx DOCX document
36C25020B0065 0005.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part5.pdf PDF
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part4.pdf PDF
36C25020B0065 0004.docx DOCX document
36C25020B0065 0003.docx DOCX document
36C25020B0065 0002.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part2.pdf PDF
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part1 (1).pdf PDF
36C25020B0065 0001.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Specifications 02.pdf PDF
36C25020B0065_1.docx DOCX document
CUY WD 04.30.2021.pdf PDF
VAMC Health Requirements 05.26.2021.pdf PDF
Notifier JA Complete REDACTED.pdf PDF
VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
Corwin Russwin JA Complete REDACTED.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CM

P

P

P

WFTS

P H

CM

P

WFTS

P H

P

CM

P WF TS

P H

CM

P

CM

CM

CM

J

█N3 L1 D38

█N3 L1 D37

FARA

█N3 L1 M40 █N3 L1 M17

█N3 L1 M67

█N3 L1 M18

█N3 L1 D56

█N3 L1 D71

█N3 L1 D61

█N3 L1 D29

█N3 L1 D28

█N3 L1 D70

█N3 L1 D31

█N3 L1 M16

█N3 L1 M99

█N9 L6 M16

█N3 L1 D36

█N3 L1 M23

█N3 L1 M21

█N3 L1 M20█N3 L1 M19

█N9 L6 M17

█N3 L1 D35

█N3 L1 D25

█N3 L1 D26

█N3 L1 D34 █N3 L1 D27

█N3 L1 M28

█N3 L1 M41

FARA

█N3 L1 D20

█N3 L1 D19

█N3 L1 M24 █N3 L1 M26

█N3 L1 M25

█N9 L6 M18

FARA

█N3 L1 D80

█N3 L1 M90 █N3 L1 D49

█N3 L1 D48█N3 L1 D47

█N3 L1 D46

█N3 L1 D45

█N3 L1 M22

█N3 L1 D32

█N3 L1 D17

█N3 L1 D18

█N3 L9 M34 EOL█N3 L1 M29█N3 L1 M30

Toilet/ Shower-1 5A141A-1

Toilet/ Shower-1 5A143A-1

Data Closet-1 5A149-1

Toilet/ Shower-1 5A147A-1

Toilet/ Shower-1 5A151A-1

Ante Room-1 5A150-1

Toilet/ Shower-1 5A158A-1

Toilet/ Shower-1 5A156A-1

Toilet/ Shower-1 5A154A-1

Toilet/ Shower-1 5A159A-1

Patient Exp.

Office-1 5A144-1

Ante Room-1 5A137-1

Isolation-1 5A136-1

Toilet/ Shower-1 5A136A-1

Toilet/ Shower-1 5A134A-1

Bedroom-1

5A134-1

Bedroom-1

5A130-1

Toilet/ Shower-1 5A130A-1

Toilet/ Shower-1 5A128A-1

Bedroom-1

5A122-1

Toilet/ Shower-1 5A122A-1

Toilet/ Shower-1 5A124A-1

Toilet/ Shower-1 5A119A-1

Stair #8-1 5A118-1

Bedroom-1

5A117-1

Toilet/ Shower-1 5A117A-1

Storage Room-1 5A116-1

Elect.

Room-1 5A114-1

Toilet/ Shower-1 5A115A-1

Bedroom-1

5A115-1

Toilet/ Shower-1 5A161A-1

Toilet/ Shower-1 5A162A-1

Toilet/ Shower-1 5A165A-1

Closet-1 5A111-1

Meds Room-1

5A113C-1

Closet-1 5A108-1

Clean Utility-1 5A107-1 Dict/

Report-1 5A113B-1

Soiled Utility-1 5A106-1

Toilet/ Shower-1 5A167A-1

Toilet/ Shower-1 5A168A-1

Toilet/ Shower-1 5A110A-1

Toilet/ Shower-1 5A104A-1

Bedroom-1

5A104-1

Bedroom-1

5A103-1

Toilet/ Shower-1 5A101A-1

Toilet/ Shower-1 5A103A-1

Comm.

Room-1 5A100-1

Bedroom-1

5A101-1

Toilet/ Shower-1 5A172A-1

Toilet/ Shower-1 5A171A-1

Office-1 5C121-1

Office-1 5C120-1

Office-1 5C119-1

Corridor-1 5C100F-1

Storage-1 5C115-1

Stair #5-1 5C112-1

Psychology Office-1 5C102-1

Phychiatry Inpatient-1

5A174-1

Surgical, Social Work-1 5A175-1

Toilet/ Shower-1 5A173A-1

Geriatrics Administration-1

5C107-1Toilet/ Shower-1 5B170A-1

Toilet/ Shower-1 5B168A-1

Toilet/ Shower-1 5B167A-1

Toilet/ Shower-1 5B166A-1

Toilet/ Shower-1 5B164A-1

Geriatrics Office-1 5C110-1

Geriatrics Administration-1

5B171-1

Office-1 5B101-1

Office-1 5B103-1

Geriatrics Office-1 5B169-1Storage-1

5B106-1

Elect.-1 5C111-1

Toilet/ Shower-1 5B100A-1

Toilet/ Shower-1 5B108A-1

Toilet/ Shower-1 5B110A-1

Bedroom-1

5B110-1

Elect.-1 5B115-1

Toilet/ Shower-1 5B114A-1

Bedroom-1

5B117-1

Toilet/ Shower-1 5B117A-1

Toilet/ Shower-1 5B118A-1

Bedroom-1

5B118-1

Stair #3-1 5B119-1

Toilet/ Shower-1 5B121A-1

Toilet/ Shower-1 5B161A-1

Toilet/ Shower-1 5B160A-1

Toilet/ Shower-1 5B153A-1

Toilet/ Shower-1 5B143A-1

Bedroom-1

5B141-1

Toilet/ Shower-1 5B141A-1

Toilet/ Shower-1 5B140A-1

Storage-1 5B140-1

Bedroom-1

5B123-1

Bedroom-1

5B126-1

Bedroom-1

5B128-1

Toilet/ Shower-1 5B128A-1

Toilet/ Shower-1 5B132A-1

Bedroom-1

5B132-1

Bedroom-1

5B134-1

Toilet/ Shower-1 5B134A-1

Toilet/ Shower-1 5B136A-1

Office-1 5B135-1

Social Worker-1 5B142-1

Office-1 5B133-1

Geriatric Fellow-1 5B144-1

Work Area 5B138

Soiled Utility-1 5B129-1

Soiled Utility 5B150

Corridor 5B100F

Corridor 5B100H

Work 5A113D

Alcove 5A153

Alcove 5A145

Alcove 5A126

Conference Room-1 5B139-1

Bedroom-1

5B136-1

Chute-1 5B145-1

Chute-1 5B131-1

Elect.-1 5B152-1

Elect.-1 5B125-1

Corridor-1 5B100B-1

Storage-1 5B162-1

Nourish-1 5B163-1

Crash 5B113A

Toilet-1 5B165-1

Office-1 5B107-1

Bedroom-1

5B108-1

Bedroom-1

5B109-1

Toilet/ Shower-1 5B109A-1

Bedroom-1

5B114-1 2 Bedroom-1

5B100-1

Storage-1 5B102-1

Bedroom-1

5B104-1

Toilet/ Shower-1 5B104A-1

Geriatrics Administration-1

5C109-1

Alcove 5C106

Lockers-1 5C104-1

Lounge-1 5C103-1

Ante Room-1 5A163-1

Toilet-1 5A166-1

Bedroom-1

5A109-1

Toilet/ Shower-1 5A109A-1

Corridor-1 5A100B-1

Control Station 5A113

Nourish Room-1 5A164-1

Alcove 5A112

Bedroom-1

5A110-1

Elect.

Room-1 5A125-1

Soiled Utility-1 5A127-1

Elect.

Room-1 5A152-1

Corridor 5A100H

Chute-1 5A146-1

Chute-1 5A132-1

Bedroom-1

5A124-1

Bedroom-1

5A128-1

Toilet-1 5A133-1

Nursing Administration-1

5C124-1

Nursing Administration-1

5C125-1

Nursing Administration-1

5C123-1

Elect.-1 5C128-1

Corridor 5A100F

Corridor-1 5B100G-1

Corridor 5A100A

Clean Utility-1 5A129-1

EMS-1

5A148-1

EMS-1

5A131-1

Comm.

Room-1 5B156-1

Shaft-1 5B157-1

Corridor 5B100E

Storage-1 5A157-1

Toilet/ Shower-1 5B147A-1

Corridor 5B100C

Toilet/ Shower-1 5B149A-1

Linen-1 5B151-1

Office, MD-1

5A142-1

Office-1 5A135-1

Work Area 5A139

Corridor 5A100E

Office-1 5A102-1

Work Area 5A105

Team Work

Room-1 5A169-1

Storage Room-1 5C126-1

Corridor-1 5C100E-1

Work Area-1

5C117-1 Office-1 5C118-1

Dict./ Report-1 5B113C-1

Storage-1 5B105-1

Office-1 5B122-1

Office-1 5B154-1

EMS-1

5B130-1

EMS-1

5B146-1

Clean Utility-1 5B127-1

Clean Utility 5B148

Bedroom-1

5B121-1

Closet-1 5B111-1

Corridor 5B100D

Meds Room-1

5B113B-1

Corridor-1 5C100A-1

Women's Restroom-1

5C101-1

Men's Restroom-1

5C100-1

Stair #6-1 5C116-1

Conference Room-1 5C113-1

Chief Nursing-1 5C114-1

Bedroom-1

5A119-1

Bedroom-1

5B155-1

Bedroom-1

5B153-1

Bedroom-1

5B149-1

Bedroom-1

5B147-1

Bedroom-1

5B143-1

Bedroom-1

5B158-1

Stair #4-1 5B159-1

Stair #9-1 5A160-1

Bedroom-1

5A159-1

Patient Elevators 5C100C

Office-1 5C127-1

Nursing Administration-1

5C122-1

Bedroom-1

5B137-1

Bedroom-1

5B161-1

Bedroom-1

5B160-1

Bedroom-1

5B170-1

Bedroom-1

5B168-1

Bedroom-1

5B167-1

Bedroom-1

5B166-1

1 Bedroom Isolation-1 5B164-1

Bedroom-1

5A173-1

Physical & Occupational

Therapy-1 5C105-1

Geriatrics Medical

Director-1 5C108-1

Bedroom-1

5A165-1

Bedroom-1

5A167-1

Bedroom-1

5A168-1

Bedroom-1

5A171-1

Bedroom-1

5A172-1

Bedroom-1

5A161-1

Bedroom-1

5A162-1

Bedroom-1

5A147-1

1 Bedroom Isolation-1 5A151-1

Bedroom-1

5A154-1

Bedroom-1

5A156-1

Bedroom-1

5A158-1

Bedroom-1

5A143-1

Ante Room-1 5A140-1

Patient/ Visitor

Lounge-1 5A138-1

Isolation-1 5A141-1

Clean Linen-1 5A155-1

Equipment-1 5A123-1

Toilet/ Shower-1 5B123A-1

Toilet/ Shower-1 5B126A-1

Service Elevators 5C100D

Toilet/ Shower-1 5B158A-1

Toilet/ Shower-1 5B155A-1

Corridor 5A100G

Head Nurse-1 5A121-1

Corridor-1 5B100J-1

Corridor-1 5A100D-1

Corridor 5C100B

Corridor 5A100C

EXPANDER PNL

EXPANDER PNL

Elect 5B100G-2

K21 K24 K25 K26 K27 K29 K30 K30a K34 K35 K36 K37 K40 K42

J21 J24 J25 J26 J27 J29 J30 J30a J34 J35 J36 J37 J40 J42

H23 H28a H30 H30a H34 H35 H36 H37 H42H41

F28a

H28a

F30 F30a

D30aD30

H24 H24b H26aH25a

L25 L26 L27 L29 L30 L33 L34 L35 L36 L37 L39 L42L24

M24M23

Q8 Q12Q9

N8 N12N9

V119V118 V122

V19V18 V22V20

T18

Q18

N118

T20

R20

T23A

R23A

Q20

P20 P23

L2L1 L17 L18 L20 L23 L16L15L13L7L6L5 L12L9L8

K3K1 K17 K18 K2

K16K15K13K7K6K5 K12K9K8

J1

H2H1 H17a H18b H2

H16aH14H7H6H4 H12H8

J20J18J17J16J15J13J12J11aJ8J7J6J5J3

H11a H15a

F12

D12

F11a

D11a

F14

D14

M20

V122 V124

V22 V24

T23A T24

R224

R23A

Q23 Q24

P23A

Q30 Q33 Q34

N30 N33 N34

43J

43L

15C E1

16C E1

18E E1

20A E1

FATC

XR

XR

XR

FAZE

FANE

NEW

NEW

FAZE

NEW

N E

W

NEW

XR

NEW

NEW

NEW

FAZE

NEW

NEW

NEWN

E

W

XR

NEW

FAZE

NEW1

XR

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title Project NumberProject Title

Building Number

Approved: Location

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Office of

Facilities

Management

FULLY SPRINKLERED

Date

05/14/21

Checked Drawn

Drawing Number

Dwg. of DateRevisions:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

D

C

B

A

E

F

D

C

B

A

E

F

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

VA FORM 08-6231, OCT 1978

DOCUMENT SET MUST BE PRINTED IN COLOR

BID DOCUMENTS SUBMISSION 05/14/21 17069

NODE 1.13 - MAIN BUILDING

FIFTH FLOOR - ADDRESSABLE

541-18-101UPGRADE FIRE ALARM

MPL CPC

FA-A-1.13

8' 16' 32' 64'

1/16" = 1' 0"

FIFTH FLOOR FIRE ALARM PLAN - ADDRESSABLE - NODE 1.13 1

NOT TO SCALE

NODE 1.13 - FIFTH FLOOR

FIRE ALARM KEY PLAN

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - FIFTH FLOOR - NODE 1.13

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Water Flow Switch N3 L1 M16 N1.13 L4

Pull Station N3 L1 M17 N1.13 L4

Pull Station N3 L1 M18 N1.13 L4

Tamper Switch N3 L1 M19 N1.13 L2

Water Flow Switch N3 L1 M20 N1.13 L2

Pull Station N3 L1 M21 N1.13 L2

Pull Station N3 L1 M22 N1.13 L1

Control Module N3 L1 M23 N1.13 L2

Pull Station N3 L1 M24 N1.13 L1

Tamper Switch N3 L1 M25 N1.13 L1

Water Flow Switch N3 L1 M26 N1.13 L1

Pull Station N3 L1 M28 N1.13 L2

Control Module N3 L1 M29 N1.13 L2 WEST DOOR HOLDS

Control Module N3 L1 M30 N1.13 L2 EAST DOOR HOLDS

Control Module N3 L1 M40 N1.13 L4

Control Module N3 L1 M41 N1.13 L2

Pull Station N3 L1 M67 N1.13 L4

Control Module N3 L1 M90 N1.13 L1

Tamper Switch N3 L1 M99 N1.13 L4

Control Module N3 L9 M34 DEMOLISH - DO NOT RECONNECT EXPANDER PANEL TRIGGER/MONITOR

Firemans Phone N9 L6 M16 N1.1 L3 FED FROM BASEMENT

Firemans Phone N9 L6 M17 N1.8 L1 FED FROM SECOND FLOOR

Firemans Phone N9 L6 M18 N1.2 L2 FED FROM BASEMENT

Smoke Detector NEW DEVICE N1.13 L2

Smoke Detector NEW DEVICE N1.13 L2

Smoke Detector NEW DEVICE N1.13 L3

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - FIFTH FLOOR - NODE 1.13

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Smoke Detector N3 L1 D17 N1.13 L2

Smoke Detector N3 L1 D18 N1.13 L2

Smoke Detector N3 L1 D19 N1.13 L1

Smoke Detector N3 L1 D20 N1.13 L2

Smoke Detector N3 L1 D25 N1.13 L2

Smoke Detector N3 L1 D26 N1.13 L2

Smoke Detector N3 L1 D27 N1.13 L2

Smoke Detector N3 L1 D28 N1.13 L4

Smoke Detector N3 L1 D29 N1.13 L4

Smoke Detector N3 L1 D31 N1.13 L4

Smoke Detector N3 L1 D32 N1.13 L1

Smoke Detector N3 L1 D34 N1.13 L2

Smoke Detector N3 L1 D35 N1.13 L2

Smoke Detector N3 L1 D36 N1.13 L2

Smoke Detector N3 L1 D37 N1.13 L4

Smoke Detector N3 L1 D38 N1.13 L4

Smoke Detector N3 L1 D45 N1.13 L1

Smoke Detector N3 L1 D46 N1.13 L1

Smoke Detector N3 L1 D47 N1.13 L1

Smoke Detector N3 L1 D48 N1.13 L1

Smoke Detector N3 L1 D49 N1.13 L1

Smoke Detector N3 L1 D56 N1.13 L2

Smoke Detector N3 L1 D61 N1.13 L4

Smoke Detector N3 L1 D70 N1.13 L4

Smoke Detector N3 L1 D71 N1.13 L3

Smoke Detector N3 L1 D80 N1.13 L1

CODED NOTES

1 PROVIDE NEW FIRE ALARM EQUIPMENT AS INDICATED. REFER TO ENLARGED PLANS ON SUBSEQUENT SHEETS FOR

ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING AND DIGITAL AUDIO FIBER OPTIC CABLE FROM NEW NODE EQUIPMENT TO NEW ZONE EQUIPMENT. CONNECT NEW FIRE ALARM POWER SUPPLY AND DIGITAL AUDIO AMPLIFIER COMPLETE AND

PROVIDE (5) NEW ADDRESSES FOR POWER SUPPLY AND (1) NEW ADDRESS FOR AMPLIFIER.

REMOVE EXISTING FIRE ALARM AMPLIFIER(S), EXTENDER EQUIPMENT, AND ALL ASSOCIATED CONTROL/MONITORING MODULES COMPLETE BACK TO SOURCE AFTER NEW FIRE ALARM SYSTEM INSTALLED, EXISTING DEVICES ARE

RECONNECTED, AND COMPLETE SYSTEM TESTING HAS BEEN COMPLETED.

DISCONNECT SLC LOOP WIRING BETWEEN ZONES AND REMOVE EXISTING CONDUIT AND WIRING. DEVICE SHOWN IS ASSUMED TO BE THE LOCATION OF THE CONNECTION BETWEEN ZONES. FIELD VERIFY CONNECTION LOCATION.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING TO EXISTING ADDRESSABLE FIRE ALARM DEVICE TO MIGRATE EXISTING DEVICES TO NEW LOOP. CONNECT DEVICES COMPLETE AND PROVIDE NEW ADDRESS FOR ALL DEVICES ON EXISTING LOOP. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING ALL DEVICES IN THE ZONE HAVE BEEN MIGRATED TO NEW

LOOP.

REMOVE EXISTING FIRE ALARM REMOTE ANNUNCIATOR COMPLETE. PATCH AND PAINT WALL TO MATCH EXISTING.

A NEW COMPARTMENT IS BEING CONSTRUCTED AS PART OF AN ADDITION PROJECT THAT IS CURRENTLY IN DESIGN. VA PROJECT NUMBER 541-377 "SCI AND ACUTE SPECIAL PROGRAMS ADDITION". FIRE ALARM ZONE EQUIPMENT IS BEING PROVIDED UNDER THE SCOPE OF THAT PROJECT. PROVIDE AN ADDITIONAL SLC LOOP #5 FOR FUTURE USE TO

CONNECT ADDRESSABLE DEVICES IN THIS COMPARTMENT.

FIRE ALARM DEVICE SCHEDULE NOTES

FA EXISTING DEVICE ADDRESS AND FUNCTION INFORMATION IS FOR REFERENCE ONLY. INFORMATION IS SOURCED

FROM PREVIOUS FIRE ALARM SYSTEM STUDY PROJECT AS WELL AS PROJECT FIRE ALARM SUBMITTALS AND AS-BUILT DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFIRMING EXISTING DEVICE ADDRESS AND

FUNCTION PRIOR TO RE-PROGRAMMING DEVICE TO NEW SYSTEM.

FB NEW NODE/LOOP INDICATES THE DESTINATION NODE AND LOOP TO WHICH THE EXISTING FIRE ALARM DEVICE SHALL BE RE-CONNECTED. PROVIDE NECESSARY FIRE ALARM CONDUIT AND WIRING REQUIRED TO RECONNECT EXISTING DEVICES TO NEW NODE AND LOOP AS INDICATED. CONTRACTOR SHALL DOCUMENT NEW DEVICE

ADDRESS FOR ALL RE-CONNECTED FIRE ALARM DEVICES.

FC CONTRACTOR SHALL PROVIDE ALL NECESSARY PROGRAMMING TO TRANSITION EXISTING DEVICE TO NEW FIRE ALARM BACKBONE SYSTEM. PROGRAMMING INCLUDES BUT IS NOT LIMITED TO DEVICE ADDRESS, UPDATING DEVICE LOCATION, DEVICE FUNCTION, DEVICE TYPE, ETC. CONTRACTOR SHALL BE PERMITTED TO MIGRATE EXISTING DEVICES FROM PREVIOUS DATABASE, IF POSSIBLE, BUT SHALL BE RESPONSIBLE FOR MANUALLY UPDATING THE AFORMENTIONED FIELDS AND MANUALLY PROGRAMMING ALL FIRE ALARM DEVICES WHERE DATA

MIGRATION FAILS.

FD REFER TO FIRE ALARM INPUT/OUTPUT MATRIX FOR DEVICE PROGRAMMING.

FE REFER TO FIRE ALARM SYSTEM SPECIFICATIONS FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

FIRE ALARM GENERAL NOTES

F1 ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE FIRE ALARM CONTROL SYSTEM IN

ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWINGS, WIRING DIAGRAMS, AND DETAILS.

F2 ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE CONDUIT SYSTEM.

F3 SMOKE DETECTORS SHALL BE INSTALLED ON CEILINGS WITH SPACING NOT TO EXCEED MANUFACTURER'S

RECOMMENDATION AND IN ACCORDANCE WITH NFPA 72.

F4 SMOKE DETECTORS SHALL BE INSTALLED WITHIN 5'-0" OF CENTERLINE OF SMOKE DOORS ON HOLD-OPEN DEVICES.

DETECTORS SHALL BE INSTALLED ON EACH SIDE OF THE DOOR PER VA FIRE PROTECTION DESIGN MANUAL.

F5 FIRE ALARM SYSTEM SHALL BE SUB-DIVIDED INTO ZONES THAT CORRESPOND TO THE SMOKE COMPARTMENTS AND

SPRINKLER ZONES PER VA FIRE PROTECTION DESIGN MANUALS.

F6 ALL EXISTING FIRE ALARM DEVICES THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDED ALL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED DEVICES - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND THE EXTENT OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID

SUBMITTAL.

F7 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL BE

DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

F8 REFER TO THE LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED "XB", "XRR", OR "XN" AND REMOVE/BLANK OFF, RELOCATE, OR REPLACE THESE COMPONENTS AS

REQUIRED.

F9 CLOSELY COORDINATE ALL DEMOLITION WORK WITH THE GENERAL CONTRACTOR TO PROVIDE PATCHING AND PAINTING

FOR EXISTING WALLS WHERE DEVICES/PANELS ARE REMOVED.

F10 CONTACT THE ENGINEER IF A QUESTION SHOULD ARISE CONCERING THE STATUS OF ANY OUTLET, DEVICE, FIXTURE, ETC.

RS RS HD

P

TS WF WF TS

PH

P

P

P

P

P

P

HDHD

TS WF

P H

P

P

P

CM

RS

RS

RS

CM

CM

P

HD

P

WF TS

PH

CMCM

CM

CM

HD

█N3 L5 D22

█N3 L5 D21

█N3 L5 D20

█N3 L5 D31

█N3 L5 D23

█N3 L5 D32 █N3 L5 D33

█N3 L5 D3

█N3 L5 D60

█N3 L5 D25

█N3 L5 M11

█N3 L5 D1

█N3 L5 D2

█N3 L5 M19

█N3 L5 D34

█N3 L5 D35

█N3 L5 M97

█N3 L5 M10 █N3 L5 D27

█N3 L5 D36

█N3 L5 D37

█N3 L5 M13 █N3 L5 D28

█N3 L5 D4

█N3 L5 M12

█N3 L5 D26

█N3 L5 M14 █N3 L5 D38

█N3 L5 D30

█N3 L5 D29

█N3 L5 D39

█N3 L5 D86

█N3 L5 M63

█N3 L5 D80

█N3 L5 M62

█N3 L5 D77 █N3 L5 D78

█N3 L5 D76 █N3 L5 D75

█N3 L5 D74

█N3 L5 D87

█N3 L5 D73

█N3 L5 M58

█N3 L5 D68█N3 L5 D67

█N3 L5 D66

█N3 L5 D62

█N3 L5 D61

█N3 L5 D88

█N3 L5 M59

█N3 L5 M60 █N3 L5 M61 █N9 L6 M18 EOL

█N3 L5 D63

█N3 L5 D64

█N3 L5 D65█N3 L5 M65

█N3 L5 D69█N3 L5 D70

█N3 L5 M64 █N3 L5 D71

█N3 L5 D90 █N3 L5 D91

█N3 L5 M55

█N3 L5 D92

█N3 L5 D93 █N3 L5 D94

█N3 L5 D95

█N3 L5 D99

█N3 L5 D98 █N3 L5 D96

█N3 L5 D97

█N3 L5 M54█N3 L5 M53

█N9 L6 M17 █N3 L5 M56

█N3 L5 M57

█N3 L5 D82

█N3 L5 D81 █N3 L5 D79

█N3 L5 D52

█N3 L5 D54█N3 L5 D89

█N3 L5 D53

█N3 L5 D72

NOT PROGRAMMED

█N9 L6 M16 EOL

█N3 L5 M22

█N3 L5 M21█N3 L5 M20█N3 L5 M23

Elect.

6A118C

Bath 6B128A

Elect.

6B124

Bath 6B120A

Bath 6B118A

Bath 6B114A

Bath 6B112A

Bath 6B108A

2 Bedroom 6B129

Bath 6B129A

Elect.

6B130Bath

6B131A

Bath 6B132A

2 Bedroom 6B132

2 Bedroom 6B136

Bath 6B136A

Bath 6B137A

1 Bedroom Isolation 6B137

Ante 6B139

2 Bedroom 6B143

Bath 6B143A

Elect.

6B144

Elect.

6B127

Elect.

6B133

Equipment Storage 6B126

Bath 6B102A

Bath 6B100A

Male Toilet 6C105

Female Toilet 6C104

Elect.

6B145

Bath 6B147A

Bath 6B150A

2 Bedroom 6B150

Bath 6B151A

2 Bedroom 6B151

Equipment Storage 6B101

Stair #5 6C109

Telehealth 6A136A

Closet 6A135A

Exam Room 6A129

Exam Room 6A130

Toilet 6A128

Soiled Utility 6A137

Elect.

6A140

Secretary 6A147

HAC

6A124

Office 6A123

Office 6A122

Office 6A121

Office 6A120

Bedroom 6A113C

Bath 6A113B

Closet 6A113D

Elect.

6A111

Telephone Data

Room 6A100

SCI/Social Work Office 6A102

Office 6A144

Clean Utility

6A118A

Bath 6A107A

Elect.

6A105

Corridor 6B100B

Corridor 6B100E

Living/Dining 6A113

Scrub 6A134

Ante 6B110

Linen Chute 6B125

HAC

6B123

Corridor 6B100D

Dictation Report 6B115B

HAC

6B135

Linen Chute 6B134

2 Bedroom 6B147

Electrical Closet

6B105A

SCI Office

Vocational Rehab 6A110

Tlt 6A118B Office

6A143

Outpaitent Clinic

Reception/ Wait

6A127

Linen Chute 6A125

HAC

6A142

Linen Chute 6A141

Corridor 6B100F

Comm 6B146

Comm.

6B119 Storage

6B116

Elect.

6B117

Closet 6B115C

Nurse Station 6B115

Staff Work 6C107

Staff Work 6C108

Corridor 6A100C

Corridor 6A100F

Elect.

6C100

Elect.

6C115

Elect.

6C101

Elect.

6A152

Corridor 6B100G

Elect.

6B113A

Conference Room 6C102

Soiled Utility 6B103

Elect.

6A112

Kitchen 6A113A

Wheelchair Storage 6B106

Laundry 6B149

Corridor 6A100B

Office 6B104

Urology Office 6A103

Stair #8 6A114

Office 6A116

Office 6A119

Office 6A117

Occupational Therapy 6A118

Office 6A145

Office 6A146

Corridor 6A100D

HAC

6A139

Office 6A131

Elect.

6A126

Office 6A133

Reception/Work 6A127A

Corridor 6A100G

Office 6A107C

Learning & Resource

Center 6A108

Office-SCI Officier 6A106

Staff Lounge 6A104

Corridor 6A100A

Office 6C103

Staff Toilet 6B138

Corridor 6B100C

Meds 6B115A

Office Nurse 6B109

Nourish 6B148

Office 6B107

Soiled Utility 6B121

Clean Utility 6B122

Stair #3 6B141

Male Toilet 6C112

Day Room 6B140

Corridor 6B100EA Office

6B142

Staff Lockers 6C110

Female Toilet 6C111

Clean Linen 6B111

Service Lobby

6C100C

Office 6A115

2 Bedroom 6B118

2 Bedroom 6B120

2 Bedroom 6B128

2 Bedroom 6B114

Stair #4 6B113

Stair #9 6A150

Office 6A148

Office 6A149

Social Work Office 6C114

2 Bedroom 6B131

2 Bedroom 6B112

2 Bedroom 6B100

2 Bedroom 6B102

1 Bedroom Isolation 6B108

Office 6C106

Recreational Therapy 6A107

Dining 6A101

SCI

Urology/Research/Pharmacist

6A151

Storage 6A107B

Office 6A147A

Corridor 6A100E

Cystostopic Room 6A135

Exam Room 6A132

Clean Utility 6A138

EMS

6C113

Corridor 6B100K

Corridor 6B100J

Staff Office

6B105B

Staff Charting 6B105

Elevator Lobby

6C100B

Corridor 6C100A

█N3 L5 M99█N3 L5 M98

(2) FCPS STROBE EXPANDER PANELS TRIGGERED BY OLD STROBE CIRCUIT N3 L9 M32 4 CIRCUITS EACH

GENERATED BY THEM.

PANEL 1: PANEL 2:

N3 L9 M32-1 N3 L9 M32-5 N3 L9 M32-2 N3 L9 M32-6 N3 L9 M32-3 N3 L9 M32-7 N3 L9 M32-4 N3 L9 M32-8

MAIN FIRE ALARM RISER TERMINAL CABINET OLD STROBE CIRCUITS N3 L9 M31-EOL, N3 L9 M33-EOL

█N3 L9 M32

█N3 L5 M66

K21 K24 K25 K26 K27 K29 K30 K30a K34 K35 K36 K37 K40 K42

J21 J24 J25 J26 J27 J29 J30 J30a J34 J35 J36 J37 J40 J42

H23 H28a H30 H30a H34 H35 H36 H37 H42H41

F28a

H28a

F30 F30a

D30aD30

H24 H24b H26aH25a

L25 L26 L27 L29 L30 L33 L34 L35 L36 L37 L39 L42L24

M24M23

Q8 Q12Q9

N8 N12N9

V119V118 V122

V19V18 V22V20

T18

Q18

N118

T20

R20

T23A

R23A

Q20

P20 P23

L2L1 L17 L18 L20 L23

L16L15L13L7L6L5 L12L9L8

K3K1 K17 K18 K2

K16K15K13K7K6K5 K12K9K8

J1

H2H1 H17a H18b H2

H16aH14H7H6H4 H12H8

J20J18J17J16J15J13J12J11aJ8J7J6J5J3

H11a H15a

F12

D12

F11a

D11a

F14

D14

M20

V122 V124

V22 V24

T23A T24

R224

R23A

Q23 Q24

P23A

Q30 Q33 Q34

N30 N33 N34

43J

NEW

NEW

NEW

EXPANDER PNL 1

EXPANDER PNL 2

FATC

FARA

XR

XR

XR

FAZE

FAZE

FAZE

FANE

CONDUIT STUB UP

TO PENTHOUSE

N E

W

NEW

NEW

NEW

NEW

XR

NEW

NEW

N E

W

NEW

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title Project NumberProject Title

Building Number

Approved: Location

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Office of

Facilities

Management

FULLY SPRINKLERED

Date

05/14/21

Checked Drawn

Drawing Number

Dwg. of DateRevisions:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

D

C

B

A

E

F

D

C

B

A

E

F

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

VA FORM 08-6231, OCT 1978

DOCUMENT SET MUST BE PRINTED IN COLOR

BID DOCUMENTS SUBMISSION 05/14/21 17069

NODE 1.14 - MAIN BUILDING

SIXTH FLOOR - ADDRESSABLE

541-18-101UPGRADE FIRE ALARM

MPL CPC

FA-A-1.14a

8' 16' 32' 64'

1/16" = 1' 0"

SIXTH FLOOR FIRE ALARM PLAN - ADDRESSABLE - NODE 1.14 1

NOT TO SCALE

NODE 1.14 - SIXTH FLOOR

FIRE ALARM KEY PLAN

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - SIXTH FLOOR - NODE 1.14

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Pull Station N3 L5 M59 N1.14 L1

Water Flow Switch N3 L5 M60 N1.14 L1

Tamper Switch N3 L5 M61 N1.14 L1

Control Module N3 L5 M62 N1.14 L2

Pull Station N3 L5 M63 N1.14 L2

Control Module N3 L5 M64 N1.14 L2

Control Module N3 L5 M65 N1.14 L2

Control Module N3 L5 M66 N1.14 L1

Pull Station N3 L5 M97 N1.14 L3

Control Module N3 L5 M98 N1.14 L2 RELEASE SECURED DOORS

Control Module N3 L5 M99 N1.14 L2 RELEASE SECURED DOORS

Control Module N3 L9 M32 N1.14 L2 EXPANDER PANEL TRIGGER/MONITOR

Firemans Phone N9 L6 M16 EOL N1.1 L3 FED FROM BASEMENT

Firemans Phone N9 L6 M17 N1.8 L1 FED FROM SECOND FLOOR

Firemans Phone N9 L6 M18 N1.2 L2 FED FROM BASEMENT

Firemans Phone N9 L6 M18 EOL N1.2 L2 FED FROM BASEMENT

Smoke Detector NEW DEVICE N1.14 L3

Smoke Detector NEW DEVICE N1.14 L2

Smoke Detector NEW DEVICE N1.14 L1

Smoke Detector NEW DEVICE N1.14 L1

Smoke Detector NEW DEVICE N1.14 L1

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - SIXTH FLOOR - NODE 1.14

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Smoke Detector N3 L5 D64 N1.14 L1

Smoke Detector N3 L5 D65 N1.14 L1

Smoke Detector N3 L5 D66 N1.14 L1

Smoke Detector N3 L5 D67 N1.14 L1

Smoke Detector N3 L5 D68 N1.14 L1

Smoke Detector N3 L5 D69 N1.14 L1

Smoke Detector N3 L5 D70 N1.14 L1

Smoke Detector N3 L5 D71 N1.14 L2

Smoke Detector N3 L5 D72 N1.14 L2

Smoke Detector N3 L5 D73 N1.14 L2

Smoke Detector N3 L5 D74 N1.14 L2

Smoke Detector N3 L5 D75 N1.14 L2

Smoke Detector N3 L5 D76 N1.14 L2

Smoke Detector N3 L5 D78 N1.14 L2

Smoke Detector N3 L5 D79 N1.14 L2

Smoke Detector N3 L5 D80 N1.14 L2

Smoke Detector N3 L5 D81 N1.14 L2

Smoke Detector N3 L5 D82 N1.14 L2

Smoke Detector N3 L5 D86 N1.14 L2

Smoke Detector N3 L5 D87 N1.14 L2

Smoke Detector N3 L5 D88 N1.14 L2

Smoke Detector N3 L5 D89 N1.14 L2

Smoke Detector N3 L5 D90 N1.14 L2

Smoke Detector N3 L5 D91 N1.14 L2

Smoke Detector N3 L5 D92 N1.14 L2

Smoke Detector N3 L5 D93 N1.14 L2

Smoke Detector N3 L5 D94 N1.14 L2

Smoke Detector N3 L5 D95 N1.14 L2

Smoke Detector N3 L5 D96 N1.14 L2

Smoke Detector N3 L5 D97 N1.14 L2

Heat Detector N3 L5 D98 N1.14 L2

Heat Detector N3 L5 D99 N1.14 L2

Pull Station N3 L5 M10 N1.14 L3

Pull Station N3 L5 M11 N1.14 L3

Pull Station N3 L5 M12 N1.14 L3

Pull Station N3 L5 M13 N1.14 L3

Pull Station N3 L5 M14 N1.14 L3

Pull Station N3 L5 M19 N1.14 L3

Water Flow Switch N3 L5 M20 N1.14 L3

Water Flow Switch N3 L5 M21 N1.14 L3

Tamper Switch N3 L5 M22 N1.14 L3

Tamper Switch N3 L5 M23 N1.14 L3

Tamper Switch N3 L5 M53 N1.14 L2

Water Flow Switch N3 L5 M54 N1.14 L2

Pull Station N3 L5 M55 N1.14 L2

Pull Station N3 L5 M57 N1.14 L2

Pull Station N3 L5 M58 N1.14 L2

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - SIXTH FLOOR - NODE 1.14

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Smoke Detector N3 L2 D60 N1.12 L1

Smoke Detector N3 L2 D61 N1.12 L1

Smoke Detector N3 L2 D62 N1.12 L1

Smoke Detector N3 L2 D63 N1.12 L1

Smoke Detector N3 L2 D64 N1.12 L1

Smoke Detector N3 L2 D65 N1.12 L1

Smoke Detector N3 L2 D66 N1.12 L1

Smoke Detector N3 L2 D67 N1.12 L1

Smoke Detector N3 L2 D68 N1.12 L1

Smoke Detector N3 L2 D69 N1.12 L1

Smoke Detector N3 L2 D70 N1.12 L1

Smoke Detector N3 L2 D71 N1.12 L1

Pull Station N3 L2 M55 N1.12 L1

Pull Station N3 L2 M60 N1.12 L1

Pull Station N3 L2 M61 N1.12 L1

Control Module N3 L2 M62 N1.12 L1

Smoke Detector N3 L5 D1 N1.14 L3

Smoke Detector N3 L5 D2 N1.14 L3

Smoke Detector N3 L5 D3 N1.14 L3

Smoke Detector N3 L5 D4 N1.14 L3

Heat Detector N3 L5 D5 N1.14 L3

Duct Detector N3 L5 D20 N1.14 L3 AC29 RETURN

Duct Detector N3 L5 D21 N1.14 L3

Duct Detector N3 L5 D22 N1.14 L3

Smoke Detector N3 L5 D23 N1.14 L3

Smoke Detector N3 L5 D25 N1.14 L3

Smoke Detector N3 L5 D26 N1.14 L3

Smoke Detector N3 L5 D27 N1.14 L3

Smoke Detector N3 L5 D28 N1.14 L2

Smoke Detector N3 L5 D29 N1.14 L2

Smoke Detector N3 L5 D30 N1.14 L2

Smoke Detector N3 L5 D31 N1.14 L3

Smoke Detector N3 L5 D32 N1.14 L3

Smoke Detector N3 L5 D33 N1.14 L3

Smoke Detector N3 L5 D34 N1.14 L3

Smoke Detector N3 L5 D35 N1.14 L3

Smoke Detector N3 L5 D36 N1.14 L3

Smoke Detector N3 L5 D37 N1.14 L3

Smoke Detector N3 L5 D38 N1.14 L2

Smoke Detector N3 L5 D39 N1.14 L2

Duct Detector N3 L5 D52 N1.14 L2

Duct Detector N3 L5 D53 N1.14 L2

Duct Detector N3 L5 D54 N1.14 L2

Heat Detector N3 L5 D60 N1.14 L3

Smoke Detector N3 L5 D61 N1.14 L1

Heat Detector N3 L5 D62 N1.14 L1

Smoke Detector N3 L5 D63 N1.14 L1

CODED NOTES

1 PROVIDE NEW FIRE ALARM EQUIPMENT AS INDICATED. REFER TO ENLARGED

PLANS ON SUBSEQUENT SHEETS FOR ADDITIONAL INFORMATION AND WORK

REQUIREMENTS.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING AND DIGITAL AUDIO FIBER OPTIC

CABLE FROM NEW NODE EQUIPMENT TO NEW ZONE EQUIPMENT. CONNECT NEW

FIRE ALARM POWER SUPPLY AND DIGITAL AUDIO AMPLIFIER COMPLETE AND

PROVIDE (5) NEW ADDRESSES FOR POWER SUPPLY AND (1) NEW ADDRESS FOR

AMPLIFIER.

REMOVE EXISTING FIRE ALARM AMPLIFIER(S), EXTENDER EQUIPMENT, AND ALL

ASSOCIATED CONTROL/MONITORING MODULES COMPLETE BACK TO SOURCE

AFTER NEW FIRE ALARM SYSTEM INSTALLED, EXISTING DEVICES ARE

RECONNECTED, AND COMPLETE SYSTEM TESTING HAS BEEN COMPLETED.

DISCONNECT SLC LOOP WIRING BETWEEN ZONES AND REMOVE EXISTING

CONDUIT AND WIRING. DEVICE SHOWN IS ASSUMED TO BE THE LOCATION OF THE

CONNECTION BETWEEN ZONES. FIELD VERIFY CONNECTION LOCATION.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING TO EXISTING ADDRESSABLE FIRE

ALARM DEVICE TO MIGRATE EXISTING DEVICES TO NEW LOOP. CONNECT

DEVICES COMPLETE AND PROVIDE NEW ADDRESS FOR ALL DEVICES ON

EXISTING LOOP. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING ALL

DEVICES IN THE ZONE HAVE BEEN MIGRATED TO NEW LOOP.

REMOVE EXISTING FIRE ALARM REMOTE ANNUNCIATOR COMPLETE. PATCH AND

PAINT WALL TO MATCH EXISTING.

EXISTING INDEPENDENT, INTERCONNECTED FIRE ALARM SYSTEM THAT IS NOT

CONNECTED TO BUILDING'S ADDRESSABLE SYSTEM. EACH DEVICE IS A

COMBINATION SMOKE DETECTOR, HORN AND STROBE CONNECTED TO 120VAC

WITH (2) AAA BATTERY BACKUP. 120V IS BEING MONITORED BY A PAM RELAY AND

MONITOR MODULE. SYSTEM SHALL BE REMOVED AND REPLACED WITH DEVICES

CONNECTED TO ADDRESSABLE SYSTEM. REMOVE EXISTING SYSTEM COMPLETE

AFTER INSTALLATION AND TESTING OF NEW DEVICES.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING AND DIGITAL AUDIO FIBER OPTIC

CABLE FROM NEW NODE EQUIPMENT TO NEW ZONE EQUIPMENT IN PENTHOUSE

ON FLOOR ABOVE. CONNECT NEW FIRE ALARM POWER SUPPLY AND DIGITAL

AUDIO AMPLIFIER COMPLETE AND PROVIDE (5) NEW ADDRESSES FOR POWER

SUPPLY AND (1) NEW ADDRESS FOR AMPLIFIER. ROUTE SHOWN IN APPROXIMATE.

CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION.

A NEW COMPARTMENT IS BEING CONSTRUCTED AS PART OF AN ADDITION

PROJECT THAT IS CURRENTLY IN DESIGN. VA PROJECT NUMBER 541-377 "SCI AND

ACUTE SPECIAL PROGRAMS ADDITION". FIRE ALARM ZONE EQUIPMENT IS BEING

PROVIDED UNDER THE SCOPE OF THAT PROJECT. PROVIDE AN ADDITIONAL SLC

LOOP #5 FOR FUTURE USE TO CONNECT ADDRESSABLE DEVICES IN THIS

COMPARTMENT.

FIRE ALARM DEVICE SCHEDULE NOTES

FA EXISTING DEVICE ADDRESS AND FUNCTION INFORMATION IS FOR REFERENCE ONLY. INFORMATION IS SOURCED

FROM PREVIOUS FIRE ALARM SYSTEM STUDY PROJECT AS WELL AS PROJECT FIRE ALARM SUBMITTALS AND AS-BUILT DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFIRMING EXISTING DEVICE ADDRESS AND

FUNCTION PRIOR TO RE-PROGRAMMING DEVICE TO NEW SYSTEM.

FB NEW NODE/LOOP INDICATES THE DESTINATION NODE AND LOOP TO WHICH THE EXISTING FIRE ALARM DEVICE SHALL BE RE-CONNECTED. PROVIDE NECESSARY FIRE ALARM CONDUIT AND WIRING REQUIRED TO RECONNECT EXISTING DEVICES TO NEW NODE AND LOOP AS INDICATED. CONTRACTOR SHALL DOCUMENT NEW DEVICE

ADDRESS FOR ALL RE-CONNECTED FIRE ALARM DEVICES.

FC CONTRACTOR SHALL PROVIDE ALL NECESSARY PROGRAMMING TO TRANSITION EXISTING DEVICE TO NEW FIRE ALARM BACKBONE SYSTEM. PROGRAMMING INCLUDES BUT IS NOT LIMITED TO DEVICE ADDRESS, UPDATING DEVICE LOCATION, DEVICE FUNCTION, DEVICE TYPE, ETC. CONTRACTOR SHALL BE PERMITTED TO MIGRATE EXISTING DEVICES FROM PREVIOUS DATABASE, IF POSSIBLE, BUT SHALL BE RESPONSIBLE FOR MANUALLY UPDATING THE AFORMENTIONED FIELDS AND MANUALLY PROGRAMMING ALL FIRE ALARM DEVICES WHERE DATA

MIGRATION FAILS.

FD REFER TO FIRE ALARM INPUT/OUTPUT MATRIX FOR DEVICE PROGRAMMING.

FE REFER TO FIRE ALARM SYSTEM SPECIFICATIONS FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

FIRE ALARM GENERAL NOTES

F1 ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE FIRE

ALARM CONTROL SYSTEM IN ACCORDANCE WITH ENGINEER APPROVED

MANUFACTURER'S SHOP DRAWINGS, WIRING DIAGRAMS, AND DETAILS.

F2 ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE

CONDUIT SYSTEM.

F3 SMOKE DETECTORS SHALL BE INSTALLED ON CEILINGS WITH SPACING NOT TO

EXCEED MANUFACTURER'S RECOMMENDATION AND IN ACCORDANCE WITH NFPA 72.

F4 SMOKE DETECTORS SHALL BE INSTALLED WITHIN 5'-0" OF CENTERLINE OF SMOKE

DOORS ON HOLD-OPEN DEVICES. DETECTORS SHALL BE INSTALLED ON EACH SIDE

OF THE DOOR PER VA FIRE PROTECTION DESIGN MANUAL.

F5 FIRE ALARM SYSTEM SHALL BE SUB-DIVIDED INTO ZONES THAT CORRESPOND TO

THE SMOKE COMPARTMENTS AND SPRINKLER ZONES PER VA FIRE PROTECTION

DESIGN MANUALS.

F6 ALL EXISTING FIRE ALARM DEVICES THAT WILL NOT BE REUSED IN THE REMODELED

INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION

SHALL INCLUDED ALL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR"

AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE

REMOVED IN OREDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING

ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING

REUSED DEVICES - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE

THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND THE EXTENT

OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID

SUBMITTAL.

F7 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT

RETAINED BY THE OWNER SHALL BE DISPOSED OF BY THE ELECTRICAL

CONTRACTOR.

F8 REFER TO THE LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION

TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED "XB", "XRR", OR "XN"

AND REMOVE/BLANK OFF, RELOCATE, OR REPLACE THESE COMPONENTS AS

REQUIRED.

F9 CLOSELY COORDINATE ALL DEMOLITION WORK WITH THE GENERAL CONTRACTOR

TO PROVIDE PATCHING AND PAINTING FOR EXISTING WALLS WHERE

DEVICES/PANELS ARE REMOVED.

F10 CONTACT THE ENGINEER IF A QUESTION SHOULD ARISE CONCERING THE STATUS

OF ANY OUTLET, DEVICE, FIXTURE, ETC.

HD HD

HD HD

HD HD HD

HD HD HD

HD HD HD

HD HD

PH TS WF

P

RS

RS

RS

CM

RS

RS

RS

MM MM MM CM CM

CMMMMM

CM CM

CMCM

CM

CM

CM

CM

MM

CM

MM

MM

MM

MM

MM

MM

HD

█N3 L1 D1 █N3 L1 D2

█N3 L1 D8█N3 L1 D4

█N3 L1 D3 █N3 L1 D5

█N3 L1 D9

█N3 L1 D10 █N3 L1 D12 █N3 L1 D6

█N3 L1 D50 █N3 L1 D51 █N3 L1 D52

█N3 L1 D7 █N3 L1 D11 █N3 L1 D42

█N3 L1 D43

TEMPORARY RECALL MODULES

(NOT BEING USED)

█N3 L1 D39 █N3 L1 D40 █N3 L1 D41

█N3 L1 D44

█N3 L1 D13

█N3 L1 D14 █N3 L1 D15

PASSENGER

ELEVATOR SHUNT

TRIP MODULES

SERVICE ELEVATOR

MODULES

█N9 L6 M17 EOL█N3 L1 M2█N3 L1 M1 █N3 L1 M3

PASSENGER ELEVATOR

RECALL MODULES

SHUTDOWN MODULE

MONITOR MODULE

FOR DUCT DETECTOR

AT BAR JOIST

OLD MODULE STYLE

DUCT DETECTOR

OLD MODULE STYLE

DUCT DETECTOR

OLD MODULE STYLE

DUCT DETECTOR

N3 L1 M6

INSIDE CABINET

NOT HOOKED UP

OLD MODULE

STYLE DUCT

DETECTOR

OLD MODULE

STYLE DUCT

DETECTOR

█N3 L1 M59 █N3 L1 M63█N3 L1 M60█N3 L1 M61

█N3 L1 M62

█N3 L1 M14

█N3 L1 M15

█N3 L1 M31

█N3 L1 M8 █N3 L1 M9█N3 L1 M42█N3 L1 M10

█N3 L1 M35█N3 L1 M36

█N3 L1 M11█N3 L1 M12█N3 L1 M13█N3 L1 M32█N3 L1 M33

█N3 L1 M4

█N3 L1 M7

DUCT DETECTOR

MONITOR

█N3 L1 M5

SHUTDOWN MODULE

█N3 L1 M6

█N3 L1 M65

█N3 L1 M66

FAZE

NEW

CONDUIT STUB UP

FROM FIFTH FLOOR

NEW

FATC

FARA

X

XR

█N3 L5 D5

XN

XN

XN

XN

XN

XN

DUCT DETECTOR

MONITOR

DUCT DETECTOR

MONITOR

MONITOR MODULE

FOR DUCT DETECTOR

AT BAR JOIST

XN

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title Project NumberProject Title

Building Number

Approved: Location

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Office of

Facilities

Management

FULLY SPRINKLERED

Date

05/14/21

Checked Drawn

Drawing Number

Dwg. of DateRevisions:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

D

C

B

A

E

F

D

C

B

A

E

F

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

VA FORM 08-6231, OCT 1978

DOCUMENT SET MUST BE PRINTED IN COLOR

BID DOCUMENTS SUBMISSION 05/14/21 17069

NODE 1.14 - MAIN BUILDING

PENTHOUSE - ADDRESSABLE

541-18-101UPGRADE FIRE ALARM

MPL CPC

FA-A-1.14b

8' 16' 32' 64'

1/16" = 1' 0"

PENTHOUSE FIRE ALARM PLAN - ADDRESSABLE - NODE 1.14.4 1

NOT TO SCALE

NODE 1.14 - PENTHOUSE

FIRE ALARM KEY PLAN

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - PENTHOUSE - NODE 1.14

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Monitor Module N3 L1 M31 N1.14 L4 PASS ELEV PWR AVAILABLE

Control Module N3 L1 M32 N1.14 L4 SERVICE ELEV SHUNT TRIP

Monitor Module N3 L1 M33 N1.14 L4 SERVICE ELEV SHUNT TRIP PWR AVAIL

Control Module N3 L1 M35 N1.14 L4 TEMPORARY RECALL MODULE

Control Module N3 L1 M36 N1.14 L4 TEMPORARY RECALL MODULE

Control Module N3 L1 M42 N1.14 L4 PASS ELEV ROBOT INTERFACE

Monitor Module N3 L1 M59 N1.14 L4

Monitor Module N3 L1 M60 N1.14 L4

Monitor Module N3 L1 M61 N1.14 L4

Control Module N3 L1 M62 N1.14 L4

Control Module N3 L1 M63 N1.14 L4

Monitor Module N3 L1 M65 N1.14 L4

Duct Detector N3 L1 M66 N1.14 L4

Monitor Module N3 L1 M66 N1.14 L4

Firemans Phone N9 L6 M17 EOL N1.8 L1 FED FROM SECOND FLOOR

Duct Detector NOT HOOKED UP N1.14 L4

Duct Detector OLD STYLE DEVICE N1.14 L4

Duct Detector OLD STYLE DEVICE N1.14 L4

Duct Detector OLD STYLE DEVICE N1.14 L4

Duct Detector OLD STYLE DEVICE N1.14 L4

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - MAIN BUILDING - PENTHOUSE - NODE 1.14

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Heat Detector N3 L1 D1 N1.14 L4

Heat Detector N3 L1 D2 N1.14 L4

Smoke Detector N3 L1 D3 N1.14 L4

Heat Detector N3 L1 D4 N1.14 L4

Smoke Detector N3 L1 D5 N1.14 L4

Heat Detector N3 L1 D6 N1.14 L4

Smoke Detector N3 L1 D7 N1.14 L4

Heat Detector N3 L1 D8 N1.14 L4

Smoke Detector N3 L1 D9 N1.14 L4

Heat Detector N3 L1 D10 N1.14 L4

Smoke Detector N3 L1 D11 N1.14 L4

Heat Detector N3 L1 D12 N1.14 L4

Smoke Detector N3 L1 D13 N1.14 L4

Heat Detector N3 L1 D14 N1.14 L4

Heat Detector N3 L1 D15 N1.14 L4

Heat Detector N3 L1 D39 N1.14 L4

Heat Detector N3 L1 D40 N1.14 L4

Heat Detector N3 L1 D41 N1.14 L4

Smoke Detector N3 L1 D42 N1.14 L4

Smoke Detector N3 L1 D43 N1.14 L4

Smoke Detector N3 L1 D44 N1.14 L4

Heat Detector N3 L1 D50 N1.14 L4

Heat Detector N3 L1 D51 N1.14 L4

Heat Detector N3 L1 D52 N1.14 L4

Water Flow Switch N3 L1 M1 N1.14 L4

Tamper Switch N3 L1 M2 N1.14 L4

Pull Station N3 L1 M3 N1.14 L4

Monitor Module N3 L1 M4 N1.14 L4

Monitor Module N3 L1 M5 N1.14 L4

Monitor Module N3 L1 M6 N1.14 L4

Control Module N3 L1 M7 N1.14 L4

Control Module N3 L1 M8 N1.14 L4 PASS ELEV PRIMARY RECALL MODULE

Control Module N3 L1 M9 N1.14 L4 PASS ELEC SECONDARY RECALL MODULE

Control Module N3 L1 M10 N1.14 L4 PASS ELEV SMOKE RECALL MODULE

Control Module N3 L1 M11 N1.14 L4 SERVICE ELEV PRIME RECALL

Control Module N3 L1 M12 N1.14 L4 SERVICE ELEV SECONDARY RECALL

Monitor Module N3 L1 M13 N1.14 L4 MECH RM SMOKE MONITOR

Control Module N3 L1 M14 N1.14 L4 PASS ELEV SHUNT TRIP

Monitor Module N3 L1 M15 N1.14 L4 PASS ELEV PWR AVAILABLE

FIRE ALARM DEVICE SCHEDULE NOTES

FA EXISTING DEVICE ADDRESS AND FUNCTION INFORMATION IS FOR REFERENCE ONLY. INFORMATION IS SOURCED

FROM PREVIOUS FIRE ALARM SYSTEM STUDY PROJECT AS WELL AS PROJECT FIRE ALARM SUBMITTALS AND AS-BUILT DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFIRMING EXISTING DEVICE ADDRESS AND

FUNCTION PRIOR TO RE-PROGRAMMING DEVICE TO NEW SYSTEM.

FB NEW NODE/LOOP INDICATES THE DESTINATION NODE AND LOOP TO WHICH THE EXISTING FIRE ALARM DEVICE SHALL BE RE-CONNECTED. PROVIDE NECESSARY FIRE ALARM CONDUIT AND WIRING REQUIRED TO RECONNECT EXISTING DEVICES TO NEW NODE AND LOOP AS INDICATED. CONTRACTOR SHALL DOCUMENT NEW DEVICE

ADDRESS FOR ALL RE-CONNECTED FIRE ALARM DEVICES.

FC CONTRACTOR SHALL PROVIDE ALL NECESSARY PROGRAMMING TO TRANSITION EXISTING DEVICE TO NEW FIRE ALARM BACKBONE SYSTEM. PROGRAMMING INCLUDES BUT IS NOT LIMITED TO DEVICE ADDRESS, UPDATING DEVICE LOCATION, DEVICE FUNCTION, DEVICE TYPE, ETC. CONTRACTOR SHALL BE PERMITTED TO MIGRATE EXISTING DEVICES FROM PREVIOUS DATABASE, IF POSSIBLE, BUT SHALL BE RESPONSIBLE FOR MANUALLY UPDATING THE AFORMENTIONED FIELDS AND MANUALLY PROGRAMMING ALL FIRE ALARM DEVICES WHERE DATA

MIGRATION FAILS.

FD REFER TO FIRE ALARM INPUT/OUTPUT MATRIX FOR DEVICE PROGRAMMING.

FE REFER TO FIRE ALARM SYSTEM SPECIFICATIONS FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

CODED NOTES

1 PROVIDE NEW FIRE ALARM EQUIPMENT AS INDICATED. REFER TO ENLARGED PLANS ON SUBSEQUENT SHEETS FOR

ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

CONTINUATION OF 3/4"C WITH NEW SLC LOOP WIRING FROM NEW NODE EQUIPMENT ON FLOOR BELOW TO NEW ZONE EQUIPMENT INDICATED. ROUTE SHOWN IS APPROXIMATE. CONTRACTOR SHALL FIELD VERIFY EXACT LOCATION.

EXISTING FIRE ALARM TERMINAL CABINET THAT CONTAINS CONTROL AND MONITOR MODULES FOR LOCAL EQUIPMENT.

REPLACE CONTROL MODULES ASSOCIATED WITH AC UNIT SHUTDOWN AS INDICATED. MAINTAIN CABINET AND EXISTING

MODULES. RECONNECT AND REPROGRAM TO NEW SYSTEM.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING TO EXISTING ADDRESSABLE FIRE ALARM DEVICE TO MIGRATE EXISTING DEVICES TO NEW LOOP. CONNECT DEVICES COMPLETE AND PROVIDE NEW ADDRESS FOR ALL DEVICES ON EXISTING LOOP. CONTRACTOR SHALL BE RESPONSIBLE FOR ENSURING ALL DEVICES IN THE ZONE HAVE BEEN MIGRATED TO NEW

LOOP.

REMOVE EXISTING FIRE ALARM REMOTE ANNUNCIATOR COMPLETE. PAINT AND PATCH WALL TO MATCH EXISTING.

REPLACE EXISTING DUCT DETECTOR WITH NEW. DETECTOR SHALL BE SYSTEM SENSOR MODEL "DNR" WITH NOTIFIER COMPATIBLE REMOVABLE AND ADDRESSABLE SMOKE DETECTION HEADS. PROVIDE NEW NOTIFIER "RTS151KEY" REMOTE TEST KEY SWITCH AND MOUNT AT AN ACCESSIBLE LOCATION. CONNECT COMPLETE TO NEW FIRE ALARM ADDRESSABLE CIRCUIT. PROVIDE NEW NOTIFIER "FRM" RELAY MODULE AND CONNECT COMPLETE TO LOCAL HVAC CONTROL PANEL FOR UNIT SHUTDOWN. COORDINATE REPLACEMENT WITH VA FACILITIES DEPARTMENT. PROVIDE 3/4"C

AND WIRING AS REQUIRED TO CONNECT ALL NEW FIRE ALARM DEVICES COMPLETE.

FIRE ALARM GENERAL NOTES

F1 ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE FIRE ALARM CONTROL SYSTEM IN

ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWINGS, WIRING DIAGRAMS, AND DETAILS.

F2 ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALLED IN 3/4" MINIMUM SIZE CONDUIT SYSTEM.

F3 SMOKE DETECTORS SHALL BE INSTALLED ON CEILINGS WITH SPACING NOT TO EXCEED MANUFACTURER'S

RECOMMENDATION AND IN ACCORDANCE WITH NFPA 72.

F4 SMOKE DETECTORS SHALL BE INSTALLED WITHIN 5'-0" OF CENTERLINE OF SMOKE DOORS ON HOLD-OPEN DEVICES.

DETECTORS SHALL BE INSTALLED ON EACH SIDE OF THE DOOR PER VA FIRE PROTECTION DESIGN MANUAL.

F5 FIRE ALARM SYSTEM SHALL BE SUB-DIVIDED INTO ZONES THAT CORRESPOND TO THE SMOKE COMPARTMENTS AND

SPRINKLER ZONES PER VA FIRE PROTECTION DESIGN MANUALS.

F6 ALL EXISTING FIRE ALARM DEVICES THAT WILL NOT BE REUSED IN THE REMODELED INSTALLATION SHALL BE REMOVED UNLESS OTHERWISE NOTED. THIS DEMOLITION SHALL INCLUDED ALL ITEMS SHOWN ON THIS PLAN THAT ARE DESIGNATED BY "XR" AND ALL OTHER ADDITIONAL ITEMS THAT ARE NOT SHOWN BUT THAT MUST BE REMOVED IN ORDER TO PRODUCE A NEAT, FINISHED, PROPERLY FUNCTIONING ELECTRICAL INSTALLATION. MAINTAIN CIRCUIT CONTINUITY TO ALL EXISTING REUSED DEVICES - PROVIDE ALL CONDUIT AND WIRING NECESSARY TO ACHIEVE THE SAME. THE CONTRACTOR SHALL FIELD VERIFY THE NATURE AND THE EXTENT OF ALL DEMOLITION WORK AND SHALL INCLUDE COST FOR THE SAME IN THE BID

SUBMITTAL.

F7 ALL EXISTING REMOVED ELECTRICAL EQUIPMENT, DEVICES, ETC. THAT ARE NOT RETAINED BY THE OWNER SHALL BE

DISPOSED OF BY THE ELECTRICAL CONTRACTOR.

F8 REFER TO THE LEGEND FOR ALL SYMBOL DESIGNATIONS. NOTE SPECIAL ATTENTION TO SELECTED EXISTING DEVICES, WIREWAYS, ETC. MARKED "XB", "XRR", OR "XN" AND REMOVE/BLANK OFF, RELOCATE, OR REPLACE THESE COMPONENTS AS

REQUIRED.

F9 CLOSELY COORDINATE ALL DEMOLITION WORK WITH THE GENERAL CONTRACTOR TO PROVIDE PATCHING AND PAINTING

FOR EXISTING WALLS WHERE DEVICES/PANELS ARE REMOVED.

F10 CONTACT THE ENGINEER IF A QUESTION SHOULD ARISE CONCERING THE STATUS OF ANY OUTLET, DEVICE, FIXTURE, ETC.

DN

R

S RS

R S

R S

R S

P

P

P

HD

T S

TSTS

TS

MM

P H

P H

RS

RS

R S

R S

R S

R S

R S

R S

R S

R S

R S

R S

R S

R S

C M

C M

C M

C M

C M

C M

C M

C M

C M

CM

CM

WF

TS

P H

R S

RS

R S

R

SC

M C

M

P

P

P

TSWF

TS

CM

CM

P

PH WF TS

P

CM

C M

C M

J J

DN

DN

DN DN

DN

█N9 L1 D41

█N9 L1 D42

█N9 L1 D43

█N9 L1 D26

█N9 L1 D46

█N9 L1 D45█N9 L1 D50

█N9 L1 D44

█N9 L1 D47

█N9 L1 D49

█N9 L1 D48

█N9 L3 D14

█N9 L1 D36

█N9 L1 D37

█N9 L1 D38

█N9 L1 D39

█N9 L1 D40

█N9 L1 D30

█N9 L1 D31

█N9 L1 D32

█N9 L1 D33

█N9 L1 D29

█N9 L1 D28

█N9 L1 D27

█N9 L1 D24█N9 L1 D34

█N9 L1 D35

█N9 L1 D25

█N9 L1 M27

█N9 L1 M57

█N9 L1 M28

█N9 L3 D15

█N9 L3 M10 █N9 L3 M9█N9 L3 M8

█N9 L6 M12

█N9 L1 M52█N9 L1 M53█N9 L1 M54

█N9 L3 M33█N9 L3 M32

█N9 L3 M35█N9 L3 M34

█N9 L3 M36 █N9 L3 M37

█N9 L3 M30

█N9 L3 M31

█N9 L3 M98

█N9 L3 M13

█N9 L3 M3

█N9 L6 M12 EOL

█N9 L3 M46█N9 L3 M45

█N9 L3 M1

█N9 L3 M38

█N9 L3 M39

█N9 L3 M5

█N9 L6 M12

█N9 L3 M7

█N9 L3 M6

█N9 L1 M55

█N9 L3 M97

█N9 L1 M56

No Respons e

Gait Lab C15

Record Storage

BAC320

Controlled Sub,/ Sec Disp

BAC318

Tech Supply

BAC317

Supervisor

BAC316

Comm

BAC308

Staff Lockers/Break

BAC303

HAC

BAC302

Mens

BAC330

Comm

BA149

Storage

BA151A

Closet

BAC312B

Closet

BAC312A

Closet

BAC298A

Work Room

BAC307

Electrical Closet

BAC309

Stairway

BAC310

Exam

BAC254

Conference Room

BAC286

Exam

BAC255

Clean Supply

BAC259

Soiled Holding

BAC258

Exam

BAC253

Triage

BAC251

Exam

BAC252

Waiting

BAC250

IT Work Offices

BAC266

2 Person Office

BAC274

2 Person Office

BAC275

Office

BAC273

Regulatory/ Fiscal Office

BAC261

Director Office

BAC271

Storage

BAC264

Office

BAC281

Copy File/Work

BAC282

HVAC

BAC241

Reception/ Waiting

BAC260

Passage

BAC260C

Passage

BAC260B

Copy/ Work Passage

BAC268

Waiting

BAC326

Elect.

BA150

2 Person Office

BAC262

Elec

BA148

Elevator Lobby

BAC325

Storage, File Room

BAC285

Staff Toilet

BAC319

Consult

BAC321

Storage

BAC301

Corridor

BAC327

Tech Sup. Mail Order

BAC312

Office BAC306Outpatient Pharmacy

BAC311

Womens

BAC329

Break Room

BAC283

Office

BAC257

Passage

BAC250B

Records

BAC256

Corridor

BAC328

4 Person Office

BAC265

Passage

BAC260A

2 Person Office

BAC269

Office

BAC272

Electrical Room

BA151

Waiting

BAC324

Corridor

BAC284

Anti-Coagulation Clinic Open Office

BAC280

Collaboration Area

BAC270B

Open Student Offices

BAC270C

Break Area/ Pantry

BAC270A

Corridor

BAC299

Corridor

BAC298

Mechanical Room

BA109

Office

BA109C

Stair B

BA109B

Closet C15E

Storage (Prosthetics)

AB205

Rad. Office

BB402

Staff Shower

BB413A

Exam

BB411

Work Room

BB413

Rad. Office

BB403

Toilet

BB413B

Office

BAC323B

Elect.

C15F

Comm.

BB309

Office/Exam Rm.

BB311

Office/Exam Rm.

BB312

Storage

BB300C

Corridor

BB300B

Elect.

C13A

Stair A

H1

Rad. Office

BB401

HAC

BB308

Corridor

BB300A

Reception

BAC322

Police Training

BAC323

Corridor

BB400A

Lockers

BB437

Men

BB435

Women

BB436

█N9 L3 D12

█N9 L3 D7

█N9 L3 D13

█N9 L3 D8

█N9 L3 D11

█N9 L3 D35█N9 L3 D33

█N9 L3 D34█N9 L3 D32

█N9 L3 D31

█N9 L3 D30

█N9 L3 D29

█N9 L3 D40

█N9 L3 D28

█N9 L3 D27

█N9 L3 D24

█N9 L3 D23

█N9 L3 D26 █N9 L3 D25

█N9 L3 D45

█N9 L3 D46

█N9 L3 D39

█N9 L3 D1

FAZE

NEW

N E

W

NEW

EXPANDER PNL

█N9 L1 M40

XR

XR

NEW

AMPLIFIER

N10A3

NEW

XR

N E

W

FAZE

FANE

NEW

NEW 12

NEW

FARA

XR

K4

K42

J40 J42

H42H41

G1 42

E41

C41

E 42

C 42

L39 L

L

R39 R42

P39 P42

48O

49O

50O

51O

52O

53O

53AO

49N

52N

53N

54N

54N1

49M

50M

51M

52M

53M

54M

49L

50L

51L

52L

53L

54L

50K

51K

52K

53K

54K

50J

51J

52J

53J

54J

50H

51H

52H

53H

54H

50G

51G

52G

53G

54G

50F

51F

52F

53F

54F

43J

43H

43G

47L

43L

43M 46M 47M

47N

50N

51N

FAZE

FANE

NEW

XR

NEW

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title Project NumberProject Title

Building Number

Approved: Location

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Office of

Facilities

Management

FULLY SPRINKLERED

Date

05/14/21

Checked Drawn

Drawing Number

Dwg. of DateRevisions:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

D

C

B

A

E

F

D

C

B

A

E

F

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

VA FORM 08-6231, OCT 1978

DOCUMENT SET MUST BE PRINTED IN COLOR

BID DOCUMENTS SUBMISSION 05/14/21 17069

NODE 2.1 - ACC BUILDING

BASEMENT - ADDRESSABLE

541-18-101UPGRADE FIRE ALARM

MPL CPC

FA-A-2.1

8' 16' 32' 64'

1/16" = 1' 0"

BASEMENT FIRE ALARM PLAN - ADDRESSABLE - NODE 2.1 1

NOT TO SCALE

NODE 2.1 - BASEMENT

FIRE ALARM KEY PLAN

FIRE ALARM DEVICE SCHEDULE NOTES

FA EXISTING DEVICE ADDRESS AND FUNCTION INFORMATION IS FOR REFERENCE ONLY. INFORMATION IS SOURCED

FROM PREVIOUS FIRE ALARM SYSTEM STUDY PROJECT AS WELL AS PROJECT FIRE ALARM SUBMITTALS AND AS-BUILT DRAWINGS. CONTRACTOR SHALL BE RESPONSIBLE FOR CONFIRMING EXISTING DEVICE ADDRESS AND

FUNCTION PRIOR TO RE-PROGRAMMING DEVICE TO NEW SYSTEM.

FB NEW NODE/LOOP INDICATES THE DESTINATION NODE AND LOOP TO WHICH THE EXISTING FIRE ALARM DEVICE SHALL BE RE-CONNECTED. PROVIDE NECESSARY FIRE ALARM CONDUIT AND WIRING REQUIRED TO RECONNECT EXISTING DEVICES TO NEW NODE AND LOOP AS INDICATED. CONTRACTOR SHALL DOCUMENT NEW DEVICE

ADDRESS FOR ALL RE-CONNECTED FIRE ALARM DEVICES.

FC CONTRACTOR SHALL PROVIDE ALL NECESSARY PROGRAMMING TO TRANSITION EXISTING DEVICE TO NEW FIRE ALARM BACKBONE SYSTEM. PROGRAMMING INCLUDES BUT IS NOT LIMITED TO DEVICE ADDRESS, UPDATING DEVICE LOCATION, DEVICE FUNCTION, DEVICE TYPE, ETC. CONTRACTOR SHALL BE PERMITTED TO MIGRATE EXISTING DEVICES FROM PREVIOUS DATABASE, IF POSSIBLE, BUT SHALL BE RESPONSIBLE FOR MANUALLY UPDATING THE AFORMENTIONED FIELDS AND MANUALLY PROGRAMMING ALL FIRE ALARM DEVICES WHERE DATA

MIGRATION FAILS.

FD REFER TO FIRE ALARM INPUT/OUTPUT MATRIX FOR DEVICE PROGRAMMING.

FE REFER TO FIRE ALARM SYSTEM SPECIFICATIONS FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

FIRE ALARM ADDRESSABLE DEVICE SCHEDULE - ACC - BASEMENT - NODE 2.1

DEVICE TYPE EXISTING FA ADDRESS NEW NODE/LOOP FUNCTION

Smoke Detector N9 L1 D24 N2.1 L2

Smoke Detector N9 L1 D25 N2.1 L2

Smoke Detector N9 L1 D26 N2.1 L2

Smoke Detector N9 L1 D27 N2.1 L2

Smoke Detector N9 L1 D28 N2.1 L2

Smoke Detector N9 L1 D29 N2.1 L2

Smoke Detector N9 L1 D30 N2.1 L2

Smoke Detector N9 L1 D31 N2.1 L2

Smoke Detector N9 L1 D32 N2.1 L2

Smoke Detector N9 L1 D33 N2.1 L2

Smoke Detector N9 L1 D34 N2.1 L2

Smoke Detector N9 L1 D35 N2.1 L2

Smoke Detector N9 L1 D36 N2.1 L2

Smoke Detector N9 L1 D37 N2.1 L2

Smoke Detector N9 L1 D38 N2.1 L2

Smoke Detector N9 L1 D39 N2.1 L2

Smoke Detector N9 L1 D40 N2.1 L2

Smoke Detector N9 L1 D41 N2.1 L2

Smoke Detector N9 L1 D42 N2.1 L2

Smoke Detector N9 L1 D43 N2.1 L2

Smoke Detector N9 L1 D44 N2.1 L2

Smoke Detector N9 L1 D45 N2.1 L2

Smoke Detector N9 L1 D46 N2.1 L2

Smoke Detector N9 L1 D47 N2.1 L2

Smoke Detector N9 L1 D48 N2.1 L2

Smoke Detector N9 L1 D49 N2.1 L2

Smoke Detector N9 L1 D50 N2.1 L2

Pull Station N9 L1 M27 N2.1 L2

Pull Station N9 L1 M28 N2.1 L2

Control Module N9 L1 M40 DEMOLISH - DO NOT RECONNECT EXPANDER PANEL TRIGGER/MONITOR

Control Module N9 L1 M52 N2.1 L2 ACTIVATE WINDOW FIRE SHUTTER

Control Module N9 L1 M53 N2.1 L2 ACTIVATE WINDOW FIRE SHUTTER

Control Module N9 L1 M54 N2.1 L2 ACTIVATE WINDOW FIRE SHUTTER

Control Module N9 L1 M55 N2.1 L2 RELEASE SECURED DOORS

Control Module N9 L1 M56 N2.1 L2

Pull Station N9 L1 M57 N2.1 L2

Duct Detector N9 L3 D1 N2.1 L1 HV2 DUCT

Duct Detector N9 L3 D7 N2.1 L2 AHU-1 RTN

Duct Detector N9 L3 D8 N2.1 L2 AHU-1 RTN

Duct Detector N9 L3 D11 N2.1 L1 AHU-1 RTN

Duct Detector N9 L3 D12 N2.1 L2 AHU-1 RTN

Duct Detector N9 L3 D13 N2.1 L2 AHU-1 RTN

Smoke Detector N9 L3 D14 N2.1 L2

Heat Detector N9 L3 D15 N2.1 L2

Duct Detector N9 L3 D23 N2.1 L2 RF51 RETURN DUCT

Duct Detector N9 L3 D24 N2.1 L2 RF51 RETURN DUCT

Duct Detector N9 L3 D25 N2.1 L2 HV1 DUCT

Duct Detector N9 L3 D26 N2.1 L2 RF1 DUCT

Duct Detector N9 L3 D27 N2.1 L2 AC-51 SUPPLY DUCT

Duct Detector N9 L3 D28 N2.1 L2 AC-51 SUPPLY DUCT

Duct Detector N9 L3 D29 N2.1 L2 AC-52 SUPPLY DUCT

Duct Detector N9 L3 D30 N2.1 L2 RF-52 RETURN DUCT

Duct Detector N9 L3 D31 N2.1 L2 AC-52 SUPPLY DUCT

Duct Detector N9 L3 D32 N2.1 L2 AC-52 SUPPLY DUCT

Duct Detector N9 L3 D33 N2.1 L2 RF-53 RETURN DUCT

Duct Detector N9 L3 D34 N2.1 L2 AC-53 SUPPLY DUCT

Duct Detector N9 L3 D35 N2.1 L2 AC-53 SUPPLY DUCT

Duct Detector N9 L3 D39 N2.1 L1 RF2 DUCT

Duct Detector N9 L3 D40 N2.1 L2 RF-52 RETURN DUCT

Duct Detector N9 L3 D45 N2.1 L1 AHU MED FILES SUPPLY DUCT

Duct Detector N9 L3 D46 N2.1 L1 AHU MED FILES RETURN DUCT

Pull Station N9 L3 M1 N2.1 L1

Pull Station N9 L3 M3 N2.1 L1

Pull Station N9 L3 M5 N2.1 L2

Tamper Switch N9 L3 M6 N2.1 L2

Water Flow Switch N9 L3 M7 N2.1 L2

Tamper Switch N9 L3 M8 N2.1 L2

Tamper Switch N9 L3 M9 N2.1 L2

Tamper Switch N9 L3 M10 N2.1 L2

Tamper Switch N9 L3 M13 N2.1 L2

Control Module N9 L3 M30 N2.1 L2 AC-53 SUPPLY - UNIT SHUTDOWN

Control Module N9 L3 M31 N2.1 L2 AC-53 RETURN - UNIT SHUTDOWN

Control Module N9 L3 M32 N2.1 L2 AC-52 SUPPLY - UNIT SHUTDOWN

Control Module N9 L3 M33 N2.1 L2 AC-52 RETURN - UNIT SHUTDOWN

Control Module N9 L3 M34 N2.1 L2 AC-51 SUPPLY - UNIT SHUTDOWN

Control Module N9 L3 M35 N2.1 L2 AC-51 RETURN - UNIT SHUTDOWN

Control Module N9 L3 M36 N2.1 L2 RF1 - SHUTDOWN

Control Module N9 L3 M37 N2.1 L2 HV1 - SHUTDOWN

Control Module N9 L3 M38 N2.1 L1 RF2 - SHUTDOWN

Control Module N9 L3 M39 N2.1 L1 AHU HV2 - SHUTDOWN

Control Module N9 L3 M45 N2.1 L1 AHU MED FILES SUPPLY - SHUTDOWN

Control Module N9 L3 M46 N2.1 L1 AHU MED FILES RETURN - SHUTDOWN

Tamper Switch N9 L3 M97 N2.1 L2

Water Flow Switch N9 L3 M98 N2.1 L2

Firemans Phone N9 L6 M12 N2.1 L1

Firemans Phone N9 L6 M12 N2.1 L1

Firemans Phone N9 L6 M12 N2.1 L2

Smoke Detector NEW DEVICE N2.1 L1

Smoke Detector NEW DEVICE N2.1 L2

Firemans Phone NO RESPONSE N2.1 L2

CODED NOTES

1 PROVIDE NEW FIRE ALARM EQUIPMENT AS INDICATED. REFER TO ENLARGED PLANS ON SUBSEQUENT SHEETS FOR

ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

PROVIDE 3/4"C WITH NEW SLC LOOP WIRING AND DIGITAL AUDIO FIBER OPTIC CABLE FROM NEW NODE EQUIPMENT TO NEW ZONE EQUIPMENT. CONNECT NEW FIRE ALARM POWER SUPPLY AND DIGITAL AUDIO AMPLIFIER COMPLETE AND

PROVIDE (5) NEW ADDRESSES FOR POWER SUPPLY AND (1) NEW ADDRESS FOR AMPLIFIER.

REMOVE EXISTING FIRE ALARM AMPLIFIER(S), EXTENDER EQUIPMENT, AND ALL ASSOCIATED CONTROL/MONITORING MODULES COMPLETE BACK TO SOURCE AFTER…