36C25018B0817-010.pdf

PDF 18 MB Posted

Attached to
Expand 8th Floor - Mental Health 506-330
Solicitation number
36C25018B0817
Issued by

About this file

36C25018B0817 S02 - Drawings VOL2-Part 5 -506-330.pdf

View the file

Other files

File Type Posted
36C25018B0817-0005000.docx DOCX document
36C25018B0817-0005001.pdf PDF
36C25018B0817-0005003.pdf PDF
36C25018B0817-0005002.pdf PDF
36C25018B0817-0004000.docx DOCX document
36C25018B0817-0003001.docx DOCX document
36C25018B0817-0003000.docx DOCX document
36C25018B0817-0002000.docx DOCX document
36C25018B0817-0001000.docx DOCX document
36C25018B0817-011.pdf PDF
36C25018B0817-005.pdf PDF
36C25018B0817-003.pdf PDF
36C25018B0817-007.pdf PDF
36C25018B0817-008.pdf PDF
36C25018B0817-012.pdf PDF
36C25018B0817-001.docx DOCX document
36C25018B0817-013.docx DOCX document
36C25018B0817-016.docx DOCX document
36C25018B0817-009.pdf PDF
36C25018B0817-006.pdf PDF
36C25018B0817-014.pdf PDF
36C25018B0817-015.pdf PDF
36C25018B0817-002.pdf PDF
36C25018B0817-004.pdf PDF
36C25018B0817-000.docx DOCX document
Show all 25

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

ARMS OFFICE

BB72A

TOILET

BB73

TOILET

BB74

OFFICE EM. MGR.

BB76

OFFICE

BB77

STORAGE

BB77C

OFFICE PHYS SEC

BB105

OFFICE INVSTGTR

BB107

OFFICE CHIEF

BB111

EVIDENCE

BB108

INTERVIEW

BB110

HOLDING

BB112

STORAGE

BB118A

TRAINING/BREAK

BB118

MEN'S LOCKER

BB120A

CORR.

CB106

STAIR

CORRIDOR

CB81

CORR.

CB80

J K L I

I

I'

22'

L

A B C D E F G H

G'F'E' H' K'

4.1

B.3

H2 A4

A4

A4

A4A4

A4 A4

A4

A4

A4

A4

C1

C1

A4

F1

A2

F1

F1

C1

A1

A1

A1

W2

C1

W2

X2

X1

X1

X1

NL

CLBB-1-2

CLBB-1-3

LBB-1-7

LBB-1-7

LBB-1-9

LBB-1-9

LBB-1-7

LBB-1-7

LSBB-1-1

LSBB-1-1

CLBB-1-2

CLBB-1-2

LSBB-1-1

LBB-1-9

LSBB-1-1

ALTD-3

UNIT 'B'

UNIT 'A'

UNIT

'B'

UNIT

'A'

LSBB-1-1

LSBB-1-1

A4 A4

ALTD-8

F1 F1 F1

F1F1F1

A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL

ITEMS SHOWN ON THIS DRAWING.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6'

LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURES UNLESS INDICATED OTHERWISE.

D. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR

LIGHTING FIXTURES.

E. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE

PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE

CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL

EQUIPMENT SCHEDULE.

G. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER

THAN 75 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

H. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER

THAN 175 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

I. LIGHTING SHALL BE FED FROM EXISTING LIGHTING PANEL(S) IN EXISTING LOCAL

ELECTRICAL ROOMS.

J. LIGHT FIXTURES INDICATED AS "EMERGENCY" IN CORRIDORS AND LARGE PUBLIC

SPACES SHALL BE ON NIGHT LIGHT (UNSWITCHED) CIRCUITS FED FROM THE

NEAREST LIFE SAFETY LIGHTING PANEL.

K. LIGHT FIXTURES IN SMALLER ENCLOSED ROOMS WHERE LIGHTING IS CONTROLLED

LOCALLY, SHALL BE FED FROM A LIFE SAFETY CIRCUIT FROM THE NEAREST

AVAILABLE LIFE SAFETY LIGHTING PANEL. THIS CIRCUIT SHALL BE FED THROUGH A

REMOTE GENERATOR TRANSFER DEVICE WHICH SENSES LOSS OF NORMAL CIRCUIT

AND TRANSFERS TO THE LIFE SAFETY CIRCUIT IN THAT CASE.

LIGHTING GENERAL NOTES

LIGHTING KEYNOTES

1. ADD TO NORMAL LIGHTING CIRCUIT IN CORRIDOR EAST OF TOILET BB74.

N

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o n e o e q u a rt e r in c h o th re e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE: As indicated

EL100B

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT KEZ

LIGHTING PLAN - BASEMENT-

UNIT B

EXPAND 8TH FLOOR

MENTAL HEALTH

NORTH

SCALE: 1/4" = 1'-0"

BASEMENT LIGHTING

PLAN - UNIT B

REVISIONS DATE

LOBBY

B184

KIOSK ALCOVE

CB184A

J K

I I

I'

17 17

H''F''E''

A B C D E F G H

G'F'E' H' J'

1.9

4.1

B.3

C2 C2 C2

P1

D2

D2

D2

D2

D2

A4 A4

D1 D1

D2

D2 D2D2D2

D2 D2 D2 D2

D2D2D2D2

CR1B-1 R1B-1

L1B-1 CL1B-1

LS1B-1

P7

P7 P7

X1

X1

NL

NL

NL

NL

NLNL

NL NL

NL

SWITCHES AT

LOBBY DESK

P3

P2

P7 P7 P7

R8

R8

LS1B-1-2

LS1B-1-2

LS1B-1-2

LS1B-1-2 LS1B-1-2

LS1B-1-2LS1B-1-2

LS1B-1-2

LS1B-1-2

L1B-1-3

R1B-1-17

R12

W1

W1 W1

W1

LS1B-1-2

LS1B-1-2

ALTD-6

ALTD-6ALTD-6

ALTD-6

UNIT 'B'

UNIT 'A'

UNIT 'B'

UNIT 'A'

LS1B-1-2 D2

NL

R4

L1B-1-3 L1B-1-5

NL

LS1B-1-2

D2

D2

LS1B-1-2

LS1B-1-2

D2LS1B-1-2

KIOSK ALCOVE

CB184A

VESTIBULE

CB184V

WAITING

CB184

COFFEE SHOP

B184A

A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL

ITEMS SHOWN ON THIS DRAWING.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6'

LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURES UNLESS INDICATED OTHERWISE.

D. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR

LIGHTING FIXTURES.

E. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE

PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE

CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL

EQUIPMENT SCHEDULE.

G. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER

THAN 75 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

H. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER

THAN 175 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

I. LIGHTING SHALL BE FED FROM EXISTING LIGHTING PANEL(S) IN EXISTING LOCAL

ELECTRICAL ROOMS.

J. LIGHT FIXTURES INDICATED AS "EMERGENCY" IN CORRIDORS AND LARGE PUBLIC

SPACES SHALL BE ON NIGHT LIGHT (UNSWITCHED) CIRCUITS FED FROM THE

NEAREST LIFE SAFETY LIGHTING PANEL.

K. LIGHT FIXTURES IN SMALLER ENCLOSED ROOMS WHERE LIGHTING IS CONTROLLED

LOCALLY, SHALL BE FED FROM A LIFE SAFETY CIRCUIT FROM THE NEAREST

AVAILABLE LIFE SAFETY LIGHTING PANEL. THIS CIRCUIT SHALL BE FED THROUGH A

REMOTE GENERATOR TRANSFER DEVICE WHICH SENSES LOSS OF NORMAL CIRCUIT

AND TRANSFERS TO THE LIFE SAFETY CIRCUIT IN THAT CASE.

LIGHTING GENERAL NOTES

LIGHTING KEYNOTES

1. PHOTOCELL CONTROL ON AND OFF.

N

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE: As indicated

EL101A

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT KEZ

LIGHTING PLAN - 1ST FLOOR

- UNIT A

EXPAND 8TH FLOOR

MENTAL HEALTH

NORTH

SCALE: 1/4" = 1'-0"

FIRST FLOOR

LIGHTING PLAN - UNIT

A

NORTH

SCALE: 12" = 1'-0"

94 - Lighting Keynotes Copy 2

A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL

ITEMS SHOWN ON THIS DRAWING.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6'

LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURES UNLESS INDICATED OTHERWISE.

D. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR

LIGHTING FIXTURES.

E. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE

PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE

CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL

EQUIPMENT SCHEDULE.

G. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER

THAN 75 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

H. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER

THAN 175 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

I. LIGHTING SHALL BE FED FROM EXISTING LIGHTING PANEL(S) IN EXISTING LOCAL

ELECTRICAL ROOMS.

J. LIGHT FIXTURES INDICATED AS "EMERGENCY" IN CORRIDORS AND LARGE PUBLIC

SPACES SHALL BE ON NIGHT LIGHT (UNSWITCHED) CIRCUITS FED FROM THE

NEAREST LIFE SAFETY LIGHTING PANEL.

K. LIGHT FIXTURES IN SMALLER ENCLOSED ROOMS WHERE LIGHTING IS CONTROLLED

LOCALLY, SHALL BE FED FROM A LIFE SAFETY CIRCUIT FROM THE NEAREST

AVAILABLE LIFE SAFETY LIGHTING PANEL. THIS CIRCUIT SHALL BE FED THROUGH A

REMOTE GENERATOR TRANSFER DEVICE WHICH SENSES LOSS OF NORMAL CIRCUIT

AND TRANSFERS TO THE LIFE SAFETY CIRCUIT IN THAT CASE.

LIGHTING GENERAL NOTES

CORRIDOR

CB184C

J K L I I

I

I'

22'

L

A B C D E F

F

G H

G'F'E' H' K'

4.1

B.3

C2 C2 C2

STAIR

W1

D2 D2

D2

D2

W1

P7

NL

NL

NL

NL NL

P5 P4

P5 P6

P5

P4 P6

P4

LS1B-1-2 LS1B-1-2

LS1B-1-2

LS1B-1-2

LS1B-1-2

L1B-1-3

R1B-1-17

R12

ALTD-6

ALTD-6

ALTD-6

UNIT 'B'

UNIT 'A'

UNIT 'B'

UNIT 'A'

/4

D2

D2

D2

D2

LS1B-1-2

LS1B-1-2

NL

COFFEE SHOP

B184A

N

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE: As indicated

EL101B

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT KEZ

LIGHTING PLAN - 1ST FLOOR

- UNIT B

EXPAND 8TH FLOOR

MENTAL HEALTH

NORTH

SCALE: 1/4" = 1'-0"

FIRST FLOOR

LIGHTING PLAN - UNIT

B

A4 A4 A4

A4

A4

A4

A4 A4

A4

A4

A4

A4

A2 A2 A2

A2A2A2

A2

A2

A2 A2 A2

A2A2A2

A4

A4 A4

A4

A4

A4

A4

A4

A4

A4 A4

A4

A4

A4

A4

A4

A4

A4 A4

A4 A4

A4

A4A4

A4 A4

A4 A4

A4 A4

A4 A4

J K IH''F''

L

G'F' POM N QE' H' SR

4'

7'

J'

3.9

K'

Q. MGMT.

A846

TEAM ROOM

A846A

SWING OFFICE

A848

CORRIDOR

FLOAT

A845

FLOAT

A844

SWING OFFICE

A842UTILIZ. MGMT.

A841

SERVICE ELEV

A843

COMMUNICATIONS

A843A

MEN'S RESTROOM

A830

WOMEN'S RESTROOM

A830A

FELLOWS ROOM

A831A

CACS & INFOMATICS

A839

PIMS

A838

ACOS

A837

EXAM

B829

OFFICE

B828

OFFICE

B800

OFFICE

B826

OFFICE

B827

OFFICE

B801

OFFICE

B802

OFFICE

B803

OFFICE

B804

OFFICE

B824

OFFICE

B825

A4 A4

X1

A2

A2 D1

A2

A2 A2

A2

A2 A2 A2

ETR

A4 A4 A4 A4 A4 A4 A4 A4

A4

A4

CL8C-1

LS8C-1

L8C-1 R8C-1

R8C-2

CR8C-1

EM8C-1

CR8D-1

CL8D-1

LS8D-1

L8D-1

R8D-1

R8D-2

BLUE TEAM

B807 A2

A4

A4

COPY/BREAK

A843B

X2 X2

X1

X1

NL

NL NL NL NL

NL

W4

W4

LS8D-1-1 LS8D-1-1 LS8D-1-1 LS8D-1-1 LS8D-1-1

LS8D-1-1

A2

LS8D-1-1

A2

A2 A2

A4

LS8C-1-2

LS8C-1-2

LS8C-1-2

LS8C-1-2

LS8C-1-2

NL

NL

NL

NL NL

NL

LS8C-1-2LS8C-1-2

A4

A4

A4A4

L8C-1-2L8C-1-2L8C-1-2

L8C-1-2

L8C-1-2

L8C-1-2 L8C-1-2

L8C-1-2

L8C-1-2

L8C-1-2

L8C-1-2

L8C-1-2

L8D-1-3

L8D-1-3 L8D-1-3

L8D-1-3

L8D-1-3 L8D-1-3 L8D-1-3 L8D-1-3

L8D-1-3

L8D-1-3

LS8D-1-1

LS8C-1-2

L8C-1-2

L8D-1-4

A2

LS8C-1-2

A2

LS8C-1-2

ALTD-7

UNIT 'B'

UNIT 'A'

UNIT 'B'

UNIT 'A'

A2

A4A4

A4

A4 A4

A4

D1

D1

D1

D1

LS8D-1-1

L8C-1-2

A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL

ITEMS SHOWN ON THIS DRAWING.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6'

LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURES UNLESS INDICATED OTHERWISE.

D. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR

LIGHTING FIXTURES.

E. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE

PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE

CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL

EQUIPMENT SCHEDULE.

G. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER

THAN 75 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

H. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER

THAN 175 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

I. LIGHTING SHALL BE FED FROM EXISTING LIGHTING PANEL(S) IN EXISTING LOCAL

ELECTRICAL ROOMS.

J. LIGHT FIXTURES INDICATED AS "EMERGENCY" IN CORRIDORS AND LARGE PUBLIC

SPACES SHALL BE ON NIGHT LIGHT (UNSWITCHED) CIRCUITS FED FROM THE

NEAREST LIFE SAFETY LIGHTING PANEL.

K. LIGHT FIXTURES IN SMALLER ENCLOSED ROOMS WHERE LIGHTING IS CONTROLLED

LOCALLY, SHALL BE FED FROM A LIFE SAFETY CIRCUIT FROM THE NEAREST

AVAILABLE LIFE SAFETY LIGHTING PANEL. THIS CIRCUIT SHALL BE FED THROUGH A

REMOTE GENERATOR TRANSFER DEVICE WHICH SENSES LOSS OF NORMAL CIRCUIT

AND TRANSFERS TO THE LIFE SAFETY CIRCUIT IN THAT CASE.

LIGHTING GENERAL NOTES

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

A

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE: As indicated

EL108A

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT KEZ

LIGHTING PLAN - 8TH FLOOR

- UNIT A

EXPAND 8TH FLOOR

MENTAL HEALTH

NORTH

SCALE: 1/8" = 1'-0"

EIGHTH FLOOR

LIGHTING PLAN - UNIT

A

J K

I

17 17

H''F''E''

16 16

15 15

L

14 14

A B C D E F G H

G'F' POM N QE' H'D' SRJ' K'

1.9

4.1

B.3

OFFICE

B804

OFFICE

B824

OFFICE

B825

A4 A4

A2

CONFERENCE/MEDIATION

C804

EEO PROGRAM

MANAGER

C803A

CORRIDOR

C8-2

OFFICE

C803

RESTROOM

C801

RESTROOM

C800

CARE CORD.

B818

KITCHENETTE

B816

SHARED OFFICE

B814

SHARED OFFICE

B821

OFFICE

B820

COMMUNICATIONS

B812

LARGE CONF.

B810

BLUE TEAM

B807

COPY

B806

CHIEF

B822a

SECRETARY

B822

X1

A4

A4

A4

A4A4A4A4A4A4A4A4A4A4A4 A4A4

A4

A4

A4

A2 A4

A4

A4

A4

A4

A2A2A2

A2

A2

A4

A4

A4

X1

X1X2

A4

TEAM ROOM

B815

A2 A2

A2A2

A2 A2

A4 A4

A4A4

A4 A4

X1

A4 A4 A4

A4

A4

A2 A2

W2

A4 A4

A4A4

CR8B-1 R8B-1

L8B-1 CL8B-1

LS8B-1

D1

D1

D1

P8

P8

D1

D1

D1 X2

A4 A4 A4

A4

NL

NL NL NLNLNLNLNL

NL

A4 A4

A4

A4

LS8B-1-1

LS8B-1-1

L8B-1-2

LS8B-1-1

LS8B-1-1LS8B-1-1LS8B-1-1LS8B-1-1LS8B-1-1LS8B-1-1

LS8B-1-1

LS8B-1-1

LS8C-1-2

LS8C-1-2

LS8B-1-1

A4

LS8B-1-1

LS8C-1-2

LS8C-1-2

LS8C-1-2LS8C-1-2

LS8C-1-2

NL

NL

NL

NL

LS8C-1-2

L8B-1-2

L8B-1-2

L8B-1-2L8B-1-2 L8B-1-2

L8B-1-2

L8B-1-2

LS8B-1-1

L8B-1-2

L8C-1-2

L8C-1-2

L8C-1-2

ETR

L8C-1-2

L8C-1-2

W2

L8B-1-2

ALTD-5

UNIT 'B'

UNIT 'A'

UNIT 'B'

UNIT 'A'

A4 A4

A. ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE FOR WIRING ALL ELECTRICAL

ITEMS SHOWN ON THIS DRAWING.

B. ALL RECESSED LIGHTING FIXTURES IN LAY-IN CEILINGS SHALL BE INSTALLED WITH 6'

LONG FLEXIBLE METAL CONDUIT.

C. ALL MOUNTING HEIGHTS FOR LIGHTING FIXTURES ARE TO THE BOTTOM OF THE

FIXTURES UNLESS INDICATED OTHERWISE.

D. SEE ARCHITECTURAL EXTERIOR ELEVATIONS FOR MOUNTING HEIGHTS OF EXTERIOR

LIGHTING FIXTURES.

E. CONDUIT AND WIRE SHALL NOT BE INSTALLED BELOW FLOOR SLAB UNLESS

INDICATED ON PLAN BY DASHED CONDUIT.

F. CIRCUIT NUMBERS AT DEVICES CORRESPOND TO PANELBOARD BREAKERS (SEE

PANELBOARD SCHEDULE). BRANCH CIRCUITS SHALL BE SIZED ACCORDING TO THE

CIRCUIT BREAKER RATING, UNLESS INDICATED OTHERWISE ON THE ELECTRICAL

EQUIPMENT SCHEDULE.

G. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 120 VOLT BRANCH CIRCUITS LONGER

THAN 75 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

H. USE #10 AWG CONDUCTORS FOR 20 AMPERE, 277 VOLT BRANCH CIRCUITS LONGER

THAN 175 FEET, UNLESS SPECIFICALLY INDICATED OTHERWISE. THIS SHALL BE

REQUIRED FOR THE ENTIRE LENGTH OF THE CIRCUIT.

I. LIGHTING SHALL BE FED FROM EXISTING LIGHTING PANEL(S) IN EXISTING LOCAL

ELECTRICAL ROOMS.

J. LIGHT FIXTURES INDICATED AS "EMERGENCY" IN CORRIDORS AND LARGE PUBLIC

SPACES SHALL BE ON NIGHT LIGHT (UNSWITCHED) CIRCUITS FED FROM THE

NEAREST LIFE SAFETY LIGHTING PANEL.

K. LIGHT FIXTURES IN SMALLER ENCLOSED ROOMS WHERE LIGHTING IS CONTROLLED

LOCALLY, SHALL BE FED FROM A LIFE SAFETY CIRCUIT FROM THE NEAREST

AVAILABLE LIFE SAFETY LIGHTING PANEL. THIS CIRCUIT SHALL BE FED THROUGH A

REMOTE GENERATOR TRANSFER DEVICE WHICH SENSES LOSS OF NORMAL CIRCUIT

AND TRANSFERS TO THE LIFE SAFETY CIRCUIT IN THAT CASE.

LIGHTING GENERAL NOTES

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

B

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE: As indicated

EL108B

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT KEZ

LIGHTING PLAN - 8TH FLOOR

- UNIT B

EXPAND 8TH FLOOR

MENTAL HEALTH

NORTH

SCALE: 1/8" = 1'-0"

EIGHTH FLOOR

LIGHTING PLAN - UNIT

B

3#1/0,#6GRD, 2"C

(EXTEND EXISTING CIRCUIT AS REQUIRED,

CIRCUIT SIZE SHOWN IS MINIMUM)

EX 75KVA XFMR

208-480/277V

(BASEMENT MAIN ELEC RM

NEAR COL. C/4)

EX SWBD #1

120/208V

(BASEMENT MAIN ELEC RM COL. C/4)

REMOVE

EX PANEL

1-L1-01

(AMBULATORY GARAGE)

NEW 1W-AHU-1

100/3

3P150A

1W-ACCH-1

(9TH FLOOR ROOF)

REFER TO MECHANICAL PLANS

FOR EXACT LOCATION

VFD

EX EMMC4-D1

480V

(4TH FLOOR - COL. G/6)

3#1/0,#6GRD, 2"C

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE: 12" = 1'-0"

E501

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT SCG

ELECTRICAL ONE-LINE

DIAGRAMS

EXPAND 8TH FLOOR

MENTAL HEALTH

NOT TO SCALE

Partial One-Line Diagrams

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 30KVA (84 AMPS). ADD NEW 20/1 CB'S AS REQUIRED. CKTS 31-42 ARE EXISTING SPACES.

NOTES:

EST. DEMAND CURRENT: 57 A

CONNECTED CURRENT: 80 A

Receptacle 26464 VA 68.89% 18232 VA EST. DEMAND LOAD: 20650 VA

Motor 2364 VA 100.00% 2364 VA CONNECTED LOAD: 28882 VA

Lighting 54 VA 100.00% 54 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

41 ... 42 -- -- Space

Motor Space BB121 1500 1 20 A 39 ... 40 -- -- Space

-- 2860 -- -- 37 ... 38 -- -- Space

COFFEE COFFEE SHOP B203 2860 2 35 A 35 ... 36 -- -- Space

-- 3300 -- -- 33 ... 34 -- -- Space

ESPRESSO COFF SHOP B203 3300 2 40 A 31 ... 32 -- -- Space

DISP COFFEE SHOP B203 1836 1 20 A 29 ... 30 20 A 1 900 Receptacle VESTIBULE B201

HOT DISP COFF SHOP B203 1008 1 20 A 27 ... 28 20 A 1 864 1W-EF-1

REFRIGS COFFEE SHOP... 1200 1 20 A 25 ... 26 20 A 1 1320 SHADES

BLENDER COFF SHOP B203 1800 1 20 A 23 ... 24 20 A 1 720 LOBBY B200

BLENDER COFF SHOP B203 1800 1 20 A 21 ... 22 20 A 1 920 LOBBY B200

ICE COFFEE SHOP B203 1200 1 20 A 19 ... 20 20 A 1 540 LOBBY B200

COFFEE SHOP B203 54 540 1 20 A 17 ... 18 20 A 1 360 KIOSKS LOBBY B200

EXISTING 1 20 A 15 ... 16 20 A 1 EXISTING

EXISTING 1 20 A 13 ... 14 20 A 1 EXISTING

EXISTING 1 20 A 11 ... 12 20 A 1 EXISTING

EXISTING 1 20 A 9 ... 10 20 A 1 EXISTING

EXISTING 1 20 A 7 ... 8 20 A 1 EXISTING

EXISTING 1 20 A 5 ... 6 20 A 1 EXISTING

EXISTING 1 20 A 3 ... 4 20 A 1 EXISTING

EXISTING 1 20 A 1 ... 2 20 A 1 EXISTING

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 10,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 208Y/120V / 3 ø / 4W

LOCATION: Space BB122 PANEL TYPE:

PANELBOARD: R1B-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 19KVA (53 AMPS). ADD NEW 20/1 CB'S AS REQUIRED. CKTS 30-42 ARE EXISTING SPACES.

NOTES:

EST. DEMAND CURRENT: 39 A

CONNECTED CURRENT: 50 A

EST. DEMAND LOAD: 14050 VA

CONNECTED LOAD: 18100 VA

Receptacle 18100 VA 77.62% 14050 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

STAFF GYM BB70 540 1 20 A 39 ... 40 -- -- Space

STAFF GYM BB70 720 1 20 A 37 ... 38 -- -- Space

STAFF GYM BB70 1000 1 20 A 35 ... 36 20 A 1 180 MICRO TRAINING/BREAK BB93

33 ... 34 20 A 1 120 ALCOVE BB74A

EWC STAFF GYM BB70 1400 1 20 A 31 ... 32 20 A 1 1200 ALCOVE BB74A

EXISTING 1 20 A 29 ... 30 20 A 1 1080 OFFICE PHYS SEC BB80

EXISTING 1 20 A 27 ... 28 -- -- --

EXISTING 1 20 A 25 ... 26 -- -- --

TRAINING/BREAK BB93 180 1 20 A 23 ... 24 20 A 3 EXISTING HVAC UNIT

REFRIG TRAINING/BREAK 1000 1 20 A 21 ... 22 20 A 1 1080 CORR. BB97

Receptacle TRAINING/BREA... 360 1 20 A 19 ... 20 20 A 1 720 OFFICE CHIEF BB82

TRAINING/BREAK BB93 1260 1 20 A 17 ... 18 20 A 1 900 ADMIN BB71

WOMEN'S LOCKER BB95 900 1 20 A 15 ... 16 20 A 1 900 OFFICE DEPUTY BB83

OPEN OFFICE BB96 1380 1 20 A 13 ... 14 20 A 1 1380 OPEN OFFICE BB96

EXISTING 1 20 A 11 ... 12 20 A 1 EXISTING

BIOMED OFFICE BB32 1080 1 20 A 9 ... 10 20 A 1 EXISTING

BIOMED OFFICE BB32 720 1 20 A 7 ... 8 20 A 1 EXISTING

EXISTING 1 20 A 5 ... 6 20 A 1 EXISTING

EXISTING 1 20 A 3 ... 4 20 A 1 EXISTING

EXISTING 1 20 A 1 ... 2 20 A 1 EXISTING

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 10,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 208Y/120V / 3 ø / 4W

LOCATION: Space 1076 PANEL TYPE:

PANELBOARD: RBB-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 9KVA (11 AMPS).

NOTES:

EST. DEMAND CURRENT: 2 A

CONNECTED CURRENT: 2 A

EST. DEMAND LOAD: 2076 VA

Other 0 VA 0.00% 0 VA CONNECTED LOAD: 2076 VA

Lighting 2076 VA 100.00% 2076 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Decorative Lighting 1402 1 20 A 5 ... 6 20 A 1 Spare

General Lighting 674 0 1 20 A 3 ... 4 20 A 1 EXISTING

EXISTING 1 20 A 1 ... 2 20 A 1 EXISTING

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: Space BB122 PANEL TYPE:

PANELBOARD: L1B-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 45KVA (54 AMPS).

NOTES:

EST. DEMAND CURRENT: 3 A

CONNECTED CURRENT: 3 A

EST. DEMAND LOAD: 2234 VA

Other 0 VA 0.00% 0 VA CONNECTED LOAD: 2234 VA

Lighting 2234 VA 100.00% 2234 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

-- -- -- 41 ... 42 -- -- --

-- -- -- 39 ... 40 -- -- --

EXIST AHU-A (RM BB49A) 3 20 A 37 ... 38 30 A 3 EXIST CU-A

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Lighting OFFICE PHYS SEC... 1290 0 1 20 A 9 ... 10 20 A 1 Spare

BIOMED OFFICE BB32 944 0 1 20 A 7 ... 8 20 A 1 Spare

EXIST LTG 1 20 A 5 ... 6 20 A 1 Spare

EXIST LTG 1 20 A 3 ... 4 20 A 1 C1

EXIST LTG 1 20 A 1 ... 2 20 A 1 C1

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: Space 1076 PANEL TYPE:

PANELBOARD: LBB-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 3KVA (4 AMPS).

NOTES:

EST. DEMAND CURRENT: 1 A

CONNECTED CURRENT: 1 A

EST. DEMAND LOAD: 842 VA

CONNECTED LOAD: 842 VA

Lighting 842 VA 100.00% 842 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Spare 1 20 A 3 ... 4 20 A 1 Spare

EXISTING 1 20 A 1 ... 2 20 A 1 842 Lighting Room B200, B201, B20...

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: Space BB122 PANEL TYPE:

PANELBOARD: LS1B-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 3KVA (4 AMPS).

NOTES:

EST. DEMAND CURRENT: 1 A

CONNECTED CURRENT: 1 A

EST. DEMAND LOAD: 444 VA

CONNECTED LOAD: 444 VA

Lighting 444 VA 100.00% 444 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

EXIST 1 20 A 3 ... 4 20 A 1 Spare

Lighting Room BB97, BB98,... 444 1 20 A 1 ... 2 20 A 1 Spare

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: Space 1076 PANEL TYPE:

PANELBOARD: LSBB-1

1811 4 Mile Rd N.E., Grand Rapids, MI 49525 www.progressiveae.com

616 361 2664 OFFICE 616 361 1493 FAX

architecture +engineering

SEVEN

GENERATIONS

4664 Campus Drive, Suite 101

Kalamazoo, MI 49008

P: 269.927.0144 www.7GenAE.com

2 3 4 5 6 7 8 9

2 3 4 5 6 7 8 91

A

B

C

D

E

F

A

B

C

D

E

F

CONSULTANTS ARCHITECT/ENGINEERS

DRAWING TITLE:

APPROVED: PROJECT DIRECTOR LOCATION

PROJECT TITLE:

DATE: CHECKED: DRAWN:

PROJECT NUMBER:

BUILDING NUMBER:

DRAWING NUMBER:

DWG. ___ OF ___

7GAE PROJECT NO.: XXXXXX FILE NAME: TITL-BLK-3042-VA.DWG

Office of

Construction and Facilities

Management

VA FORM 08-6231

o n e e ig h th i n c h o e q u a rt e r in c h o e e ig h th s in c h o e h a lf i n c h o e q u a rt e rs i n c h o e i n c h o e a n d o n e h a lf i n c h e s o e i n c h e s o

6 "

Department of Veterans

68 East Michigan Ave.

Battle Creek, MI 49017

P: 269.224.3182 www.wbkengineering.com

451 Hungerford Dr. 4th Floor

Rockville, MD 20850

P: 301.770.3520 F: 301.770.3521 www.nikasolutions.com 205

SCALE:

E502

506-330

ANN ARBOR VAMC

OCT. 27, 2017

1W

SDT SCG

ELECTRICAL SCHEDULES EXPAND 8TH FLOOR

MENTAL HEALTH

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 30KVA (83 AMPS)

NOTES:

EST. DEMAND CURRENT: 21 A

CONNECTED CURRENT: 21 A

EST. DEMAND LOAD: 7420 VA

CONNECTED LOAD: 7420 VA

Receptacle 7420 VA 100.00% 7420 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Spare 1 20 A 29 ... 30 20 A 1 Spare

Spare 1 20 A 27 ... 28 20 A 1 Spare

Spare 1 20 A 25 ... 26 20 A 1 Spare

Spare 1 20 A 23 ... 24 20 A 1 Spare

Spare 1 20 A 21 ... 22 20 A 1 Spare

Spare 1 20 A 19 ... 20 20 A 1 Spare

Spare 1 20 A 17 ... 18 20 A 1 Spare

Spare 1 20 A 15 ... 16 20 A 1 Spare

SWING OFFICE A848 540 1 20 A 13 ... 14 20 A 1 Spare

CONFERENCE A846a 740 1 20 A 11 ... 12 20 A 1 540 UTILIZ. MGMT. A841

Q. MGMT. A846 580 1 20 A 9 ... 10 20 A 1 720 UTILIZ. MGMT. A841

Q. MGMT. A846 780 1 20 A 7 ... 8 20 A 1 900 FLOAT A843

Q. MGMT. A846 780 1 20 A 5 ... 6 20 A 1 900 FLOAT A844

Q. MGMT. A846 940 1 20 A 3 ... 4 20 A 1 EXISTING

EXISTING 1 20 A 1 ... 2 20 A 1 EXISTING

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 10,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA1 VOLTAGE: 208Y/120V / 3 ø / 4W

LOCATION: ELECTRICAL A844C PANEL TYPE:

PANELBOARD: R8D-1

EXISTING PANEL. NO EXISTING LOAD.

NOTES:

EST. DEMAND CURRENT: 4 A

CONNECTED CURRENT: 4 A

Other 0 VA 0.00% 0 VA EST. DEMAND LOAD: 3502 VA

Motor 1870 VA 100.00% 1870 VA CONNECTED LOAD: 3502 VA

Lighting 1632 VA 100.00% 1632 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 1870 FCU'S

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Lighting Q. MGMT. A846 1432 0 1 20 A 3 ... 4 20 A 1 200 Lighting CORRIDOR 13

NO SPACE -- -- 1 ... 2 -- -- NO SPACE

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: ELECTRICAL A844C PANEL TYPE:

PANELBOARD: L8D-1

EXISTING PANEL. NO EXISTING LOAD

NOTES:

EST. DEMAND CURRENT: 0 A

CONNECTED CURRENT: 0 A

EST. DEMAND LOAD: 275 VA

CONNECTED LOAD: 275 VA

Lighting 275 VA 100.00% 275 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Spare 1 20 A 3 ... 4 20 A 1 Spare

Lighting Room A846, 13 275 1 20 A 1 ... 2 20 A 1 Spare

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: ELECTRICAL A844C PANEL TYPE:

PANELBOARD: LS8D-1

EXISTING PANEL. EXISTING LOAD IS 9KVA (25 AMPS).

NOTES:

EST. DEMAND CURRENT: 33 A

CONNECTED CURRENT: 39 A

EST. DEMAND LOAD: 12065 VA

CONNECTED LOAD: 14130 VA

Receptacle 14130 VA 85.39% 12065 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Receptacle WOMEN'S... 350 1 20 A 29 ... 30 20 A 1 1000 REFRIG COPY/BREAK A840a

Spare 1 20 A 27 ... 28 20 A 1 360 COPY/BREAK A840a

Spare 1 20 A 25 ... 26 20 A 1 540 COPY/BREAK A840a

23 ... 24 20 A 1 1000 COPIER COPY/BREAK A840a

FELLOWS ROOM A832 900 1 20 A 21 ... 22 20 A 1 580 UTILIZ. MGMT. A839

OFFICE B801 720 1 20 A 19 ... 20 20 A 1 580 UTILIZ. MGMT. A839

OFFICE B803 900 1 20 A 17 ... 18 20 A 1 720 PIMS A838

OFFICE B804 900 1 20 A 15 ... 16 20 A 1 1080 EXAM A836

OFFICE B805 900 1 20 A 13 ... 14 20 A 1 900 OFFICE B828

EXISTING 1 20 A 11 ... 12 20 A 1 900 OFFICE B826

EXISTING 1 20 A 9 ... 10 20 A 1 900 OFFICE B825

EXISTING 1 20 A 7 ... 8 20 A 1 900 OFFICE B824

EXISTING 1 20 A 5 ... 6 20 A 1 EXISTING

EXISTING 1 20 A 3 ... 4 20 A 1 EXISTING

EXISTING 1 20 A 1 ... 2 20 A 1 EXISTING

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 10,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MLO

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA1 VOLTAGE: 208Y/120V / 3 ø / 4W

LOCATION: Space B829 PANEL TYPE:

PANELBOARD: R8C-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 3KVA (4 AMPS).

NOTES:

EST. DEMAND CURRENT: 7 A

CONNECTED CURRENT: 7 A

Other 0 VA 0.00% 0 VA EST. DEMAND LOAD: 5425 VA

Motor 3116 VA 100.00% 3116 VA CONNECTED LOAD: 5425 VA

Lighting 2309 VA 100.00% 2309 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 3116 FCU'S

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Spare 1 20 A 3 ... 4 20 A 1 Spare

EXISTING 1 20 A 1 ... 2 20 A 1 0 2309 Lighting MEN'S RESTROOM...

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: Space B829 PANEL TYPE:

PANELBOARD: L8C-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 3KVA (4 AMPS).

NOTES:

EST. DEMAND CURRENT: 1 A

CONNECTED CURRENT: 1 A

EST. DEMAND LOAD: 519 VA

CONNECTED LOAD: 519 VA

Lighting 519 VA 100.00% 519 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Spare 1 20 A 3 ... 4 20 A 1 Spare

EXISTING 1 20 A 1 ... 2 20 A 1 519 Lighting PASSAGE A846F

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: Space B829 PANEL TYPE:

PANELBOARD: LS8C-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 11KVA (31 AMPS). ADD NEW 20/1 CB'S AS REQUIRED- CKTS 31-42 ARE EXISTING SPACES.

NOTES:

EST. DEMAND CURRENT: 35 A

CONNECTED CURRENT: 42 A

EST. DEMAND LOAD: 12580 VA

CONNECTED LOAD: 15160 VA

Receptacle 15160 VA 82.98% 12580 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

CONFERENCE/MEDIATION... 740 1 20 A 33 ... 34 -- -- Space

EEO PROGRAM MANAGER... 720 1 20 A 31 ... 32 -- -- Space

OFFICE C809 720 1 20 A 29 ... 30 20 A 1 200 FLUSH VALVES/AUTO FAUC...

CARE CORD. B818 400 1 20 A 27 ... 28 20 A 1 900 CHIEF B822a

CARE CORD. B818 400 1 20 A 25 ... 26 20 A 1 900 SHARED OFFICE B821

CARE CORD. B818 400 1 20 A 23 ... 24 20 A 1 720 SHARED OFFICE B821

KITCHENETTE/COPY B816 720 1 20 A 21 ... 22 20 A 1 900 PASSAGE A846F

REFRIG B816 1000 1 20 A 19 ... 20 20 A 1 500 COPIER KIT/COPY B807

TEAM B815 1100 1 20 A 17 ... 18 20 A 1 760 HOSPITALIST B808

PVT OFF B814, B815 900 1 20 A 15 ... 16 20 A 1 580 HOSPITALIST B808

COPIRE PVT OFF B814 1000 1 20 A 13 ... 14 20 A 1 740 LARGE CONF. B810

EXISTING 1 20 A 11 ... 12 20 A 1 860 LARGE CONF. B810

EXISTING 1 20 A 9 ... 10 20 A 1 EXISTING

EXISTING 1 20 A 7 ... 8 20 A 1 EXISTING

EXISTING 1 20 A 5 ... 6 20 A 1 EXISTING

EXISTING 1 20 A 3 ... 4 20 A 1 EXISTING

EXISTING 1 20 A 1 ... 2 20 A 1 EXISTING

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 10,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MLO

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA1 VOLTAGE: 208Y/120V / 3 ø / 4W

LOCATION: ELECTRICAL B813 PANEL TYPE:

PANELBOARD: R8B-1

EXISTING PANEL. ESTIMATED EXISTING LOAD IS 3KVA (4 AMPS).

NOTES:

EST. DEMAND CURRENT: 4 A

CONNECTED CURRENT: 4 A

Other 0 VA 0.00% 0 VA EST. DEMAND LOAD: 3172 VA

Motor 2078 VA 100.00% 2078 VA CONNECTED LOAD: 3172 VA

Lighting 1094 VA 100.00% 1094 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 2078 FCU'S

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Spare 1 20 A 3 ... 4 20 A 1 Spare

EXISTING 1 20 A 1 ... 2 20 A 1 0 1094 Lighting...

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: ELECTRICAL B813 PANEL TYPE:

PANELBOARD: L8B-1

EXISTING PANEL. NO EXISTING LOAD.

NOTES:

EST. DEMAND CURRENT: 0 A

CONNECTED CURRENT: 0 A

EST. DEMAND LOAD: 397 VA

CONNECTED LOAD: 397 VA

Lighting 397 VA 100.00% 397 VA

LOAD CLASSIFICATION CONNECTED DEMAND FACTOR CALCULATED

PANEL TOTALS

Space -- -- 41 ... 42 -- -- Space

Space -- -- 39 ... 40 -- -- Space

Space -- -- 37 ... 38 -- -- Space

Space -- -- 35 ... 36 -- -- Space

Space -- -- 33 ... 34 -- -- Space

Space -- -- 31 ... 32 -- -- Space

Space -- -- 29 ... 30 -- -- Space

Space -- -- 27 ... 28 -- -- Space

Space -- -- 25 ... 26 -- -- Space

Space -- -- 23 ... 24 -- -- Space

Space -- -- 21 ... 22 -- -- Space

Space -- -- 19 ... 20 -- -- Space

Space -- -- 17 ... 18 -- -- Space

Space -- -- 15 ... 16 -- -- Space

Space -- -- 13 ... 14 -- -- Space

Spare 1 20 A 11 ... 12 20 A 1 Spare

Spare 1 20 A 9 ... 10 20 A 1 Spare

Spare 1 20 A 7 ... 8 20 A 1 Spare

Spare 1 20 A 5 ... 6 20 A 1 Spare

Spare 1 20 A 3 ... 4 20 A 1 Spare

Lighting Room A846F, A846b,... 397 1 20 A 1 ... 2 20 A 1 Spare

LOAD DESCRIPTION

LTS RCPTS MTRS OTHER

BKR

P AMP CIRCUIT

BKR

AMP P

OTHER MTRS RCPTS LTS

LOAD DESCRIPTION

SPECIAL:

A.I.C. RATING: 14,000 AMPS SYMMETRICAL

FEEDER: SEE ONE-LINE DIAGRAM MAIN DEVICE: 225 A MAIN CB

FED FROM: BUS AMPS: 225 AMPS

MOUNTING: SURFACE NEMA 1 VOLTAGE: 480Y/277V / 3 ø / 4W

LOCATION: ELECTRICAL B813 PANEL TYPE:

PANELBOARD: LS8B-1

101 - GI002 - COVER SHEET VOL- 2
Sheets
AE200 - EXTERIOR ELEVATIONS
AE300 - BUILDING SECTIONS
AE301 - BUILDING SECTIONS
AE320 - WALL SECTIONS
AE321 - WALL SECTIONS
AE322 - WALL SECTIONS
AE323 - WALL SECTIONS
AE324 - WALL SECTIONS
AE330 - PLAN DETAILS
AE331 - PLAN DETAILS
AE332 - SECTION DETAILS
AE410 - VERTICAL CIRCULATION
AE411 - VERTICAL CIRCULATION
AE412 - VERTICAL CIRCULATION
AI420 - INTERIOR ELEVATIONS
AI421 - INTERIOR ELEVATIONS
AI500 - WALL TYPES
AI520 - CASEWORK DETAILS
AI521 - CASEWORK DETAILS
AI530 - INTERIOR DETAILS
AI531 - INTERIOR DETAILS
AI540 - INTERIOR FINISH DETAILS
AI600 - DOOR AND FRAME SCHEDULE
AW001 - INTERIOR SIGNAGE TYPES
AW002 - INTERIOR SIGNAGE TYPES
AW100 - SIGNAGE PLAN & SCHEDULE - BASEMENT
AW101 - SIGNAGE PLAN & SCHEDULE - FIRST FLOOR
GC100 - CONSTRUCTION PHASING - BASEMENT
GC101 - CONSTRUCTION PHASING - 1ST FLOOR
GC102 - CONSTRUCTION PHASING - 2ND FLOOR
GI001 - COVER SHEET VOL. 1
GI002 - COVER SHEET VOL. 2
GI003 - GENERAL INFORMATION & SYMBOL LEGEND
ID001 - INTERIOR FINISH KEY
ID002 - INTERIOR FINISH SCHEDULE - BASEMENT & FIRST FLOOR
ID100 - INTERIOR FINISH PLAN - BASEMENT
ID101 - INTERIOR FINISH PLAN - 1ST FLOOR
102 - FX001 - FIRE SPRINKLER GENERAL
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
103 - FX100 - FIRE SPRINKLER DEMO - BASEMENT
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
104 - FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
105 - FX108 - FIRE SPRINKLER DEMO - EIGHT FLOOR
Sheets
FA108 - FIRE ALARM DEMO - EIGHT FLOOR
FA208 - FIRE ALARM NEW - EIGHT FLOOR
FX108 - FIRE SPRINKLER DEMO - EIGHT FLOOR
FX208 - FIRE SPRINKLER NEW - EIGHT FLOOR
GI108 - LIFE SAFETY ANALYSIS - EIGHT FLOOR
106 - FX200 - FIRE SPRINKLER NEW - BASEMENT
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
107 - FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
108 - FX208 - FIRE SPRINKLER NEW - EIGHT FLOOR
Sheets
FA108 - FIRE ALARM DEMO - EIGHT FLOOR
FA208 - FIRE ALARM NEW - EIGHT FLOOR
FX108 - FIRE SPRINKLER DEMO - EIGHT FLOOR
FX208 - FIRE SPRINKLER NEW - EIGHT FLOOR
GI108 - LIFE SAFETY ANALYSIS - EIGHT FLOOR
109 - FA001 - FIRE ALARM GENERAL
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
110 - FA100 - FIRE ALARM DEMO - BASEMENT
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
111 - FA101 - FIRE ALARM DEMO - 1ST FLOOR
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
112 - FA108 - FIRE ALARM DEMO - EIGHT FLOOR
Sheets
FA108 - FIRE ALARM DEMO - EIGHT FLOOR
FA208 - FIRE ALARM NEW - EIGHT FLOOR
FX108 - FIRE SPRINKLER DEMO - EIGHT FLOOR
FX208 - FIRE SPRINKLER NEW - EIGHT FLOOR
GI108 - LIFE SAFETY ANALYSIS - EIGHT FLOOR
113 - FA200 - FIRE ALARM NEW - BASEMENT
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
114 - FA201 - FIRE ALARM NEW - 1ST FLOOR
Sheets
FA001 - FIRE ALARM GENERAL
FA100 - FIRE ALARM DEMO - BASEMENT
FA101 - FIRE ALARM DEMO - 1ST FLOOR
FA200 - FIRE ALARM NEW - BASEMENT
FA201 - FIRE ALARM NEW - 1ST FLOOR
FX001 - FIRE SPRINKLER GENERAL
FX100 - FIRE SPRINKLER DEMO - BASEMENT
FX102 - FIRE SPRINKLER DEMO - 1ST FLOOR
FX200 - FIRE SPRINKLER NEW - BASEMENT
FX201 - FIRE SPRINKLER NEW - 1ST FLOOR
GI001 - LIFE SAFETY CODE ANALYSIS
GI100 - LIFE SAFETY ANALYSIS - BASEMENT
GI102 - LIFE SAFETY ANALYSIS - 1ST FLOOR
115 - FA208 - FIRE ALARM NEW - EIGHT FLOOR
Sheets
FA108 - FIRE ALARM DEMO - EIGHT FLOOR
FA208 - FIRE ALARM NEW - EIGHT FLOOR
FX108 - FIRE SPRINKLER DEMO - EIGHT FLOOR
FX208 - FIRE SPRINKLER NEW - EIGHT FLOOR
GI108 - LIFE SAFETY ANALYSIS - EIGHT FLOOR
116 - PP001 - GENERAL PLUMBING INFORMATION
Sheets
PD010 - PLUMBING DEMO PLANS - U.G. AND PIPE BASEMENT
PD100 - PLUMBING DEMOLITION PLAN - BASEMENT
PD101 - PLUMBING DEMOLITION PLAN - 1ST FLOOR
PD107A - PLUMBING DEMOLITION PLAN - 7TH FLOOR - UNIT A
PD108A - PLUMBING DEMOLITION PLAN - 8TH FLOOR - UNIT A
PD108B - PLUMBING DEMOLITION PLAN - 8TH FLOOR - UNIT B
PL010A - ENLARGED PLUMBING PLAN - PIPE BASEMENT - UNIT A
PL010B - ENLARGED PLUMBING PLAN - PIPE BASEMENT - UNIT B
PL100A - ENLARGED PLUMBING PLAN - BASEMENT - UNIT A
PL100B - ENLARGED PLUMBING PLAN - BASEMENT - UNIT B
PL101A - ENLARGED PLUMBING PLAN - 1ST FLOOR - UNIT A
PL101B - ENLARGED PLUMBING PLAN - 1ST FLOOR - UNIT B
PL107A - PLUMBING PLAN - 7TH FLOOR - UNIT A
PL107B - PLUMBING PLAN - 7TH FLOOR - UNIT B
PL108A - PLUMBING PLAN - 8TH FLOOR - UNIT A
PL108B - PLUMBING PLAN - 8TH FLOOR - UNIT B
PL140 - PLUMBING ROOF PLAN

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it.