This federal contract opportunity is for project #541-18-101 to upgrade the fire alarm system at the Louis Stokes VA Medical Center in Cleveland, Ohio. The multi-phase project will install a new campus fiber loop and NotifierA head end units in phase one. Phase two will rewire and reprogram existing field devices such as strobes, horns, pull stations, and smoke detectors to report to the appropriate zone's control panel. The project magnitude is between $2,000,000 and $5,000,000 and shall be completed within 425 calendar days of receiving the notice to proceed. Interested parties must register at beta.sam.gov for solicitation documents posting around November 24, 2020, with bid opening approximately 30 days later. Questions may be emailed to the contracting officer by the specified cutoff date. The contracting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

File Type Posted
36C25020B0065 0010.docx DOCX document
WD Cuyahoga 07.30.2021.pdf PDF
280500 - COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY. - Revised 7-26 -2021.pdf PDF
36C25020B0065 0009.docx DOCX document
36C25020B0065 0008.docx DOCX document
36C25020B0065 0007.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part7.pdf PDF
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part6.pdf PDF
36C25020B0065 0006.docx DOCX document
36C25020B0065 0005.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part5.pdf PDF
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part4.pdf PDF
36C25020B0065 0004.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part3.pdf PDF
36C25020B0065 0003.docx DOCX document
36C25020B0065 0002.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Drawings_Part2.pdf PDF
36C25020B0065 0001.docx DOCX document
541-18-101 - Upgrade Fire Alarm - Bid Documents Specifications 02.pdf PDF
36C25020B0065_1.docx DOCX document
CUY WD 04.30.2021.pdf PDF
VAMC Health Requirements 05.26.2021.pdf PDF
Notifier JA Complete REDACTED.pdf PDF
VHA Directive 1192.01, Seasonal Influenza Prevention Program for VHA Health Care Personnel.pdf PDF
Corwin Russwin JA Complete REDACTED.pdf PDF
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

EAST BLVD.

E

S

T

E A

S T

B L V

D

MAGNOLIA DR.

H A

Z E

L D

R

E . 1

S

T

MT. SINAI DR.

M A R

TIN

LU

TH

ER

KIN

G D

R

S

59459

M.P. LONG

R

E

S

O F

I

R

G E

NO

I

S

P

E

N

E

D

ERT

L EA

E I N

G

R

T

S

TE

A

H

F OO

IO

17069

Drawing Title

Approved: Division Chief

Location

Project Title Date

Checked Drawn DRAWING NO.Building Number

Project No.

Office of

Facilities

Management

Dwg. of o n e e ig h th i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e i n c h o n e f o o t o n e a n d o n e h a lf i n c h e s o n e f o o t th re e i n c h e s o n e f o o t

VA FORM 08-6231, OCT 1978 1

2 3 4 5 6 7 8 9

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A B

C D

E F

FACILITY MANAGER

DATE

SHOP FOREMAN 138

APPROVALS

CHIEF Planning and Construction

DATE

CHIEF, Occupational Health & Safety

APPROVALS

DIRECTOR 00

DATE

ASSOCIATE DIRECTOR 00A (B)

APPROVALS

Approved: Service Director

CHIEF, IRMCHIEF, ENGINEERING 138

DEPARTMENT OF VETERANS AFFAIRS MEDICAL CENTER - WADE PARK

10701 EAST BLVD. CLEVELAND, OH. 44106

PROJECT NO.

Veterans Administration Medical Center

TOTAL PROJECT AREA: CAMPUS-WIDE

DESIGN CODES:

2018 Life Safety Code, ABA Accessibility Standards, 2018 IBC

OCCUPANCY,USE GROUP:

Health Care, I-2

FIRE SUPPRESSION: Fully Sprinklered

TRAVEL DISTANCES: (LSC 18.2.6)

Room Remote Point to Exit: 200'

(LSC 18.2.6.2.1)

Suite Remote Point to Exit Access Door

(LSC 18.2.5.7.3.4) : 100'

Suite Remote Point to Exit: 200'

(LSC 18.2.5.7.3.4)

TYPE OF CONSTRUCTION: (LSC A.8.2.1.2)

Type 1 - 332

EXTERIOR BEARING WALLS: (LSC A.8.2.1.2)

3 Hours

INTERIOR BEARING WALLS: (LSC A.8.2.1.2)

3 Hours

STRUCTURAL COLUMNS: (LSC A.8.2.1.2)

3 Hours - Supporting more than 1 floor 2 Hours - Supporting one floor only 2 Hours - Supporting roof only

FLOOR - CEILING ASSEMBLIES: (LSC A.8.2.1.2)

2 Hours

ROOF - CEILING ASSEMBLIES: (LSC A.8.2.1.2)

1 1/2 Hours

INTERIOR NONBEARING WALLS: (LSC A.8.2.1.2)

0 Hour

EXTERIOR NONBEARING WALLS: (LSC A.8.2.1.2)

0 Hour

EXIT ENCLOSURES (LSC 7.1.3.2.1)

Existing: 1 Hour New: 2 Hours

SHAFT ENCLOSURES (LSC 8.6.5)

4 Stories or more: 2 Hours Less than 4 stories: 1 Hour

SMOKE BARRIERS: (LSC 18.3.7.3)

1 Hour

EXIT ACCESS CORRIDORS: (LSC 18.3.6.2.2)

0 Hour, Smoke Partitions

SUITE WALLS: (18.2.5.7.1.2)

0 Hour, Smoke Partitions

HAZARDOUS AREA PROTECTION (LSC 18.3.2.1)

Labs, non-severe hazard materials: 0 Hour Labs, severe hazard materials: 1 Hour Soiled linen rooms >64 gal.: 1 Hour Storage rooms larger than 100 sf: 1 Hour

CODE INFORMATION

DRAWING INDEX

U.S. GOVERNMENT PRINTING OFFICE: 1983-400-285

VICINITY PLAN

Scale = None

Perspectus Architecture

FFH | now IMEG Mechanical & Electrical Engineers 672 East Royalton Road Broadview Heights, Ohio 44147

Architect 1300 East 9th Street Suite 910 Cleveland, Ohio 44114

UPGRADE FIRE ALARM

BID DOCUMENTS SUBMISSION

Refer to phasing descriptions on drawing FA-L-0.1 for additional information.

PHASE 0:

PHASE 1A AND 1B:

PHASE 2:

Total project duration is 780 days from Notice of Award.

PHASING NOTES

1.

2.

PROJECT DURATION

DURATION IN CALENDAR DAYS DAYS FROM NOTICE OF AWARD

120 DAYS 1 - 120

480 DAYS 121 - 600

DAYS 601 - 780

Contractor to coordinate all work with the entire set of documents.

Contractor to cooperate with the Owner's occupancy of the facility and shall execute the work with as little interfere to normal operating functions of the Medical Center as possible. See also spec 01 00 00.

UPGRADE FIRE ALARM

541-18-101

CPCMPL

COVER SHEET

X-0.1

541-18-101

05/14/2021

VAMC - WADE PARK

SHEET

NUMBER

SHEET NAME

FA-A-3.3 NODE 3.3 - CARES TOWER FIRST FLOOR - ADDRESSABLE

FA-A-3.4 NODE 3.4 - CARES TOWER SECOND FLOOR - ADDRESSABLE

FA-A-3.5 NODE 3.5 - CARES TOWER THIRD FLOOR - ADDRESSABLE

FA-A-3.6 NODE 3.6 - CARES TOWER FOURTH FLOOR - ADDRESSABLE

FA-A-3.7 NODE 3.7 - CARES TOWER FIFTH FLOOR - ADDRESSABLE

FA-A-3.8 NODE 3.8 - CARES TOWER SIXTH FLOOR AND PENTHOUSE - ADDRESSABLE

FA-A-4.1a NODE 4.1 - RESEARCH WING BASEMENT AND FIRST FLOOR - ADDRESSABLE

FA-A-4.1b NODE 4.1 - RESEARCH WING SECOND AND THIRD FLOOR - ADDRESSABLE

FA-A-5.1 NODE 5.1 - ENERGY CENTER BASEMENT AND FIRST FLOOR - ADDRESSABLE

FA-A-6.1a NODE 6.1 - LAB WAREHOUSE BASEMENT - ADDRESSABLE

FA-A-6.1b NODE 6.1 - LAB WAREHOUSE FIRST FLOOR - ADDRESSABLE

FA-A-6.1c NODE 6.1 - LAB WAREHOUSE PENTHOUSE - ADDRESSABLE

FA-N-1.1 NODE 1.1 - MAIN BUILDING BASEMENT - NOTIFICATION

FA-N-1.2 NODE 1.2 - MAIN BUILDING BASEMENT - NOTIFICATION

FA-N-1.3a NODE 1.3 - MAIN BUILDING SUB-BASEMENT - NOTIFICATION

FA-N-1.3b NODE 1.3 - MAIN BUILDING BASEMENT - NOTIFICATION

FA-N-1.3c NODE 1.3 - PARKING STRUCTURE BASEMENT - NOTIFICATION

FA-N-1.3d NODE 1.3 - PARKING STRUCTURE FIRST FLOOR - NOTIFICATION

FA-N-1.3e NODE 1.3 - PARKING STRUCTURE SECOND FLOOR - NOTIFICATION

FA-N-1.3f NODE 1.3 - PARKING STRUCTURE THIRD FLOOR - NOTIFICATION

FA-N-1.4 NODE 1.4 - MAIN BUILDING FIRST FLOOR - NOTIFICATION

FA-N-1.5 NODE 1.5 - MAIN BUILDING BASEMENT AND FIRST FLOOR - NOTIFICATION

FA-N-1.6 NODE 1.6 - MAIN BUILDING FIRST FLOOR - NOTIFICATION

FA-N-1.7 NODE 1.7 - MAIN BUILDING FIRST FLOOR - NOTIFICATION

FA-N-1.8 NODE 1.8 - MAIN BUILDING SECOND FLOOR - NOTIFICATION

FA-N-1.9 NODE 1.9 - MAIN BUILDING SECOND FLOOR - NOTIFICATION

FA-N-1.10 NODE 1.10 - MAIN BUILDING SECOND AND THIRD FLOOR - NOTIFICATION

FA-N-1.11 NODE 1.11 - MAIN BUILDING THIRD FLOOR - NOTIFICATION

FA-N-1.12 NODE 1.12 - MAIN BUILDING FOURTH FLOOR - NOTIFICATION

FA-N-1.13 NODE 1.13 - MAIN BUILDING FIFTH FLOOR - NOTIFICATION

FA-N-1.14a NODE 1.14 - MAIN BUILDING SIXTH FLOOR - NOTIFICATION

FA-N-1.14b NODE 1.14 - MAIN BUILDING PENTHOUSE FLOOR - NOTIFICATION

FA-N-2.1 NODE 2.1 - ACC BUILDING BASEMENT - NOTIFICATION

FA-N-2.2 NODE 2.2 - ACC BUILDING FIRST FLOOR - NOTIFICATION

FA-N-2.3 NODE 2.2 AND 2.3 - ACC BUILDING SECOND FLOOR - NOTIFICATION

FA-N-2.4 NODE 2.4 - ACC BUILDING THIRD FLOOR - NOTIFICATION

FA-N-2.5 NODE 2.5 - ACC BUILDING FOURTH FLOOR AND PENTHOUSE - NOTIFICATION

FA-N-3.1 NODE 3.1 - CARES TOWER LEVEL A - NOTIFICATION

FA-N-3.2 NODE 3.2 - CARES TOWER BASEMENT - NOTIFICATION

FA-N-3.3 NODE 3.3 - CARES TOWER FIRST FLOOR - NOTIFICATION

FA-N-3.4 NODE 3.4 - CARES TOWER SECOND FLOOR - NOTIFICATION

FA-N-3.5 NODE 3.5 - CARES TOWER THIRD FLOOR - NOTIFICATION

FA-N-3.6 NODE 3.6 - CARES TOWER FOURTH FLOOR - NOTIFICATION

FA-N-3.7 NODE 3.7 - CARES TOWER FIFTH FLOOR - NOTIFICATION

FA-N-3.8 NODE 3.8 - CARES TOWER SIXTH FLOOR AND PENTHOUSE - NOTIFICATION

FA-N-4.1a NODE 4.1 - RESEARCH WING BASEMENT AND FIRST FLOOR - NOTIFICATION

FA-N-4.1b NODE 4.1 - RESEARCH WING SECOND AND THIRD FLOOR - NOTIFICATION

FA-N-5.1 NODE 5.1 - ENERGY CENTER BASEMENT AND FIRST FLOOR - NOTIFICATION

FA-N-6.1a NODE 6.1 - LAB WAREHOUSE BASEMENT - NOTIFICATION

FA-N-6.1b NODE 6.1 - LAB WAREHOUSE FIRST FLOOR AND PENTHOUSE - NOTIFICATION

FA-R-0.1 DEMOLITION FIRE ALARM SYSTEM BACKBONE DIAGRAM

FA-R-0.2 NEW FIRE ALARM SYSTEM BACKBONE DIAGRAM

FA-D-0.1 FIRE ALARM SYSTEM DETAILS

SHEET

NUMBER

SHEET NAME

X-0.1 COVER SHEET

A-1-01 BUILDING 1 - PARTIAL ARCHITECTURAL FLOOR PLANS

FP-1-01 PARTIAL SECOND AND FIFTH FLOOR FIRE PROTECTION PLAN

M-1-01 PARTIAL SECOND AND FIFTH FLOOR MECHANICAL PLANS

FA-L-0.1 ELECTRICAL SYMBOL LEGEND AND GENERAL NOTES

FA-L-0.2 FIRE ALARM INPUT/OUTPUT AND ZONE TRIGGER MATRIX

FA-K-SB SUB-BASEMENT FIRE ALARM ZONE KEY PLAN

FA-K-B BASEMENT FIRE ALARM ZONE KEY PLAN

FA-K-1 FIRST FLOOR FIRE ALARM ZONE KEY PLAN

FA-K-2 SECOND FLOOR FIRE ALARM ZONE KEY PLAN

FA-K-3 THIRD FLOOR FIRE ALARM ZONE KEY PLAN

FA-K-4 FOURTH FLOOR FIRE ALARM ZONE KEY PLAN

FA-K-5 FIFTH FLOOR FIRE ALARM ZONE KEY PLAN

FA-K-6 SIXTH FLOOR FIRE AND PENTHOUSE ALARM ZONE KEY PLANS

FA-E-1.1 BUILDING 1 - MAIN TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (1 OF 5)

FA-E-1.2 BUILDING 1 - MAIN TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (2 OF 5)

FA-E-1.3 BUILDING 1 - MAIN TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (3 OF 5)

FA-E-1.4 BUILDING 1 - MAIN TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (4 OF 5)

FA-E-1.5 BUILDING 1 - MAIN TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (5 OF 5)

FA-E-2.1 BUILDING 2 - ACC - ENLARGED FIRE ALARM EQUIPMENT LOCATION PLANS

FA-E-3.1 BUILDING 3 - CARES TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (1 OF 3)

FA-E-3.2 BUILDING 3 - CARES TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (2 OF 3)

FA-E-3.3 BUILDING 3 - CARES TOWER - ENLARGED FIRE ALARM EQUIPMENT PLANS (3 OF 3)

FA-E-4.1 BUILDING 4 - RESEARCH WING - ENLARGED FIRE ALARM EQUIPMENT PLANS (1 OF 1)

FA-E-5.1 BUILDING 5 - ENERGY CENTER - ENLARGED FIRE ALARM EQUIPMENT PLANS (1 OF 1)

FA-E-6.1 BUILDING 6 - PALMS/LAB WAREHOUSE - ENLARGED FIRE ALARM EQUIPMENT PLANS (1 OF 1)

FA-A-1.1 NODE 1.1 - MAIN BUILDING BASEMENT - ADDRESSABLE

FA-A-1.2 NODE 1.2 - MAIN BUILDING BASEMENT - ADDRESSABLE

FA-A-1.3a NODE 1.3 - MAIN BUILDING SUB-BASEMENT - ADDRESSABLE

FA-A-1.3b NODE 1.3 - MAIN BUILDING BASEMENT - ADDRESSABLE

FA-A-1.3c NODE 1.3 - PARKING STRUCTURE BASEMENT - ADDRESSABLE

FA-A-1.3d NODE 1.3 - PARKING STRUCTURE FIRST FLOOR - ADDRESSABLE

FA-A-1.3e NODE 1.3 - PARKING STRUCTURE SECOND FLOOR - ADDRESSABLE

FA-A-1.3f NODE 1.3 - PARKING STRUCTURE THIRD FLOOR - ADDRESSABLE

FA-A-1.4 NODE 1.4 - MAIN BUILDING FIRST FLOOR - ADDRESSABLE

FA-A-1.5 NODE 1.5 - MAIN BUILDING BASEMENT AND FIRST FLOOR - ADDRESSABLE

FA-A-1.6 NODE 1.6 - MAIN BUILDING FIRST FLOOR - ADDRESSABLE

FA-A-1.7 NODE 1.7 - MAIN BUILDING FIRST FLOOR - ADDRESSABLE

FA-A-1.8 NODE 1.8 - MAIN BUILDING SECOND FLOOR - ADDRESSABLE

FA-A-1.9 NODE 1.9 - MAIN BUILDING SECOND FLOOR - ADDRESSABLE

FA-A-1.10 NODE 1.10 - MAIN BUILDING SECOND AND THIRD FLOOR - ADDRESSABLE

FA-A-1.11 NODE 1.11 - MAIN BUILDING THIRD FLOOR - ADDRESSABLE

FA-A-1.12 NODE 1.12 - MAIN BUILDING FOURTH FLOOR - ADDRESSABLE

FA-A-1.13 NODE 1.13 - MAIN BUILDING FIFTH FLOOR - ADDRESSABLE

FA-A-1.14a NODE 1.14 - MAIN BUILDING SIXTH FLOOR - ADDRESSABLE

FA-A-1.14b NODE 1.14 - MAIN BUILDING PENTHOUSE - ADDRESSABLE

FA-A-2.1 NODE 2.1 - ACC BUILDING BASEMENT - ADDRESSABLE

FA-A-2.2 NODE 2.2 - ACC BUILDING FIRST FLOOR - ADDRESSABLE

FA-A-2.3 NODE 2.2 AND 2.3 - ACC BUILDING SECOND FLOOR - ADDRESSABLE

FA-A-2.4 NODE 2.4 - ACC BUILDING THIRD FLOOR - ADDRESSABLE

FA-A-2.5 NODE 2.5 - ACC BUILDING FOURTH FLOOR AND PENTHOUSE - ADDRESSABLE

FA-A-3.1 NODE 3.1 - CARES TOWER LEVEL A - ADDRESSABLE

FA-A-3.2 NODE 3.2 - CARES TOWER BASEMENT - ADDRESSABLE

VAMC

A11 A12

12A

WW

12A

YY

9A

ZZ

Clean Linen

Storage

2D120

Patient Room

#11

2D121

REWORK SPRINKLER PIPING. PROVIDE

NEW UPRIGHT PENDENT SPRINKLER IN

NEW FIRE ALARM EQUIPMENT ROOM.

Corridor

5B100H

Toilet/ Shower-1

5B104A-1

Storage-1

5B105-1

Elect

5B100G-2

K16

BRANCH 1" SPRINKLER LINE

FROM CORRIDOR MAIN.

SPRINKLER NEW ELECT

CLOSET WITH UPRIGHT

PENDENT, QUICK RESPONSE.

Bedroom-1

5A122-1

Toilet/ Shower-1

5A119A-1

Bedroom-1

5A119-1

Corridor-1

5A100D-1

L33 L34

REWORK SPRINKLER PIPING.

PROVIDE NEW UPRIGHT

PENDENT SPRINKLER IN NEW

FIRE ALARM EQUIPMENT ROOM.

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Revisions: Date

DOCUMENT SET MUST BE PRINTED IN COLOR

FULLY SPRINKLERED

17069BID DOCUMENTS SUBMISSION 05/14/21

UPGRADE FIRE ALARM 541-18-101

DMLLDH

PARTIAL SECOND AND FIFTH

FLOOR FIRE PROTECTION PLAN

FP-1-01

05/14/21

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL SECOND FLOOR FIRE PROTECTION PLAN

(ZONE 1.10.2) 3

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL FIFTH FLOOR FIRE PROTECTION PLAN

(ZONE 1.13.3) 2

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL FIFTH FLOOR FIRE PROTECTION PLAN

(ZONE 1.13.1) 1 NNN

FIRE SUPPRESSION GENERAL NOTES:

A.

B.

C.

D.

E.

F.

LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK, AND EQUIPMENT IS PRESUMED FROM EXISTING DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE

PERFORMED AS INDICATED ON THESE DRAWINGS.

COORDINATE ALL SHUT-DOWNS OF EXISTING MECHANICAL SYSTEMS WITH VA COR A MINIMUM OF TEN

WORKING DAYS IN ADVANCE.

PROVIDE ADEQUATE SERVICE CLEARANCE FOR ALL MECHANICAL EQUIPMENT. REFER TO INSTRUCTIONS

FROM THE EQUIPMENT MANUFACTURER.

NEW PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL DRAWINGS FOR

LOCATION OF PANELS.

THE FIRE SUPPRESSION CONTRACTOR SHALL PROVIDE DETAILS DESIGN OF THE SPRINKLER SYSTEM.

REFER TO SPECIFICATIONS.

THE FIRE SUPPRESSIONS SYSTEM IS PERFORMANCE SPECIFIED. ALL SPRINKLER PIPE SIZES SHALL BE

DETERMINED BY FIRE PROTECTION CONTRACTOR, BASED ON HYDRAULIC CALCULATIONS.

ALL OUTLINED AREAS SHALL BE 100% FULLY SPRINKLERED WITH A

WET-TYPE SPRINKLER SYSTEM IN ACCORDANCE WITH NFPA 13 AND VA

SPECIFICATIONS. SPRINKLER HEADS SHALL BE INSTALLED SO AS TO

ACCOMMODATE ANY NEW CEILINGS. COORDINATE SPRINKLER HEAD

LAYOUT WITH ARCHITECTURAL REFLECTED CEILING PLAN. REFER TO

MECHANICAL SPECIFICATIONS AND FIRE SUPPRESSION NOTES FOR

ADDITIONAL INFORMATION.

Bedroom-1

5A122-1

Toilet/ Shower-1

5A119A-1

Bedroom-1

5A119-1

Corridor-1

5A100D-1

L33 L34

X x

S

A X x

S

A X x

S

A

X - 12 x 8 SA

"ø

S

A

X - 18 x 10 RA

X - 22 x 10 RA

X - 26 x 10 RA

X - 10 x 6 RA

X - 10 x 6 EA

6"ø

S-2 100

CTE

X-VAV

Corridor

5B100H

Toilet/ Shower-1

5B104A-1

Storage-1

5B105-1

K16

X - 10 x 8 RA

X - 12 x 10 SA

X - 9"ø SA

6"ø SA

X - 75 x 12 SA

6"ø

S-2 100

CTE

X - 10 x 8 SAX - 18 x 10 SA

X - 12 x 10 SA

X-VAV

A11 A12

12A

WW

12A

YY

9A

ZZ

6"ø SA

6"ø

S1 100

CTE

X

"ø

S

A

X x

S

A

X - 8"ø SA

X - 8"ø SA

X - 10 x 12 RA

X x

R

A

X-VAV

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

74490

L.D. HENDRIX, JR

GN

SS

AION EL

T

F EGE

P R O R

SI NRE I

E E R

D

E

ATS

ET O

OI

HOF

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Revisions: Date

DOCUMENT SET MUST BE PRINTED IN COLOR

FULLY SPRINKLERED

17069BID DOCUMENTS SUBMISSION 05/14/21

UPGRADE FIRE ALARM 541-18-101

DMLLDH

PARTIAL SECOND AND FIFTH

FLOOR MECHANICAL PLANS

M-1-01

05/14/21

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL FIFTH FLOOR MECHANICAL PLAN

(ZONE 1.13.1) 1

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL FIFTH FLOOR MECHANICAL PLAN

(ZONE 1.13.3) 2

0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'0' 2' 4' 8' 16'

1/4" = 1'-0"

PARTIAL SECOND FLOOR MECHANICAL PLAN

(ZONE 1.10.2) 3

MECHANICAL GENERAL NOTES:

A.

B.

C.

D.

E.

CALL OUTS:

DUCTWORK SYMBOLS:

ABBREVIATIONS:

GENERAL SYMBOLS:

NOTES:

LOCATIONS AND ROUTING OF EXISTING PIPING, DUCTWORK AND EQUIPMENT IS PRESUMED FROM EXISTING

DRAWINGS. MECHANICAL CONTRACTOR SHALL FIELD VERIFY ALL PRIOR TO COMMENCEMENT

OF CONSTRUCTION. NOTIFY ENGINEER OF ANY CONDITIONS WHICH WILL NOT PERMIT THE WORK TO BE

PERFORMED AS INDICATED ON THESE DRAWINGS.

NEW DUCTS OR PIPING SHALL NOT BE ROUTED ABOVE ELECTRICAL PANELS. REFER TO ELECTRICAL

DRAWINGS FOR LOCATION OF PANELS.

UNLESS NOTED OTHERWISE, BRANCH DUCTS TO DIFFUSERS SHALL BE THE SAME SIZE AS THE NECK OF THE

DIFFUSER.

MECHANICAL DRAWINGS ARE DIAGRAMATICAL. WHERE DUCT SIZE SHOWN IS IN CONFLICT WITH STRUCTURE OR OTHER BUILDING SYSTEM, CONTRACTOR MAY MODIFY DUCT SIZE AND PROVIDE EQUIVALENT FREE AREA

DUCT.

CONTRACTOR SHALL REMOVE AND REPLACE CEILING TILES AND GRID AS REQUIRED TO COMPLETE DEMOLITION AND NEW WORK IN AREAS OUTSIDE OF RENOVATION PROJECT. CONTRACTOR SHALL BE

RESPONSIBLE FOR REPLACING ANY TILES OR GRID DAMAGED DUE TO THIS WORK.

CTE CONNECT TO EXISTING

RA

SA

RETURN AIR

SUPPLY AIR

AIR DISTRIBUTION DEVICE (DIFFUSERS, REGISTERS AND GRILLES)

MARK TYPE

S2

(INCHES)

FACE SIZE

12x12

COLORSTYLE

ALUMINUMWHITE

MATERIAL

NOTES

(INCHES)

NECK SIZE

6"ØSUPPLY

DIFFUSER

PLAQUE FACE

DUCT MOUNTED

1. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.

MANUAL BALANCING DAMPER ON DUCT

ROUND DUCT SIZE12"Ø

RECTANGULAR DUCT SIZE24x18

REFERENCE TO CODED NOTE

TO BE MOUNTED OVER ACCESSIBLE CEILING

EXISTING TO REMAINX

EQUIPMENT OR FIXTURE MARK

AIR DISTRIBUTION DEVICE

REFERENCE TO GENERAL NOTE

TYPE

CONNECTION SIZE AT

DEVICE

EQUIPMENT

TYPE

UNIT NUMBER

X

NECK

XX

X-X

NN N

MECHANICAL SYMBOLS:

S1 12x12 ALUMINUMWHITE 16"ØSUPPLY

DIFFUSER

PLAQUE FACE

LAY-IN

ABBREVIATIONS

DEDICATED NEUTRAL CONDUCTORS

AC ABOVE COUNTER AT 9" UNLESS OTHERWISE NOTED

AF AMP FRAME

AFC ABOVE FINISHED CEILING

AFF ABOVE FINISHED FLOOR

AT AMP TRIP

BC BELOW COUNTER AT 18"AFF UNLESS OTHERWISE NOTED

BFC BELOW FINISHED CEILING

CM CEILING MOUNTED

EC ELECTRICAL CONTRACTOR

EG EQUIPMENT GROUND

GC GENERAL CONTRACTOR

GFCI GROUND FAULT CIRCUIT INTERRUPTER

IG ISOLATED GROUND

ITD INFORMATION TECHNOLOGY DEPARTMENT

PROVIDE DEFINITION: FURNISH, INSTALL AND CONNECT COMPLETE.

X EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO REMAIN

XB INDICATES EXISTING OUTLET, LIGHTING FIXTURE, CONDUIT, ETC - TO BE REMOVED.

PROVIDE BLANK COVER FOR OUTLET AND MAINTAIN CIRCUIT CONTINUITY.

XL NEW LOCATION OF EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC.

XN EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REPLACED WITH NEW OF

SPECIFIED TYPE

XR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, CONDUIT, ETC. - TO BE REMOVED COMPLETE-

MAINTAIN CIRCUIT CONTINUITY TO ADJACENT OUTLETS, EXTEND CONDUIT AND WIRING AS

REQUIRED.

XRR EXISTING OUTLET, DEVICE, LIGHTING FIXTURE, ETC. - TO BE REMOVED AND REINSTALLED

AT NEW LOCATION - EXTEND CONDUIT AND WIRING AS REQUIRED

MC MECHANICAL CONTRACTOR

MLO MAIN LUGS ONLY

NEC NATIONAL ELECTRICAL CODE

NF NOT FUSED

OFE OWNER FURNISHED EQUIPMENT

TC TELECOMMUNICATIONS CONTRACTOR

TCC TEMPERATURE CONTROLS CONTRACTOR

TV TELEVISION

VDC VOICE/DATA CONTRACTOR

VFD VARIABLE FREQUENCY DRIVE

WM WIREMOLD

WP WEATHERPROOF ENCLOSURE - NEMA 4

DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH CIRCUITS

WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED.

ROUTE NO MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.

GENERAL ELECTRICAL INSTALLATION NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

ALL MOUNTING HEIGHTS ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.

ALL NEW WALL MOUNTED ELECTRICAL DEVICES ARE TO BE INSTALLED FLUSH IN WALL UNLESS OTHERWISE NOTED. ALL ELECTRICAL CONDUIT SHALL BE CONCEALED BEHIND FINISHED WALLS AND ABOVE FINISHED CEILING UNLESS OTHERWISE NOTED. THE COST TO CUT AND PATCH WALLS SHALL BE THE RESPONSIBILITY OF THE TRADE REQUIRING THE

CUTTING.

CONTRACTOR IS RESPONSIBLE FOR REMOVAL AND REPLACEMENT OF CEILINGS REQUIRED FOR ELECTRICAL WORK.

CONTRACTOR SHALL REPLACE ANY DAMAGED CEILING TILES.

PRIOR TO INSTALLATION, VERIFY PRECISE LOCATION OF NEW OR RELOCATED WALL OR CEILING MOUNTED DEVICES

WITH ARCHITECTURAL ELEVATIONS AND REFLECTED CEILING PLANS.

COORDINATE ALL SHUT-DOWNS OF EXISTING ELECTRICAL SYSTEMS WITH OWNER A MINIMUM OF FOURTEEN (14) WORKING DAYS IN ADVANCE. ALL SHUT-DOWNS SHALL OCCUR DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON

WEEKDAYS ("OFF-HOURS"). INCLUDE ALL PREMIUM TIME CHARGES IN BID.

ALL NOISE GENERATING OPERATIONS, INCLUDING CUTTING OF CEILINGS, WALLS AND FLOORS, CORING, DRILLING, ETC.

SHALL BE SCHEDULED DURING WEEKENDS OR BETWEEN 8:00PM AND 7:00AM ON WEEKDAYS ("OFF-HOURS"). INCLUDING

ALL PREMIUM TIME CHARGES IN BID.

CONTRACTOR SHALL CONNECT ALL MECHANICAL EQUIPMENT COMPLETE PER MANUFACTURER'S WIRING DIAGRAMS AND INSTRUCTIONS. COORDINATE WITH MECHANICAL CONTRACTOR AND VERIFY LOCATION, VOLTAGE, AMPS, NO. OF WIRES, AND PROTECTION REQUIREMENTS PRIOR TO ROUGH-IN. CONTACT ENGINEER WITH ANY DISCREPANCIES FROM DESIGN

DRAWINGS.

PROVIDE LIQUID-TIGHT FLEXIBLE METAL CONDUIT FOR FINAL CONNECTION TO MECHANICAL EQUIPMENT OR OTHER

EQUIPMENT WHICH MAY PROPAGATE VIBRATION.

ALL FLUORESCENT LAMPS THAT WILL NOT BE REUSED SHALL BE DISPOSED OF IN ACCORDANCE WITH EPA STANDARDS, AND WRITTEN EVIDENCE OF PROPER DISPOSAL SHALL BE FURNISHED TO THE OWNER.

ALL WORK SHALL BE PERFORMED IN STRICT CONFORMANCE WITH THE PHASING REQUIREMENTS OF THE PROJECT. ALL

COSTS ASSOCIATED WITH THESE REQUIREMENTS SHALL BE INCLUDED IN THE BID SUBMITTAL.

CONTRACTOR IS RESPONSIBLE FOR PROVIDING TEMPORARY LIGHTING TO ADEQUATELY LIGHT ALL CONSTRUCTION AREAS, TEMPORARILY PARTITIONED AREAS, AND EXIT CORRIDORS MAINTAINED DURING CONSTRUCTION.

DEFINITION: "PROVIDE" - FURNISH, INSTALL AND CONNECT COMPLETE.

PROJECT AND PHASING SCOPE LINES INDICATE WHERE GENERAL CONSTRUCTION BOUNDARIES OCCUR. ELECTRICAL

WORK AND UTILITY TIE-INS MAY OCCUR OUTSIDE OF SCOPE LINES.

FIRE ALARM SYSTEM

F

F

F

RS

CM

MM

TS

FS

FIRE ALARM SYSTEM NOTES:

FIRE ALARM SYSTEM SHALL BE MANUFACTURED BY NOTIFIER. DEVICE MODEL NUMBERS LISTED IN THESE DOCUMENTS SHALL BE CONSIDERED BASIS OF DESIGN. CONTRACTOR SHALL RETAIN AN AUTHORIZED NOTIFIER REPRESENTATIVE TO PROVIDE COMPLETE

SYSTEM INSTALLATION DOCUMENTATION AND SHOP DRAWINGS.

ALL FIRE ALARM SYSTEM DEVICES SHALL BE CONNECTED COMPLETE TO THE NEW ALARM SYSTEM CONTROL PANEL(S) IN ACCORDANCE WITH ENGINEER APPROVED MANUFACTURER'S SHOP DRAWING WIRING DIAGRAMS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING A FULLY CODE COMPLIANT FIRE ALARM SYSTEM. DEVICES SHOWN ON PLAN ARE FOR

REFERENCE ONLY.

PROVIDE A 2-GANG MINIMUM SIZE BACKBOX FOR ALL OF THE ABOVE FIRE ALARM DEVICES.

ALL FIRE ALARM SYSTEM CONDUCTORS SHALL BE INSTALL IN 3/4" MINIMUM SIZE COMPLETE CONDUIT SYSTEM WITH COLOR CODED

WIRING AS INDICATED ON SHOP DRAWINGS - MAINTAIN FACILITY COLOR CODING.

ALL NETWORK AND NETWORK CABLES SHALL BE "COMMUNICATION GRADE" TYPE CABLE.

FURNISH, INSTALL AND CONNECT ALL FIRE ALARM DEVICES IN ACCORDANCE WITH WIRING DIAGRAMS PREPARED BY SYSTEM

VENDOR.

REFER TO SPECIFICATIONS SECTION 283100 FOR ELECTRICAL REQUIREMENTS AND PERFORMANCE SPECIFICATION.

GENERAL EVACUATION BUILDINGS SHALL BE CONSIDERED PUBLIC MODE (PARKING GARAGE, ENERGY CENTER, PALMS/LAB

WAREHOUSE, ETC). ALL OTHER BUILDING SHALL BE CONSIDERED PRIVATE MODE.

FIRE ALARM PANELS - NOTIFIER.

MOUNTING INDICATED FOR EACH TYPE:

FACP - FIRE ALARM CONTROL PANEL.

FARA - FIRE ALARM REMOTE ANNUNCIATOR PANEL

FAEP - FIRE ALARM EXTENDER PANEL - PROVIDES POWER TO VISUAL NOTIFICATION APPLIANCES, DOOR HOLDERS, AND

MISC. FIRE ALARM DEVICES. CONNECT TO 120V LIFE SAFETY CIRCUIT. REFER TO FIRE ALARM SYSTEM RISER

DIAGRAM FOR ADDITIONAL INFORMATION AND WORK REQUIREMENTS.

FATC - FIRE ALARM TERMINAL CABINET

FANE - FIRE ALARM NODE EQUIPMENT - CONSISTING OF FACP AND DIGITAL VOICE CONTROLLER. REFER TO DETAILS FOR

ADDITIONAL INFORMATION.

FAZE - FIRE ALARM ZONE EQUIPMENT - CONSISTING OF FIRE ALARM EXTENDER PANEL AND DIGITAL AMPLIFIER. REFER

TO DETAILS FOR ADDITIONAL INFORMATION.

FAAP - FIRE ALARM ANNUNCIATION PANEL - NOTIFIER ONYXWORKS FIRSTVISION - FLUSH MOUNTED AT 5'-0" AFF TO TOP

OF DEVICE. COORDINATE EXACT LOCATION WITH VA COR PRIOR TO ROUGH-IN.

MANUAL FIRE ALARM PULL STATION - MOUNT AT 48" AFF TO CENTERLINE OF DEVICE.

FIRE ALARM VISUAL SIGNAL DEVICE (ADA TYPE) MOUNTED 80" AFF UNLESS NOTED. WHITE HOUSING WITH RED "FIRE"

LETTERING.

SAME AS ABOVE BUT CEILING MOUNTED.

FIRE ALARM AUDIBLE VISUAL (SPEAKER/STROBE) SIGNAL DEVICE (ADA TYPE) MOUNTED 80"AFF UNLESS NOTED. WHITE

HOUSING WITH RED "FIRE" LETTERING.

SAME AS ABOVE BUT CEILING MOUNTED.

SMOKE DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC TYPE - CEILING MOUNTED.

EL - ELEVATOR RECALL

DUCT DETECTOR - ADDRESSABLE INTELLIGENT PHOTOELECTRIC DETECTOR, SAMPLING TUBES AND PROGRAMMABLE RELAY BASE. PROVIDE DUCT DETECTOR TEST/RESET SWITCH WITH REMOTE INDICATOR LAMP FOR EACH DUCT

DETECTOR. (TEST SWITCH MAY NOT BE SHOWN ON PLANS)

MAGNETIC TYPE DOOR HOLDER OUTLET. 24VDC.

PNEUMATICALLY ACTUATED COMBINATION SMOKE/FIRE DAMPER - FURNISHED AND INSTALLED BY THE MC. EC SHALL

PROVIDE (1) CONTROL MODULE AND (1) MONITOR MODULE.

CONTROL MODULE - ADDRESSABLE RELAY FOR CONTROL OF SMOKE DAMPERS, ELEVATOR RECALL, MAGNETIC DOOR

HOLDERS, AUTOMATIC DOORS, ETC.

MONITOR MODULE - ADDRESSABLE SUPERVISED DEVICE FOR MONITORING TAMPER SWITCH , FLOW SWITCH, DAMPER

POSITION,ETC.

TAMPER SWITCH - MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL TAMPER SWITCH. ELECTRICAL CONTRACTOR

SHALL PROVIDE MONITOR MODULE AND TEST SWITCH.

FLOW SWITCH - MECHANICAL CONTRACTOR SHALL FURNISH AND INSTALL FLOW SWITCH. ELECTRICAL CONTRACTOR SHALL

PROVIDE MONITOR MODULE AND TEST SWITCH.

D

F1.

F2.

F3.

F4.

F5.

F6.

F7.

F8.

DH

F

F

GENERAL LEGEND

CODED NOTE - "1" INDICATES NOTE NUMBER

REVISION REFERENCE NUMBER

MECHANICAL EQUIPMENT IDENTIFIER

DETAIL REFERENCE - "1" INDICATES DETAIL NUMBER, "E0.1" INDICATES DRAWING NUMBER

COLUMN REFERENCE GRID

INDICATES EXISTING CONSTRUCTION WALL TYPE

INDICATES DEMOLITION WALL TYPE

INDICATES NEW CONSTRUCTION WALL TYPE

INDICATES EXISTING SMOKE BARRIER

AC

E0.1

A

LIGHTING AND CONTROLS LEGEND

LED LIGHTING FIXTURE CONNECTED TO NORMAL CIRCUIT AS INDICATED - TYPE AS SPECIFIED IN SCHEDULE, "A" INDICATES TYPE, "3" INDICATES CIRCUIT NUMBER ASSIGNMENT, "a" INDICATES LOCAL SWITCHING CONTROL. CONNECT FIXTURES SO

THAT ALL LAMPS ARE CONTROLLED BY

A aS

POWER DISTRIBUTION EQUIPMENT

208/120V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED

480/277V-3PH-4W-SN PANELBOARD UNLESS OTHERWISE NOTED

SPECIAL PANEL OR PULLBOX - SIZE AND TYPE AS NOTED

NON-FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES, "NF" INDICATES NOT FUSED

FUSED DISCONNECT SWITCH - SIZE AND TYPE AS NOTED, WITH TYPE RK1 FUSES

GROUNDING BUS BARGB

20A-1P-120/277V WALL SWITCH - MOUNTED AT 48" AFF UNLESS OTHERWISE NOTED S

WIRING DEVICES/TERMINATIONS

20A-125V, HOSPITAL GRADE, GROUNDED DUPLEX RECEPTACLE, MOUNTED IN (1) GANG BACKBOX AT 18" UNLESS

OTHERWISE NOTED. CONNECTED TO NORMAL POWER

JJ JUNCTION BOX, CEILING OR WALL MOUNTED, 4" SQ. WITH GROUND LUG, UNLESS OTHERWISE NOTED:

3/4" MINIMUM SIZE CONCEALED CONDUIT WITH #12 AWG, THWN STRANDED COPPER CONDUCTORS PLUS SEPARATE #12 GROUND ( ), AND CONDUIT WIRE FILLS IN ACCORDANCE WITH N.E.C. - EMT MAY BE USED IN INTERIOR STUD WALLS, AND ABOVE FINISHED CEILINGS. DEDICATED NEUTRAL CONDUCTORS ARE REQUIRED FOR ALL 120V AND 277V BRANCH CIRCUITS. MULTIWIRE BRANCH CIRCUITS WITH SHARED NEUTRAL CONDUCTORS ARE NOT PERMITTED. ROUTE NO

MORE THAN (3) BRANCH CIRCUIT HOMERUNS PER EACH CONDUIT RUN.

N# - L# - M#

NODE

SLC LOOP

CIRCUIT

TRIGGER MODULE:

# = ADDRESS

EXISTING FIRE ALARM VISUAL CIRCUIT

N# - A# - S# - #

NODE

AMP SPEAKER

EXISTING FIRE ALARM AUDIO CIRCUIT

CIRCUIT

N# - L# - D#

NODE DEVICE ADDRESS

M: MODULE

D: DETECTOR

EXISTING FIRE ALARM ADDRESS

N# - L# - M#

SLC LOOP

CIRCUIT

N#A - Z# - L#

NODE

ZONE

FIRE ALARM EXTENDER PANEL

NAC OUTPUT CIRCUIT #

NEW FIRE ALARM VISUAL CIRCUIT

N#B - Z# - S#

NODE

ZONE

DIGITAL AUDIO AMPLIFIER

OUTPUT CIRCUIT #

NEW FIRE ALARM AUDIO CIRCUIT

N#A - L# - D#

NODE

SLC LOOP

CIRCUIT

DEVICE ADDRESS

M: MODULE

D: DETECTOR

NEW FIRE ALARM ADDRESS

N#A - L# - M#

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Revisions: Date

DOCUMENT SET MUST BE PRINTED IN COLOR

FULLY SPRINKLERED

17069BID DOCUMENTS SUBMISSION 05/14/21

UPGRADE FIRE ALARM 541-18-101

CPCMPL

ELECTRICAL SYMBOL LEGEND

AND GENERAL NOTES

FA-L-0.1

05/14/21

NOT TO SCALE

EXISTING FIRE ALARM ADDRESSES 1

COMPLETE FIRE ALARM SHOP DRAWINGS (MINIMUM SCALE: 1/16" = 1'-0") THAT INDICATE ALL NEW AND EXISTING EQUIPMENT, FIRE ALARM DEVICES, BACKBONE CABLING, FIRE ALARM SYSTEM CROSS-CONNECTION SCHEMATIC, AND RE-WORK WIRING NECESSARY TO PERFORM

PROJECT SCOPE. CONTRACTOR SHALL FIELD VERIFY PRIOR TO SUBMITTAL.

A PROJECT SCHEDULE, ESTABLISHED ON A WEEKLY BASIS, THAT INCLUDES EQUIPMENT PROCUREMENT, PHASE DURATIONS, AREAS BEING AFFECTED (INCLUDING EXPECTED DURATION OF WORK IN EACH AREA), ANTICIPATED TESTING AND SYSTEM SHUTDOWNS, ESTIMATED

MANPOWER, ETC.

PROPOSED TESTING PROCEDURES INCLUDING NEW BACKBONE SYSTEM TESTING, FIRE ALARM DEVICE MIGRATION TESTING, FULL BUILDING TESTING, AND CAMPUS-WIDE SYSTEM TESTING. INCLUDE SAMPLE TESTING SCRIPTS, SIGN-OFF SHEETS, TESTING REPORTS, ETC.

INSTALL ALL NEW HEAD-END SYSTEM EQUIPMENT (INCLUDING FIRE ALARM CONTROL PANELS, DIGITAL VOICE COMMAND UNITS, FIRE ALARM NOTIFICATION POWER EXTENDER PANELS, DIGITAL AUDIO AMPLIFIERS, MONITORING WORKSTATIONS, NETWORKING COMPONENTS, BACKBONE

CABLING, ETC.)

PROVIDE DETECTORS, MODULES, AND NOTIFICATION DEVICES TEMPORARILY CONNECTED TO THE NEW BACKBONE TO SIMULATE THE NEW

ZONES FOR TESTING PURPOSES.

COMPLETE ALL SYSTEM PROGRAMMING AND TEST FOR FUNCTIONALITY TO ENSURE ALARM NOTIFICATION AND SYSTEM OUTPUT ACTIONS

PERFORM AS PER DESIGN SPECIFICATIONS.

PROVIDE HARD-WIRED, CROSS-CONNECT BETWEEN NEW AND EXISTING BACKBONE SYSTEMS. SYSTEMS SHALL BE CONNECTED SUCH THAT ACTIVATION OF AN ALARM ON NEW OR EXISTING SYSTEM SYSTEM SHALL TRIGGER AN ALARM ON ALL FIRE ALARM CONTROL PANELS ON CAMPUS. THIS FUNCTIONALITY SHALL BE EQUIVALENT TO THE CURRENT BUILDING ALARM PROGRAMMING. THE CONTRACTOR MUST MAINTAIN CAMPUS FIRE ALARM FUNCTIONALITY (OTHER THAN DESIGNATED, SCHEDULED, FIRE ALARM SYSTEM IMPAIRMENTS) THROUGHOUT THE

PROJECT.

CONSOLIDATE EXISTING FIRE ALARM NOTIFICATION APPLIANCE CIRCUITS (NAC) AND SIGNALING LINE CIRCUITS (SLC).

ESTABLISH NEW FIRE ALARM ZONES COORDINATED WITH EXISTING SMOKE COMPARTMENTS AS INDICATED ON PLANS.

ENSURE THAT ALL DEVICES IN EACH COMPARTMENT ARE ABLE TO BE RECONNECTED TO NEW NACs AND SLCs FROM THE NEW FIRE ALARM CONTROL SYSTEM AS INDICATED ON PLANS. FIRE ALARM ZONES MAY REQUIRE MORE THAN (1) NAC OR SLC, BUT NO SINGLE NAC OR SLC SHALL

SERVE MORE THAN (1) FIRE ALARM ZONE/SMOKE COMPARTMENT.

CONTRACTOR SHALL MIGRATE INDIVIDUAL NAC AND SLC CIRCUITS ON THE FLOOR TO THE NEW FIRE ALARM CONTROL SYSTEM.

ALL DEVICES SHALL BE RE-TESTED FOR FUNCTIONALITY PRIOR TO MOVING TO THE NEXT FLOOR. PROVIDE WRITTEN REPORT OF TESTING THAT INCLUDES DEVICE IDENTIFICATION (ADDRESS, LOCATION, OR OTHER IDENTIFYING CHARACTERISTICS) AND CONFIRMATION OF FUNCTIONALITY.

FINAL FUNCTIONAL TESTING SHALL BE WITNESSED BY VA COR AND/OR VA SAFETY/SECURITY AND SIGNED OFF BY CONTRACTOR AND WITNESS.

THE CONTRACTOR SHALL PROGRESS TO THE SUBSEQUENT FLOOR IN THE SAME BUILDING AND REPEAT THIS PROCESS UNTIL THE ENTIRE

BUILDING IS COMPLETED.

ONCE COMPLETE, THE BUILDING FIRE ALARM SYSTEM SHALL BE RE-TESTED AS A COMPLETE SYSTEM. PROVIDE WRITTEN REPORT OF TESTING AND CONFIRMATION OF FUNCTIONALITY. FINAL FUNCTIONAL FULL SYSTEM TESTING SHALL BE WITNESSED BY VA COR AND/OR VA SAFETY/SECURITY AND SIGNED OFF BY CONTRACTOR AND WITNESS. UPON COMPLETION OF TESTING, THE BUILDING CROSS-CONNECT TO THE EXISTING SYSTEM CAN BE DISABLED/REMOVED. THE NEW SYSTEM SHALL THEN BE OPERATED AS AN INDEPENDENT BUILDING.

UPON SUCCESSFUL COMPLETION OF A BUILDING, THE CONTRACTOR SHALL MOVE TO THE NEXT BUILDING AND REPEAT THE PROCESS. AFTER THE FINAL BUILDING HAS BEEN COMPLETED AND TRANSITIONED TO THE NEW SYSTEM AND ALL BUILDINGS HAVE BEEN INDEPENDENTLY TESTED, INTER-BUILDING TESTING SHALL BE CONDUCTED TO ENSURE PROPER FUNCTIONALITY.

PHASING SHALL CONSIST OF (3) MAIN PHASES WITH PHASE 1 COMPRISED OF (2) SUB-PHASES WHICH SHALL BE SET UP TO RUN CONCURRENTLY:

PHASE 0: PRECONSTRUCTION (SUBMITTALS, SCHEDULES, MOBILIZATION, ETC)

PRIOR TO CONSTRUCTION, CONTRACTOR SHALL SUBMIT WITH FIRE ALARM PRODUCT DATA:

a.

b.

c.

SCHEDULE SHALL BE UPDATED ON A WEEKLY BASIS AND PROVIDED TO THE VA FOR APPROVAL.

FIRE ALARM SUBMITTAL SHALL NOT BE APPROVED UNLESS THESE ADDITIONAL REQUIREMENTS ARE MET.

PHASE 1A: NEW SYSTEM HEAD END AND BACKBONE INSTALLATION

A COMPLETE, NEW FIRE ALARM SYSTEM HEAD END AND BACKBONE SHALL BE INSTALLED AND COMMISSIONED PRIOR TO CUTOVER OF EXISTING

FIRE ALARM INITIATION AND NOTIFICATION DEVICES.

AS PART OF THE BACKBONE INSTALLATION, THE CONTRACTOR SHALL:

a.

b.

c.

d.

PHASE 1B: REWORK EXISTING ADDRESSABLE AND NOTIFICATION APPLIANCE LOOPS

THIS WORK SHALL RUN CONCURRENTLY WITH PHASE 1A.

CONTRACTOR SHALL REWORK EXISTING FIRE ALARM SYSTEM CONDUIT AND WIRING TO AUDIO AND VISUAL NOTIFICATION APPLIANCES, ADDRESSABLE DEVICES (SMOKE DETECTORS, DUCT DETECTORS, MODULES, ETC.) AND 24V FIRE ALARM POWER DEVICES (I.E. MAGNETIC DOOR

HOLDERS).

a.

b.

c.

REFER TO SUBSEQUENT DRAWINGS THAT IDENTIFY EXISTING SMOKE COMPARTMENTS AND THEIR NEW CORRESPONDING FIRE ALARM SYSTEM

ZONE.

FOR BIDDING PURPOSES, CONTRACTOR SIMULTANEOUS RE-WORK OF EXISTING FIRE ALARM DEVICES SHALL BE LIMITED TO (2) SMOKE COMPARTMENTS. ADDITIONAL COMPARTMENTS MAY BE MADE AVAILABLE AT THE VA'S DISCRETION.

AS PART OF THE WEEKLY SCHEDULE UPDATES, THE CONTRACTOR SHALL PROVIDE NOTIFICATION OF UPCOMING WORK IN NEW SMOKE

COMPARTMENTS TO THE VA COR AND VA SAFETY/SECURITY.

SHOULD THE VA DETERMINE A SMOKE COMPARTMENT CANNOT BE TURNED OVER TO THE CONTRACTOR AS SCHEDULED, NON-HEALTHCARE OCCUPANCIES (SUCH AS THE LAB WAREHOUSE, PALMS, OR RESEARCH WING) SHALL BE DESIGNATED AS SWING SPACES.

PHASE 2: RECONNECT EXISTING DEVICES TO NEW FIRE ALARM SYSTEM AND DEMOLITION OF EXISTING INFRASTRUCTURE

UPON INSTALLATION AND COMISSIONING OF THE NEW FIRE ALARM SYSTEM HEAD-END AND BACKBONE AND THE COMPLETION OF ALL FIRE ALARM DEVICE RE-WORK, EXISTING ADDRESSIBLE DEVICES AND NOTIFICATION APPLIANCES SHALL BE MIGRATED TO THE NEW SYSTEM. THIS

MIGRATION SHALL OCCUR ONE BUILDING AT A TIME ON A FLOOR BY FLOOR BASIS.

a.

b.

c.

d.

e.

AFTER THE NEW SYSTEM HAS PASSED FINAL TESTING, THE EXISTING SYSTEM INFRASTRUCTURE CAN BE DECOMMISSIONED AND DEMOLISHED

COMPLETE.

PHASING NOTES

NOT TO SCALE

NEW FIRE ALARM CIRCUIT DESIGNATIONS 2

LIGHTING FIXTURE SCHEDULE

TYPE DESCRIPTION DRIVER VOLTAGE FIXTURE WATTAGE LAMP TYPE EFFICACY COLOR TEMP

A 4-1/2"D X 4-3/4"H X 2'L WALL-MOUNTED LED STRIP LIGHT, DIE-FORMED COLD ROLLED STEEL HOUSING, WHITE INJECTION MOLDED END PLATES, SMOOTH OPAL WHITE ACRYLIC LENS, HIGH REFLECTANCE WHITE FINISH PAINTED AFTER FABRICATION, RUST INHIBIT TREATMENT, 800-1000 LUMENS

0-10V DIMMING (STANDARD) UNIV. (120/277) 10 VA LED 80 lm/W 4000 K

B 4-1/2"D X 4-3/4"H X 4'L WALL-MOUNTED LED STRIP LIGHT, DIE-FORMED COLD ROLLED STEEL HOUSING, WHITE INJECTION MOLDED END PLATES, SMOOTH OPAL WHITE ACRYLIC LENS, HIGH REFLECTANCE WHITE FINISH PAINTED AFTER FABRICATION, RUST INHIBIT TREATMENT, 1600-2000 LUMENS

0-10V DIMMING (STANDARD) UNIV. (120/277) 23 VA LED 87 lm/W 4000 K

(MIN)

(MIN)

SURGERY - AFTER 8:00 PM

PACU - AFTER 8:00 PM

CATH LABS - AFTER 6:00 PM

ENDOSCOPY - AFTER 6:00 PM

RADIOLOGY - AFTER 6:00 PM

RESEARCH WING - COORDINATE WITH VA COR ON A CASE-BY-CASE BASIS TO VOID DISRUPTION TO ONGOING RESEARCH STUDIES.

DIRECTOR'S SUITE - AFTER 6:00 PM

ATRIUM - AFTER 6:00 PM

CANTEEN - AFTER 6:00 PM

NON-PATIENT HALLWAYS - AFTER 6:00 PM

THE FOLLOWING AREAS REQUIRE WORK OUTSIDE OF NORMAL BUSINESS HOURS:

a.

b.

c.

d.

e.

NOISE-GENERATING WORK RESTRICTIONS (SAW CUTTING, CORE DRILLING, ETC.)

a.

b.

c.

d.

e.

GENERAL PROJECT NOTES

STATEMENT OF BID ITEMS:

A.

B.

C.

D.

E.

BID ITEM I , FIRE ALARM, WORK INCLUDES ALL LABOR, MATERIAL, EQUIPMENT AND SUPERVISION TO PERFORM THE REQUIRED CONSTRUCTION WORK ON THIS PROJECT INCLUDING THE INSTALLATION OF A COMPLETE NEW HEAD-END FIRE ALARM SYSTEM, RECONNECTION OF EXISTING FIRE ALARM DEVICES TO NEW HEAD-END FIRE ALARM SYSTEMS, AND REMOVAL OF EXISTING HEAD-END FIRE ALARM SYSTEM COMPLETE WITH

ALL RELATED CUTTING AND PATCHING OF THE WORK AREA SURFACES AND FINISHES.

BID ITEM II (ALTERNATE NO. 1): SAME AS ABOVE EXCEPT DEDUCT FIRE WATCH SERVICES FROM CONTRACTOR SCOPE.

BID ITEM III (ALTERNATE NO. 2): SAME AS ABOVE EXCEPT DEDUCT REPLACEMENT OF DUCT DETECTORS INDICATED ON PLANS.

BID ITEM IV (ALTERNATE NO. 3): SAME AS ABOVE EXCEPT DEDUCT NODE EQUIPMENT ON “A LEVEL”, 1ST FLOOR, 3RD FLOOR, AND 5TH FLOOR OF CARES TOWER AND 1ST AND 2ND FLOORS OF THE AMBULATORY CARE CENTER (ACC). NODE CABLING WILL BE PROVIDED TO THESE LOCATIONS AND TERMINATED FOR CONNECTION TO FUTURE EQUIPMENT. PROVIDE ADDITIONAL SLC CARDS IN NODE EQUIPMENT ON FLOORS ABOVE OR BELOW AND CONNECT ZONE EQUIPMENT COMPLETE TO THOSE NODES. EACH ZONE SHALL RECEIVE A UNIQUE SLC LOOP FROM THE NODE EQUIPMENT ON THE FLOOR ABOVE OR FLOOR BELOW AND ALL ADDRESSABLE DEVICES SHALL BE CONNECTED COMPLETE.

PROVIDE NECESSARY CONDUIT AND WIRING AS REQUIRED TO CONNECT ZONE EQUIPMENT (POWER EXTENDER PANELS AND AMPLIFIERS).

BID ITEM V (ALTERNATE NO. 4): SAME AS ABOVE EXCEPT DEDUCT REWIRING OF ADDRESSIBLE FIRE ALARM INITIATION DEVICES. EXISTING LOOPS SHALL BE CONNECTED COMPLETE TO THE NEAREST NODE PANEL AND DEVICES SHALL BE PROGRAMMED TO ACTIVATE THE PROPER NOTIFICATION APPLIANCES IN THE ZONE IN WHICH THEY ARE LOCATED. PROVIDE NECESSARY ADDITIONAL SLC CARDS IN NODE EQUIPMENT

TO ACCOMMODATE ALL EXISTING SLC CIRCUITS.

1.

2.

1.

2.

3.

4.

5.

6.

7.

CONTRACTOR SHALL PROVIDE FIRE WATCH SERVICES IN ALL AFFECTED AREAS AS REQUIRED BY MOST RECENT EDITION OF NFPA 101. PROVIDE

NO LESS THAN (1) HOUR NOTICE TO AHJ PRIOR TO IMPLEMENTATION OF A FIRE WATCH.

PROVIDE FIRE WATCH WHEN FIRE ALARM SYSTEM IS OUT-OF-SERVICE FOR MORE THAN (8) HOURS IN A 24-HOUR PERIOD.

FIRE WATCH SERVICES SHALL:

FIRE WATCH PERSONNEL SHALL FOLLOW FEDERAL OSHA REQUIREMENTS (SECTION 1915.504) AND SHALL BE TRAINED PER OSHA (SECTION 1915.508)

FIRE WATCH GENERAL NOTES

MAINTAIN A RECORD OF FIRE ALARM IMPAIRMENTS THROUGHOUT THE PROJECT DURATION

PROVIDE A MINIMUM OF (1) SUITABLE FIRE WATCH PATROL FOR EACH FLOOR OF EACH BUILDING THAT IS AFFECTED BY THE SYSTEM

IMPAIRMENT BUT NO MORE THAN 40,000 SQ. FT.

FOR EXAMPLE: AN IMPAIRMENT DISABLES (2) FLOORS OF CARES TOWER AND (2) FLOORS OF ACC SIMULTANEOUSLY FOR MORE THAN 8

HOURS IN A 24-HOUR PERIOD OF TIME. A MINUMUM OF (4) FIRE WATCH PATROLS WOULD BE REQUIRED FOR THE DURATION

OF THIS IMPAIRMENT.

PROVIDE CONTINUOUS PATROL OF ALL AREAS AFFECTED BY THE IMPAIRMENT TO LOOK FOR EVIDENCE OF SMOKE, FIRE, OR ABNORMAL

CONDITIONS.

NOTIFY THE PROPER VA FIRE SAFETY PERSONNEL IF EMERGENCY CONDITIONS ARE DETECTED.

PREVENT FIRES FROM OCCURING OR SPREADING

EXTINGUISH SMALL FIRES

PROTECT THE PUBLIC FROM FIRE OR LIFE SAFETY DANGERS.

BE TRAINED IN THE BUILDING FLOOR PLAN TO SURVEY BOTH OCCUPIED AND UNOCCUPIED AREAS FOR FIRE CONDITIONS.

BE TRAINED IN THE LOCATIONS OF MANUAL FIRE ALARM STATIONS AND FIRE PROTECTION EQUIPMENT.

FIRE ALARM - VOICE MESSAGE COORDINATION:

A. CONTRACTOR SHALL PROVIDE, IN THEIR BID, (2) 2-HOUR MEETINGS WITH VA CONSTRUCTION AND VA SAFETY/POLICE SERVICES TO DISCUSS VOICE ALARM NOTIFICATIONS. MEETINGS SHALL BE TO DETERMINE EXACT VERBIAGE OF ALARM MESSAGE TO BE DELIVERED TO ZONES.

ALARM MESSAGES SHALL BE DETAILED IN FIRE ALARM SYSTEM SUBMITTAL AND SHALL BE REQUIRED FOR APPROVAL OF SUBMITTAL.

THE FOLLOWING AREAS SHALL BE CONSIDERED INFECTION CONTROL CLASS III, UNLESS OTHERWISE INSTRUCTED BY COR:

a. ALL SURGERY RELATED AREAS b.PHARMACY

c. ENDOSCOPY d.PACU

e. MICU

f. PCU

g. CATH LABS

h. STERILE PROCESSING AND STORAGE

i. RADIOLOGY

j. DIALYSIS

COORDINATE EXACT LOCATIONS AND REQUIREMENTS WITH COR AND REFER TO SPECIFICATIONS SECTION "01 35 26 - SAFETY REQUIREMENTS" FOR ADDITIONAL INFORMATION. CONTRACTOR SHALL INCLUDE ALL INFECTION CONTROL MITIGATION AND REQUIRED CLEANING IN BID.

INFECTION CONTROL NOTES

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title Project NumberProject Title

Building Number

Approved: Location

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Office of

Facilities

Management

FULLY SPRINKLERED

Date

05/14/21

Checked Drawn

Drawing Number

Dwg. of DateRevisions:

o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

D

C

B

A

E

F

D

C

B

A

E

F

1 2 3 4 5 6 7 8 9 10

1 2 3 4 5 6 7 8 9 10

VA FORM 08-6231, OCT 1978

DOCUMENT SET MUST BE PRINTED IN COLOR

BID DOCUMENTS SUBMISSION 05/14/21 17069

FIRE ALARM INPUT/OUTPUT

AND ZONE TRIGGER MATRIX

541-18-101UPGRADE FIRE ALARM

MPL CPC

FA-L-0.2

NOT TO SCALE

FIRE ALARM SYSTEM

AUDIO/VISUAL TRIGGER MATRIX -

GENERAL INITIATIONNOT TO SCALE

FIRE ALARM SYSTEM

GENERAL INPUT OUTPUT MATRIX

NOT TO SCALE

FIRE ALARM SYSTEM

AUDIO/VISUAL TRIGGER MATRIX -

WATERFLOW INITIATION

FIRE ALARM TRIGGER MATRICES ARE INTENDED TO INDICATE THE ZONES THAT ALARM BASED ON THE ZONE IN WHICH

THE FIRE OR WATERFLOW ORIGINATES.

THERE ARE (2) MODES OF ALARM: AUDIBLE COMMANDS ONLY (VOICE SIGNAL) AND AUDIBLE/VISUAL ALARM (TEMPORAL

THREE ALARM AND STROBES).

BASED ON THEIR PROXIMITY TO THE ZONE OF ORIGIN OF THE FIRE (THE LEFT COLUMN), THE FIRE ALARM SYSTEM

ZONES RESPOND ACCORDING TO THE MATRIX (THE REMAINING COLUMNS).

FOR EXAMPLE:

EXCEPTION:

FIRE ALARM MATRIX GENERAL NOTE

A FIRE ORIGINATES IN ZONE 2.4.2 (ACC BUILDING). THE ZONE OF ORIGIN WOULD RECEIVE AN AUDIBLE/VISUAL ALARM (TEMPORAL THREE ALARM AND STROBES). THE ZONES ON THE FLOOR ABOVE AND FLOOR BELOW (ZONES 2.2.3, 2.3.1, 2.4.1, 2.5.1 AND 2.5.2) WOULD RECEIVE AUDIBLE COMMANDS ONLY (VOICE SIGNAL). ALL OTHER SMOKE ZONES WOULD RECEIVE NO FIRE ALARM NOTIFICATION.

A WATER FLOW SIGNAL ORIGINATES IN THE SAME ZONE 2.4.2 (ACC BUILDING). ALL ZONES FED BY THE FLOW SWITCH (ASSUMED TO BE ALL ZONES ON THE SAME FLOOR AS THE ZONE OF ORIGIN, ZONE 2.4.1

IN THIS EXAMPLE) WOULD RECEIVE AN AUDIBLE/VISUAL ALARM (TEMPORAL THREE ALARM AND

STROBE). THE ZONES ON THE FLOOR ABOVE AND FLOOR BELOW (ZONES 2.2.3, 2.3.1, 2.5.1 AND 2.5.2)

WOULD RECEIVE AUDIBLE COMMANDS ONLY (VOICE SIGNAL). ALL OTHER SMOKE ZONES WOUD

RECEIVE NO FIRE ALARM NOTIFICATION.

SURGERY (ZONES 1.10.1 AND 1.10.2) ONLY RECEIVE NOTIFICATION WHEN THEIR OWN ZONE IS IN

ALARM. SURGERY IS NOT NOTIFIED WHEN ADJACENT ZONES ARE IN ALARM AS THEY ARE NOT

EXPECTED TO ASSIST DEFEND-IN-PLACE MEASURES FOR FIRES OUTSIDE THEIR ZONE.

FA-E-3.1

FA-E-3.1

FA-E-3.1

FA-E-1.1

K21 K24 K25 K26 K27 K29 K30 K30a K34 K35 K36 K37 K40 K42

J21 J24 J25 J26 J27 J29 J30 J30a J34 J35 J36 J37 J40 J42

H23 H28a H30 H30a H34 H35 H36 H37 H42H41

F28a

H28a

C1 28

B28

A28

F30 F30a

D30aD30

B30

A30

C1 31

B31

A31

H24 H24b H26aH25a

G1 37

E37

C37

G1 42

E41

C41

E 42

C 42

L25 L26 L27 L29 L30 L33 L34 L35 L36 L37 L39 L42L24

M24M23

M37

L2

Z5 Z6 Z7 Z8 Z10 Z12 Z114A Z115B Z116B Z117C Z118D

Z19 Z22

AA22AA19A

Y115B Y116B Y117C Y118D

X15B X16B X17C X18D

W115B W116B W117B W118D

Y19 Y22

W22W19W18

Y5 Y6 Y7 Y8 Y10 Y12

W5 W6 W7 W8 W10 W12

V5 V6 V7 V8 V12

T5 T6 T7 T8 T12

V9

T9

Q6 Q7 Q8 Q12Q9

N6 N7 N8 N12N9

Z113

Y113

X13 X14A

W13 W14A

V119V118 V122

V19V18 V22V20V13

T13

Q13

N13

V15 V16 V17

T18T15 T16 T17

Q18Q15 Q16 Q17

N118 N15 N16 N17

R5R2R1

P2P1 P5

T20

R20

T23A

R23A

Q20

P20 P23

L2L1 L17 L18 L20 L23L16L15L13L7L6L5 L12L9L8

K3K1 K17 K18 K20K16K15K13K7K6K5 K12K9K8

J1

H2H1 H17a H18b H20H16aH14H7H6H4 H12H8

J20J18J17J16J15J13J12J11aJ8J7J6J5J3

H11a H15a

F12

D12

B12

F11a

D11a

C1 11

B11

A11 A12

F14

D14

C1 14

B14

A14

E2

C2

G1 14

E4

C4

G1

E1

C1

L2 1 L2 5

M20

G18 b

AA22 AA24A AA25 AA26 AA27 AA29 AA30 AA32 AA34 AA35 AA36 AA37

Z24

Y24

W22

Z25 Z26 Z27 Z29 Z30 Z32

Y25 Y26 Y27 Y29 Y30 Y32

BB29 BB30 BB32 BB34 BB35 BB36 BB37

Z22

Y22

Z34 Z35 Z36 Z37

Y34 Y35 Y36 Y37

W24 W25 W26 W27 W29 W30 W33 W34 W35 W36 W37

V122 V124

V22 V24 V25 V26 V27 V29 V30 V33 V34 V35 V36 V37

T23A T24 T27 T30 T33 T34

U35 U36

T37

S26 S29

R224

R23A R25 R37 R39 R42

Q23 Q24

P23A

Q25 Q26 Q27 Q29 Q30 Q33 Q34 Q35 Q36

N25 N26 N27 N29 N30 N33 N34 N35 N36

P37 P39 P42

K21 K24 K25 K26 K27 K29 K30 K30a K34 K35 K36 K37 K40 K42

J21 J24 J25 J26 J27 J29 J30 J30a J34 J35 J36 J37 J40 J42

H23 H28a H30 H30a H34 H35 H36 H37 H42H41

F28a

H28a

C1 28

B28

A28

F30 F30a

D30aD30

B30

A30

C1 31

B31

A31

H24 H24b H26aH25a

G1 37

E37

C37

G1 42

E41

C41

E 42

C 42

L25 L26 L27 L29 L30 L33 L34 L35 L36 L37 L39 L42L24

M24M23 M37

L2

Z5 Z6 Z7 Z8 Z10 Z12 Z114A Z115B Z116B Z117C Z118D

Z19 Z22

AA22AA19A

Y115B Y116B Y117C Y118D

X15B X16B X17C X18D

W115B W116B W117B W118D

Y19 Y22

W22W19W18

Y5 Y6 Y7 Y8 Y10 Y12

W5 W6 W7 W8 W10 W12

V5 V6 V7 V8 V12

T5 T6 T7 T8 T12

V9

T9

Q6 Q7 Q8 Q12Q9

N6 N7 N8 N12N9

Z113

Y113

X13 X14A

W13 W14A

V119V118 V122

V19V18 V22V20V13

T13

Q13

N13

V15 V16 V17

T18T15 T16 T17

Q18Q15 Q16 Q17

N118N15 N16 N17

R5R2R1

P2P1 P5

T20

R20

T23A

R23A

Q20

P20 P23

L2L1 L17 L18 L20 L23L16L15L13L7L6L5 L12L9L8

K3K1 K17 K18 K20K16K15K13K7K6K5 K12K9K8

J1

H2H1 H17a H18b H20H16aH14H7H6H4 H12H8

J20J18J17J16J15J13J12J11aJ8J7J6J5J3

H11a H15a

F12

D12

B12

F11a

D11a

C1 11

B11

A11 A12

F14

D14

C1 14

B14

A14

E2

C2

G1 14

E4

C4

G1

E1

C1

L2 1 L2 5

M20

G18 b

AA22 AA24A AA25 AA26 AA27 AA29 AA30 AA32 AA34 AA35 AA36 AA37

Z24

Y24

W22

Z25 Z26 Z27 Z29 Z30 Z32

Y25 Y26 Y27 Y29 Y30 Y32

BB29 BB30 BB32 BB34 BB35 BB36 BB37

Z22

Y22

Z34 Z35 Z36 Z37

Y34 Y35 Y36 Y37

W24 W25 W26 W27 W29 W30 W33 W34 W35 W36 W37

V122 V124

V22 V24 V25 V26 V27 V29 V30 V33 V34 V35 V36 V37

T23A T24 T27 T30 T33 T34

U35 U36

T37

S26 S29

R224

R23A R25 R37 R39 R42

Q23 Q24

P23A

Q25 Q26 Q27 Q29 Q30 Q33 Q34 Q35 Q36

N25 N26 N27 N29 N30 N33 N34 N35 N36

P37 P39 P42

Y2W2U2S2P2

R5

S11P11

S12P12

S15P15

S17P17

S19P19

S21P21

S25

S28P28

V11

X7

X11

V13 X13

O31K31H31

F32

G33 H33 M33 O34

O35

O38

K39

K36

G37 H37

H40

B26

B27

A29

C30

C27 F27 H27 K27 O27

H23 K23 O23

A24 E24 F24

A22 C22 G22

A20

C20

G20

A18

C18

J18

K19 N19 O19

A16

C16

J16

N17

A14

C14

J14 N15

A10

C10

A8

C8

J10

J8

A4

C4

O4

A1

C1

1N

2M

1K

1H

1G

1E

1C

3B 4B 5B 6B 8B7B

3D 4D 5D 6D 8D7D

3F 4F 5F 6F 8B7F

3J 4J 5J 6J 8J7J

3L 4L 5L 6L 8L7L

H1 B1

H2

H3

H4

H5

H6

H7

H8

H9

H10

H11

G1

G2

G3

G4

G5

G7

F1

F2

F3

F4

F5

F7

C1

C2

C3

A2

D5

E5

G8 F8 E8

G9 F9 E9

G10 F10 E10

G11 F11 E11

E10 D10 C10 B10 A10

E11 D11 C11 B11 A11

E12 D12 C12 B12 A12

19.2

BB.1

19.2

AA.5

23.1

AA.5

24.3

AA.5

25.2

AA.5

26.5

AA.5

28.8

AA.5

24.3

BB.5

25.2

BB.5

26.5

BB.5

28.8

BB.5

23.1

BB.5

24.3

CC.6

25.2

CC.6

25.2

DD

26.5

DD

28.8

DD

34.6

DD

35.9

DD

28.9

CC.1

28.8

CC.2

26.5

CC.2

DD

30.1

DD

DD

34.6

CC.1

35.6

CC.1

32.2

CC.1

30.1

CC.1

37.1

CC.1

41.3

CC.1

37.1

AA.7

41.5

AA.7

42.5

Z.1

48O

49O

50O

51O

52O

53O

53AO

49N

52N

53N

54N

54N1

49M

50M

51M

52M

53M

54M

49L

50L

51L

52L

53L

54L

50K

51K

52K

53K

54K

50J

51J

52J

53J

54J

50H

51H

52H

53H

54H

50G

51G

52G

53G

54G

50F

51F

52F

53F

54F

43J

43H

43G

47L

43L

43M 46M 47M

47N

32E 35.5E 36.5E

32D

32C

32B

32.5D

32.5C

32.5B

32E

35.5D

35.5C

32E

36.5D

36.5C

36.5B 38.8B

36.5A 38.8A

C6 D6 E6 F6

C5 D5 E5 F5 G5

B6A6

B4A4

D3 E3 F3 G3

D2 E2 F2 G2

D1 E1 F1 G1

C7 D7 E7 F7B7

14D

F2

15C

F2

16C

F2

17B

F1

14D

E1

15C

E1

16C

E1

18E

E1

20A

E1

21E

E1

25B

E1

26B

E1 27B

E1

25B

F2

26B

F2 27B

F2

24C

F1

14D

C2

15C

C2

16C

C2

18E

C2

20A

C2

21E

C2

25B

C2

26B

C2 27A

C2

14D

A1

15C

A1

16C

A1

18E

A1

20A

A1

25B

A1

26B

A1 27A

A1

14C

XX

15C

XX

16C

XX

18E

XX

20AXX 21E

XX

25B

XX

26B

XX

27C

XX

14C

UU

15C

UU

16C

UU

18E

UU

20A

UU

21E

UU

25B

UU

26B

UU

27C

UU

14F

RR

15C

RR

16C

RR

18E

RR

20A

RR

21E

RR

25B

RR

26B

RR

27C

RR

28B

YY

32A

ZZ

28B

UU

28B

SS

32A

SS

32A

UU

32A

VV

12A

WW

12A

YY

9A

ZZ

9A

VV

9A

TT

9A

SS

11B

SS

11B

RR

12A

RR

12A

TT

21F

D

25C

D

25D

D

27D

D

27D

B

50N

51N

UP TO BASEMENTROUTED IN EXISTING

PATHWAY

DOWN FROM BASEMENT

UP TO BASEMENT

DOWN FROM BASEMENT

ZONE 3.1.1

ZONE 3.1.2

ZONE 3.1.3

ZONE 1.3.5

FALSL1

208V

BUILDING #1 - MAIN BUILDING

BUILDING #2 - AMBULATORY CARE CENTER (ACC)

BUILDING #3 - CARES TOWER

BUILDING #4 - RESEARCH WING

BUILDING #5 - ENERGY CENTER

BUILDING #6 - PALMS/LAB WAREHOUSE

BUILDING LEGEND

NODE AND ZONE EQUIPMENT

• (1) 24"W CABINET WITH FACP AND DVC.

• (1) 24"W CABINET WITH FAEP AND AMPLIFIER.

ZONE EQUIPMENT ONLY

• (1) 24"W CABINET WITH FAEP AND AMPLIFIER.

NODE CABLING

• 6-STRAND, SINGLE-MODE, TIGHT-BUFFER,

INDOOR, FIBER OPTIC CABLE IN COMPLETE 3/4"

EMT CONDUIT SYSTEM.

EQUIPMENT LEGEND

672 EAST ROYALTON ROAD

BROADVIEW HTS., OHIO 44147

TEL. (440) 546-9696

FAX: (440) 546-9699

S

59459

M.P. LONG

R

ES

O F

I R

GE

NOI

S

P

E

N E

DERT

L EA

E I N

G

R

TS

TEA HF OO

IO

CONSULTANTS: ARCHITECT:

Drawing Title

Approved: Location

Project Title

Date Checked Drawn

Drawing Number

Building Number

Project Number

Office of

Facilities

Management

Dwg. of o n e e ig h th in c h o n e fo o t o n e q u a rt e r in c h o n e fo o t th re e e ig h th s in c h o n e fo o t o n e h a lf in c h o n e fo o t th re e q u a rt e rs in c h o n e fo o t o n e in c h o n e fo o t o n e a n d o n e h a lf in c h e s o n e fo o t th re e in c h e s o n e fo o t

VA FORM 08-6231, OCT 1978

1 2 3 4 5 6 7 8 9 10

A

1 2 3 4 5 6 7 8 9 10

B

C

D

E

F

A

B

C

D

E

F

LOUIS STOKES MEDICAL CENTER 10701 EAST BLVD.

Revisions: Date

DOCUMENT SET MUST BE PRINTED IN COLOR

FULLY SPRINKLERED

17069BID DOCUMENTS SUBMISSION 05/14/21

UPGRADE FIRE ALARM 541-18-101

CPCMPL

SUB-BASEMENT FIRE ALARM ZONE

KEY PLAN

FA-K-SB

05/14/21

NOT TO SCALE

SUB-BASEMENT FIRE ALARM ZONE KEY PLAN 1

PATHWAY SHOP DRAWING REQUIREMENT

APPROXIMATE ROUTING SHOWN ON THIS DRAWING FOR THE FIRE ALARM SYSTEM CLASS X FIBER LOOP INDICATES GENERAL SCOPE OF WORK. CONTRACTOR MUST FIELD VERIFY ACTUAL ROUTING AND SUBMIT "PATHWAY SHOP DRAWING" TO VA COR FOR APPROVAL AND COORDINATION. DRAWING SHALL BE MINIMUM 1" = 40'-0" SCALE AND SHALL INDICATE, BUT IS NOT LIMITED TO, PROPOSED ROUTE, PULLBOXES, PENETRATION THROUGH FLOORS AND LIFE SAFETY BARRIERS (SMOKE AND FIRE), ETC. WHERE ROUTING IS ABOVE FINISHED CEILINGS IN OCCUPIED AREAS, INDICATE APPROXIMATE LENGTH OF TIME AND EXTENT OF WORK.

PATHWAY SUPPORT, ID, AND COORDINATION REQUIREMENT

INDEPENDENTLY SUPPORT CONDUITS AS REQUIRED PER SPECIFICATIONS. PROVIDE IDENTIFICATION TAG ON CONDUIT ON 10FT INTERVALS. TAG SHALL READ "FIBER OPTIC CABLES" "FIRE ALARM NETWORK CLASS X LOOP". FIBER IN PUBLIC SPACES SHALL BE INSTALLED DURING OFF-HOURS TO MINIMIZE INTERRUPTION TO HOSPITAL FUNCTION.

COORDINATE SCHEDULING WITH VAMC COR.

DN

DN

DN

DN

FA-E-3.1

FA-E-3.1

FA-E-3.1

FA-E-1.1

FA-E-2.1

FA-E-2.1

FA-E-1.1

FA-E-4.1

FA-E-6.1

FA-E-1.1

FA-E-1.1

FA-E-1.1

FA-E-1.1

FA-E-1.1

FA-E-1.1

FA-E-1.1

FA-E-1.1

FA-E-5.1

FA-E-5.1

FA-E-1.1

K21 K24 K25 K26 K27 K29 K30 K30a K34 K35 K36 K37 K40 K42

J21 J24 J25 J26 J27 J29 J30 J30a J34 J35 J36 J37 J40 J42

H23 H28a H30 H30a H34 H35 H36 H37 H42H41

F28a

H28a

C1 28

B28

A28

F30 F30a

D30aD30

B30

A30

C1 31

B31

A31

H24 H24b H26aH25a

G1 37

E37

C37

G1 42

E41

C41

E 42

C 42

L25 L26 L27 L29 L30 L33 L34 L35 L36 L37 L39 L42L24

M24M23

M37

L2

Z5 Z6 Z7 Z8 Z10 Z12 Z114A Z115B Z116B Z117C Z118D

Z19 Z22

AA22AA19A

Y115B Y116B Y117C Y118D

X15B X16B X17C X18D

W115B W116B W117B W118D

Y19 Y22

W22W19W18

Y5 Y6 Y7 Y8 Y10 Y12

W5 W6 W7 W8 W10 W12

V5 V6 V7 V8 V12

T5 T6 T7 T8 T12

V9

T9

Q6 Q7 Q8 Q12Q9

N6 N7 N8 N12N9

Z113

Y113

X13 X14A

W13 W14A

V119V118 V122

V19V18 V22V20V13

T13

Q13

N13

V15 V16 V17

T18T15 T16 T17

Q18Q15 Q16 Q17

N118N15 N16 N17

R5R2R1

P2P1 P5

T20

R20

T23A

R23A

Q20

P20 P23

L2L1 L17 L18 L20 L23L16L15L13L7L6L5 L12L9L8

K3K1 K17 K18 K20K16K15K13K7K6K5 K12K9K8

J1

H2H1 H17a H18b H20H16aH14H7H6H4 H12H8

J20J18J17J16J15J13J12J11aJ8J7J6J5J3

H11a H15a

F12

D12

B12

F11a

D11a

C1 11

B11

A11 A12

F14

D14

C1 14

B14

A14

E2

C2

G1 14

E4

C4

G1

E1

C1

L2 1 L2 5

M20

G18 b

AA22 AA24A AA25 AA26 AA27 AA29 AA30 AA32 AA34 AA35 AA36 AA37

Z…

This is the start of the file's text. The full file is on GovTribe.